Loading...
HomeMy WebLinkAboutPermit 2007-0507 Revised Residential Renovation Load Calcs2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Manual S Compliance Report Feb 04, 2021Date: Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 Project Information Residential RenovationFor: 1633 NW Sweetbay Circle, Palm City, FL 34990 Cooling Equipment Design Conditions °F76.7Entering coil DB:Btuh34193Sensible gain:°F90.4Outdoor design DB: °F63.7Entering coil WB:Btuh7015Latent gain:°F77.4Outdoor design WB: Btuh41208Total gain:°F75.0Indoor design DB: cfm1608Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: RA1648AJ1NB+RH1T4821STANJAModel:RuudManufacturer: cfm1608Actual airflow: % of load105Btuh35796Sensible capacity: % of load134Btuh9405Latent capacity: %79SHR:% of load110Btuh45201Total capacity: Heating Equipment Design Conditions °F69.0Entering coil DB:Btuh35687Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: RXBH-1724A15CModel:RUUDManufacturer: cfm1608Actual airflow: °F21Temp. rise:% of load103kW10.8Output capacity: Meets all requirements of ACCA Manual S. Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Load Short Form Feb 04, 2021Date: Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 Project Information Residential RenovationFor: 1633 NW Sweetbay Circle, Palm City, FL 34990 Design Information InfiltrationClgHtg Blower doorMethod9041Outside db (°F) 3 (partial) / 1Shielding / stories7570Inside db (°F) 50 Pa / 1959 cfmPressure / AVF1529Design TD (°F) L-Daily range 5050Inside humidity (%) 5724Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make RUUD Make Ruud Trade Trade RUUD Model RXBH-1724A15C Cond RA1648AJ1NB AHRI ref Coil RH1T4821STANJA AHRI ref 201294088 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.8 Sensible cooling Btuh37350 Heating output Btuh36851 Latent cooling Btuh7650 Temperature rise °F21 Total cooling Btuh45000 Actual air flow cfm1608 Actual air flow cfm1608 Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.60 Static pressure in H2O0.60 Space thermostat Load sensible heat ratio 0.83 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Office 87 3299 2146 149 101 Breakfast Nook 50 0 0 0 0 Existing Home 2476 32388 32048 1459 1507 Entire House 2612 35687 34193 1608 1608 Other equip loads 0 0 Equip. @ 1.00 RSM 34193 Latent cooling 7015 TOTALS 2612 35687 41208 1608 1608 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Building Analysis Feb 04, 2021Date: Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 Project Information Residential RenovationFor: 1633 NW Sweetbay Circle, Palm City, FL 34990 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:56.924.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 1959 cfmPressure / AVF7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 20.071224.0Walls 16.7596811.4Glazing 000Doors 7.025141.0Ceilings 24.486983.33.3Floors 13.347312.2Infiltration 18.66654Ducts 00Piping 00Humidification 00Ventilation 0Adjustments 100.035687Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 12.843832.5Walls 35.71221323.4Glazing 000Doors 12.743501.7Ceilings 000Floors 4.114090.7Infiltration 21.57369Ducts 00Ventilation 13.14470Internal gains 00Blower 0Adjustments 100.034193Total Latent Cooling Load = 7015 Btuh Overall U-value = 0.118 Btuh/ft²-°F Data entries checked. 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Component Constructions Feb 04, 2021Date: Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 Project Information Residential RenovationFor: 1633 NW Sweetbay Circle, Palm City, FL 34990 Design Conditions Location:CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:56.924.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) Blower doorMethod)L(15-Daily range (°F) 3 (partial) / 1Shielding / stories77-Wet bulb (°F) 50 Pa / 1959 cfmPressure / AVF7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block Wall R-4.1 14392.5923054.154.10.143556n 6632.5910624.154.10.143256e 13192.5921144.154.10.143510s 7202.5911544.154.10.143278w 41412.5966344.154.10.1431600all Partitions Partition Wall 2 x 4 R-11 2421.454882.9311.00.101167 Windows Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (4.22 ft window ht, 3.35 ft sep.); 7 ft head ht 10210.812112.800.4409n Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (5.17 ft window ht, 1 ft sep.); 7 ft head ht 16210.819212.800.44015n 17110.820312.800.44016n 19212.819212.800.44015s 87827.640712.800.44032w 52227.624212.800.44019w 192519.9123612.800.44097all Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (6.69 ft window ht, 3 ft sep.); 7 ft head ht 22810.827012.800.44021n 27012.827012.800.44021s 49811.854112.800.44042all Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (1.67 ft window ht, 1 ft sep.); 7 ft head ht 12823.07112.800.4406e Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (7.08 ft window ht, 3 ft sep.); 7 ft head ht 61429.726412.800.44021e Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (7.17 ft window ht, 2 ft sep.); 7.2 ft head ht 124229.753312.800.44042e Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = old concrete (0.22); 2 ft overhang (8.75 ft window ht, 0.2 ft sep.); 8.8 ft head ht 94317.54077.5400.26054e 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 2 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (3.92 ft window ht, 1 ft sep.); 7 ft head ht 49112.849112.800.44039s Single Pane: Single Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 1827.591817.5400.26024s Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (6.67 ft window ht, 1 ft sep.); 7 ft head ht 96628.044012.800.44034w Double Pane: Double Pane; NFRC rated (SHGC=0.25); 50% blinds 45°, medium; foreground = green grass (0.23); 2 ft overhang (8 ft window ht, 1 ft sep.); 8 ft head ht 283228.3127612.800.440100w 99818.54077.5400.26054w 383024.9168310.900.260154all Doors (none) Ceilings Encapsulated Roof R-20 1671.222171.5920.00.405137 R-30 Under Attic 41831.6922970.9330.00.0322476 Floors Slab on Grade 00869834.201.180254 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Project Summary Feb 04, 2021Date:Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 Project Information Residential RenovationFor: 1633 NW Sweetbay Circle, Palm City, FL 34990 AEM & Associates PO Box 3752 Jupiter, Fl 33469 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90 Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15 Daily range L Relative humidity %50 Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh29033 Structure Btuh26825 Ducts Btuh6654 Ducts Btuh7369 Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none)(none) Humidification Btuh0 Blower Btuh0 Piping Btuh0 Equipment load Btuh35687 Use manufacturer's data y Rate/swing multiplier 1.00 Infiltration Equipment sensible load Btuh34193 Method Latent Cooling Equipment Load SizingBlower door Shielding / stories 3 (partial) / 1 50 Pa / 1959 cfmPressure / AVF Structure Btuh4017 Ducts Btuh2998 Central vent (0 cfm) Btuh0 CoolingHeating (none) 26122612Area (ft²)Equipment latent load Btuh7015 2351023510Volume (ft³) Air changes/hour 0.210.38 Equipment Total Load (Sen+Lat)Btuh41208 Equiv. AVF (cfm) 83148 Req. total capacity at 0.83 SHR ton3.4 Heating Equipment Summary Cooling Equipment Summary Make RUUD Make Ruud Trade Trade RUUD Model RXBH-1724A15C Cond RA1648AJ1NB AHRI ref Coil RH1T4821STANJA AHRI ref 201294088 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW10.8 Sensible cooling Btuh37350 Heating output Btuh36851 Latent cooling Btuh7650 Temperature rise °F21 Total cooling Btuh45000 Actual air flow cfm1608 Actual air flow cfm1608 Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.047 Static pressure in H2O0.60 Static pressure in H2O0.60 Space thermostat Load sensible heat ratio 0.83 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 1 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Right-J® Worksheet Feb 04, 2021Date:Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 1 Room name Entire House Office 2 Exposed wall 254.2 ft 26.5 ft 3 Room height 9.0 ft 9.0 heat/coolft 4 Room dimensions ft14.5x6.0 5 Room area 2612.3 ft²87.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 nn 4.154.15 2.592.59 617 556 2305 1439 0 0 0 0 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 9 0 121 102 0 0 0 0 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 15 0 192 162 0 0 0 0 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 16 0 203 171 0 0 0 0 11 GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 21 0 270 228 0 0 0 0 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ee 4.154.15 2.592.59 378 256 1062 663 54 48 201 125 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 23.0023.00 6 2 71 128 6 2 71 128 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 29.7229.72 21 0 264 614 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 29.7229.72 42 0 533 1242 0 0 0 0 GG Double PaneDouble Pane 0.2600.260 ee 7.547.54 17.4817.48 54 9 407 943 0 0 0 0 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ss 4.154.15 2.592.59 608 510 2114 1319 131 107 442 276 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 39 39 491 491 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 15 15 192 192 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 21 21 270 270 0 0 0 0 GG Single PaneSingle Pane 0.2600.260 ss 7.547.54 7.597.59 24 24 181 182 24 24 181 182 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ww 4.154.15 2.592.59 518 278 1154 720 54 35 145 91 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 27.5527.55 32 4 407 878 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 27.5527.55 19 2 242 522 19 2 242 522 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 28.0428.04 34 3 440 966 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 28.3228.32 100 8 1276 2832 0 0 0 0 GG Double PaneDouble Pane 0.2600.260 ww 7.547.54 18.4818.48 54 4 407 998 0 0 0 0 PP Partition Wall 2 x 4 0.101Partition Wall 2 x 4 0.101 --2.932.93 1.451.45 167 167 488 242 0 0 0 0 CC Encapsulated Roof R- 0.405Encapsulated Roof R- 0.405 --1.591.59 1.221.22 137 137 217 167 87 87 138 106 CC R-30 Under AtticR-30 Under Attic 0.0320.032 --0.930.93 1.691.69 2476 2476 2297 4183 0 0 0 0 FF Slab on GradeSlab on Grade 1.1801.180 --34.2234.22 0.000.00 2612 254 8698 0 87 27 907 0 6 c) AED excursion 1291 191 Envelope loss/gain 24302 20946 2326 1621 12 a) Infiltration 4731 1409 532 158 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 3550 150 Subtotal (lines 6 to 13)29033 26825 2858 1930 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 29033 26825 2858 1930 15 Duct loads 23%27%6654 7369 15%11%440 216 Total room load 35687 34193 3299 2146 Air required (cfm)Air required (cfm)1608 1608 149 101 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Feb-04 21:40:43 Right-Suite® Universal 2021 21.0.03 RSU26566 Page 2 ...Working Drawings\Residential Renovation CO2.rup Calc = MJ8 Front Door faces: E Residential RenovationJob:Right-J® Worksheet Feb 04, 2021Date:Entire House Jayvee LayugBy: ProCalcs, LLC P.O. Box 882032, Port Saint Lucie, FL 34988 Phone: 772-882-5700 Email: tom@procalcs.net Web: www.ProCalcs.Net License: CAC1815254 1 Room name Breakfast Nook Existing Home 2 Exposed wall 19.2 ft 208.5 ft 3 Room height 9.0 heat/coolft 9.0 heat/coolft 4 Room dimensions ft49.5x1.0 ft2475.8x1.0 5 Room area 49.5 ft²2475.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 nn 4.154.15 2.592.59 41 26 110 68 576 529 2195 1370 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 0 0 0 0 9 0 121 102 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 15 0 192 162 0 0 0 0 .GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 0 0 0 0 16 0 203 171 11 GG Double PaneDouble Pane 0.4400.440 nn 12.7612.76 10.7610.76 0 0 0 0 21 0 270 228 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ee 4.154.15 2.592.59 0 0 0 0 324 208 861 537 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 23.0023.00 0 0 0 0 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 29.7229.72 0 0 0 0 21 0 264 614 GG Double PaneDouble Pane 0.4400.440 ee 12.7612.76 29.7229.72 0 0 0 0 42 0 533 1242 GG Double PaneDouble Pane 0.2600.260 ee 7.547.54 17.4817.48 0 0 0 0 54 9 407 943 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ss 4.154.15 2.592.59 41 26 110 68 437 377 1563 975 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 0 0 0 0 39 39 491 491 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 15 15 192 192 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ss 12.7612.76 12.7612.76 0 0 0 0 21 21 270 270 GG Single PaneSingle Pane 0.2600.260 ss 7.547.54 7.597.59 0 0 0 0 0 0 0 0 WW Block Wall R-4.1Block Wall R-4.1 0.1430.143 ww 4.154.15 2.592.59 90 56 230 144 374 188 778 486 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 27.5527.55 0 0 0 0 32 4 407 878 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 27.5527.55 0 0 0 0 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 28.0428.04 34 3 440 966 0 0 0 0 GG Double PaneDouble Pane 0.4400.440 ww 12.7612.76 28.3228.32 0 0 0 0 100 8 1276 2832 GG Double PaneDouble Pane 0.2600.260 ww 7.547.54 18.4818.48 0 0 0 0 54 4 407 998 PP Partition Wall 2 x 4 0.101Partition Wall 2 x 4 0.101 --2.932.93 1.451.45 0 0 0 0 167 167 488 242 CC Encapsulated Roof R- 0.405Encapsulated Roof R- 0.405 --1.591.59 1.221.22 50 50 79 61 0 0 0 0 CC R-30 Under AtticR-30 Under Attic 0.0320.032 --0.930.93 1.691.69 0 0 0 0 2476 2476 2297 4183 FF Slab on GradeSlab on Grade 1.1801.180 --34.2234.22 0.000.00 50 19 656 0 2476 209 7135 0 6 c) AED excursion 450 650 Envelope loss/gain 2008 2111 19967 17213 12 a) Infiltration 386 115 3813 1136 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 4 920 Appliances/other 0 3400 Subtotal (lines 6 to 13)2394 2226 23781 22669 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -2394 -2226 2394 2226 14 Subtotal 0 0 26174 24895 15 Duct loads 24%29%0 0 24%29%6214 7153 Total room load 0 0 32388 32048 Air required (cfm)Air required (cfm)0 0 1459 1507