HomeMy WebLinkAboutREG SPECS - 2-9-21Bulletin LP-T R122H
March 2010
Type R122H First -Stage Reguiaior
Introduction
The Type R122H is an Underwriters Laboratories listed
regulator designed for Two -Stage LP -Gas systems.
The unit is designed to reduce the tank pressure to an
outlet pressure of 10 psig. The compact size makes it
ideal for small domestic applications and underground
tanks. The outlet pressure setting is nonadjustable
and is factory set at a nominal 10 psig. Screened drip -
lip vents are oriented over the outlet as standard.
Features
20 Year Recommended Replacement Life - The
R122H is designed using rugged time proven
design concepts and constructed of corrosion
resistant materials, both internally and externally.
With proper installation and periodic inspection and
maintenance the R122H regulator will meet a 20
Year Recommended Replacement Life.
• Dual Gauge Taps - Built-in 118 inch NPT gauge
taps onficed to a number 54 drill size on both
the inlet and outlet side of the regulator allow for
easy testing.
• Durability - A fluorocarbon valve disc is utilized
to improve lockup performance in systems with
contaminated gas.
• Improved Regulation - A large fabric -reinforced
diaphragm and stabilizer clip deliver accurate and
stable regulation.
• Easy Installation - The units compact size and
easily accessible inlet and outlet wrench flats make
installation easy even in the tightest installations.
Figural. Type R122H First -Stage Regulator
Superior Overpressure Protection - The
combination of a high capacity relief valve and large
vent provide overpressure protection that exceeds
UL standards When used in conjunction with a
R622 or R652, the two -stage system will limit the
downstream pressure from the second -stage to 2
psig even in a double failure situation.
Corrosion -Resistant - Added corrosion resistance
from an internal and external coating process for all
castings prior to painting, stainless steel relief valve
spring and retainer and a corrosion resistant relief
valve seat.
Positive Draining Spring Case - When installed
properly with the spring case vent pointed down,
the design alloys moisture formed in the spring
case to drain out limiting the problems with
corrosion and freezing water in the spring case.
® www.FISHERregulators.comllP.
EMERSON
Process Management
Bulletin LP-7: R122H
Table 1. Ordering btformalron
TYPE NUMBER
CAPACITY BTUIMR
CONNECTIONS
NOMINAL OUTLET SETTING
PROPANE111
INLET x OUTLET
I
R 122f44W
1.100.000
114-a h x 1124nch NPT
10 psmg (0.69 ban
1 Candy eti boae0 an 30 PW (ZO? ban Ode! WeSWM smW Z^ droop
u4.1a try
0
a
OR
nos
FlSurs 2. TYF8 R122H Drmenstans
lamsl
LP -Gas Egu[pmeet
Emerson Process Management
Regulator Technologies. Inc.
USA - Headquarters
Mditley. Texas 75069-1872 USA
Telephone: 1(800) 558,653
Telephone. 1 (972) 548-3574
For blades adom anon visit wwwAshenegutators.cwrAp
Tha E mmww logo b a QsQeark and samoo am* d (Ea emw EiKme Co. AB ovw matt am the MV" of ti mr proWecwe ammners. Rum is a mark owmea W Fww Cams. Inc.. a
buwj= of Enrafa 9 RUM Mardoeffad.
The mrmenls d Oft pubctmaoo are pmeaaabod dx ft mobonW fxupo:as Daly. and w m every etkrl r m base made oo tntwm Mw esaaasy. my am not lobe o nsbuod as ar
expcass ar etesp0e4 re�+alrmp tlao Onxs<cr11 ar aasvum dnaMed kerem Or MM use Or M*DC bdO Vft masemva Me ngM to ntoft or Deprave Q10 03 ns ar gnCMeWXM arsuor
pnoduaa al any tame Srttemort aooxe.
&mrsam Pm mm Mn agamw does nu aasrrne mowsMV ON the w*cbomuss or mwasnum of wW product. ftespwmsbMV Oar proper sebebm. use and aogr4xsamoe ar a v won
Peooess Ida wgu and Mold d oeer, 4 9d* vale an puromw
EMERSON..
CfarMw ProoW ManaW=4 it W=wTe00**W& ft.. 2003. 2010: M it ft ReservW Process Management
Bulletin 71.1:R622
Type R622 Pressure Reducing Regulator
• Comp;
• Protec
Screet
• Hinh Capacity
telief
• Inlet and Outlet Pressure Gauge Taps
Figure 1. Type R622 Pressure ReUuang Re9+riot1 '
Introduction
Type R622 direct -operated. spring -loaded regulators
provide economical pressure reducing control in
a variety of residential, commercial. and industrial
FISHER
leight
applications. These regulators can be used mth
natural. manufactured. or propane gases and have the
same inlet and outlet pressure capabilities.
EMERSON
Bulletin 71.1: R6 22
Specifications
Body Size and End Connection Style0) Pressure Registration
1/2 NPT inlet and outlet Internal
Maximum Allowable Inlet Pressure()
Operating: 125 psig (8,6 bar)
Emergency: 125 psig (8.6 bar)
Except 1.8 to 2.2-inches w.c. (4 to 5 mbar) spring
range which has operating and emergency
pressures of 60 psig (4,1 bar)
Maximum Allowable Outlet (Casing) Pressure()
Operating to Avoid Internal Part Damage:
3 psid (0.21 bar d) above outlet pressure setting
Emergency: 20 psi (I A bar)
Outlet Pressure Ranges
See Table 1
Orifice Size
1/84nch (3.2 mm) orifice
Flow Coefficients
Wide -Open C. for Relief Siting: 12.5
Wide -Open C„ for Relief Sizing: 0.36
Ci: 35
IEC Sizing Coefficients
XT: 0.78
Fp: 0.82
FL: 0.89
Flow Capacities
See Table 2
Relief Performance
See Figure 4
Internal Relief Performance
Start -to -Discharge is 8 to 22-inches w.c.
(20 to 55 mbar) for setpoints from
1.8 to 20-inches w.c. (4 to 50 mbar)
Start -to -Discharge is 140 to 200% over setpoint
from 20-inches w.c. to 2.2 psig (50 to 152 mbar)
Spring Case Vent Connections
3/4 NPT with removable screen
Temperature Capabilities('()
-20- to 160-F (-29° to 71 °C)
Approximate Weight
2.35 pounds (1 kg)
Construction Materials
Body, Spring Case, Diaphragm Plate, and
Orifice: Aluminum
Diaphragm, Disk, and O-ring: Nitrile (NBR)
Adjusting Screw and Pushpost: Delrin®
Closing Cap: ASA Thermoplastic (UV -Ray Resistant)
Control Spring: Zinc -plated steel
Machine Screw, Spring Seat,
and Lever: Zinc -plated steel
Valve Stem: Zinc
Relief Valve Spring, Relief Spring Retainer,
Lever Pin, and Vent Screen: Stainless steel
I. fie �e17t e n Liss BEIfiQtpl a any spoRamte stendzro tartttauor+ snotaa not pe eXC600ed
oewO tb a mM awned tri E 1. Qb Porn de Kemp n 2M Co.
In addition, Type R622 regulators have internal relief
across the diaphragm to help minimize overpressure.
Any outlet pressure above the start -to -discharge point
of the non-adjustable relief valve spring moves the
diaphragm off of the relief valve seat, allowing excess
pressure to bleed out through the screened spring
case vent.
rabte t. Outlet Pressure Ranges
Specifications
The Specfications seclion fists specifications 1brType R622
Pressure Reducing Regulators. As it originally comes
from the factory, specifications for a given regulator
are stamped on the spring case nameplate.
OUTLET PRESSURE RANGE
CONTROL SPRING PART
NUMBER
CONTROL SPRING
COLOR CODE
SPRING WIRE DIAMETER
tNCHES (111tr1)
SPRING FREE LENGTH.
INCHES (halt)
1.8 to 2.24nChes w.c. 14 to 5 n%ar)
5 to 74ndtes w.c. (12 to 17 mbar)
T 14453TOO 12
T 14398T00 t2
Purple
Orange
0.051 (1.30)
0.Ow (1,58)
3.40 (86.4)
3.40 (86A)
6.5 to 94neries w.c. (16 to 22 mbar)
T 14399TOO12
lfettow
0.067 (1.70)
3.61 (91.7)
9 to 134Kties w.c. (22 to 32 mbar)
T 144007M 12
staler
0.072 (1,83)
4.10 004)
13 to 20-Mdtes w.c. (32 to 50 mbar)
T 14401 TOO 12
GMY
0.080 (2.03)
3.60 (91.4)
16 to 35-mdles W.C. (40 to 87 mbar)
T 1440270012
Ptrtk
0.093 (2.36)
3.52 (89.4)
1 to 2.2 psig (69 to 152 mbar)
T14403TOO12
LkPI Blue
0 105 (2.67)
3.66 (93.0)