HomeMy WebLinkAboutTSP55277 DENZIL VELARDE 02 01 2021 plans stamp 2 2 2021SYSTEM CAPACITY: 20.13 KW DC / 14.64 KW AC PV PANELS: (61) Q.PEAK DUO-G5 330W BY Q.CELL COMBINER: (1) IQ COMBINER 3 BY ENPHASE INVERTER: (61) IQ7 BY ENPHASE RACKING SYSTEM: CROSSRAIL 48-XL BY EVEREST OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL COVER SHEET C-1 1 PROJECT LATITUDE PROJECT LONGITUDE WIND EXPOSURE MIN AMBIENT TEMP MAX AMBIENT TEMP AHJ 27.551449 -80.413055 º C MAX WIND SPEED PROJECT DESCRIPTION C-1 COVER SHEET E-1 E-2 S-1 S-2 D-1 PV MODULES DATA SHEET GENERAL NOTES C 157 ST. LUCIE COUNTY D-2 D-3 SMART MONITORING DATA SHEET INVERTER DATA SHEET RACKING PLAN SAFETY LABELS STRUCTURAL PLAN ONE LINE RISER DIAGRAM 35 1 º C MPH C-2 SAFETY PLANS ROOF PLAN VIEW / BOS LOCATION1N.T.S. LOCATION MAP / WIND ZONES2N.T.S. IRRADIANCE MAP3N.T.S. 3D RENDERING4N.T.S. DRAWINGS INDEX "PROPERTY SIDE FACING ST R E E T " PROJECT INFORMATION NORTH PV DISCONNECT IQ COMBINER BOX EXISTING ELECTRICAL METER PER FL. STATUTE 377.705 (REVISED 7/1/2017), I RAFAEL A. GONZALEZ SOTO, P.E. 83104 AN ENGINEER LICENSED PURSUANT TO CHAPTER 471, CERTIFY THAT THE PV ELECTRICAL SYSTEM AND ELECTRICAL COMPONENTS ARE DESIGNED AND APPROVED USING THE STANDARDS CONTAINED IN THE MOST RECENT VERSION OF THE FLORIDA BUILDING CODE. APPLICABLE CODES: 2020 FLORIDA BUILDING CODE 7TH EDITION, ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES, NEW ELECTRICAL CODE, NFPA 70 AND NEC 2017. ALL WIND DESIGN CRITERIA AND PARAMETERS ARE FOR HIP AND GABLE RESIDENTIAL ROOFS, CONSIDERING FROM A 7° TO A MAXIMUM 27° (2/12 TO A MAXIMUM 6/12 PITCH ROOF IN SCHEDULE. ALL RESIDENTIAL ROOFS SHALL NOT EXCEED 30'-0" MEAN ROOF HEIGHT. ROOF SEALANTS SHALL CONFORM TO ASTM C920 AND ASTM 6511, AND IT IS RESPONSIBILITY OF THE CONTRACTOR TO PILOT FILL ALL HOLES. CONTRACTOR SHALL ENSURE ALL ROOF PENETRATIONS TO BE INSTALLED AND SEALED PER 2020 FLORIDA BUILDING CODE 7TH EDITION OR LOCAL GOVERNING CODE. ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE (NEC) 2017, LOCAL STATE CODES, AND OTHER APPLICABLE LOCAL CODES. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER CONDUCTORS IN THE BUILDING. CONNECTORS TO BE TORQUED PER DEVICE LISTING, OR MANUFACTURERS RECOMMENDATIONS. NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING. REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMANENTLY ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS, LABELS SHALL COMPLY WITH ARTICLE 690 VI OF THE NEC 2017 OR OTHER APPLICABLE STATE AND LOCAL CODES. SEE LABELS AND MARKING PAGE FOR MORE INFORMATION. RACKING ROOF MOUNT SYSTEM SHALL BE INSTALLED FOLLOWING MANUFACTURERS INSTRUCTION SPEC'S, INCLUDING ALL GROUNDING WEEB CLIPS, GROUND LUGS, AND RAIL SPLICE KITS FOR ELECTRICAL CONTINUITY. MECAWIND TOOL IS BASED ON THE C&C WIND LOADS FOR ENCLOSED BUILDINGS. DESIGN WIND PRESSURES ARE CALCULATED USING ASCE 7-16 EQUATION 30.6-1. ALL NOTES IN FIGURES ASCE 7-16 30.4-1 AND 30.4-2(A,B AND /67C) HAVE BEEN INCORPORATED. MEAN ROOF HEIGHT MUST BE LESS THAN 60 FEET. NORTH SAFETY PLAN C-2 2 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL NOTES: 1.INSTALLERS SHALL DRAW IN DESIGNATED SAFETY AREA AROUND HOME 2.INSTALLERS SHALL UPDATE NAME ADDRESS AND PHONE NUMBER OF NEAREST URGENT CAR FACILITY RELATIVE TO THE SITE BEFORE STARTING WORK NAME: LOCATION OF NEAREST URGENT CARE FACILITY ADDRESS: PHONE NUMBER: SAFETY PLAN1N.T.S. "PROPERTY SIDE FACING STREET" PV DISCONNECT COMBINER BOX EXISTING ELECTRICAL METER 6 2320$ 2320$ 2320$ 2320$ -% 4 1EM$3R 5 PV RAILS TO BE BONDED WITH #8 BARE WIRE BRANCH #1 1 3 A1.1 A1.2 A1.3 A1.4 A1.5 A1.6 A1.7 A1.8 A1.9 A1.10 A1.11 B1.12 B1.13 B1.14 B1.15 B1.16 1 B1.1 B1.2 B1.3 B1.4 B1.5 B1.6 B1.7 B1.8 B1.9 B1.10 B1.11 B1.12 B1.13 B1.14 B1.15 BRANCH #2 2 B1.8 C1.9 C1.10 C1.11 C1.12 C1.13 C1.14 C1.15 2 1 B1.1 B1.2 B1.3 B1.4 B1.5 B1.6 BRANCH #3 2 B1.7 D1.8 D1.9 D1.10 E1.11 E1.12 E1.13 E1.14 E1.15 1 C1.1 C1.2 C1.3 C1.4 C1.5 D1.6 BRANCH #4 2 D1.7 3 3 3 FUSED 80A 7 8 9 EXISTING UNDERGROUNG SERVICE 240V/120V 150A BUS BAR 3 #1/0 THWN-2 INVERTER TOTAL OUTPUT: 61A SAFETY RATING (125%): 76.25A TOTAL PV SYSTEM OCPD: 80A MAIN BREAKER RATING: 150A BUS BAR RATING: 150A 120% BACKFEED RATING: 30A METER150$ 11 10 16T+:12*R281' NEMA 3R JUNCTION BOX LEGEND: 1 2 3 5 4 7 8 9 6IQ7 240V MICROINVERTER FROM ENPHASE POWER: 250W, IMAX: 1.25A EFF @240V: 97.5% 2 ENPHASE Q CABLE #12 AWG THWN-2 1 #8 BARED WIRE GROUND 3/4" EMT CONDUIT PV SYSTEM DISCONNECT RATED FOR 100A AIC RATING 100KA 2 #4 L1,L2 THWN-2 1 #4 THWN-2 NEUTRAL 1 #8 THWN-2 GROUND 1" EMT CONDUIT 8 #10 THWN-2 1 #8 THWN-2 GROUND 3/4" EMT CONDUIT ENPHASE IQ COMBINER BOX RATED FOR 125A, NEMA 3R ENCLOSURE WITH SPACE FOR 4 - BREAKER 1" WIDE PER POLE AIC 10KA - SEE D-2 PV INTERCONNECTION POINT REFER TO DWG D-3 DATE SHEET EXISTING UTILITY ELECTRICAL METER AND MAIN BREAKER 10 11 2 #4 L1,L2 THWN-2 1 #4 THWN-2 NEUTRAL 1" EMT CONDUIT (61) Q.PEAK DUO-G5 330W BY Q.CELL REFER TO SHEET D-1 WIRE SIZES, QUANTITY & TYPE RACEWAY SIZE, TYPE, LOCATION & INFO.WIRE AMPACITY CALCULATIONS ADDITIONAL INFORMATION WIRE TAG CONDUCTOR QTY. SIZE & TYPE NEUTRAL QTY. SIZE & TYPE GROUND QTY. SIZE & TYPE RACEWAY SIZE & TYPE RACEWAY LOCATION RACEWAY HEIGHT ABOVE ROOF OUTPUT CURRENT 125% OF OUTPUT CURRRENT MIN OCPD WIRE DE-RATED CALCULATION DIST.VOLTAGE VOLTAGE DROP % CONDUIT FILL %WIRE RATING AMBIENT TEMP # OF COND. FINAL AMPACITY AC.1 (BEFORE JB) AC.2(FROM JB TO COMBINER BOX) AC.3(FROM COMBINER BOX TO SERVICE) (2)Q CABLE #12 AWG THWN-2 (4) #10 AWG THWN-2 (2) #4 AWG THWN-2 N/A N/A (1) #4 AWG THWN-2 (1) #8 AWG BARE COPPER (1) #8 AWG THWN-2 (1) #8 AWG THWN-2 NOT APPLICABLE 3/4" EMT CONDUIT 1" EMT CONDUIT UNDER ARRAY ABOVE ROOF EXTERIOR WALL 1/2" TO 3-1/2" 1/2" TO 3-1/2" "N/A" 13A 13A 61A 16.25A 16.25A 76.25A 20A 20A 80A 40A X 0.76 X 1 = 30.4 A 40A X 0.76 X 0.8 = 24.3 A 95A X 0.76 X 1 = 72.2 A 10 FT. 20 FT. 5 FT. 350V 350V 240V 0.11% 0.21% 0.1% 6.4% 8.1% 7.7% OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL ONE LINE RISER DIAGRAM E-1 3 ONE LINE RISER DIAGRAM1N.T.S. LABEL LOCATION: AC DISCONNECT, POINT OF INTERCONNECTION PER CODE: NEC 690.13 (B) LABEL LOCATION: AC DISCONNECT, MAIN PANEL PER CODE: NEC 110.27 (C) OSHA 1910.145(f)(7) WARNING ELECTRICAL SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING TURN OFF PHOTVOLTAIC AC DISCONNECT PRIOR TO WORKING INSIDE PANEL DO NOT DISCONNECT UNDER LOAD WARNING POWER SOURCE OUTPUT CONNECTION. DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING: PHOTOVOLTAIC POWER SOURCE CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SYSTEM SHUTDOWN MAIN PHOTOVOLTAIC SYSTEM DISCONNECT LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.15, NEC 690.13(B) WARNING SECOND SOURCE IS PHOTOVOLTAIC SYSTEM DUAL POWER SOURCE SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION, TO SHUTDOWN CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS WITHIN ARRAY REMAIN ENERGIZED IN SUNLIGHT SOLAR ELECTRIC PV PANELS PHOTOVOLTAIC AC DISCONNECT RATED AC OUTPUT CURRENT: NOMINAL OPERATING AC VOLTAGE: 61 A 240V MAXIMUM VOLTAGE MAXIMUM CIRCUIT CURRENT MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED) 480 VDC 16 A 240 V 60 HZ MAXIMUM AC POWER NOMINAL OPERATING AC FREQUENCY MAXIMUM AC CURRENT NOMINAL OPERATING AC VOLTAGE 14.64 KW 61 AMPS MAX OVERCURRENT DEVICE RATING FOR AC MODULE PROTECTION 15 AMPS N/A LABEL LOCATION: AC DISCONNECT PER CODE: NEC 690.13 (B) LABEL LOCATION: MAIN SERVICES DISCONNECT, DC CONDUIT PER CODE: NEC 690.31 (G) (3) LABEL LOCATION: INVERTER PER CODE: NEC 690.53 LABEL LOCATION: AC DISCONNECT PER CODE: NEC 690.54 LABEL LOCATION: INVERTER PER CODE: NEC 690.52 LABEL LOCATION: MAIN SERVICE PANEL PER CODE: NEC 690.45(B)(5) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 705.12 (B)(3) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 705.12(B)(2)(3)(b) LABEL LOCATION: POINT OF INTERCONNECTION PER CODE: NEC 690.33(E)(2) & NEC 690.15 (C) SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION, TO SHUTDOWN CONDUCTORS OUTSIDE THE ARRAY. CONDUCTORS WITHIN ARRAY REMAIN ENERGIZED IN SUNLIGHT SOLAR ELECTRIC PV PANELS LABEL LOCATION: AC DISCONNECT, MAIN PANEL PER CODE: NEC 690.56(C)(3) LABEL LOCATION: AC DISCONNECT, MAIN PANEL PER CODE: NEC 690.56(C)(3) LABEL LOCATION: AC DISCONNECT POINT OF INTERCONNECTION PER CODE: NEC 690.56(C) CAUTION PHOTOVOLTAIC SYSTEM CIRCUIT IS SUPPLY SIDE SAFETY LABELS E-2 4 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL PV SAFETY LABELS DATA1N.T.S. UPDATED SYSTEM DESCRIPTIONA 01-29-2021 A NORTH EXISTING ELECTRIC METER COMBINER BOX PV DISCONNECT OBS OBS OBS OBS OBS OBS OBS OBS A1.11 A1.1 B1.12 B1.16 B2.1 B2.15 B3.1 B3.8 C3.9 C3.15 C4.1 C4.5 D4.6E4.15 D4.10E4.11 ARRAY B TILT=20º AZIMUTH= 183º (S) ARRAY A TILT=20º AZIMUTH= 183º (S) ARRAY C TILT=20º AZIMUTH= 3º (N) ARRAY D TILT=20º AZIMUTH= 93º (E) ARRAY E TILT=20º AZIMUTH= 273º (W) SOLAR MODULE - TYP. SEE 2-1 ROOF MOUNTS LOCATED AT CENTER OF ROOF TRUSS - TYP. WOOD TRUSSES/RAFTERS LOCATION - INSTALLER MUST VERIFY IN FIELD 4' 4' 66.34" 39.37" Q.PEAK DUO-G5 330W UL 1703 CERTIFIED MAX. PV MODULE SURFACE LOAD: 113.00 psf APPLIED WIND LOAD: 68.68 psf NOTES: -INSTALL MID CLAMPS BETWEEN MODULES AND ENDS CLAMPS AT THE END OF EACH ROW OF MODULES. -ALUMINUM RAILS SHOULD ALWAYS BE SUPPORTED BY MORE THAN ONE FOOTING ON BOTH SIDES OF THE SPLICE. RISK CATEGORY ZONES 1 2r 2e (PSF) PRESSURES SPAN (FT) MAX. CANTILEVER (IN) MAX. EXPOSURE CATEGORY ROOF SLOPE (°) ROOF TYPE ULTIMATE WIND SPEED NOMINAL WIND SPEED mph mph PRESSURE ZONE: MEAN ROOF HEIGHT: PERIMETER WIDTH: KD KZT KH VELOCITY PRESSURE (q) = 0.60*0.00256* KHKZTKDV2 EXTERNAL PRESSURE COEFFICIENT Z1 EXTERNAL PRESSURE COEFFICIENT Z2e EXTERNAL PRESSURE COEFFICIENT Z2n TOTAL ROOF AREA sq.-ft sq.-ft TOTAL MODULES: TOTAL PHOTOVOLTAIC AREA: WIND LOAD (PSF): TOTAL WIND LOAD (LBS): TOTAL ROOF MOUNTS: TENSION FORCE PER MOUNT (LBS): INTERNAL PRESSURE COEFFICIENT 0.18 2n 3e 3r EXTERNAL PRESSURE COEFFICIENT Z2r EXTERNAL PRESSURE COEFFICIENT Z3e EXTERNAL PRESSURE COEFFICIENT Z3r 49.74 49.74 79.34 79.34 79.34 111.91 4 2 2 2 N/A N/A - - - - - - ' ' ' ' 16 8 8 8 N/A N/A " " " " 0.7 0.7 0.7 0.7 0.7 0.7 -1.5 -1.5 -2.5 -2.5 -2.5 -3.6 VELOCITY PRESSURE (ASD) 29.99 175 157 II C 20 GABLED 1&2 23.35 4.0 0.85 1.0 0.849 4,557.00 61 1,106.39 -68.68 -75,986.87 174 -436.71 OBS ROOF OBSTRUCTIONS PV MODULES TRUSSES OR RAFTERS ROOF MOUNTS & RAIL ROOF SLOPE XX.X ARRAY # STRING # MODULE # STRUCTURAL PLAN S-1 5 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL STRUCTURAL ROOF PLAN & PV MODULES LAYOUT1N.T.S. SOLAR MODULE N.T.S.2 LEGEND & SYMBOLS WEIGHTED AVERAGE WORST CASE MODULE: ZONE 1: 36% ZONE 2: 64% (0.36) + (0.64) = psf49.74 79.34 68.68 ROOF'S GENERAL NOTES: 1- CONTRACTOR/INSTALLER TO VERIFY ROOF CONDITIONS FOR PROPER INSTALLATION OF THE PV SYSTEM. 2- CONTRACTOR/INSTALLER TO NOTIFY THE OWNER IMMEDIATELY OF ANY ROOF DEFICIENCIES AND/OR REPAIR REQUIRED TO INSTALL THE PV SYSTEM. 3- EOR DOES NOT ASSUME ANY RESPONSIBILITY FOR THE INSTALLATION OF ANY PV SYSTEM ON DEFICIENT ROOFS. 4-CONTRACTOR/INSTALLER ASSUMES ALL RESPONSIBILITY TO INSTALL AS PER MANUFACTURER STANDARDS. UPDATED CALCULATIONSA 01-29-2021 A A A OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL RACKING PLAN S-2 6 SHINGLE ROOF MOUNT DETAIL & DATA1N.T.S. SOLAR MODULE REFER TO SHEET D-1 EVEREST CROSSRAIL (48-XL VERSION) REFER TO DATA SHEET 6'' TYP.2'' CLEARANCE TYP . 1/4" SS 18-8 BOLT 1/4" SS SERRATED FLANGE NUT REFER TO DATA SHEET ATTACHMENT DIAGRAM 2 ROWS OF RAILS PER MODULE CROSSRAIL END CLAMP L-FOOT ASCE 7-16 Velocity Pressure qz10 = 0.00256Kz Kzt Kd V2 Where: qz10 = ASCE 7-16 velocity pressure evaluated at mean roof height (psf) Kz = velocity pressure exposure coefficient Kzt = topographic factor Kd = wind directionality factor V = basic wind speed (mph) from ASCE 7-16 maps referred to as ultimate wind speed maps in 2020 FBC. As an example, for an array having an area of 158.04 sq.-ft., the total uplifting (resultant) force acting on the array would be -39.1 psf x 158.04 sq. ft. = -6,179.364 lb. Knowing this resultant force, the design engineer can now determine the number of attachment points and the size of the mounting hardware necessary to safely carry this load. Live Loads: Live loads associated with photovoltaic systems are usually assumed to be distributed uniformly and are small, on the order of 4 psf or less. Lag Screw Installation Guidelines 1. Determine location for the Mount on roof by drilling through the center of truss from bottom with 5/32" drill bit. 2. Mark mounting holes for Mount on underlayment. Mounting holes should be centered on the trusses. 3. Drill 15/64" pilot hole. 4. Apply sealant to bottom of Mount. 5. Place Mount over roof underlayment with holes in roof. 6. Apply sealant to bottom of Mount, apply sealant to lag screws and fasten Mount securely to trusses. 7. Apply additional sealant to top assembly to be sure all penetrations are sealed. Notes: (1) Thread must be embedded in the side grain of a Trusses or other structural member integral with the building structure. (2)Lag Bolts must be located in the middle third of the structural member. (3)These values are not valid for wet services. (4)This table does not include shear capacities. If necessary, contact a local engineer to specify lag bolt size with regard to shear forces. (5)Install lag bolts with head ad washer flush to surface (no gap). Do nor over-torque. (6)Withdrawal design values for lag screw connections shall be multiplied by applicable adjustment factors if necessary. See table 10.3.1 in the American Wood Council NDS for Wood Construction. ROOF DECK S-5 BRACKET PULL OUT CALCULATIONS Ultimate Pull Out Strength per Clamp 798 lbs Max. Pull Out Strength Required per Clamp 436.71 Allowable Clamp Pull Out Strength Safety Factor 1.83 DISTRIBUTED LOAD CALCULATIONS PV MODULES & RACKING WEIGHT = (INDIVIDUAL MODULE WEIGHT + 3.5 LBS) * (MODULE QTY) = (44.73 LBS) * (61) = 2,728.31 LBS PER SQUARE FEET (PSF) ARRAY LOAD = PV MODULES & RACKING WEIGHT / TOTAL ARRAY AREA = 2,728.31 LBS / 1,106.39 SQFT = 2.47 PSF HENCE, ROOF WILL CARRY THE ADDITIONAL SOLAR SYSTEM LOAD EVEREST CROSSRAIL 48-XL FLUSH MOUNT SYSTEM SPAN TABLE (inches) 60 CELLS PORTRAIT OR LANDSCAPE EXPOSURE C ROOF SLOPE (degs.) WIND SPEED (mph) GROUND SNOW: 0 psf ZONE 1 (inches) ZONE 2 (inches) ZONE 3 (inches) 7°-27° 110 94 80 65 115 92 76 62 120 91 72 59 130 86 67 55 140 81 62 51 150 77 58 48 160 72 54 44 170 67 51 42 180 64 48 39 UPDATED DETAIL & CALCULATIONSA 01-29-2021 A PV MODULES DATASHEET D-1 7 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL SMART MONITORING DATASHEET D-2 8 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL INVERTER DATASHEET D-3 9 OF 9 12221 N US HIGHWAY 301 THONOTASASSA, FL 33592 (813) 982 -9001 #EC13008093 CONTRACTOR CONTACT INFORMATION REV DESCRIPTION CONTRACTOR LOGO DATE ENGINEERING STAMPENGINEER CONTACT INFORMATION C.A.32661 255 GIRALDA AVE CORAL GABLES, FL 33134 DESIGN@ENGIPARTNERS.COM 786 - 393 - 4740 DENZIL VELARDE 10-16-2020 8704 CITRUS PARK BLVD, FORT PIERCE, FL, 34951 SHEET TITLE: SHEETS: ENG. RAFAEL A. GONZALEZ SOTO, PE SHEET NAME: PROJECT ADDRESS: CUSTOMER: ENGINEER OF RECORD: DATE: 1301-610-0085-000-9 PARCEL NUMBER: PROJECT ID: TSP55277 ISSUED FOR PERMIT 10-21-2020 ENGIPARTNERS, LLC TITAN SOLAR POWER FL