HomeMy WebLinkAbout20036-01M-3-Model1 1 /2" STRAPS
TO STRUCTURE
STAINLESS STEEL
BAND II INSULATED FLEX DUCT
3" SHAFT INSERT
1 1/2" INSULATION
RADIUS NOT LESS THAN
1 1/2 x DUCT DIA.
BRANCH
DUCT
BUTTERFLY DAMPER '
OPERATOR ON 1 1/2"
STAND-OFF TO ALLOW
FOR INSULATION
USE ROUND SHEET METAL -
DUCT HERE TO LIMIT FLEX
DUCT TO 10'-0" IN LENGTH
6"SADDLE -
INSULATE BELLS
CEILING DIFFUSER
(TYP•)
TAKE -OFF FITTING
3" SHAFT INSERT
STAINLESS STEEL BAND
LCEILING
NOTE: USE BORDER TYPE 1
WHERE IN HARD CLGS. -
BORDER TYPE C WHEN EXPOSED
I CEILING DIFFUSER.
DIRECTION SECURE FLEX DUCT TO TAKE -OFF INSULATE BELLS.
SEE HVAC FLOOR
OF AIR I FITTING WITH STAINLESS STEEL
I SCREW DRIVER OPERATED BAND PLAN FOR LOCATION
FLOW
I OF DIFFUSER.
BRANCH FLEXIBLE DUCT �I
DUCT I STRAP
I
I
DAMPER CEILING
I
SADDLE
I
1 1/2"
INSULATION
NOTE: USE BORDER TYPE 1
WHERE IN HARD CLGS. -
BORDER TYPE C WHEN EXPOSED
PROVIDE GASKET BETWEEN TAKE OFF
FITTING AND BRANCH DUCT.
A FLEX DUCT CONNECTION DETAILS
DX COOLING
COIL
TO VALVE
MOISTURE SIGHT GLASS
NOTES:
1. PROVIDE ACCUMULATOR IF DEVELOPED
LENGTH IS GREATER THAN 50'
2. PROVIDE REFRIGERANT PIPE SIZES
RECOMMENDED BY MFG.
3. SEE ALSO REFRIGERANT SYSTEM
NOTES
CHARGE VALVE W/CAP
IF NOT PROVIDED WITH
UNIT
CONDENSING
UNIT SEE
DETAIL &
SCHEDULE
BASE
SENSING BULB
FILTER DRYER —
WITH REPLACEABLE
CORE
ISOLATION VALVES (TYPICAL)
BALL TYPE ISOLATION VALVES
IF NOT PROVIDED WITH UNIT
E REFRIGERANT PIPING SCHEMATIC
RETURN AIR DUCT - SEE PLAN FOR SIZE
SUPPLY AiP
TRANSITION
UP -FLOW AIR
UNIT - SEE
CONSTRUCT FLLI7VIYI JVrfVI\1 URJL I I\NIYIL rl\V VIVL ILmCf\VLIIVI VYLI\1 LVVV JLIVJVI',
FROM I �" X I � X Is" STEEL a ENCLOSE WITH WATER GARD PRIMARY PAN SENSOR #401475B
OR SECONDARY DRAIN HOLE SENSOR #401490B
I DUCT BOARD - SEAL WITH TAPE a MASTIC. WITH ALARM. WATER GARD, INC.
12211 CEDAR GAP, HOUSTON, TX 77072
(PH 888-652-9800)
* PLACE AIR HANDLING UNIT IN THE ROOM SO THAT SERVICE TO
THE UNIT & FILTER REPLACEMENT CAN BE ACCOMPLISHED.
B VERTICAL AHU DETAIL AHU- I
SCALE _ (N.T.S.)
SUCTION LINE
LIQUID LINE
THREADED CAP WITH % "O
HOLE DRILLED IN TOP,
HAND TIGHTENED.
THREADED CAP,
HAND TIGHTENED
AIR
HANDLER
SLOPE TO UNIT
DRAIN F=pv�
— DRAIN PAN
9u
CASING SLEEVE
UNION
NOTE:
1. FILL TRAP MANUALLY ON INITIAL START-UP.
2. PIPE SIZE SHALL NOT BE LESS THAN DRAIN PAN CONNECTION SIZE.
3. A = 1" + FAN SUCTION S.P.
B = A / 2
4. ALL CONDENSATE PIPING TO BE PVC.
S. INSULATE ALL DRAIN LINES WITH %" ARMAFLEX
F I CONDENSATE DRAIN TRAP DETAIL
SCALE _ (N.T.S.)
a
U
U
0
O.A. INTAKE o
Ln
of
SUPPLY AIR DUCT - SEE PLAN FOR SIZE PROVIDE
TRANSITION TO SUIT MFG. OPENING
FLEX
MD
UP -FLOW AIR HANDLING
UNIT - SEE SCHEDULE FILTER VD
C.D. —�
TRAP
FLOOR
WALL
RETURN GRILL IN WALL
DUCT SUPPORT
CONSTRUCT PLENUM SUPPORT BASE FRAME-1PROVIDE EMERGENCY OVERFLOW SENSOR
FROM I" X I" X" STEEL B ENCLOSE WITH WATER GARD PRIMARY PAN SENSOR #401475B
OR SECONDARY DRAIN HOLE SENSOR #40149OB
I" DUCT BOARD - SEAL WITH TAPE a MASTIC. WITH ALARM. WATER GARD, INC.
12211 CEDAR GAP, HOUSTON, TX 77072
(PH 888-652-9800)
* PLACE AIR HANDLING UNIT IN THE ROOM SO THAT SERVICE TO
THE UNIT & FILTER REPLACEMENT CAN BE ACCOMPLISHED.
SCALE=(N.TS)I C I VERTICAL AHU DETAIL AHU-2, 3, & 4
SECURE TO STRUCTURE
ABOVE AS RECOMMENDED
BY SMACNA
1 20 GA GALV.
METAL STRAP
LJ['/ or �
-SHEET METAL SCREW,
RIVET OR BOLT TO
BOTH SIDES OF DUCT.
TYPE 'A'
TYPICAL RECTANGULAR DUCT
BAND ur 3h11VIL JILC
AS HANGER STRAP
vLK
AD RATED
STENER
'i 1 - 1IG 1
TYPICAL ROUND DUCT
G I DUCT SUPPORT DETAILS
SCALE _ (N.T.S.)
DUCT SCHEDULE
DUCT DIMENSIONS TYPE
INCHES HANGER
UP TO 18
A
19 TO 30
A/B
30 TO 60
B
NOTE:
8'4' MAX HANGER SPACING
SECURE TO STRUCTURE
ABOVE AS RECOMMENDED
BY SMACNA
HANGER ROD
SIZE:
I
TYPE 'B' '11fX%"XW
GALVANIZED
ANGLE
TYPICAL AIR COOLED CONDENSING UNIT.
DO NOT LOCATE UNIT WHERE THE
UPBLAST WILL STRIKE ANY OVERHANG.
LOCATE UNIT MINIMUM OF 2'-0"
FROM BUILDING EXTERIOR WALL
ANCHOR UNIT TO PAD WITH GALV. STEEL —
TIE -DOWN CLIPS, 2 PER SIDE, WITH MIN. 1/4"
DIA. EXPANSION BOLTS 0 1 1/2" EMBEDMENT
DEPTH, #12 X 3/4" SCREW INTO CASING.
SUCTION & LIQUID
REFRIGERANT LINES
RUN REFRIGERANT LINES SHORTEST
DISTANCE TO BLDG. EXTERIOR WALL.
SEE PLANS FOR CONTINUATION.
PAD TO BE 4" LARGER ALL AROUND
THAN UNIT, FURNISHED WITH #4
REBARS AT 6" O.C. BOTH WAYS
C�
NEOPRENE PAD. (TYPICAL FOR 4)
8" THICK CONCRETE PAD.
4" ABOVE GRADE AND
4" BELOW GRADE
MIN. 3000 PSI
NOTE: INSTALL TO WITHSTAND 170 MPH WINDS.
D I AIR COOLED CONDENSING UNIT DETAIL
SCALE _ (N.T.S.)
BAND ONE HALF —ROUND
MAY BE USED IF DUCT
SHAPE IS MAINTAINED
3/8" DIA. THREADED
STEEL HANGER ROD
SEE PLAN FOR EXHAUST
DUCT CONTINUATION
AND TERMINATION f
DUCT SLEEVE\ `
EXHAUST
DUCT
FLEX. CONNECTION
TO EXHAUST FAN
CABINET FAN
Fort Pierce
Engineering, Inc.
Dependable Mechanical, Electrical
& Plumbing Design
Reg. No. 28173
315 South 7th Street
Fort Pierce, FL. 34950
Phone: 772 672-4636
Fax: 772 672-4637
a
Q
H
r>~
vs
w
w
Q
0
�10
w
Q
o
x
Lo
W
x
r0
a
x
�
�o
�.,
w
SCALE _ (N.T.S.)
F —1
U
O�
W W
W
Q
O Q:� 0)
I` O ;d-
U
L� rr)
W
V
�ll
Y�
C�
Z
Q
Q
�-
Q Q
O o
W
=
z
O
U O
z
LL
O
U
U
Ld
J
_j
L w
Li
U
O E:
�
w
z
O
C4
o
O 0�
UPPER ATTACHMENTS Q� O O
IN ACCORDANCE WITH ° Iz M LL_
SMACNA DETAILS ENGINEER SEAL
♦♦IIIIIIII//I
RUBBER -IN -SHEAR ♦`�♦\C 3;•SVOeO ��e
VIBRATION ELIMINATORS �`tF';•��CENS�•.�9��
(TYPICAL FOR ALL 4 •
HANGER RODS) yF;' No.60982 •�*
-P •; STATE OF
. O . <v
/011A_ ♦``
CEILING Eric J. Svoboda, PE
P.E. No. 60982
THESE DOCUMENTS, ALONG WITH THE CONCEPTS AND OR DESIGNS
PRESENTED HEREIN ARE INTEN➢ED ONLY FOR THE SPECIFIC
PURPOSE AND CLIENT OF FORT PIERCE ENGINEERING, INC. FOR
EXHAUST FAN WHICH THEY WERE PREPARED. REUSE OR IMPROPER RELIANCE ON
THESE DOCUMENTS WITHOUT WRITTEN AUTHORIZATION AND
ADAPTATION BY FORT PIERCE ENGINEERING, INC. SHALL BE
CEILING GRILLE
WITHOUT LIABILITY TO THE SAME. COPYRIGHT®2020, FORT
PIERCE ENGINEERING, INC. ALL RIGHTS RESERVED.
SHEET TITLE
MECHANICAL
DFTAII q
This item has been Digitally signed
electronically signed and by Eric Svoboda
sealed by Eric J Svoboda, PE,
using a SHA-1 authentication Date: 2020.11.11
code. Printed copies of this 1 0.33.25-05'00'
document are not considered
signed and sealed and the SHA- Adobe Acrobat
I authentication code must be
verified on any electronic version:
copes. 2020.013.20064
H I CEILING CABINET EXHAUST FAN DETAIL
SCALE _ (N.T.S.) SCALE _ (N."F.S.)
ISSUE DATE: 11-11-2020
DRAWN: EJS
APPROVED: EJS
DRAWING NUMBER
M-3
SHEET 3 OF 3
20036-01