FL# FL1654-R20
Application Type Revision
Code Version 2014
Application Status Approved
Comments
Archived O
Product Manufacturer POLYGLASS USA
• Address/Phone/Email 150 Lyon Drive
Fernley, NV 89408
(570)384-1230 Ext 242
jakins@polyglass.com
Authorized Signature James Akins
jakins@polyglass.com
Technical Representative Steve Wadding
Address/Phone/Email 150 Lyon Drive
Fernley, NV 98408
(602)363-7139
stevew@polyglass.com
Quality Assurance Representative James Akins
Address/Phone/Email 555 Oakridge_Road
Humboldt Industrial Pkwy
Hazleton,PA 18201
(800)894-4563
jakins@polyglass.com
Category Roofing
Subcategory Modified Bitumen Roof System
Compliance Method Evaluation Report from a Florida Registered Architect or a Licensed
Florida Professional Engineer
O Evaluation Report-Hardcopy Received
Florida Engineer or Architect Name who developed Robert Nieminen
the Evaluation Report
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 10/06/2018
Validated By John W. Knezevich, PE
0 Validation Checklist-Hardcopy Received
Certificate of Independence FL1654 R20 COT 2017 01 COI Nieminen.odf
Referenced Standard and Year(of Standard) Standard Year
ASTM D6162 2000
ASTM D6163 2000
ASTM D6164 2005
ASTM D6222 2008
ASTM D6509 2009
FM 4470 1992
FM 4474 2004
UL 1897 2008
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method Method 1 Option D
Date Submitted 02/15/2017
Date Validated 02/16/2017
Date Pending FBC Approval 02/18/2017
Date Approved 04/04/2017
Summary of Products
FL# Model,Number or Name Description
1654.1 Polyglass SBS and APP Modified SBS and APP modified bitumen roof systems
Bitumen Roof Systems
Limits of Use Installation Instructions
Approved for use in HVHZ:No FL1654 R20 II 2017 02 FINAL At ER POLYGLASS MODBIT FL1654-
Approved for use outside HVHZ:Yes R20.Ddf
Impact Resistant:N/A Verified By: Robert Nieminen PE-59166
Design Pressure:+N/A/-622.5 Created by Independent Third Party: Yes
Other: 1.)The design pressure in this application Evaluation Reports
relates to one particular assembly over concrete FL1654 R20 AE 2017 02 FINAL ER POLYGLASS MODBIT FL1654-
deck. Refer to the ER Appendix for other systems and R20.Ddf
deck types. 2.)Refer to ER,Section 5 for other Limits Created by Independent Third Party:Yes
of Use.
Back Next
Contact Us::2601 Blair Stone Road,Tallahassee FL 32399 Phone:850-487-1824
The State of Florida is an AA/EEO employer.Copyright 2007-2013 State of Florida.::Privacy Statement::Accessibility Statement::Refund Statement
Under Florida law,email addresses are public records.If you do not want your e-mail address released in response to a public-records request,do not send electronic
mail to this entity.Instead,contact the office by phone or by traditional mail.If you have any questions,please contact 850.487.1395.*Pursuant to Section
455.275(1),Florida Statutes,effective October 1,2012,licensees licensed under Chapter 455,F.S.must provide the Department with an email address if they have
one.The emails provided may be used for official communication with the licensee.However email addresses are public record.If you do not wish to supply d'
personal address,please provide the Department with an email address which can be made available to the public.To determine if you are a licensee under Chapter
455,F.S.,please click here.
Product Approval Accepts:
om® rCbid MW
Credit Card
Safe
�TRINITYIERD
j-,'kPPENDix'l:'ATTAcHMENT.REQUIREMENTS'FOff.WlNci'UpLiFT.,RESIST4r4CE,.'--.--
Table Deck Application Type Description Page
1A Wood New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 5
1B-1 Wood New or Reroof(Tear-Off) A-2 Mech.Attached Anchor Sheet Bonded Insulation,Bonded Roof Cover 5-9
IB-2 Wood New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet Bonded Insulation,Bonded Roof Cover 10-11
1C Wood New,Reroof(Tear-Off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 12
1D Wood New,Reroof(Tear-Off)or Recover C Mech.Attached insulation,Bonded Roof Cover 13-14
1E Wood New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover 15-16
IF-1 Wood New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet(nails),Bonded Roof Cover 17-19
IF-2 Wood New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet(screws&plates),Bonded Roof Cover 20-22
1G Wood New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 22
2A Steel or Structural concrete New,Reroof(Tear-off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 23-26
2B Steel or Structural concrete New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 27-29
2C Steel or Structural concrete New,Reroof(Tear-Off)or Recover D Prelim.Attached Insulation,Mech.Attached Base Sheet,Bonded Roof Cover 30-31
3A Structural concrete New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 32-38
3B Structural concrete New or Reroof(Tear-Off) F Non-Insulated,Bonded Roof Cover 38
4A LWIC New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 39-40
4B LWIC New or Reroof(Tear-off) A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 41
4C LWIC New or Reroof(Tear-Off) E Non-Insulated,Mech.Attached Base Sheet Bonded Roof Cover 42-44
SA CWF New or Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof-Cover 45
SB CWF New,Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover 46
5C CWF New,Reroof(Tear-off)or Recover B Mech.Attached Base Insulation,Bonded Top Insulation,Bonded Roof Cover 47
5D CWF New,Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 47
5E CWF New,Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 47
6A Gypsum Reroof(Tear-Off) A-1 Bonded Insulation,Bonded Roof Cover 48-50
613 Gypsum Reroof(Tear-Off)or Recover A-2 Mech.Attached Anchor Sheet,Bonded Insulation,Bonded Roof Cover so
6C Gypsum Reroof(Tear-Off)or Recover C Mech.Attached Insulation,Bonded Roof Cover 51
ED Gypsum Reroof(Tear-Off)or Recover E Non-Insulated,Mech.Attached Base Sheet,Bonded Roof Cover 51
•
7A Various Recover A-1 Bonded Insulation,Bonded Roof Cover 52-55
7B Various Recover F Non-Insulated,Bonded Base Sheet,Bonded Roof Cover 55
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above-deck roof components. Roof decks and structural members shall be In accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Insulation/base sheet fasteners shall be of sufficient length for the following deck engagement:
>Wood: Minimum 0.75-inch penetration.
>Steel: Minimum 0.75-Inch penetration and engage the top flute of the steel deck.
>Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
3. Unless otherwise noted,insulation may be any one layer or combination of polylsocyanurate, polystyrene,wood fiberboard, perlitei, gypsum-based roof board or mineral-wool roof board that meets the QA
requirements of F.A.C.Rule 61G20-3 and is documented as meeting FBC 1505.1 and,for foam plastic,FBC Chapter 26,when Installed with the roof cover.
Exterior Research and DesIM U.C.d/b/a Trinity[ERD Evaluation Report 99290.02.08-1118 for FL1654-1120
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION Revision 18:02/15/2017
Prepared by: Robert Nierninen,PE-59166 Polyglass USA,Inc.;(570)384-1230 Appendix 1,Page 1 of 55
QO
TRINITY I ERD
4. Minimum 200 psi,minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D(mechanically attached base sheet,bonded roof cover),whereby the base
sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and
structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5. Unless otherwise noted,insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application;the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ Hot asphalt(HA): Full coverage at 25-30 Ibs/square.
➢Dow Insta-Stik Roofing Adhesive(D-IS): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c.
➢Millennium One Step Foamable Adhesive(M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c.
➢Millennium PG-1 Pump Grade Adhesive(M-PG1): Continuous 0.25 to 0.5-inch wide ribbons,12-inch o.c.
➢OMG OlyBond 500(OB500): Continuous 0.75 to 1-inch wide ribbons,12-inch o.c.(PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced.
➢OlyBond Classic(OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive&Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons,12-inch o.c.
➢Note: When multiple layers(s)of insulation and/or coverboard are installed in ribbon-applied adhesive,board joints shall be staggered.
➢Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
6. Unless otherwise noted,all insulations are flat-stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum
Design Pressure(MDP)limitations. In no case shall these values be used to'increase'the MDP listings in the tables;rather if MDP listing below meets or exceeds that listed for a particular system in the tables,then
the thinner board listed below may be used as a drop-in for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive(M-OSFA): MDP -157.5 psf (Min.0.5-inch thick)
➢ Millennium PG-1 Pump Grade Adhesive(M-PG1): MDP -157.5 psf (Min.0.5-inch thick)
➢OMG OlyBond 500(OB500): MDP -45.0 psf (Min.0.5-inch thick Multi-Max FA-3)
➢OMG OlyBond 500(OB500): MDP -187.5 psf (Min.0.5-inch thick ISO 95+GL)
➢OMG OlyBond 500(OB500): MDP -315.0 psf (Min.0.5-inch thick ENRGY 3)
➢OMG OlyBond 500(OB500): MDP -487.5 psf (Min.0.5-inch thick ACFoam II)
➢ICP Adhesives&Sealants CR-20: MDP -117.5 psf (Min.1.0-inch thick)
7. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
8. For mechanically attached components or partially bonded insulation,the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16,and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated,pressure criteria. Commonly used methods are ANSI/SPRI WD-1, FM Loss
Prevention Data Sheet 1-29, RAS 117 and RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29(January 2016)for Zone 2/3
enhancements. •
9. For fully bonded assemblies,the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16,and no rational analysis is permitted.
10. For mechanically attached components over existing decks,fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 orTAS 105.
11. For existing substrates in a bonded recover installation,the existing roof system shall be examined for compatibility and bond performance with the selected adhesive,,and the existing roof system shall be capable of
resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ANSI/SPRI IA-1,ASTM E907, FM Loss
Prevention Data Sheet 1-52 or TAS 124.
12. For Recover Applications using System Type D,the insulation is optional;however,the existing roof system shall be suitable for a recover application.
13. LWIC shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced,refer to current LWIC Product Approval for specific deck
construction and limitations. For systems where specific LWIC is not referenced,the minimum design mix shall be 300 psi. In all cases,the minimum top-coat thickness is 2-inches. For LWIC over structural concrete,
reference is made to FBC Section 1917.4.1,Point 1.
Exterior Research and Design,LLG d/b/a Trinity(ERD Evaluation Report 139290.02.08-1118 for FL3654-R20
Certificate of Authorization k9503 F8C NON-HVHZ EVALUATION Revision 18:02/15/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass USA,Inc.;(570)384-1230 Appendix 1,Page 2 of 55
��TRINITYIERD
14. Unless otherwise noted,refer to the following references for bonded base,ply or cap sheet applications.
'!'r�,TABLE`1`PO11YGGAss:RoOF COVERS 7
Reference Layer Material Application
BP-AA Base Ply One or more plies Polyglass G2 Base,FBC Approved ASTM D4601,Type 11 Hot Asphalt at 20-40
(Base and Ply sheets,Asphalt- Ply One or more plies Polyglass Ply IV,Polyglass Ply V1,FBC Approved ASTM D2178,Type IV or VI lbs/square
Applied) Note: Asphalt-applied sheets or insulation shall not be applied to poly film surfaced membranes.
Base Ply One ply Elastobase(sand/sand),Elastoflex V,Elastoflex 56,Elastoflex S6 Type 11,Polyglass HT Base 650 PG350 at 1.5-2.0
SBS-CAI Cap Ply Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type 11,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield gal/square
TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed)
Base Ply One ply Elastobase(sand/sand),Elastoflex V,Elastoflex S6,Elastoflex S6 Type 11 Polyplus 35 at 1.5-2.0
SBS-CA2 Cap Ply Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type 11,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,Elastoshield gal/square
TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed)
Base Ply or Ply One or more plies Elastobase(sand/sand or poly/sand),Elastobase P(sand/sand or poly/sand),Elastoflex V,Elastoflex S6,Elastoflex
SBS-AA S6 Type 11,Polyglass HT Base 650 Hot Asphalt at 20-40
(SBS,Asphalt-Applied) Cap Ply Elastoflex V,Elastoflex VG,Elastoflex VG FR,Elastoflex 56,Elastoflex S6 Type 11,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G, lbs/square
Elastoshield TS-G FR,Polyfresko G SBS(sand-backed),Polyfresko G SBS FR(sand-backed)
Note: Asphalt-applied sheets or insulation shall not be applied to poly film surfaced membranes.
Base Ply or Ply One or more plies Elastobase(sand/poly),Elastobase(poly/poly),Elastoflex V,Elastoflex S6,Elastoflex S6 Type 11,Polyglass HT Base
SBS-TA 650 Torch-Applied
(SBS,Torch-Applied) Cap Ply Elastoflex V,Elastoflex VG,Elastoflex VG FR,Elastoflex S6,Elastoflex S6 Type 11,Elastoflex S6 G,Elastoflex S6 G FR,Elastoshield TS-G,
Elastoshield TS-G FR,Polyfresko G SBS(poly-film backed),Polyfresko G SBS FR(poly-film backed)
Base Ply One or more plies Elastoflex SA V Base,Elastoflex SA V FR Base,Elastoflex SA V Plus,Elastoflex SA V Plus FR
SBS-SA Cap Ply Elastoflex SA P,Elastoflex SA P FR,Polyreflect Self-Adhering
(SBS,Self-Adhering) Note: Unless otherwise noted,permissible membrane substrates for SBS-SA are limited to the SBS-SA Base Ply options herein,
Elastobase(poly/sand)or Elastobase(poly/poly).
PG350 at 1.5-2.0
APP-CA1 Cap Ply Polyflex G FR gal/square
APP-TA Base Ply or Ply One or more plies Polyglass APP Base,Polyflex,Polybond Torch-Applied
(APP,Torch-Applied) Cap Ply Polyflex,Polyflex G,Polyflex G FR,Polybond,Polybond G,Polyfresko G,Polyfresko G FR
APP-SA Cap Ply Polyflex SA P,Polyflex SA P FR,Polyfresko G SA,Polykool -SA are limited to the SBS-SA Base Ply options herein, Self-Adhering •
(APP,Self-Adhering) Note: Unless otherwise noted,permissible membrane substrates forAPP-SA
Elastobase(poly/sand)or Elastobase(poly/poly).
15. Any of the following FBC Approved coatings may be applied to the top roof membrane without adverse effect on the system wind load performance. Refer to current Roofing Materials Directory for fire ratings
associated with coating usage.
> PG200 Non Fibered Roof Coating;
> PG300 Fibered Roof Coating;
> PG600 Non-Fibered Aluminum Roof Coating;
> PG650 Fibered Aluminum Roof Coating;
> PG700 High Quality Elastomeric Roof Coating or KM Acryl 25;
> PG700QS(Quick Set)High Quality Elastomeric Roof Coating or KM Acryl 25-QS(for granule-surfaced APP or SBS only);
> PG800 Asphalt Emulsion Roof Coating;
> Polyplus 60 Premium Non-Fibered Aluminum Roof Coating;
> Polyplus 65 Premium Fibered Aluminum Roof Coating;
> Polybrite 70 Premium Grade Elastomeric Roof Coating or KM Acryl 15;
Exterior Research and Design,U.C.d/b/a Trinity)ERD Evaluation Report P9290.02.08-1118 for F1.1654-1120
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION Revision 18:02/15/2017
Prepared by: Robert Nleminen,PE-59166 Polyglass USA,Inc.;(570)384-1230 Appendix 1,Page 3 of 55
QO
TRINITY I ERD
➢ Polybrite 70QS(Quick Set)Premium Grade Elastomeric Roof Coating or KM Acryl 15-Q$(for granule-surfaced APP or SBS only);
➢ Polybrite 90 High Solids Silicone Roof Coating or Polybrite 95 Silicone Roof Coating.
16. The following represent priming requirements for gypsum-based coverboards:
➢ Dens Deck and Dens Deck Prime shall be field-primed with PG100 prior to self-adhering or torch-applied membrane application. No priming is required for hot-asphalt membrane applications.
➢ SECUROCK Gypsum-Fiber Roof Board does not require field priming for any membrane application.
17. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure(MDP)limitations. The lesser of the MDP listings below vs.those in Table 3A
applies:
'VOAYOKBARRIEROPTIONS'sTRUCTU r , 'RAL CONCRETE DECK;'ADHERED INSULATIONPERSTABLE 3Ai�: '
Vapor Barrier
Option# Primer Insulation Adhesive MDP(psf)
Type Attach
VB-1. PG100 Elastoflex SA V Plus Self-Adhering Inta-Stik or CR-20,12-inch o.c. -60.0
VB-2. PG100 Polyglass APP Base Torch-applied Inta-Stik or CR-20,12-inch o.c. -75.0
VB-3. PG100 Elastoflex SA P Self-Adhering Insta-Stik,12-inch o.c. -75.0
VB-4. PG100 Elastoflex SA P Self-Adhering Millennium One Step Foamable Adhesive,12-inch o.c. -157.5
VB-5. PG100 Elastoflex SA P Self-Adhering CR-20,12-inch o.c. -270.0
VB-6. PG100 Elastoflex SA V Base,Elastoflex SA V FR Base, Self-Adhering Millennium One Step Foamable Adhesive,Millennium PG-1 Pump Grade -290.0
Elastoflex SA V Plus,Elastoflex SA V Plus FR Adhesive,OlyBond 500 or CR-20,12-inch o.c.
18. "MDP"=Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads.Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design,LLC.d/b/a Trinity(ERD Evaluation Report P9290.02.08-1118 for FL1654-R20
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION Revision 18:02/15/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass USA,Inc.;(570)384-1230 Appendix 1,Page 4 of 55
QOTRINITYIERD
TABLE 1F 2 WOOD.DECKS NEW'CONSTRUMON�REROOF(TEAR OFFJ ORRECOVERT ` ' L= t
„SYSTE.M TYPEE NONi-1NgIL4.A ED'M F!EIN1CAllY`A'i1,ACFiED BASE,Si{EE7'(SCRE�its&`_¢LAiE.$),�B'ONDED:ROOF,,C.OVER '`
System Base Sheet Roof Cover(Note 14) MDP
No. Deck(Note lj Type Fasten Attach Base Ply Cap (pso
25ELF-ADHERING BASE PLY:y, - -
W-134 Min.19/32- Elastobase,Elastobase P Dekfast Hex with Dekfast#14 or Trufast 3"Metal 12-inch o.c.in 4-inch lap and 12-inch o.c.in two SBS-SA SBS-SA,APP-SA,SBS- -52.5'
inch plywood (poly-film top) Insulation Plate with Trufast HD (2),equally spaced,staggered center rows TA,APP TA
Min.19/32- Elastobase,Elastobase P Dekfast Hex with Dekfast#14 or Trufast 3"Metal 12-inch o.c.in 4-inch lap and 12-inch o.c.In two
W-135 Polyflex 5ABase APP-TA -52.5 i
Inch plywood (poly-film top) Insulation Plate with Trufast HD (2),equally spaced,staggered center rows
W-136 Min.19/32- Elastobase,Elastobase P OMG Flat Bottom Plates(square)with Roofgrip#12 12-inch o.c.in 4-inch lap and 12-inch o.c.in two SBS-SA SBS-SA,APP-SA,SBS- _60.0'
inch plywood (poly-film top) (2),equally spaced,staggered center rows TA,APP-TA
W-137 Min.19/32- Elastobase,Elastobase P OMG Flat Bottom Plates(square)with Roofgrip#12 12-inch o.c.in 4-inch lap and 12-inch o.c.in two Polyflex SA Base APP-TA 60.0'
inch plywood (poly-film top) (2),equally spaced,staggered center rows
TABLEaGcx WOOD DECKSNEW"CONSTRUCTION oR REROOF;(TEAR-:OFF);;' °+
;SYSTEM.TYPE F NON-INSULATED,BONDED ROOF C01/ER
System Roof Cover(Note 14) MDP(psf)
No Deck(Note 1) Primer Joint Treatment Base Ply Ply Cap Ply
W-138 Min.15/32- None None SBS-SA (Op BS-SA,SBS- SBS-SA,APP-SA,SBS- _90.0
inch plywood TA,APP-TA TA,APP-TA
W-139 Min.15/32 (Optional)PG100 None
inch plywood Polyflex SA Base (Optional)APP-TA APP-TA 90.0
W-140 Min.15/32- PG100 None SBS-SA (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- _97 5
inch plywood TA,APP-TA TA,APP-TA
Min.15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Elastoflex SA V Base or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- 97 5
W-141 inch plywood (Optional)PG100 place to create continuous bond. Elastoflex SA V FR Base TA,APP-TA TA,APP-TA
W 142 Min.15/32- WB-3000 None SBS-SA (Optional) SBS-SA,APP-SA,SBS- -105.0 •
Inch plywood TA,APP-TA
W-143 Min.15/32- Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into Elastoflex SA V Plus or (Optional)SBS-SA,SBS- SBS-SA,APP-SA,SBS- -135.0
inch plywood (Optional)PG100 place to create continuous bond. Elastoflex SA V Plus FR TA,APP-TA TA,APP-TA,
Min.15/32-
Plywood joints are covered with 4-inch wide strips of Elastoflex SA V Plus,rolled into
W-144 inch plywood (Optional)PG100 place to create continuous bond. Polyflex SA Base (Optional)APP-TA APP-TA 135.0
Exterior Research and Design,U.C.d/b/a Trinity(ERD Evaluation Report P9290.02.08-1118 for FL1654-1120
Certificate of Authorization#9503 FBC NON-HVHZ EVALUATION Revision 18:02/15/2017
Prepared by: Robert Nieminen,PE-59166 Polyglass USA,Inc.;(570)384-1230 Appendix 1,Page 22 0_55