HomeMy WebLinkAboutSLCSO Visitation Building Heat LoadSLCSO Visitation Building HVAC Load Analysis for St. Lucie County Sheriffs Dept. 900 North Rock Road Fort Pierce, Florida E86 1xftw1Qr4m?m-' CHVACCOMM, MCIAL. HVAC LoAiDs This item has been Digitally signed electronically signed and by Eric Svoboda Baled by Eric J Svoboda, PE, using a SHA-1 authentication Date: 2020.11.1 1 code. Printed copies of this 10:34:28-05'00' document are not considered signedandsealedandthe SHA- Adobe Acrobat I authentication code must be verified on any electronic version: copies. 2020.013.20064 Qpeaoe�-�a�aoaoo E FJO®� o O �� • �'\ ��••Y DOOpP No 60902 " � o m � • o e Y . STATE OF i,I! b eoG�•S, . •0 R A •• C? o0 Prepared By: Eric J. Svoboda, PE Fort Pierce Engineering, Inc. 315 South 7th Street Fort Pierce, FL 34950 772-672-4636 Thursday, October 29, 2020 Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Enqineerinq ASLCSO Visitation Buildinq Fort Pierce, FL 34950 Page 2 General Project Data Input General Project Information Project file name: SLCSO Visitation Building Heat Load.CH8 Project title: SLCSO Visitation Building Designed by: Eric J. Svoboda, PE Project date: Monday, July 07, 2008 Weather reference city: FORT PIERCE, FLORIDA, USA Client name: St. Lucie County Sheriffs Dept. Client address: 900 North Rock Road Client city: Fort Pierce, Florida Company name: Fort Pierce Engineering, Inc. Company representative: Eric J. Svoboda, PE Company address: 315 South 7th Street Company city: Fort Pierce, FL 34950 Company phone: 772-672-4636 Company fax: 772-672-4637 Barometric pressure: 29.894 in.Hg. Altitude: 25 feet Latitude: 27 Degrees Mean daily temperature range: 15 Degrees Starting & ending time for HVAC load calculations: 7am - 10pm Number of unique rooms in this project: 13 Building Default Values Calculations performed: Both heating and cooling loads Lighting requirements: 2.00 Watts per square foot Equipment requirements: 1.00 Watts per square foot People sensible load multiplier: 250 Btuh per person People latent load multiplier: 200 Btuh per person Room sensible safety factor: 0 % Room latent safety factor: 0 % Room heating safety factor: 0 % People diversity factor: 100 % Lighting profile number: 0 Equipment profile number: 0 People profile number: 0 Building default ceiling height: 9.00 feet Building default wall height: 12.00 feet Internal Operatina Load Profiles C = 100 hr hr hr hr hr hr hr hr hr hr I hr hr hr hr hr hr hr hr hr hr hr hr hr hr 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 c c c c C C c c c c C C C c c c c C C C c c C c 2 C C C C C C C C C C C C C C C C C C C C C C C C 3 C c c C C C c C c c c C C C c c c C C C C C C C 4 C C C C C C C C C C C C C C C C C C C C C C C C 5 C C c c C C C C C c c c C C C c c C C C C C C c 6 C C C C C C C C C C C C C C C C C C C C C C C C 7 C C c c C C C C C C C C C C C C c C C C C C C C 8 c C C c C C c c c C C C C C C C C C C C C c C C 9 C C C c C C C C C C C C C C C C c C C C C C C C 10 C C c c C C C C c C C c C C C C C C C C C C C C Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Enqineerinq SLCSO Visitation Buildinq Fort Pierce FL 34950 Page 3 General Pro "ect Data Input cont'd Building -Level Design Conditions Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction August 95 80 50% 75 66.33 6 Winter 42 75 Master Roofs Roof ASHRAE Roof Dark Susp. No. Roof# U-Fac Color Ceil 1 1 0.050 No No Roof #1 Description: Metal Roof, R-20 Master Walls Wall ASHRAE Wall Wall No. Group U-Fac Color 1 C 0.095 D Wall #1 Description: Block wall, 8" sand & gravel, hollow core, siding exterior, interior finish, 1" extruded poly, R-5.0 Master Partitions Partition Partition Cool Heat No. U-Factor T-D T-D 1 0.095 10 10 Partition #1 Description: Block partition, 8" sand & gravel, hollow core, siding exterior, interior finish, 1" extruded poly, R- 5.0 Master Glass Glass Summer Winter Glass Interior Interior No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef 1 0.810 0.830 1.000 1 0.550 Glass #1 Description: Default Glass Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Enqineerinq SLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 4 Building Summmy Loads Building peaks in August at 3pm. tBldg Load Area Sen %Tot Lat Sen Net %Net escri tions Quan Loss Loss Gain Gain Gain Gain Roof 6,732 11,108 18.29 0 14,747 14,747 8.27 Wall 3,720 11,662 19.20 0 7,320 7,320 4.11 Glass 96 2,629 4.33 0 3,748 3,748 2.10 Floor Slab 318 6,506 10.71 0 0 0 0.00 Skin Loads 31,906 52.53 0 25,815 25,815 14.48 Lighting 13,464 0 0.00 0 45,941 45,941 25.78 Equipment 6,732 0 0.00 0 22,971 22,971 12.89 Pool Latent 0 0 0.00 0 0 0 0.00 People 63 0 0.00 12,600 15,750 28,350 15.91 Partition 360 342 0.56 0 342 342 0.19 Cool. Pret. 0 0 0.00 0 0 0 0.00 Heat. Pret. 0 0 0.00 0 0 0 0.00 Cool. Vent. 800 0 0.00 36,054 17,584 53,638 30.09 Heat. Vent. 800 28,486 46.90 0 0 0 0.00 Cool.lnfil. 0 0 0.00 0 0 0 0.00 Heat.lnfil. 0 0 0.00 0 0 0 0.00 Draw-Thru Fan 0 0 0.00 0 1,175 1,175 0.66 Blow-Thru Fan 0 0 0.00 0 0 0 0.00 Reserve Cap. 0 0 0.00 0 0 0 0.00 Reheat Cap. 0 0 0.00 0 0 0 0.00 Supply Duct 0 0 0.00 0 0 0 0.00 Return Duct 0 0 0.00 0 0 0 0.00 Misc. Supply 0 0 0.00 0 0 0 0.00 Misc. Return 0 0 0.00 0 0 0 0.00 Building Totals 60,734 100.00 48,654 129,578 178,232 100.00 Building Sen %Tot Lat Sen Net %Net Summary Loss Loss Gain Gain Gain Gain Ventilation 28,486 46.90 36,054 17,584 53,638 30.09 Infiltration 0 0.00 0 0 0 0.00 Pretreated Air 0 0.00 0 0 0 0.00 Room Loads 32,248 53.10 12,600 110,819 123,419 69.25 Plenum Loads 0 0.00 0 0 0 0.00 Fan/Duct/Misc Loads 0 0.00 0 1,175 1,175 0.66 Building Totals 60,734 100.00 48,654 129,578 178,232 100.00 Check Figures Total Building Supply Air (based on a 21 ° TD): 4,910 CFM Total Building Vent. Air (16.29% of Supply): 800 CFM Total Conditioned Air Space: 6,732 Sq.ft Supply Air Per Unit Area: 0.7293 CFM/Sq.ft Area Per Cooling Capacity: 453.3 Sq.ft/Ton Cooling Capacity Per Area: 0.0022 Tons/Sq.ft Heating Capacity Per Area: 9.02 Btuh/Sq.ft Total Heating Required With Outside Air: 60,734 Btuh Total Cooling Required With Outside Air: 14.85 Tons Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 5 Air Handier #1 - AHU 1 - Summa Loads Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A. No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM Volume CFM/S ft CFM/S ft W.Exh Act.CFM Act.CFM 1 Lobby 750 6,991 19,301 2,000 Direct Direct 9am August 10 324 814 0 115 115 6,750 0.43 1.09 0 176 143 2 RR 1 56 637 1,335 200 Direct Direct 3pm August 1 30 56 0 9 9 504 0.53 1.01 0 16 10 3 RR 2 56 172 1,029 200 Direct Direct 2pm August 1 8 43 0 9 9 504 0.14 0.77 0 4 8 4 RR 3 56 172 1,029 200 Direct Direct 2pm August 1 8 43 0 9 9 504 0.14 0.77 0 4 8 5 North Office 230 482 3,472 400 Direct Direct 2pm August 2 22 146 0 35 35 2,070 0.10 0.64 0 12 26 6 Reception 270 446 3,869 400 Direct Direct 2pm August 2 21 163 0 42 42 2,430 0.08 0.60 0 11 29 7 Hall 36 59 699 200 Direct Direct 2pm August 1 3 29 0 6 6 324 0.08 0.82 0 1 5 8 South Office 170 977 2,911 400 Direct Direct 4pm August 2 45 123 0 26 26 1,530 0.27 0.72 0 25 22 Room Peak Totals: 1,624 9,937 33,644 4,000 Total Rooms: 8 20 460 1,419 0 250 250 Unique Rooms: 8 14,616 0.28 0.87 0 250 250 Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 6 Air Handler #1 - AHU 1 - Total Load Summa Air Handler Description: AHU 1 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.13 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 3pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.03 grains, Htg: 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Because of the diversity in room, plenum and ventilation loads, the room sensible peak time in August at gam is different from the total system peak time, hence the air system CFM was computed using a room sensible load of 32,415. Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 9,937 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 8,902 Btuh 250 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 18,839 Btuh Heating Supply Air: 9,937 / (.999 X 1.08 X 20) = 460 CFM Winter Vent Outside Air (54.3% of supply) = 250 CFM Room space sensible gain: 31,153 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 340 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 31,493 Btuh Cooling Supply Air: 32,754 / (.999 X 1.1 X 21) = 1,419 CFM Summer Vent Outside Air (17.6% of supply) = 250 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 5,495 Btuh 250 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 5,495 Btuh Total sensible gain on air handling system: 36,988 Btuh Room space latent gain: 4,000 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 11,267 Btuh Total latent gain on air handling system: 15,267 Btuh Total system sensible and latent gain: 52,255 Btuh Check Figures Total Air Handler Supply Air (based on a 21 ° TD): 1,419 CFM Total Air Handler Vent. Air (17.62% of Supply): 250 CFM Total Conditioned Air Space: 1,624 Sq.ft Supply Air Per Unit Area: 0.8739 CFM/Sq.ft Area Per Cooling Capacity: 372.9 Sq.ft/Ton Cooling Capacity Per Area: 0.0027 Tons/Sq.ft Heating Capacity Per Area: 11.60 Btuh/Sq.ft Total Heating Required With Outside Air: 18,839 Btuh Total Cooling Required With Outside Air: 4.35 Tons Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 7 Air Handler #2 - AHU 2 - Summary Loads Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A. No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM Volume CFM/Sgft CFM/Sgft W.Exh Act.CFM Act.CFM 9 Visitation 1,960 7,533 31,494 4,000 Direct Direct 2pm August 20 349 1,379 0 250 250 17,640 0.18 0.70 0 250 250 Room Peak Totals: 1,960 7,533 31,494 4,000 Total Rooms: 1 20 349 1,379 0 250 250 Unique Rooms: 1 17,640 0.18 0.70 0 250 250 Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 8 Air Handler #2 - AHU 2 - Total Load Summa Air Handler Description: AHU 2 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.13 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.89 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 2pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.77 grains, Htg: 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 7,533 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 8,902 Btuh 250 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 16,435 Btuh Heating Supply Air: 7,533 / (.999 X 1.08 X 20) = 349 CFM Winter Vent Outside Air (71.6% of supply) = 250 CFM Room space sensible gain: 31,494 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 330 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 31,824 Btuh Cooling Supply Air: 31,824 / (.999 X 1.1 X 21) = 1,379 CFM Summer Vent Outside Air (18.1 % of supply) = 250 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 5,495 Btuh 250 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 5,495 Btuh Total sensible gain on air handling system: 37,319 Btuh Room space latent gain: 4,000 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 11,267 Btuh Total latent gain on air handling system: 15,267 Btuh Total system sensible and latent gain: 52,586 Btuh Check Figures Total Air Handler Supply Air (based on a 21 ° TD): 1,379 CFM Total Air Handler Vent. Air (18.13% of Supply): 250 CFM Total Conditioned Air Space: 1,960 Sq.ft Supply Air Per Unit Area: 0.7035 CFM/Sq.ft Area Per Cooling Capacity: 447.3 Sq.ft/Ton Cooling Capacity Per Area: 0.0022 Tons/Sq.ft Heating Capacity Per Area: 8.39 Btuh/Sq.ft Total Heating Required With Outside Air: 16,435 Btuh Total Cooling Required With Outside Air: 4.38 Tons Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 9 Air Handler #3 - AHU 3 - Summmy Loads Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A. No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM Volume CFM/Sgft CFM/Sgft W.Exh _ Act.CFM Act.CFM 10 Storage East 1,566 5,720 23,273 2,200 Direct Direct 3pm August 11 265 1,019 0 150 150 14,094 0.17 0.65 0 150 150 Room Peak Totals: 1,566 5,720 23,273 2,200 Total Rooms: 1 11 265 1,019 0 150 150 Unique Rooms: 1 14,094 0.17 0.65 0 150 150 Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 10 Air Handler #3 - AHU 3 - Total Load Summa Air Handler Description: AHU 3 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.10 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 3pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.03 grains, Htg: 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 5,720 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 5,341 Btuh 150 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 11,061 Btuh Heating Supply Air: 5,720 / (.999 X 1.08 X 20) = 265 CFM Winter Vent Outside Air (56.6% of supply) = 150 CFM Room space sensible gain: 23,273 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 244 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 23,517 Btuh Cooling Supply Air: 23,517 / (.999 X 1.1 X 21) = 1,019 CFM Summer Vent Outside Air (14.7% of supply) = 150 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 3,297 Btuh 150 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 3,297 Btuh Total sensible gain on air handling system: 26,814 Btuh Room space latent gain: 2,200 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 6,760 Btuh Total latent gain on air handling system: 8,960 Btuh Total system sensible and latent gain: 35,774 Btuh Check Figures Total Air Handler Supply Air (based on a 21 ° TD): 1,019 CFM Total Air Handler Vent. Air (14.72% of Supply): 150 CFM Total Conditioned Air Space: 1,566 Sq.ft Supply Air Per Unit Area: 0.6507 CFM/Sq.ft Area Per Cooling Capacity: 525.3 Sq.ft/Ton Cooling Capacity Per Area: 0.0019 Tons/Sq.ft Heating Capacity Per Area: 7.06 Btuh/Sq.ft Total Heating Required With Outside Air: 11,061 Btuh Total Cooling Required With Outside Air: 2.98 Tons Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Page 11 Air Handler #4 - AHU 4 - Summary Loads Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A. No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM Volume CFM/Sgft CFM/Sgft W.Exh Act.CFM Act.CFM 11 Storage West 1,470 7,595 22,632 2,000 Direct Direct 3pm August 10 352 983 0 139 139 13,230 0.24 0.67 0 126 135 12 Office 64 570 1,305 200 Direct Direct 9pm August 1 26 57 0 6 6 576 0.41 0.89 0 9 8 13 RR 48 892 1,228 200 Direct Direct 9pm August 1 41 53 0 5 5 432 0.86 1.11 0 15 7 Room Peak Totals: 1,582 9,057 25,165 2,400 Total Rooms: 3 12 420 1,093 0 150 150 Unique Rooms: 3 14,238 0.27 0.69 0 150 150 Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc. Fort Pierce Engineerinq ASLCSO Visitation Buildinq Fort Pierce FL 34950 Pa e 12 Air Handler #4 - AHU 4 - Total Load Summa Air Handler Description: AHU 4 Constant Volume - Proportion Supply Air Fan: Draw-Thru with program estimated horsepower of 0.10 HP Fan Input: 0% motor and fan efficiency with 0 in. water across the fan Sensible Heat Ratio: 0.91 --- This system occurs 1 time(s) in the building. --- Air System Peak Time: 4pm in August. Outdoor Conditions: Clg: 95' DB, 80' WB, 131.77 grains, Htg: 42' DB Indoor Conditions: Clg: 75' DB, 50% RH, Htg: 75° DB Summer: Ventilation controls outside air, ----- Winter: Ventilation controls outside air. Room Space sensible loss: 9,057 Btuh Infiltration sensible loss: 0 Btuh 0 CFM Outside Air sensible loss: 5,341 Btuh 150 CFM Supply Duct sensible loss: 0 Btuh Return Duct sensible loss: 0 Btuh Return Plenum sensible loss: 0 Btuh Total System sensible loss: 14,398 Btuh Heating Supply Air: 9,057 / (.999 X 1.08 X 20) = 420 CFM Winter Vent Outside Air (35.7% of supply) = 150 CFM Room space sensible gain: 24,955 Btuh Infiltration sensible gain: 0 Btuh Draw-thru fan sensible gain: 262 Btuh Supply duct sensible gain: 0 Btuh Reserve sensible gain: 0 Btuh Total sensible gain on supply side of coil: 25,217 Btuh Cooling Supply Air: 25,217 / (.999 X 1.1 X 21) = 1,093 CFM Summer Vent Outside Air (13.7% of supply) = 150 CFM Return duct sensible gain: 0 Btuh Return plenum sensible gain: 0 Btuh Outside air sensible gain: 3,297 Btuh 150 CFM Blow-thru fan sensible gain: 0 Btuh Total sensible gain on return side of coil: 3,297 Btuh Total sensible gain on air handling system: 28,514 Btuh Room space latent gain: 2,400 Btuh Infiltration latent gain: 0 Btuh Outside air latent gain: 6,760 Btuh Total latent gain on air handling system: 9,160 Btuh Total system sensible and latent gain: 37,674 Btuh Check Figures Total Air Handler Supply Air (based on a 21 ° TD): 1,093 CFM Total Air Handler Vent. Air (13.73% of Supply): 150 CFM Total Conditioned Air Space: 1,582 Sq.ft Supply Air Per Unit Area: 0.6906 CFM/Sq.ft Area Per Cooling Capacity: 503.9 Sq.ft/Ton Cooling Capacity Per Area: 0.0020 Tons/Sq.ft Heating Capacity Per Area: 9.10 Btuh/Sq.ft Total Heating Required With Outside Air: 14,398 Btuh Total Cooling Required With Outside Air: 3.14 Tons Z:\ ...\SLCSO Visitation Building Heat Load.CH8 Thursday, October 29, 2020, 03:06 PM