HomeMy WebLinkAboutProduct Approval (3) NEMO I etc. Certificate of Authorization#32455 353 Christian Street,Unit#13 Oxford,CT 06478 (203)262-9245 ENGINEER EVALUATE TEST CONSULT EVALUATIONREP00 TAMKO Building Products, LLC Evaluation Report 3m-TAM-20-FBCER.A-RO PO Box 97 FL12328-119 Galena, KS 66739 Date of Issuance:09/29/2020 (417)624-6644 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for compliance with the 7eh Edition(2020)Florida Building Code sections noted herein. DESCRIPTION: TAMKO Roof Underlayments LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein and FBC 1507.1.1. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change. Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEW ETC, LLC of any changes to the product(s), the Quality Assurance or the production.facility location(s). NEMO ETC, LLC requires a complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded 'by the words "NEMOletc. Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 5. Prepared by: _ •h L Robert JI.M.•Nieminen -P.E. '- rs:.op`+v.` � '.�•;n, T, " The facsimile seal appearing was authorized by Robert Fonda Registration No.59166 Florida DC4ANE1983 s'••�-•• c.•,.�` ' Nfeminen,P.E.on 09/29/2020.This does not serve as an '••••+++++`" electronically signed document. Y sl g CERTIFICATION OF INDEPENDENCE: 1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire,a financial interest in any company manufacturing or distributing products it evaluates. 2.- NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. 'Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nfeminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof,is/was used for permitting or design guidance unless retained specifically for that purpose. ©2019,MEMO ETC,LLC UN DEMO etc. ROOFING COMPONENT EVALUATION 1. •• Product Category: Roofing Sub-Category: Underlayment Compliance Statement: TAMKO Roof Underlayments, as produced by TAMKO Building Products LLC, have demonstrated compliance with the following sections of the 7"Edition(2020)Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /Conditions of Use set forth herein. 2. + •D Section Property Standard Year 1507.1.1/R905.1.1 Material standard ASTM D226 2009 1507.1.1,1507.2.4,1507.2.9.2/ Material standard ASTM D1970 2015 R905.1.1,R905.2.8.2 1507.2.9.2,1507.6.5/R905.2.8.2, Material standard ASTM D6380 2013 R905.5.4 Ent(ty Examination Reference Date PRI(TST5878) ASTM D1970 TAP-388-02-01 10/04/2017 PRI(TST5878) ASTM D226,Type II TAP-420-02-01 04/19/2018 PRI(TST5878) ASTM D1970 TAP-447-02-01 10/19/2018 PRI(TST5878) ASTM D6380 847T0009 12/21/2019 PRI(TST5878) ASTM D6380 847T00010 12/21/2019 PRI(TST5878) ASTM D226,Type II . TAP-351-02-01 04/25/2016 PRI(TST5878) ASTM D226,Type II TAP-351-02-02 05/04/2016 UL LLC(TST9628) ASTM D226,Type II 13CA12269 03/14/2014 UL LLC(QUA9625) Quality Assurance Service Confirmation 10/20/2020 UL LLC(QUA9625) Quality Assurance Florida BCIS Current 14. •a s Product Material Standard Plant(s) Description 4.1 No.30 UL ASTM D226,Type II Joplin,MO Asphalt-saturated organic felt Green Cove Springs,FL 4.2 No.30 ASTM ASTM D226,Type II Phillipsburg,KS. Asphalt-saturated organic felt 4.3 TAM-FELT® ASTM D226,Type II Green Cove Springs,FL Asphalt-saturated organic felt Moisture Guard® ASTM D1970 Joplin,MO Self-adhering,fiberglass reinforced SBS modified bitumen roof underlayment with a mineral top surface. 4. TW Underlayment ASTM D19701 Columbus,KS Self-adhering,SBS modified bitumen roof underlayment with a polymer-film top surface. 4.6 TW Seam Tape ASTM D1970 Columbus,KS Self-adhering,SBS modified bitumen deck seam-tape with a polymer-film top surface. 4.7 ASTM Slate Surfaced Roll ASTM D6380, Green Cave Springs,FL Asphalt-saturated organic mat,coated on Roofing Class M,Type II both sides with asphalt and surfaced with granules. 1 Agreement between purchaser and seller,as set forth in Section 4.3,Note 1 of ASTM D1970-15,should be established as to slip resistance of TW Underlayment. NEMO ETC,LLC Evaluation Report 3m-TAM-20413CER.A-110 Certificate of Authorization#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 2 of 5 NEW etc. Product Material Standard Plant(s) Description 4.8 ASTM Tile Underlayment ASTM D6380, Green Cove Springs,FL Asphalt-saturated organic felt,coated on Class M,Type II both sides with asphalt and surfaced with granules. 5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions(i.e.,Broward and Miami-Dade Counties). 5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural.members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 for requirements and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations concerning the use of foam plastic insulation. 5.5 TAMKO Roof Underlayments may be used with any prepared roofcoverwhere the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.6 Allowable Roof Covers: TABLE 1:,ROOF COVER OPTIONS Asphalt Clay and Concrete Tile Metal Slate or Wood Underlayment Shingles (1507.3) Slate-Type (1507.2)' Mechanical Adhesive- Panels Shingles Shingles Shingles Shakes "Attach Set (1507.4) (1507.5) (1507.7) (1507.8) (1507.9) No.30 UL Yes Yes Yes Yes Yes Yes Yes Yes 'See 5.6.1 See 5.6.1 No.30 ASTM Yes Yes Yes Yes Yes Yes Yes Yes See 5.6.1 See 5.6.1 TAM-FELT® Yes No No Yes Yes Yes Yes Yes Yes Yes Moisture Guard® Yes No No No No Yes Goint strips, Qolntstrips, 1507.1.1.3/ 1507.1.1.3/ R905.1.1.3) R905.1.1.3) Yes Yes TW Underlayment Yes No No Yes Yes Yes Qolntstrips, Qolntstrips, 1507.1.1.3/ 1507.1.1.3/ R905.1.13) R905.1.1.3) Yes ' Yes Yes Yes . 'Yes Yes TW Seam Tape Qolntstrips, No No Qolntstrips, Point strips, Qolntstrips, Qolntstrips, Goint strips, 1507.1.1.1/ 1507AAA/ 1507.1.1.1/ 1507.1.1.1/ 1507.1.1.3/ 1507.1.1.3/ R905.1.1.1) R905.1.1.1). R905.1.1.1) •R905.1.1.1) R905.1.1.3) R905.1.1.3) ASTM Slate Surfaced Roll Yes Yes Roofing (Valley Liner) (cap Sheet In 2- NO No NO NO No No ply system) Yes ASTM Tile Underlayment Yes (Cap 3heetInz- No No No No No No • _, (Valley Liner) ply system) ' NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-RO Certificate of Authorization#32455 7TM EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-119 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 3 of 5 J UN MEMO I etc. 5.6.1 No. 30 UL or No. 30 ASTM may be used as a mechanically attached anchor sheet followed by an asphalt-applied ASTM Slate Surfaced Roll Roofing or ASTM Tile Underlayment. 5.7 Allowable Substrates: TABLE 2: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS Underlayment Application Primer Substrates Moisture Guard®or TW Underlayment self-adhering (Optional)ASTM D41 plywood None No.30 UL,No.30 ASTM or TAM-FELT® TW Seam Tape self-adhering (Optional)ASTM D41 plywood ASTM Slate Surfaced Roll Roofing or ASTM Tile Underlayment hot asphalt None No.30 UL,No.30 ASTM or TAM-FELT® 5.8 Attachment Limitations: 5.8.1 For use under mechanically attached NON-TILE prepared roof coverings,attachment shall be in accordance with the manufacturer's installation instructions, but—for mechanically attached underlayments or base sheets - not less than FBC 1507.1.1 or R905.1.1. 5.8.2 For use under tile roof systems,attachment shall be in accordance with the manufacturer's installation instructions, but—for mechanically attached base sheets-not less than: • FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,Appendix A,Table 1(for Two-Ply Asphalt Applied Hot Mop Underlayment) 5.9 Exposure Limitations: TABLE 3: EXPOSURE LIMITATIONS Underlayment Prepared Roof Cover Maximum Exposure(days)* Installation Type No.30 UL,No.30 ASTM,TAM-FELT® Moisture Guard®,TW Underlayment,TW Seam Tape Any 30 ASTM Slate Surfaced Roll Roofing,ASTM Tile Underlayment *Maximum exposure shall not exceed the manufacturer's recommendations,which may be less than 30 days. 5.10 Tile Slippage Limitations: When loading roof tiles on the underlayment in direct-deck tile roof assemblies,the tile shall be staged atop battens during loading of the roof tiles. 16. INSTALLATION' 6.1 TAMKO Roof Underlayments shall be installed in accordance with TAMKO Building Products LLC installation instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application,and prime the substrate (if applicable). 6.3 No.30 UL,No.30 ASTM: 6.3.1 Non-Tile Applications: Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D226,Type 11)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-R0 Certificate of Authorization#32455 7m EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9 TAMKO Roof Underlayrnents Revision 0:09/29/2020 Page 4 of 5 e NNEMOjetc. 6.3.2 Tile Applications: No.30 UL or No.30 ASTM are limited to use as a mechanically attached base sheet in the"TWO-PLY SYSTEM"from FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,followed by ASTM Slate Surfaced Roll Roofing, ASTM Tile Underlayment applied in hot asphalt,or other FBC Approved hot-asphalt applied cap sheet. Refer to FRSA/TRI,Sixth Edition,Appendix A,Table 1 for attachment requirements. 6.4 TAM-FELT°: " 6.4.1 Non-Tile Applications: Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D226,Type II)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6.5 Moisture Guar&,.:TW Underlayment:" 6.5.1 Shall be installed in compliance with requirements for an approved self-adhering underlayment (ASTM D1970) in FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof covering to be installed,and the manufacturer's installation instructions. When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in accordance with FBC 1507.1.1 or R905.1.1. 6.6 ASTM'Slate'Surfaced Roll°Roofing,ASTM Tile Underlayment: 6.6.1 Tile Applications: ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are limited to use as the Hot Asphalt applied "Cap Sheet"in the"TWO-PLY SYSTEM"from FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition. Refer to Section 5.8.2 for attachment limitations. Refer to Section 5.10 for tile staging limitations. 6.6.2 Valley Liner: ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are acceptable for use as a valley liner in accordance with FBC 1507.2.9.2 or FBC Residential R905.2.8.2. Installation shall be in accordance with the manufacturer's instructions before applying shingles. BUILDINGIPERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. MANUFACTURING PLANTS' Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer to Section 4 herein for products and production locations having met codified material standards. 9. 'QUALITY AssURANCE ENTITY' UL LLC—QUA9625;(414)248-6409; Karen.buchmann@ul.com -END OF EVALUATION REPORT- NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-R0 Certificate of Authorization#32455 7'H EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 5 of 5 I i • NEMO I etc, Certificate of Authorization#32455 353 Christian Street,Unit#13 Oxford,CT.06478 (203)262-9245 ENGINEER EVALUATE TEST CONSULT 'EVALUAT1 ON REPORT TAMKO Building Products,.LLC Evaluation Report 3m-TAM-20-FBCER.A-RO PO Box 97 FL12328-119 Galena, KS 66739 Date of Issuance:09/29/2020 (417)624-6644 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for compliance with the 7eh Edition(2020)Florida Building Code sections noted herein, DESCRIPTION: TAMKO Roof Underlayments LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted herein and FBC 1507.1.1. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s)changes,the referenced Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change. Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEW ETC, LLC of any changes to the product(s), the Quality.Assurance or the production facility location(s). NEW ETC, LLC requires a complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by.the words "NEMOl etc: Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 5. Prepared by: _ Robert J.M.Nieminen,P.E. '• .. i pi+: The facsimile seal appearing was authorized by Robert Florida Registration No.59166 FloridaDCAANE1983 ' '' 7,Ski•;• g,•,r Nieminen,P.E.on 09/29/2020.This does not serve as an ��'•��ml"' electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. NEW ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. NEMO ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E.does not have nor will acquire,a financial interest in any company manufacturing or distributing products for which the.evaluation reports are being issued. 4. Robert Nieminen, P.E.does not have, nor will acquire,a financial interest in any other entity involved in the approval process of the product. S. This is a building code evaluation. Neither NEW ETC,LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 9)2019,NEMO ETC,LLC NNEMO I etc. ROOFING COMPONENT EVALUATION e• Product Category: Roofing Sub-Category: Underlayment Compliance Statement: TAMKO Roof Underlayments, as produced by TAMKO Building Products LLC, have demonstrated compliance with the following sections of the 7th Edition(2020)Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations /Conditions of Use set forth herein. 12. eA•. Section Property Standard Year 1507.1.1/R905.1A Material standard ASTM D226 2009 1507.1.1,1507.2.4,1507.2.9.2/ Material standard ASTM D1970 2015 R905.1.1,R905.2.8.2 1507.2.9.2,1507.6.5/R905.2.8.2, Material standard ASTM D6380 2013 R905.5.4 Entity Examination Reference Date PRI(TST5878) ASTM D1970 TAP-388-02-01 10/04/2017 PRI(TST5878) ASTM D226,Type II TAP-420-02-01 04/19/2018 PRI(TST5878) ASTM D1970 TAP-447-02-01 10/19/2018 PRI(TST5878) ASTM D6380 847T0009 12/21/2019 PRI(TST5878) ASTM D6380 947T00010 12/21/2019 PRI(TST5878) ASTM D226,Type II TAP-351-02-01 04/25/2016 PRI(TST5878) ASTM D226,Type II TAP-351-02-02 05/04/2016 UL LLC(TST9628) ASTM D226,Type II 13CA12269 03/14/2014 UL LLC(QUA9625) Quality Assurance Service Confirmation 10/20/2020 UL LLC(QUA9625) Quality Assurance Florida BCIS Current • ••® s • Product Material Standard Plant(s) Description 4.1 No.30 UL ASTM D226,Type II Joplin,MO Asphalt-saturated organic felt Green Cove Springs,FL 4.2 No.30 ASTM ASTM D226,Type II Phillipsburg,KS Asphalt-saturated organic felt 4.3 TAM-FELT® ASTM D226,Type II Green Cove Springs,FL Asphalt-saturated organic felt .4 Moisture Guard® ASTM D1970 Joplin,MO Self-adhering,fiberglass reinforced SBS modified bitumen roof underlayment with a mineral top surface. 4.5 TW Underlayment ASTM D19701 Columbus,KS Self-adhering,SBS modified bitumen roof underlayment with a polymer-film top surface. 4.6 TW Seam Tape ASTM D1970 Columbus,KS Self-adhering,SBS modified bitumen deck seam-tape with a polymer-film top surface. 4.7 ASTM Slate Surfaced Roll ASTM D6380, Green Cove Springs,FL Asphalt-saturated organic mat,coated on Roofing Class M,Type II both sides with asphalt and surfaced with granules. 1 Agreement between purchaser and seller,as set forth in Section 4.3,Note 1 of ASTM D1970-15,should be established as to slip resistance of TW Underlayment. NEMO ETC,LLC Evaluation Report 3m-TAM-20413CER.A-110 Certificate ofAuthorization#32455 7'"EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-119 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 2 of 5 r *NEMO I etc. Product Material Standard Plant(s) Description 4.8 ASTM Tile Underlayment ASTM D6380, Green'Cove Springs,FL ''Asphalt-saturated organic felt,coated on Class M,Type II both sides with asphalt and surfaced with granules. LIMITATIONS: 5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen,P.E.are,in anyway,the Designer of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for.that purpose. 5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions(i.e.,Broward and Miami-Dade Counties). 5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 for requirements and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements. and limitations concerning the use of foam plastic insulation. 5.5 TAMKO Roof Underlayments may be used with any prepared roof coverwhere the product is specifically referenced within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. 5.6 Allowable Roof Covers: TABLE 1:•ROOF COVER OPTIONS Clay and Concrete Tile Slate or Asphalt 1507 ),3 Metal Wood Underlayment Shingles ( Slate-Type ( in7.2) Mechanical Adhesive- Panels Shingles Shingles Shingles Shakes Attach Set (1507.4) (1507.5) (1507.7) (1507.8) (1507.9) No.30 UL Yes Yes Yes Yes Yes Yes Yes Yes 'See 5.6.1 See 5.6.1 No.30 ASTM Yes Yes Yes Yes Yes Yes Yes Yes See 5.6.1 See 5.6.1 TAM-FELT® Yes No No Yes Yes Yes Yes Yes Yes Yes Moisture Guard® Yes No No, No olni Yes strips, i oint t�aisozil % so7.11 % R905.1.1.3) R905.1.1.3) Yes Yes TW Underlayment Yes No No Yes. Yes. Yes Uointstrips, Qolntstrips, _ 1507.1.1.3/ 1507.1.1.3/ R905.1:1.3) R905.1.1.3) Yes Yes Yes Yes Yes Yes TW Seam Tape. (lointstrips, No No Uolntstrips, Qolntstrips, Qointstrips, Uointstrips, (Joint strips, 1507:1.1.1/ 1507.1.1.1/ 1507.1.1.1/ 1507.1.1.1/ 1507.1.1.3/ 1507.1.1.3/ R905.1.1.1) . R905.1.1.1) R905.1.1.1) R905.1.1.1) R905.1.1.3) R905.1.1.3) ASTM Slate Surfaced Roll Yes Yes Roofing (Valley Liner) (Cap Sheet in 2- 'No No No No No No ply system) Yes Yes ASTM Tile Underlayment (Cap Sheet In2- No No No No No No (Valley Liner) ply system) NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-R0 Certificate of Authorizatfon#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 3 of 5 NMEMO 6 etc. 5.6.1 No. 30 UL or No. 30 ASTM may be used as a mechanically attached anchor sheet followed by an asphalt-applied ASTM Slate Surfaced Roll Roofing or ASTM Tile Underlayment. 5.7 Allowable Substrates: TABLE 2: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS Underlayment Application Primer Substrates Moisture Guard®or TW Underlayment self-adhering (Optional)ASTM D41 plywood None No.30 UL,No.3b ASTM or TAM-FELTO TW Seam Tape self-adhering (Optional)ASTM D41 plywood ASTM Slate Surfaced Roll Roofing or hot asphalt None No.30 UL,No.30 ASTM or TAM-FELT® ASTM Tile Underlayment 5.8 Attachment Limitations: 5.8.1 For use under mechanically attached NON-TILE prepared roof coverings,attachment shall be in accordance with the manufacturer's installation instructions, but—for mechanically attached underlayments or base sheets - not less than FBC 1507.1.1 or R905.1.1. 5.8.2 For use under the roof systems,attachment shall be in accordance with the manufacturer's installation instructions, but—for mechanically attached base sheets-not less than: • FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,Appendix A,Table 1(for Two-Ply Asphalt Applied Hot Mop Underlayment) 5.9 Exposure Limitations: TABLE 3: ExPOSURE LIMITATIONS Underlayment Prepared Roof Cover Maximum Exposure(days)* Installation Type No.30 UL,No.30 ASTM,TAM-FELT® Moisture Guard®,TW Underlayment,TW Seam Tape Any 30 ASTM Slate Surfaced Roll Roofing,ASTM Tile Underlayment "Maximum exposure shall not exceed the manufacturer's recommendations,which may be less than 30 days. 5.10 Tile Slippage Limitations: When loading roof tiles on the underlayment in direct-deck tile roof assemblies,the tile shall be staged atop battens during loading of the roof tiles. INSTALLATION- 6.1 TAMKO Roof Underlayments shall be installed in accordance with TAMKO Building Products LLC installation instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust and debris prior to application,and prime the substrate (if applicable). 6.3 No.30 UL,No.30 ASTM: 6.3.1 Non-Tile Applications: Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D226,Type II)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. NEMO ETC,LLC Evaluation Report 3m-TAM-20•FBCER.A-R0 Certificate of Authorisation#32455 7'H EDITION(2020)FBC NON-HVHZ EVALUATION F1.12328-119 TAMKO Roof Underlayments Revision 0:09/29/2020 Page 4 of 5 r iVEnno I etc. 6.3.2 Tile Applications: No.30 UL or No.30 ASTM are limited to use as a mechanically attached base sheet in the`TWO-PLY SYSTEM"from FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,followed by ASTM Slate Surfaced Roll Roofing,ASTM Tile Underlayment applied in hot asphalt, or other FBC Approved hot-asphalt applied cap sheet. Refer to FRSA/TRI,Sixth Edition,Appendix A,Table 1 for attachment requirements. „6.4 TAM-FELT®: .. 6.4.1 Non-Tile Applications: Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM D226,Type II)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the manufacturer's installation instructions. 6.5 Moisture Guard®,TW,U.nderlayment: 6.5.1 Shall be installed in compliance with requirements for an approved self-adhering underlayment(ASTM D1970) in FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof covering to be installed,and the manufacturer's installation instructions. When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in accordance with FBC 1507.1.1 or R905.1.1. 6.6.. ASTM Slate Surfaced Roll-Roofing,ASTM,T(le Underlayment: 6.6.1 Tile Applications: ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are limited to use as the Hot Asphalt applied "Cap Sheet'in the'TWO-PLY SYSTEM"from FRSA/TRI Florida High Wind Concrete and Clay Roof rile Installation Manual, Sixth Edition. Refer to Section 5.8.2 for attachment limitations. Refer to Section 5.10 for tile staging limitations. 6.6.2 Valley Liner: ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are acceptable for use as a valley liner in accordance with FBC 1507.2.9.2 or FBC Residential R905.2.8.2. Installation shall be in accordance with the manufacturer's instructions before applying shingles. As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. L�._MANUFACTURING PLANTS: Contact the named CIA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 CIA requirements. Refer to Section 4 herein for products and production locations having met codified material standards. -ITY ASSURANCE ENTITY: UL LLC—QUA9625;(414)248-6409; Karen.buchmann@ul.com -END OF EVALUATION REPORT- NEMO ETC,LLC Evaluation Report 3m-TAM-20-F8CER.A-R0 Certificate of Authorization H32455 7'"EDITION(2020)FBC NON-HVHZ EVALUATION F1.12328-119 TAIVIKO Roof Underlayments Revision 0:09/29/2020 Page 5 of 5