ICC-ES Report
:00 . • • a 09
This report is subject to renewal 09/2017,
DIVISION: 06,00 00=WOOD, PLASTICS AND COMPOSITES
SECTION:06 16 00 'SHEATHING
DIVISION: 07 00 00—THERMAL AND MOISTURE PROTECTION .
SECTION: 07 30 05—ROOFING FELT AND UNDERLAYMENT
REPORT HOLDER:`
HUBER ENGINEERED WOODSJLC
'ONE`RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE,SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
EVALUATION SUBJECT:
ZIP SYSTEM° AND ZIP SYSTEM+TM ROOF SHEATHING
ACC . 1CC ICC
C
PMG LISTED .
Look for the trusted marks of Conformity! +
"2014 Recipient of Prestigious Western States Seismic Policy CounciIN l
i'JVSSPC Award in Excellence`." 01"11Otral
A Subsidiary of couF����
� FTu•.-
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attribute �eead
specifically addressed, nor are they to be construed as an endorsement of the subject of the report 'r
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any,product covered by the report. AIM `"*
Copyright© 2015 ICC Evaluation Service, LLC.AII'rights reserved.
\ ICC EVALUATION
\ L
C SERVICE
Widely AcceptedandTrusted
IMES Evaluation Report ESR-1473*
Reissued September 2015
This report is subject to renewal.September 2017.
wwwJcc-es.ord j (800)423-6587 1 .(562) 699-0543 A Subsidiary of the International Code Council°
DIVISION:06 00 00—WOOD, PLASTICS,AND required in Chapter 15 of the IBC-and Chapter 9 of the
COMPOSITES IRC. The OSBsubstrate complies with U.S. DOC PS-2 for
Section:06,116 00—Sheathing wood structural panels and is overlaid on one side with a
medium-density, phenol-impregnated, polymer-modified
DIVISION:07 00 00—THERMAL.AND MOISTURE sheet material. The standard-size panels.:are nominally
PROTECTION 4 feet by 8 feet. Oversize panels, wider than 4 feet
Section:07 30 05—Roofing Felt and Underlayment (1219 mm) or longer than 8 feet (2438 mm), or both, are
also produced. The panels are available with either a
REPORT HOLDER: square-finished-edge .profile a tongue-and-groove edge
profile or a machined edge profile. The proprietary seam
HUBER ENGINEERED WOODS,LLC tape is a self-adhering sheet-type membrane consisting of
ONE RESOURCE SQUARE acrylic adhesive laminated to a polyolefin backing, and the ,
10925 DAVID TAYLOR-DRIVE,'SUITE 300 face of the tape is labeled with ESR-1473. The tape is
CHARLOTTE,NORTH CAROLINA 28262 0,012 inch thick (0.30 mm)' with a minimum,width 'of,
(800)933-9220 _ 3 inches(76:2 mm);and comes in rolls of varying length. .
www.huberwood.cbm 4.0 INSTALLATION
EVALUATION SUBJECT: 4.1 General:
ZIP SYSTEM®AND ZIP SYSTEM+TM ROOF SHEATHING Installation of ZIP System® and ZIP •System+TM roof
sheathing must comply with the applicable code,this report
1.0 EVALUATION SCOPE and the manufacturer's published installation instructions.
The installation instructions are to be available at the
Compliance with.the following codes: jobsite at all times during installation. The instructions
■ 2015,2012 and 2009 International.Building Codee(IBC) within this report must govern if there are any conflicts
between the manufacturer's published instructions and this
■ 2015, 2012 and 2009.International Residential.Code° report.
(IRC).
4.2 Application:
■ 2013 Abu Dhabi International Building Code(ADIBC)t The ZIP System® and ZIP •System+TM roof sheathing
IThe ADIBC is based on the 2009 IBC.-2009 IBC code sections referenced panels must be installed with the longer dimension
in this report are the same sections in the ADIBC. perpendicular to the roof framing and fastened to the
Properties evaluated: :roof framing in accordance with the applicable code for
■ Structural wind uplift resistance wood structural panels. The panels must be installed in
accordance with the panel span rating as shown on the
11il Nonclassified roof covering panels. All corners are to be securely fastened. Tongue-
Classified roof covering and-groove and machined edge panels are designed to
provide the correct gap size at'the panel edges during
■•Weather resistance installation. Squared-edged panels must be spaced apart a
2.0 USES minimum of 1/9 inch (3.18 mm) at the time of installation.,,
End joints of adjacent panel runs must be staggered. The
ZIP System® and ZIP System+TM •roof sheathing panels panel must be installed with the laminated phenol-
are used 'as combination- roof, sheathing and roof impregnated polymer-modified sheet material facing to
underlayment. the exterior. All ZIP.System® and ZIP System+Tee roof
3.0 DESCRIPTION sheathing seams must. be sealed,with the Zip System®
tape. All overlay surfaces must be free of any significant
The ZIP System® and ZIP System+TM roof Sheathing presence of debris particles or sawdust prior to installation
panels are wood structural panels having a laminated of the ZIP System tape. Overlay surfaces must be void of
facer. The ZIP System+TM panels are manufactured using any free water prior to application of the ZIP System®tape.
a different resin than the Zip System®panels. .The panels The ZIP System®tape edges must be sealed and the tape
are installed with a proprietary seam tape,which allows the is to be centered within +/- 112 inch �12.7 mm) of all panel'
systems to be used as an alternate to the underlayment edge seam centers. All ZIP System and ZIP System+TM
*Revised November 2015
/CC-ES Evaluation Reports are not to he construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed ss^
as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by lCC Evaluddon Service,LLC,express or implied asRAN
to any finding or other matter in this report,or as to any produci covered by the report.
Copyright O 2015]CC Evaluation Service,LLC. All rights reserved. Page 1 of 2
J
ESR-1473 I Most WdelyAcce, and Trusted Page 2 of 2
' roof sheathing surface defects, openings, cracks, etc.,,that wood structural panels with either a 24/16, 32/16 or
completely penetrate the 'overlay and substrate, and 40/20 span rating.
caused by handling or construction work, must be covered
® � ® 5,4 In jurisdictions enforcing the IBC, the roof covering
with the ZIP Systemo tape. The ZIP System tape'must system incorporating the panels is limited. to
extend a minimum of 1 inch(25.4 mm)past the panel edge
® installations in the following construction types:
7-joint intersections. The ZIP System tape must be
adhered .to the ZIP System® and ZIP System+TM roof • Type 111-B and Type V-B
sheathing. Wrinkles in the ZIP System. seam tape are
acceptable unless they create a leak path to the-panel Type Ill-A or Type V-A under the conditions
seam. specified in footnote d of IBC Table 601
4.3 Roof Assemblies Type III-A or Type V-A under the conditions
specified in footnote b of IBC Table 601, for
4.3.1 Classified Roof Coverings occupancies other than Group F-1, H, M and S-1
4.3.1.1 Class A: Underlayment is not required for a In jurisdictions enforcing the IRC, the roof covering
minimum 1/2-inch thick Zip_System+TM roof•sheathing with system incorporating the panels may be installed on
Class A asphalt glass fiber mat shingles. structures constructed in accordance with the IRC.
4.3.1.2 .Class B: Underlayment is not required for a 5.6 Enclosed attics and rafter spaces must be ventilated
minimum 7/,6-inch thick Zip System® roof sheathing with in accordance with the applicable code, except where
Class A asphalt glass fiber mat shingles. unvented conditioned attic assemblies are permitted
4.3.2 Nonclassified'Roof Coverings: The ZIP System® by 2015 and 2012 IRC Section R806,5 or 2009 IRC
and ZIP System+rm roof sheathing panels are'limited to Section R806.4. .
installation on buildings permitted to have nonclassified 5.6 An ice barrier must be provided as required by
roof coverings using code-complying asphalt-fiberglass Section 1507.2.8.2 of the IBC and Section R905.2.7
shingles, metal shingles, metal panels,wood shakes,wood of the 2015 IRC and Section R905.2.7.1.-of the 2012
shingles, built-up roofing, slate and slate-type shingles, and 2009 IRC.
and clay and concrete tile roof coverings. Roof coverings
may be applied directly to the taped ZIP Systeme and ZIP 5.7 Installation is limited to roofs having a slope of 2:12
System+TM roof, panels unless multi-layer underlayments (16.67%slope)or greater.
are required. 5.8 ZIP Systeme and ZIP System+TM roof sheathing
4.4 Wind Uplift sign loads and ZIP Systemt Resistance: panels are manufactured by Huber Engineered
Wind uplift de
e and ZIP Woods, LLC, in Crystal Hill, Virginia; Commerce,
System+TM roof wood structural panel allowable uplift Georgia; Broken Bow, Oklahoma; and Easton, Maine,
resistance shall be determined in accordance with under a quality-control program with inspections by
Sections 1609 and 2304.8.2 of the 2015 IBC or 2304.7.2 of ICC-ES.
the 2012 and,2009 IBC and. Section R301.2.1 of the IRC. 6.0 EVIDENCE SUBMITTED
Roof coverings must be fastened.to the sheathing with
mechanical fasteners sufficient to resist the design uplift Data in accordance with the ICC-ES Acceptance Criteria
load. for Wood Structural Panel Roof Sheathing Factory-
faminated with an Alternative Roof Underlayment(AC266),
5.0 CONDITIONS OF USE dated May 2008(editorially updated October 2015). "
The ZIP System® and ZIP System+TM roof sheathing 7,0 IDENTIFICATION
panels described in this report comply with, or are suitable ®
alternatives to what is specified in, those codes listed in Each ZIP System and ZIP System+TM roof sheathing
Section 1.0 of this report, subject to . the following panel covered by this report must bear a label that includes
conditions: the manufacturer's name (Huber Engineered Woods, LLC)
and address; the product'name; the evaluation report
5.1 This evaluation report• and the manufacturer's number(ESR-1473); and the grade, performance category .
published installation instructions, when required by and bond classification.
the code official, must be submitted at the time of
permit application. The panel mill label and span rating, grade, performance
category and bond classification label must be visible on
5.2 The ZIP System® and ZIP System+TM roof sheathing the bottom face of panels,opposite•the laminated facer..
panels must be manufactured, identified and installed.
in accordance with this report and the manufacturer's The ZIP Systeme tape roll is labeled with the product
published installation instructions.' . name and the evaluation report number(ESR-1473).
5.3 The ZIP Systeme and ZIP System+TM roof sheathing
panels are limited to code-approved structural use for
•
s
ICC EVALUATION
c SERVICE
Accepted and Trusted
IMES Evaluation Report ' ESR-1473 FBC Supplement
Reissued September 2015,
This report is subject to.renewal September 2017.
wwmicc-es.orq (1300) 423-6587 (562) 699-0543; A Subsidiary-of the International Code Council®
DIVISION: 06 00 00—WOOD;PLASTICS,AND COMPOSITES',
Section:06 16 00—Sheathing.
DIVISION:07 00 00=THERMAL AND,MOISTURE PROTECTION
Section: 07 30 05—Roofing Felt and Underlayinent
REPORT HOLDER:
HUBER ENGINEERED WOODS,'LLC
ONE RESOURCE SQUARE
10925 DAVID TAYLOR DRIVE,SUITE 300
CHARLOTTE, NORTH CAROLINA 28262
° (800)933-9220
www.huberwood.com
EVALUATION SUBJECT:
ZIP SYSTEM®AND ZIP SYSTEM+fm ROOF SHEATHING
1.0 . REPORT PURPOSE AND,SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that ZIP System® and Zip System+TM roof sheathing,
recognized in ICC-ES master evaluation report ESR-1473, has.:also been"evaluated for compliance with the codes noted
below.
Applicable code editions:
■'2014 Florida Building Code—Building
■'2014 Florida Building Code—Residential
2.0 _CONCLUSIONS
'The ZIP System®and ZIP System+TM roof sheathing,described in Sections.2A through 7.0 of the master evaluation report
ESR-1473, complies with the'2014 Florida. Building Code—Building and the 2014 'Florida Building Code—Residential,
provided the design and installation are-in accordance with the'Intbrnational Building Codee provisions noted in the master
report, and with the condition that wind uplifting design loads must be determined in accordance with Section. 1609 of the
Florida Building Code—Building and Section R301.2.1 of the'Florida Building Code—Residential.
Use of the ZIP System® and ZIP System+Ten roof sheathing 'for compliance with the High-Velocity Hurricane Zone , -
provisions of the 2014 Florida-Building Code Building and the 2014 Florida Building Code—Residential has not been
evaluated and is outside the scope of the evaluation report.
For products failing under Florida Rule 9N-3, verification that the report holder's quality-assurance program is audited by a
quality-assurance entity approved by the Florida Building Commission for.the type of inspections being conducted is the
responsibility of an approved validation entity(or the code official, when the report holder does not possess an approval by
,the Commission).
This supplement expires concurrently with the master report, reissued September 2015 grid revised November 2015.
ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed,nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use.There is no warranty by ICC Evaluation Service,LLC,express or implied,as
to anyftnding or other matter in this report,or as to any produc{covered by the,report.
Copyright 0 2015 ICC Evaluation Service,LLC. All rights reserved. Page 1 of 1
Page 1 of 1
° p.
BCIS Home Log In 1 User Registration . Hot Topic I Submit Surcharge Stats&Fads Publications,� FBC Staff BCIS site Map Links.( Search R
F r'da
Product Approval
USER:Public User
'.:�rayy:lYc3
r *
Product Aooroval Menu>Product or Aoollcation Search>Application List -
Search Criteria Refine Search
Code Version 2014 FL# 17147
.Application Type ALL Product Manufacturer ALL
Category ALL Subcategory ALL
Application Status ALL Compliance Method ALL
Quality Assurance Entity ALL Quality.Assurance Entity Contract Expired ALL
Product Model,Number or Name ALL Product Description ALL
Approved for use in HVHZ ALL Approved for use outside HVHZ ALL
Impact Resistant ALL Design Pressure ALL
Other ALL
°
Search Results-Applications
FL# Tvoe Manufacturer Validated By Status
FL17147- Revision Huber Engineered Woods LLC ICC Evaluation Service, Approved
R1 Category:Structural.Components LLC.
History Subcategory:Products Introduced as a•Result of New (205)599-9600
Technology
`Approved by DBPR.Approvals by DBPR shall be reviewed and ratified by the POC and/or the Commission if necessary.
Contact Us::2601 Blair Stone Road.Tallahassee FL 32399 Phone:850-487-1824 ,
The State of Florida is an AA/EEO employer.Copyright 007- 013 State of Florida.::Privacy S atement::Accessibility Statement;:Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-maii address released in response to a public-records request,do not send
electronic mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to
Section 455.275(3),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if
they have one.The emails provided may be used for official communication with the licensee.However email addresses are public record:If you do not wish to
supply a personal address,please provide the Department with an email address which:can be made available to the public.To determine if you are a licensee under
Chapter 455,F.S.,please click here.
Product Approval Accepts:
- Egg® rCg ® -
Credit Card
Safe,
f
https://www.floridabuilding.ori/pr/pr_app_lst.aspx 4/12/2017
- - - =------- rage i of 1
PrOeWofial OuWflbn
m
BCIS Home I Log In User Registration i Hat Topics I Submit Surcharge Stats&,Facts, Publications Ft3C Staff; fICIS Site Map i Links Search j
Fbr'da
rV Product Approval
10 USER:Public User
Product Approval Menu>Product or Application Search>Application List>Application Detail. '
FL# ' FL17147-R1-
Application Type Revision
Code Version 2014
Application Status Approved
Comments ,
Archived L
Product Manufacturer Huber Engineered Woods LLC
Address/Phone/Email 10925 David Taylor Drive
Suite 300
Charlotte,NC 28262 ,
a (704)548-5442
kurt.koch@huber.com
Authorized Signature Kurt Koch
kurt.koch@huber.com
Technical Representative Ken W.Hix
Address/Phone/Email 1446 Hwy 334
'Commerce,GA 30530
(706)336-3041
ken.hix@huber.CDM
Quality Assurance Representative Walker Campbell
Address/Phone/Email 1446 Hwy 334
Commerce,GA 30530
(704)562=1053
walker.campbell@huber.com
Category Structural Components
Subcategory Products Introduced as a Result of New Technology
Compliance Method Evaluation Report from a,Product Evaluation Entity
Evaluation Entity ICC Evaluation Service,LLC
Quality Assurance Entity ICC Evaluation Service
Quality Assurance Contract Expiration Date 10/01/2017
Validated By -ICC Evaluation Service,LLC.
Certificate of Independence FL17147 R1 COI Certificate of Independence for Evaluation,Ddf
Referenced Standard and Year(of Standard) Standard Year
ICC-Evaluation Service AC310 2015
Equivalence of Product Standards
Certified By Approved Evaluation Entity
FL17147 R1 Eauiv AC310.Ddf
Sections from the Code
https://www.floridabuilding.org/pr/pr_app_dtl.a'spx?param=wGEVXQwtDgvCo3 EapiIlBd... 4/12/2017
Page 2 of 2'
Product Approval Method Method 1 Option C
Date Submitted 08/31/2015
Date Validated 09/16/2015
Date Pending FBC Approval
Date Approved 09/20/2015
Summary of Products
FL# Model,Number or Name Description
17147.1 ZIP System(R)Wail Sheathing ZIP System(R)Wall Sheathing
Limits of Use Installation Instructions
Approved for use in HVHZ:No FL17147 R1 II ZIP Sheathing Install Manual-2013 Ddf
Approved for use outside HVHZ:Yes Verified By: ICC Evaluation Service, LLC
Impact Resistant:No Created by_IndependentThird Party:
Design Pressure: N/A Evaluation Reports
Other:limited to structural aspects of panel FL17147 R1 AE ESR-1474(2).Ddf
FL17147 R1 AE ESR1474.pdf
Back F1
Contact Us::2601 Blair Stone Road Tallahassee F Phone:550-487-1824
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement t:Refund Statemert
Under Florida law,email addresses are public records.If you do not want your e-mail address released In response to a public-records request,do nut send
electronic mail to.this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.-Pursuant to
Section 455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if
they have one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to
supply a personal address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under
` Chapter 455,F.S.,please click here_.
Product Approval Accepts:
h� Log
® `:: —
Credit Card
Safe
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvCo3 EapiIlBd... 4/12/2 017
-
n
r ^ ? a•_ .+yr^' _ _ i'}'ry..r� '?'ev .`.c ! t" - `lrt
•�s+.�. .r, rt Xd �X��[ :..� t�-�s �$ S {�,,,.. � � ,ti Ott`M..�.�'���a s _. -) j �Yt� r _ � � '•�
_ ." ;� n s � :"'R'r it �. i '�` � ;+_ .✓ _•l. `:
'Y
r'. B ^ r i #`t� :`9 x r �},,S �s s•" - � .fir{`ai �. + • �" • ,
.. _ - 7 '�F, �;'� .:dui♦ _, ` �4 .S r '°'!'�A.3!. ^n .i-` + f
•� r .a ,4�,� r wr�h,. ac„ay4't.r:,r� '°` s � . '� s c `1 �"��y4s ;, .. _ �.V ��-�'
w t ..,4 �; `_I ,... t �,�;,K` 'v � .z � a� .fx.T�r•1 w - i> ;7 f i ,ram=
,.y r + r, C �.- i s,t L+r i"��� ,�*�+�s'- <� �yr _7t.` Idsr rY, `, d_„rt ,. . rF:s .+� "-K •d` ,��,•v � = i I.« _ xr, �.t
'
tp
dr' I a r +,,� 4 s h 1 a' t a '• �t �' `�
a�`i' '.t f, � t t a'�• ♦ �.:4'i.2'*a#'..t'.`�.1p�' �! 3�a f -7 t:7'€ +'+Xe r�r{y' 4' �3i - '.t � � 1' Sl'
T =j`F t`-,: 1t -.x, -1 a.. ,. a '".. i �' >,� ;,a• "�'' _t';A..,.. - i •,,:µ.�,r ♦1'. ; ^F
l. :fT'" t v ..t'l,y; 1 t i •_' +.y _ r � ',rr ...'^' .. - s .. >� _ -�'
AIWA TM
^ � , .,�'yqY'• •'" �t � q :t3{ �u.Y�y�1.�-i� '�I`,3 i � ��.. i' r ;r 2� - �� � , 4;. " � s .. 't�
«J.`^i�.z';; �� f�3 3 `!�i'A-.. � 1.�"7w, 'tY• +t � � T P�• -___�..-�...i....._+3.i ....__....�_....., .� __ _ _-..�^ sue:_. ... _ _.. t.
�.. t Iry ZIJAPSYSteM
MW ROOF& WALL SHEATHING
FASTER.TIGHTER. ENERGY EFFICIENT.
—f FROM THE
CREATORS OF igdvanrech
YeT
e d
l
ZIP System"Roof & Wall Sheer_ `-f .� ? M
.///
INSTALLATION MANUAL systemTROOF&WALL SHEATHING
C011t@IItS FASTER.TIGHTER. ENERGY EFFICIENT.
02 ZIP System" Sheathing Installation On Roofs 08 ZIP System"Roof&Wall Sheathing -Window
Installation Flanged Windows&Brick Mould Windows
03 ZIP System'" Tape Installation -
Roof Panel Seams 09 ZIP SystemO Roof & Wall Sheathing - Window
Installation Brick Mould Windows (continued)
04 ZIP System'" Tape Installation -
Roof Panel Seams (continued) 10 ZIP System" Roof & Wall Sheathing -
Penetration Openings
05 Roof Covering Installation Instructions
11 ZIP System° Roof & Wall Sheathing
06 ZIP Systems Roof & Wall Sheathing Installation Installation Details
07 ZIP System" Tape Installation - Panel Seams 12 ZIP System-' Roof & Wall Sheathing
Installation Details (continued)
ATTENTION: This installation guide is intended to provide general ZIP System Roof &Wall sheathing can be used with a range of exterior
information for the designer and end user.The following guidelines claddings and roof coverings. Approved wall coverings include brick,
will help you safely and properly install the ZIP System°Roof&Wall vinyl, stone, wood fiber cement, wood and cedar shakes, traditional hard
wall sheathing.We urge you, and anyone installing this product,to coat stucco and specified drainable EIFS applications, however it is
read these guidelines in order to minimize any risk of safety hazards not recommended for use with adhesively attached EIFS. Approved roof
and to prevent voiding any applicable warranties. This manual is coverings include asphalt-fiberglass shingles,metal tiles and panels,clay and
a general installation guide and does not cover every installation concrete tiles, slate and slate-type shingles and wood shakes and shingles.
condition. Proper installation shall be deemed to mean the most Follow all cladding and roof covering manufacturer's installation instructions.
restrictive requirement specified by Huber Engineered Woods (HEW),
local building code,engineer or architect of record or other authority ZIP System Roof & Wall sheathing can be used on buildings of Type
having jurisdiction. You are fully and solely responsible for all safety III (Roof Applications ONLY) and Type V construction and construction
requirements and code compliance.For additional information contact permitted under the IRC.
Huber Engineered Woods LLC. ZIP System'Roof&Wall Sheathing Includes:
ZIP System°Roof&Wall Sheathing Safety Guidelines ZIP System sheathing panels with built-in moisture barrier_with preprinted
- Follow all OSHA regulations and any other safety guidelines and safety fastening and tape guides
practices during installation and construction. ZIP System tape
- Use approved safety belts and/or hamesses or other fall protection equipment.
- Install ZIP.System panels and tape only in dry conditions and on dry surfaces. Storage and Handling
Do not install in rain,snow,frost or other slippery conditions. - Set panel stack on three supports (stickers)to keep off the ground.
Outdoors,cover panels loosely with waterproof protective material.
- Wear rubber-soled or other high-traction footwear while installing ZIP System -
sheathing in a roof application.Do not wear footwear with wom soles or heels. Anchor covers top of the stack,but keep away from sides and bottom
ai
- Ensure the roofing surface is free from oil, chemicals, sawdust, dirt, tools, to assure good air circulation.
electric cords, air hoses, clothing and anything else that might create a In high moisture environments,cut banding on the panel stack to prevent
tripping hazard, edge damage.
- Install temporary toe boards along the ZIP System sheathing roof surface. ZIP System°Roof&Wall Sheathing Notes and Limitations:
Do not use on roofs with slopes less than 2/12.
What Is ZIP System'Roof&Wall Sheathing? Do not use abutted against general stone or-masonry without providing a
ZIP System Roof&Wall sheathing is code-recognized as a wood structural minimum of a 1/2"gap.
panel, roofing underlayment ()CC-ES ESR-1473), water-resistive barrier Do not install ZIP System tape in temperatures less than 20'F
and air barrier (ICC-ES ESR-1474). ZIP System Roof & Wall sheathing ZIP System products are not recommended for manufactured housing
has a built-in moisture barrier that lets you say good-bye to building paper applications that are built under a federal building code administered by
or housewrap on the walls and felt paper on the roof.' Simply install the the U.S.Department of Housing and Urban Development(HUD).
panels, tape the seams, and you have a structural wall sheathing, water- Do not use panel edge clips(H-Clips)with ZIP System Roof&Wall sheathing
resistive barrier and air barrier or a structural roof sheathing and roofing without expressed written approval from Huber Engineered Woods."
underlayment all from one product. Do not use ZIP System tape to permanently seal around circular roof
projections (plumbing vents,pipes,curved walls,etc.)
Contents (continued)
Wall Coverings Wet Blown Cellulose Insulation
ZIP System Roof &Wall sheathing should be covered with the finished - In addition to following manufacturer installation instructions,we recommend
roof covering or exterior cladding within 180 days of installation. a maximum moisture content of the cellulose of less than 25%measured at
Finished roof and exterior cladding products should be installed per the inside surface of the ZIP System panel before closing the wall cavity.
the manufacturer's installation instructions.
Per the recommendation of the Western Red Cedar Lumber Association Secondary Coatings
and the U.S.Forest Products Laboratory,wood siding should be primed Do not apply secondary coatings or treatments to ZIP System Roof & Wall
before installation. sheathing panels with the exception of the following:
When original roofing or claddings'are removed and replaced on existing ZIP - HEW approved fire resistant coatings. Fire resistant coatings must be
System sheathing, the roof or wall should be covered with an additional tested and approved by HEW for use with ZIP System panels.
roofing underlayment or water resistive barrier prior to installation of the - Field applied water-soluble borate insecticide or fungicide treatments
new finished roofing or cladding. applied to the non overlay side of the panel. See technical tip, "Termite
Treatments on ZIP System Roof&Wall Sheathing,"on zipsystem.com for
Note:In cladding systems requiring multiple layers of water-resistive barriers, more information.
like traditional hard-coat stucco,ZIP System sheathing is intended only to Permeable laminated radiant barrier foil or paint.For a radiant barrier foil or
replace the first layer. coating to be considered permeable,it must have an applied permeance of
five perms or greater as tested by the ASTM E 96 wet cup standard.For a
radiant foil, the permeance evaluation would include any adhesive and/or
backer used to laminate a foil. For a radiant paint/coating, the permeance
evaluation should be conducted at the applied thickness of the paint/coating.
ZIP System Roof and Wall sheathing replaces only the first layer in mulfi-undedayment systems.
Edge support is not required by code with 112(32/16 span rated)and 518(40/20 span rated)performance category.sheathing it the framing does not exceed 24'o.c.
and the total load does not exceed 93 psi for 1/2 and 156 psi for 518 performance categories.This is based an 11180 deflection criteria for total load.
ZIP.System®Roof&Wall Sheathing Insta.1►,01on Manual
OL
ZIP System® Sheathing Installation on Roofs
Overview:ZIP System Roof&Wall sheathing is composed of ZIP System panels and ZIP System seam sealing tape.ZIP Systems Roof& Wall Sheathing
panels should be fully installed before the seam sealing tape is applied.In general;the ZIP System roof sheathing panels should be installed from the lowest point
on the roof to the highest:It is at the discretion of the installer whether to apply tape from the top down or from the bottom up. However,working from the highest
sections of the roof and working down will minimize foot traffic on the tape.The following installation steps are presented as guidelines and a general outline of
the installation process.These are manufacturer installation recommendations—please visit zipsystem.com for a library of flashing and installation details.You are
fully and solely responsible for all safety requirements.Good construction and safety practices should be followed at all times.
Step 1.
Ensure that the panel surface is dry and clean of any nails, sawdust,or
other debris or protrusions prior to installing or walking on the panels.
After ensuring compliance with all OSHA and local code safety
guidelines, install ZIP System sheathing panels with the moisture
barrier surface facing outside. The Iona edge(8') should be oriented
perpendicular to the framing members,and panels should be installed
with the 4'edge seams staggered a minimum of 24".
1/8'spacing between square edges of all adjacent panels is recommended,
in accordance with industry standards for wood sheathing. (Tongue&
8'Panel Edges 4'Panel Edges
Groove panels are designed to self-space and do not require manual
spacing on the 8'edges.) I
The unique edge profile is Maintain 1/8"space
designed to accommodate where 4'edges meet.
incremental panel Unique edge profile is on
expansion and does not 8'edges only.
require manual gapping
along the 8'edges.
Step 2.
Ensure that ZIP System panels span at least three framing members and
a framing member supports the entire 4'edge of the panels.
Fasten the ZIP System Roof&Wall sheathing panel to the framing
members with code approved fasteners spaced at the appropriate
edge and intermediate spacing. It is the responsibility of the general
contractor to verify proper fastener type and spacing prior to installation.
Apply the fasteners 3/8"from the panel ends and comers.
An ideal installation would be where fastener heads are flush with the
panel surface. However,due to variations in materials and limitations
on equipment, this may be difficult to achieve in some situations. It
is not required to tape over overdriven fasteners unless the fastener
head creates a hole through the entire panel thickness. Please see
the technical tip,"Overdriven Fasteners in ZIP System Roof and Wall
Sheathing,"for more information.
Step 3.
Install temporary toe boards as necessary when applying the ZIP System
sheathing panels up the slope of the roof planes.
03
ZIP System'"-Tape Installation - Roof Panel Seams
Apply ZIP.System tape,after all-ZIP System Roof&Wall sheathing panels are fully fastened to roof framing members.Only ZIP System tape should be used to
seal the seams of ZIP System.panels.Ensure that the panel surfaces are dry and free of any nails,sawdust and other debris,or protrusions.Avoid stepping
on tape in high temperature environments.ZIP System tape is a contact tape that requires pressure for an adequate seal.
Step 1.
- Apply ZIP System tape to every vertical and horizontal,panel seam. It is
at the discretion of the installer whether to apply tapefrom the top down
or from the bottom up. However,.working from the highest sections of
the roof and working down will minimize foot traffic on the tape..
Ensure that the tape is.centered over-the seam within+/-1%2"to provide
adequate coverage and to ensure that wrinkles in the tape are minimized. _
Ensure that tape lengths are continuous across the S"horizontal edge
of the panels.If splices are unavoidable,create an overlapping splice
of at least 3".Apply moderate pressure onto the surface of the tape to
ensure a secure bond between the panel and the tape.
Use ZIP System tape gun or tape roller to apply-pressure to the tape
and smooth out any wrinkles.
Take special care to remove any voids and/or trapped air at splice
areas and T-joints.
Step 2. .
For valley areas of framing,we recommend you use 6"wide ZIP System
tape.This tape is wider than panel seam tape and is designed to give you
optimal protection in valley areas.
Starting from the bottom and working your way up,apply one continuous
piece of 6"tape so that the center of the tape is over the valley seam. .
Use the tape gun or tape roller.to apply pressure to the tape to ensure
proper contact with the panel and to eliminate any wrinkles that might
have occurred in the tape.Take special'care to seat tape completely
into the valley.
Note:
It is important to pay extra attention to valley taping as water is
directed toward the valleys during rain events. .A
Self-adhering ice and water barriers may be.required by code.ZIP
System tape is not considered a replacement for self-adhering ice
and water barriers.Therefore,when self-adhering ice and water
barriers are required,they should be installed in addition to ZIP
System tape.
ZIP System,"Roof&Wall Sheathing Installation Manual. �u
04
ZIP System'Tape Installation - Roof Panel Seams(dontinue,d)
Step 3.
If 6'ZIP System tape.is not available,use.two continuous pieces of 3.75"
ZIP System panel seam tape over the entire length of the valley seam,
overlapping the.pieces on the valley seam by at least 1.".
Starting from the bottom,install the first piece of tape overlapping the
valley seam by at least 1". First piece
- Use the tape gun or tape roller to apply pressure to the tape to ensure of tape '
proper contact with the panel and'to eliminate any wrinkles that might
have occurred in the tape.
- Apply the second piece of tape,overlapping the first piece in the valley
seam by 1
- Repeat use of the tape.gun or roller to make sure the tape is adequately
adhered and tightly pressed into the valley seam. second piece
Note: of tape
- It is important to pay extra attention to valley taping as water is
directed toward the valleys during rain events.
Self-adhering ice and water barriers may be required by code.ZIP
System tape is not considered a replacement for self-adhering ice
and water barriers.Therefore,when self-adhering ice and water
barriers are required,they should be installed in addition to ZIP
System tape.
Step 4.
To provide temporary weather protection to roof/wall intersections
of dormers or other wood-sheathed projections, apply 2" of the tape
,width up the vertical projection from where it intersects with the roof. _X
The remaining tape width can be adhered to the ZIP System roof
sheathing panels.
Use the tape gun or tape roller to apply pressure to the tape and smooth
out any wrinkles.
Step 5.
Install ZIP System tape over hips and ridges by.centering the tape over
the peak seam.Apply tape in sufficient length to completely extend the
length of the hip or ridge.
Starting from the lowest point of the flip and working up,press tape into
place keeping tape centered over the hip.Apply moderate pressure
onto the surface of the tape to ensure a secure bond between the panel
and the tape.
Cut ridge tape as required for ventilation p6or to installing ridge vent.
Step 6.
Tape over toe board nail holes once the.toe boards are removed,working
from the highest toe boards to the lowest.
05
Roof Covering Installation Instructions
ZIP System Roof&Wall sheathing is a code recognized sheathing and underlayment and is approved for use with the following roof coverings:
Asphalt-fiberglass Shingles
Metal Roofs(shingles and panels)
Clay Tile
Concrete'rite
Slate and Slate-type Shingles
Wood Shingles
Wood Shakes
When installing roof coverings,follow applicable codes and manufacturer's suggested instructions.Some roof coverings require a slip-sheet in addition to
conventional underlayment.Where slip-sheets are required,they should be installed over ZIP System sheathing panels.
Note:Visit zipsystem.com for updates and installation details.
Asphalt-fiberglass Shingles
Apply asphalt shingles directly to ZIP System sheathing.For roofs with a slope of 2/12 or greater but less than 4/12,additional underlayment may be required.
Install asphalt-fiberglass shingles according to applicable codes and manufacturer's installation instructions.
Metal Roof Coverings
Metal roof coverings may be applied.to ZIP System sheathing provided that the.roof covering manufacturer's installation instructions and applicable
codes are followed.
Fasteners used to secure the ZIP System Roof&Wall sheathing panels to supporting framing must be compatible with the specific metal roof covering
used. Galvanized fasteners shall be used with galvanized roof coverings, aluminum-zinc coated fasteners shall be used with aluminum-zinc coated roof
coverings and 300 series stainless steel fasteners shall be used with copper roofs.Stainless steel fasteners are acceptable with all metal roof types.
In addition, metal roof flashing shall also be made of a material compatible with the specific metal roof covering used.Apply metal shingles on roofs with
slopes of 3/12 or greater.
Clay and Concrete Tile Roof Coverings
ZIP System Roof&Wall sheathing is intended toreplace the first layer in a two-layer or multi-layer underlayment system. When installing clay or
concrete tile roof coverings,follow the installation recommendations of FRSA/TRI 07320.Install tile roofs according to applicable codes and manufacturer's
installation instructions.
Slate and Slate-type Shingles
Apply slate and slate-type shingles on roofs with slopes of 4/12 or greater.Install slate and slate-type shingles according to applicable codes and manufacturer's
installation instructions.
Wood Shingles
ZIP System Roof&Wall sheathing is intended to replace the first layer of underlayment required by the IBC and/or the IRO.Additional layers of underlayment
may be required by code depending on the local climate. Apply wood shingles on roofs with slopes of 3/12 or greater. Install wood shingles according to
applicable codes and manufacturer's installation instructions.
Wood Shakes
ZIP System Roof&Wail sheathing is intended to replace the first layer of underlayment required by the IBC and/or the IRC.Additional layers of underlayment
may be required by code depending on the local climate.ZIP System roof sheathing is not to be construed as a replacement for interiayment. Apply wood
shakes on roofs with slopes of 4/12 or greater.Install mood shakes according to applicable codes and manufacturer's installation instructions.
,ZIP System°Roof&Wall Sheathing Inst&t ,t*,Dn Manual i
06
ZIP System° Sheathing Installation on.Walls
Overview:ZIP System Roof&Wall sheathing is composed of ZIP System panels and ZIP System seam sealing tape.ZIP System"Roof&Wall Sheathing
panels should be fully installed before the seam sealing tape is applied.The following installation steps are presented as a general outline of the installation
process.These are manufacturer installation recommendations—please visit zipsystem.com for a library of flashing and installation details.You are fully and
solely responsible for all safety requirements.Good construction and safety practices should be followed at all times.
Step 1. Install ZIP System Roof & Wall sheathing panels positioned
with the water-resistive barrier facing outside. The panels may
be installed with the long side of the panel oriented either
horizontally or vertically,to the framing members.Walls that are,
designed to resist lateral shear forces and sheathed with wood
structural panels typically require solid framing or blocking behind
all panel edges. If oriented horizontally, block horizontal joints if
wall is designed for bracing or as a shear wall.
1/8' spacing between square edges of all adjacent panels is
recommended in accordance with industry standards for wood
sheathing installation.
8'and 4'
8'Panef Edges Panel Edges 4'Panel Edges
Ri
The unique edge profile is Maintain 1/8"space where Maintain 1/8'space
designed to,accommcdate 8'.panel edges meet 4' where 4'edges meet.
incremental panel panel edges.Unique edge Uni-que.edge profile is on
expansion and does not profile does not provide '8'edges only.'
require manual gapping the full 1/8"recommended
along the 8'edges.' space in this situation.'
Step 2.Fasten the panels to the framing members with code,approved
fasteners.,Space fasteners 6"o.c.along supported edges and 12"
o.c.at intermediate supports,unless otherwise specified by local
code or the designer of record.It is the responsibility of the general-
contractor to verify proper fastener type and spacing prior to
installation.Apply the fasteners 3/8"from the ends and corners.
An ideal installation would be where fastener heads are flush with
the panel surface. However, due to variations in materials and
limitations on equipment,this may be difficult to achieve in some.
situations. It.is not required to tape ,over overdriven fasteners
unless the fastener head creates a hole through the entire panel.
thickness. Please see the technical tip'"Overdriven Fasteners in
Zip System Roof and Wall Sheathing," on zipsystem.com for "
more information.
07
ZIP System'Tape Installation -Wall Panel Seams
Apply ZIP System tape after all ZIP System Roof&Will sheathing panels are fully fastened to wall-framing members.Only ZIP System tape should be used
to seal the seams of ZIP'System panels. Ensure that the panel surface is dry and free of sawdust and dirt prior to taping.ZIP,System tape is a contact
tape that requires pressure foe an adequate seal..
Step 1. Tape all seams using ZIP System tape. Ensure that the tape-
is centered over the seam within +/- 112" to provide'adequate
coverage and that wrinkles in tape are minimal.
Use the ZIP System tape gun or roller to apply pressure.to the tape
and smooth out any wrinkles.
Step 2. Wherever tape splices occur at a horizontal or vertical seam,create
an overlapping.splice of at least'3".
At T-joints,the tape pieces should overlap by at least 1".Apply,
moderate pressure onto the•surface of the tape to ensure a secure
bond between the panel and the tape.
Use the ZIP System tape gun or roller to apply pressure to the.tape
and smooth out any wrinkles.
Take special care to remove any voids and/or trapped air at splice
areas and T-joints. „
Step 3. Tape inside and outside comer"seams.
N
Iru de comer seam
QVOutside comer seam
Note:Tape over any areas of the panel or tape that are damaged during construction.
ZIP System"Roof&Wall Sheathing Install ti- Manual --�
08
ZIP System - Window Installation DISCLAIMER:The following steps represent a general overview for the proper installatfonof window flashing.Please defer to%onsult
the installafion instructions of your window manufacturer as well as code requirements in your jurisdiction for full installation details.
Flanged Windows
1. Fasten the ZIP System sheathing \ 5. Cut a length of ZIP System tape or another
to the wood frame and install '� \ adhesive-backed flashing tape (must meet ICC-
ZIP System tape to all wall panel � .> \. ES Acceptance Criteria for Flashing Materials.
seams, as detailed,in sections . - r z
(AC148)) and apply to the header, ensuring that
02 and 03. the flashing overlaps the jamb (lashings.'
,l Once the tape is in place,use the tape gun or roller
to seal the flashing to the sheathing.
N, '
'DO NOT tape bottom flange.
2. ZIP System tape may be used as pan flashing if 6. From the interior,apply low-pressure polyurethane
installed in accordance with flanged window foam (for windows)between the rough opening '
installation details posted on zipsystem.com. and the window frame.(Caulk sealant compatible = ,
Other adhesive-based flashing tapes(must meet with the sill flashing may be used at the sill if the
I ICC-ES Acceptance Criteria for Flashing Materials opening between the sill flashing and window
(AC148))maybe used as pan flashing if installed is too narrow to allow the use of low-pressure
per ASTM 2112-07.Apply the flashing to cover polyurethane foam.)
the bottom of the opening, overhanging onto the
When using ZIP System tape, butyl, 100%
sheathing by at least 2"and extending a minimum
silicone or sealants are acceptable.
of 6"up each jamb. � polyurethane p
Do not use latex sealants with ZIP System tape.If
using another flashing tape, follow the flashing
manufacturer's recommendation in selecting a
sealant compatible with that flashing.
3. Apply sealant around inside face of mounting �
Brick Mould Windows
flange. Sealant must be gapped at the sill
to permit drainage. Install and level window per \ 1. Fasten the ZIP System sheathing
manufacturer's installation instructions. Verify 's to the wood frame and install
sealant compatibility with window manufacturer.
pa riY ip�;� ZIP System tape to all wall panel
When usingZIPS stem toe as an flashing, `
Y P P 9 �.� seams, as detailed in sections
butyl, 100% silicone or polyurethane sealants 02.and 03.
are acceptable.Do not use latex or other water-
based sealants.
� r
4. Out two pieces of ZIP System tape or another 2. If recommended by the window
adhesive-backed flashing tape (must meet ICC- `• manufacturer,cut a strip of wood
ES Acceptance Criteria for Flashing Materials ' \ to function as a back dam at the
(AC148))and apply to each of the window jamb sill. The wood strip should have
flanges, ensuring the jamb flashings overlap the a length equal to the width of the
sill flashing. \ rough opening and a height and
width of at least 1/2".Position the
Once the tape is in place,use the tape gun or roller block at the inside edge of the
to seal the flashing to the sheathing. window frame.
09
ZIPS stem - Window Installation DISCLAIMER:The following steps represent a general overview for the proper installation of window flashing.Please defer to/consult
Y the installation instructions of your window manufaclurer as well as code requirements in your jurisdiction for full installation details.
Brick Mould Windows(continued)
3. ZIP System tape may be used as pan flashing if 7. Cut a piece of rigid head flashing so that when
installed in accordance with brick mould window installed,it is flush with the edges of the exterior
installation details posted on zipsystem.com. � moulding of the window.Apply a bead of sealant
Other adhesive-based flashing tapes(must meet to the back and bottom surface of the rigid
ICC-ES Acceptance Criteria for Flashing Materials head flashing.Use sealant recommended by the
(AC148))may be used as pan flashing if installed flashing manufacturer.
per ASTM 2112-07.Apply the flashing to cover s
the bottom of the opening,overhanging onto the
sheathing by at least 2"and extending a minimum
of 6"up each jamb.
8. Secure the rigid head flashing to ZIP System
wall sheathing.
i
4. For vertical jambs,cut ZIP System tape or another i
adhesive-backed flashing tape (must meet ICC-
ES Acceptance Criteria for Flashing Materials
(AC148)) and apply to each of the window jambs.
Ensure that they cover the entire inside of the rough
opening as well as overlap onto the sheathing by g. Cut a length of ZIP System tape or another
at least 2". Flashing shall also extend above the \`
adhesive-backed flashing tape(must meet[CC-ES
rough opening,such that it will project 1" beyond Acceptance Criteria for Flashing Materials(AC148))
the exterior trim of the window. and apply to the rigid head flashing, ensuring
Once the tape is in place,use the tape gun or roller that the adhesive-backed flashing overlaps the
to seal the flashing to the sheathing. jamb(lashings.
Once the tape is in place,use the tape gun or roller
to seal the flashing to the sheathing.
5. Apply sealant to jambs and header allowing for
drainage at the sill in accordance with window
manufacturer's installation instructions. When 1 D.From the interior, apply low-pressure polyurethane
using ZIP System tape,use a butyl,polyurethane foam(for windows)between the rough opening and
or 100% silicone sealant. Do not use latex or the window frame. (Caulk sealant compatible with
other water-based sealants with ZIP System the sill flashing may be used at the sill if the opening
tape.When using another flashing tape,follow the between the sill flashing and window is too narrow
flashing manufac-turer's recommendations in to allow the use of low-pressure polyurethane foam.)
selecting a sealant compatible with that flashing.
When using ZIP System tape,butyl,100%silicone
• or polyurethane sealants are acceptable. Do not
use latex or other water-based sealants with ZIP
System tape. If using another flashing tape, follow
the flashing manufacturer's recommendation in
6. Install and level window per manufacturer's selecting a sealant compatible with that flashing.
,installation instructions. � � •
ZIP System"Roof&Wall Sheathing Instanarl—nrt Manual
.. � ram✓) �J -
10
ZIP System Penetration-Openings DISCLAIMER:The following steps represent a general overview for the proper installation of penetration flashing.Please defer to/consul
your code requirements in your jurisdiction for full installation details.
WALLA EMBLY
ZIP SYST,&W WALL SHEATHNG
„ �•� _ W(k.O DH Lf.GA METAL STUCS
2
WALL ASSEMSLY � _ 718-CHGAPRECCMMENDED AT
ZIP SYSTEMA'n'AIt SHEAVING `'^ PANEL EDGES
Waco CA LT.GAMETAL STLDS :IR O FIWI!SE PRCVTJEO 3Y - �' -
MACHNEO PRCFZEO EDGES
I,?-W 1GNRECCWJE\DEO AT
PANEL EDGESUNLEW ZPSYST—L—A--INSTALLED
OTHERWtSEPRCVIOM BY S �. OVER ALL JCIITS IN ZIP SYSTEMA - '
rM
MACHINED FROFILEG ECGES -�, WALL SHEATHNG} )�. �,� - �,
ZP SYSTE`M TAPE INSTALLED GVEiLAP TAPE A MINIMUM OF Avg
A OVER ALL JCLN s114 ZP SYSiE.YD I :: .1-INCH AT ALL TJCINTS
WALL SREArING), r "'
WSTALL Z:P SY„'�TAPE AT ALL
mSRLA,TAPEA MNIALMCF EVERICRCCR.NERS ,i�v:M'a. '--�• :'�Y,--~✓:
14KCH M AIL TJOINIS
• INSTALL ZIP SYSTEMDTAY_AT ALI - FASTEN Z'P SYSTEV.flWA.i ,�'+•
INTFJiICR CCRl_FIS SHEATHNG AS REOUIREC BY 9 _
OESIO CF-RECCRO OR LOCAL
SL9 NG CGOE
FASTENZPASREMD EOS
S SICT WGASRECCOCRL
DESIGNERCF.iECCRO CR lIXX
BUILDWG CCCE '
WALLASSEMBLY WALL ASSEMBLY
ZIP SYSTEM®WALL SHEATHING -ZIP SrSTEN WALL SHEATHING
WOOD OR LT,GA.METAL STUDS - WOOD OP.LT.GA.METAL STUDS
,
118-INCH GAP RECOMMENDED AT 1184NCH GAP RECOMMENDED AT
PANEL EDGES UNLESS PANEL EDGES UNLESS -
OTHER'AnSE PROVIDED BY .>, OTHERWISE PROVIDED BY
MACHINED PROFILED EDGES (,•.\ MACHINED PROFILED EDGES - f.-"•,'�:;f'%j�,,
INSTALLZIP SYSTEMAJTAPEOR �1��1 INSTALL ZIP SYSTEIJ,®TAPE OR
BACKED FLASHING(MUST `+3>:
ADHESIVE B . .Z:'•a � .'ADHESIVE BACKED FLASHING(MUST•'++,'•r;y'
MEETAC148)IN SEQUENCE FROM MEET AC148)IN SEQUENCE FROM •,;y!, f:2
BOTTOM,SIDES,THEN TOP TO i BOTTOM,SIDES,THEN TOP TO-
ENSURE SHINGLE LAP OFADHES ENSURE SHINGLE LAP OF ADHESIVE
BACKED FLASHING •;'r;.:~.:> ••
:��.... BACKED FLASHING
ZIP SYSTEMSTAPE(INSTALLED ;•.✓+.-:- �< ZIP SYSTEMS TAPE(INSTALLED
OVER ALL JOINTS IN ZIP SYSTEMS �'�r+ >: OVER ALL JOINTS IN ZIP SYSTEMO
WALL SHEATH ) WALL SHEATHING)
ING. ^-.�;:"'::
.
OVERLAP TAPE A MINIMUM OF OVERLAP TAPE A MINIMUM OF
1•MCHAT ALL T-JOINTS 1-INCH AT ALL T-JOINTS f f
„
USE FLANGED VENT HOODS "
USE FLANGED ELECTRICAL
BOXES OR MEMBRANE FLASHING
TO PROVIDE FLANGES FOR
ELECTRICAL BOXES ,
`�•/ 11
ZIP System Sheathing Installation Details on Walls —visit zipsystem.com for more details.
WALL ASSEMBLY WALL ASSEMBLY -1-T
VINYL/WOOD/FIBER.CEMENT SIDING T
(INSTALLED IN ACCORDANCE WITH F11- BRICK VENEER
CLADDING MANUFACTURER'S AIR SPACE(AS PRESCRIBED BY `\
LOL BUILDING CODE)
INSTALLATION RECOMMENDATIONS) ZIP SYSTEM WALL SHEATHING \
ZIP SYSTEM®WALL SHEATHING WOOD OR LT,GA.METAL STUDS
WOOD OR LT.GA.METAL STUDS
TOP EDGE OF FLASHING TAPED TO TOP EDGE OF FLASHING TAPED 77`
WALL SHEATHING WITH ZIP SYSTEM® WITH ZIP SYSTEMt TAPE OR
TAPE OR ADHESIVE BACKED ADHESIVE BACKED FLASHING. \�
FLASHING.(MUST MEET AC148) (MUST MEET AC148) �,\
CODE APPROVED FLASHING�I
CODE APPROVED BASE '`N`�
FLASHING �
, '" WEEP HOLES(AS PRESCRIBED
FOUNDATION BY LOCAL BUILDING CODE) "� �i //•
WALL ASSEMBLY
WALL ASSEMBLY BRICK VENEER
VNY L ViocDIFIBER CEMENT SMING AIR SPACE(AS PRESCRIBED BY
(INSTALLED IN ACCORDANCE WITH LOCAL BUILDING CODE)
CLADDING MANUFACTURERS ZIP SYSTEM&WALL SHEATHING
INSTALLATION RECOMMENDATIONS) WOOD OR LT.GA.METAL STUDS
ZIP SYSTEM©WALL SHEATHING
WOOD OR LT.GA.METAL STUDS
118-INCH GAP RECOMMENCED AT
L& CH GAP RECOMMENCED AT .0 / PANEL EDGES UNLESS IN .I
PANEL EDGES UNLESS OTHERWSE PROVIDED BY '
OTHERARSE ��,, MACHINED PROFILED EDGES \ \
MACHINED PROFILED EDGES \ r�r
TAP SYSTEM®TAPE(INSTALLED \\ �( .."� ZIP SYSTEM1)TAPE(1SISTALLED
OVER ALL JOINTS IN ZIP SYSTEMS - `•" OVER ALL JOINTS IN ZIP SYSTEM& J� �I �'\ •... �Sa
WALL SHEATHING).
WALL SMEATHINGL I \ ` I`�'^: \
\\�✓ ,, .ri
OVERLAP TAPE A MINIMUM OF •� I� 11
OVERLAP TAPEA MINIMUM OF ��\ 1�
14NCH AT ALL T.IOWTS 1-INCH AT ALL T-JOINTS I \
iM NCM GAP RECOMMENDED AT \ \�I
PANEL EDGES UNLESS PANEL EDGES
UNLESS
AT �J
OTHERWISE PROVIDED BY I PANEL EDGES UNLESS
MACHINED PROFILED EDGES \+ OTHERWISE PROVIDED G \ �.f
MACHINED PROFLED EDGES
FASTEN ZIP SYSTEM&WALL
SHEATHING AS REQUIRED BY FASTEN ZIP SYSTEMS WALL
DESIGNER-CF-RECORD OR LOCAL SHEATHING AS REQUIRED BY
BUXDING CODE DESIGNER-CF•RECORD OR LOCAL
BUILDING CODE
Note:For optimal air leakage reduction,all untaped edges of the panels can be caulked,gasketed or sealed with a weather stripping material.
-ZIP System'Roof&Wall Sheathing Installation Manual
12
ZIP System Sheathing Installation Details on Walls (continued)
WALL BEYOND
i
WALL ASSEMBLY BACKDAM PER WINDOW
BRICK VENEER MANUFACTURER'S INSTALLATION
AIR SPACE(AS PRESCRIBED BY RECOMMENDATIONS.
LOCAL BUILDING CODE)
ZIP SYSTEM®WALL SHEATHING INSTALL CODE-RECOGNIZED
WOOD OR LT.GA.METAL STUDS '
SILL/PAN FLASHING IN ROUGH
OPENING PRIOR TO WINDOW
INSTALLATION.
TOP EDGE OF FLASHING TAPED
WITH ZIP SYSTEM®TAPE OR `•�,� ,
ADHESIVE BACKED FLASHING. �
TOP EDGE OF FLASHING TAPED
(MUST MEET AC148) .\ WITH ZIP SYSTEM®TAPE OR 13
ADHESIVE BACKED FLASHING.
(MUST MEET AC148)
CODE APPROVED FLASHING
WEEPS(AS PRESCRIBED BY
WEEPS(AS PRESCRIBED BY �� LOCAL BUILDING CODE) �\ `
LOCAL BUILDING CODE)
STEEL LINTEL CODE APPROVED FLASHING
INSTALL WINDOW IN WALL ASSEMBLY
ACCORDANCE WITH DETAILS BRICK VENEER
24A-24D OR 25A-25D AIR SPACE(AS PRESCRIBED BY
LOCAL BUILDING CODE)
ZIP SYSTEM®WALL SHEATHING
WALL BEYOND i WOOD OR LT.GA.METAL STUDS
WALL ASSEMBLY
CODE APPROVED CLADDING
(INSTALLED IN ACCORDANCE WITH
CLADDING MANUFACTURER'S
INSTALLATION RECOMMENDATIONS)
EXTERIOR RIGID INSULATION
DRAINAGE PLANE(101N.Y8")
ZIP SYSTEM@ WALL SHEATHING
WOOD OR LT.GA.METAL STUDS
TOP EDGE OF FLASHING TAPED TO
WALL SHEATHING WITH ZIP SYSTEM®
TAPE OR ADHESIVE BACKED
FLASHING. (MUST MEET AC148)
CODE APPROVED FLASHING
,.
FOUNDATION
Note:For optimal air leakage reduction,all'untaped edges of the panels can be caulked,gasketed or sealed with a weather stripping material.