TAMKO Building Products, LLC Evaluation Report 3m-TAM-20-FBCER.A-R0
PO Box 97.. FL12328-R9
Galena, KS 66739 Date of Issuance:09/29/2020
(417)624-6644
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the.applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The products described herein have been evaluated for
compliance with the 71h Edition(2020)Florida Building Code sections noted herein.
DESCRIPTION: TAMKO Roof Underlayments
LABELING: Labeling shall be in accordance with the requirements of.the Accredited Quality Assurance Agency noted
herein and FBC 1507.1.1.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such.time as the named product(s)changes,the referenced
Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change.
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words "NEMOletc. Evaluated" may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5.
Prepared by:
Robert J.M.Nieminen P.E.
.ti. rr The facsimile seal appearing was authorized by Robert
Florida Registration No.59166 Florida DCA AIVE1983 S ":�.•�" Nleminen,P.E.on 09/29/2020.This does not serve as an
'd m n'" electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC.does not have, nor does it intend to acquire or will it acquire,a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEW ETC,LLC is not owned,operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire,a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued. . .
4. Robert Nieminen,P.E. does not have, nor will acquire,a financial interest in any other"entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC,LLC nor Robert Nieminen,P.E.are,in any way,the Designer of Record for any
project on which this Evaluation Report,or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
02019,NEMO ETC,LLC
F
I1
ONEMOJetc.
ROOFING COMPONENT EVALUATION
1. s•
Product Category: Roofing
Sub-Category: Underlayment
Compliance Statement: TAMKO Roof Underlayments, as produced by TAMKO Building Products LLC, have
demonstrated compliance with the following sections of the 7th Edition(2020)Florida Building Code through testing
in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations
/Conditions of Use set forth herein.
2. STANDARDS'
Section Property Standard Year
1507.1.1/R905.1.1 Material standard ASTM D226 2009
1507.1.11 1507.2.4,1507.2.9.2/ Material standard ASTM D1970 2015
R905.1.1,R905.2.8.2
1507.2.9.2,1507.6.5/R905.2.8.2, Material standard ASTM D6380 2013
R905.5.4
Entity Examination Reference Date
PRI(TST5878) ASTM D1970 TAP-388-02-01 10/04/2017
PRI(TST5878) ASTM D226,Type II TAP420-02-01 04/19/2018
PRI(TST5878) ASTM D1970 TAP-447-02-01 10/19/2018
PRI(TST5878) ASTM D6380 847T0009 12/21/2019
PRI(TST5878) ASTM D6380 847T00010 12/21/2019
PRI(TST5878) ASTM D226,Type II TAP-351-02-01 04/25/2016
PRI(TST5878) ASTM D226,Type II TAP-351-02-02 05/04/2016
UL LLC(TST9628) ASTM D226,Type 11 13CA12269 03/14/2014
UL LLC(QUA9625) Quality Assurance Service Confirmation 10/20/2020
UL LLC(QUA9625) Quality Assurance Florida BCIS Current
4 PRODUCT-IJESCRIPTIOW
Product Material Standard Plant(s) Description
4.1 No.30 UL ASTM D226,Type II Joplin,MO Asphalt-saturated organic felt
Green Cove Springs,FL
4.2 No.30 ASTM ASTM D226,Type 11 Phillipsburg,KS Asphalt-saturated organic felt
4.3 TAM-FELT® ASTM D226,Type 11 Green Cove Springs,FL Asphalt-saturated organic felt
4.4 Moisture Guardm ASTM D1970 Joplin,MO Self-adhering,fiberglass reinforced SBS
modified bitumen roof underlayment with a
mineral top surface.
4.5 TW Underlayment ASTM D19701 Columbus,KS Self-adhering,SIBS modified bitumen roof
underlayment with a polymer-film top
surface.
4.6 TW Seam Tape ASTM D1970 Columbus,KS Self-adhering,SIBS modified bitumen deck
seam-tape with a polymer-film top surface.
4.7 ASTM Slate Surfaced Roll ASTM D6380, Green Cove Springs,FL Asphalt-saturated organic mat,coated on
Roofing Class M,Type II both sides with asphalt and surfaced with
granules.
1 Agreement between purchaser and seller,as set forth in Section 4.3,!Vote 1 of ASTM D1970-15,should be established as to slip resistance of TW
Underlayment.
NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-R0
Certificate of Authorization#32455 7'"EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9
TAMKO Roof Underlayments Revision 0:09/29/2020
Page 2 of 5
s
is
NNEMOletc.
Product 'Material Standard Plant(s) Description
4.8 ASTM Tile Underlayment ASTM D6380, Green Cove Springs,FL Asphalt-saturated organic felt,coated on
Class M,Type II both sides with asphalt and surfaced with
granules.
1--S. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen,P.E.are,in any way,the Designer
of Record for any project on which this Evaluation Report,or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for,that purpose.
5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions(i.e.,Broward and Miami-Dade
Counties).
5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.4 This.Evaluation Report does not include evaluation of fire classification..Refer to FBC 1505 for requirements and
limitations regarding roof assembly fire classification. Refer to FBC 2603-for requirements and limitations
concerning the use of foam plastic insulation.
5.5 TAMKO Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
5.6 Allowable Roof Covers:
TABLE 1: ROOF COVER OPTIONS
Clay and Concrete Tile Slate or
Asphalt Metal Wood
(150Z3) Slate-Type
Underlayment . Shingles
(150Z2) Mechanical Adhesive- Panels Shingles Shingles Shingles Shakes
Attach Set (15o7A) (15oZ5) (15oZ7) (15oZa) (ISOZ9)
No.30 UL Yes Yes Yes Yes Yes Yes Yes Yes
See 5.6.1 See 5.6.1
No.30 ASTM Yes Yes Yes Yes Yes Yes Yes Yes
See 5.6.1 See 5.6.1
TAM-FELT® Yes No No Yes Yes Yes Yes Yes
Yes Yes
Moisture Guard® Yes No No No No Yes Qolntstrips, Qolntstrips,
1507.1.1.3/ 1507.1.1.3/
R905.1.1.3) R905.1.1.3)
Yes Yes
TW Underlayment Yes No No Yes Yes Yes Qolntstrips, Qolntstrips,
1507.1.1.3/ 1507.1.1.3/
R905.1.1.3) R905.1.1.3)
Yes Yes Yes Yes Yes Yes
TW Seam Tape Goint strips, No No GoInt strips, Qolntstrips, uointstrips, (joint strips, (Joint strips,
1507.1.1.1/ 1507.1.1.1/ 1507.1.1.1/ 1507.1.2.1/ 1507.1.1.3/ 1507.1.1.3/
R905.1.1.1) R905.1.1.1) A905.1.1.1) R905.1.1.1) R905.1.1.3), R905.1.1.3)
ASTM Slate Surfaced Roll Yes Yes
R00fing (Valley Liner) (Cap Sheet In 2- No No No No No No
ply system)
Yes
ASTM Tile Underlayment Yes (Cap sheet In 2- No No No No No No
(Valley Liner) ply system)
NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-RO
Certificate of Authorization#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-R9
TAMKO Roof Underlayments Revision 0:09/29/2020
Page 3 of 5
ONEMO I etc.
5.6.1 No. 30 UL or No, 30 ASTM may be used as a mechanically attached anchor sheet followed by an asphalt-applied
ASTM Slate Surfaced Roll Roofing or ASTM Tile Underlayment.
5.7 Allowable Substrates:
TABLE 2: SUBSTRATE OPTIONS FOR ADHERED LINDERLAYMENTS
Underlayment Application Primer Substrates
Moisture Guard®or TW Underlayment self-adhering (Optional)ASTM D41 plywood
None No.30UL,No.30 ASTM orTAM-FELT®
TW Seam Tape self-adhering (Optional)ASTM D41 plywood
ASTM Slate Surfaced Roll Roofing or hot asphalt None No.30 UL,No.30 ASTM or TAM-FELT®
ASTM Tile Underlayment
5.8 Attachment Limitations:
5.8.1 For use under mechanically attached NON-TILE prepared roof coverings,attachment shall be in accordance with the
manufacturer's installation instructions, but—for mechanically attached underlayments or base sheets - not less
than FBC 1507.1.1 or R905.1.1.
5.8.2 For use under the roof systems,attachment shall be in accordance with the manufacturer's installation instructions,
but—for mechanically attached base sheets-not less than:
• FRSA/TRI Florida High Wind Concrete and Clay Roof Tile installation Manual,Sixth Edition,Appendix A,Table
1(for Two-Ply Asphalt Applied Hot Mop Underlayment)
5.9 Exposure Limitations:
TABLE 3: ExPOSURE LIMITATIONS•
Underlayment Prepared Roof Cover Maximum Exposure(days)*
Installation Type
No.30 UL,No.30 ASTM,TAM-FELT®
Moisture Guard®,TW Underlayment,TW Seam Tape Any 30
ASTM Slate Surfaced Roll Roofing,ASTM Tile Underlayment
"Maximum exposure shall not exceed the manufacturer's recommendations,which may be less than 30 days.
5.10 Tile Slippage Limitations: When loading roof tiles on the underlayment in direct-deck tile roof assemblies,the tile
shall be staged atop battens during loading of the roof tiles.
6.1 TAMKO Roof Underlayments shall be installed in accordance with TAMKO Building Products LLC installation
instructions subject to the Limitations set forth in Section 5 herein and the specifics noted below.
6.2 Re-fasten any loose decking panels,and check for protruding nail heads. Sweep the substrate thoroughly to remove
any dust and debris prior to application,and prime the substrate (if applicable).
6.3 No.30 UL,No.30 ASTM:
6.3.1 Non-Tile Applications:
mechanically attache S Shall be Installed In compliance with requirements for an approvedm an ally d underlayment (ASTM
D226,Type II)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to
be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the
manufacturer's installation instructions.
NEMO ETC,LLC Evaluation Report 3m-TAM-20-FBCER.A-R0
Certificate ofAuthorL-ation#32455 7-EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-119
TAMKO Roof Underlayments Revision 0:09/29/2020
Page 4 of 5
s
Y {
NNEMOjetc.
6.3.2 Tile Applications:
No.30 UL or No.30 ASTM are limited to use as a mechanically attached base sheet in the"TWO-PLY SYSTEM"from
FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,Sixth Edition,followed by ASTM Slate
Surfaced Roll Roofing,ASTM Tile Underlayment applied in hot asphalt,or other FBC Approved hot-asphalt applied
cap sheet. Refer to FRSA/TRI,Sixth Edition,Appendix A,Table 1 for attachment requirements.
6.4 TAM-FELT®:
6.4.1 Non-Tile Applications:
Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM
D226,Type II)in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to
be installed, and the manufacturer's installation instructions. FBC requirements take precedence over the
manufacturer's installation instructions.
6.5 Moisture Guard®;,TW Underlayment:
6.5.1 Shall be installed in compliance with requirements for an approved self-adhering underlayment (ASTM D1970) in
FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof covering to
be installed,and the manufacturer's installation instructions.
When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in
accordance with FBC 1507.1.1 or R905.1.1.
6.6 ASTMSIate Surfaced Roll Roofing,ASTM Tile Underlayment:
6.6.1 Tile Applications:
ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are limited to use as the Hot Asphalt applied "Cap
Sheet"in the"TWO-PLY SYSTEM"from FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,
Sixth Edition.
Refer to Section 5.8.2 for attachment limitations.
Refer to Section 5.10 for tile staging limitations.
6.6.2 Valley Liner:
ASTM Slate Surfaced Roll Roofing and ASTM Tile Underlayment are acceptable for use as a valley liner in accordance
with FBC 1507.2.9.2 or FBC Residential R905.2.8.2. Installation shall be in accordance with the manufacturer's
instructions before applying shingles.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer
to Section 4 herein for products and production locations having met codified material standards.
OTY AssuRANcE ENTITY:
UL LLC—QUA9625;(414)248-6409; Karen.buchmannC@ul.com
-END OF EVALUATION REPORT-
MEMO ETC,LLC Evaluation Report 3m-TAM-20-1`13CER.A-110
Certificate of Authorization#32455 P EDITION(2020)FBC NON-HVHZ EVALUATION FL12328-119
TAMKO Roof Underlayments Revision 0:09/29/2020