.,FORM R405-2014
LORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
- I Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: THE GRAND CARLTON Builder Name: WYNNE DEVELOPMENT
Street: WYNNE DEVELOPMENT Permit Office: ST. LUCIE COUNTY
City,State,Zip: FT. PIERCE, FL, Permit Number:
Owner: 'aj Jurisdiction:
Design Location: FL,ST_LUCIE_CO_INTL County:: ST.LUCIE COUNTY(Florida Climate Zone 2)
I
1. i ew construction or existing New(From Plans) 9. Wall Types(1437.3 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Ext Insul,Exterior R=4.1 1250.00 ft2
b.Frame-Wood,Exterior R=11.0 187.33 ft2
3. Number of units,if multiple family 1 c.N/A R= ft2
I
d. N/A 2
4. Number of Bedrooms 2 R= ft.
10.Ceiling Types (1446.0 sqft.) Insulation Area
5. ills this a worst case? Yes a. Under Attic(Vented) R=30.0 1446.00 ft2
6. (Conditioned floor area above grade(ft2) 1446 b. N/A R= ft2
11 Conditioned floor area below grade(ft2) 0 c. R= ft2
11.Duct
s R ft2
7. 1 indows(139.2 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6 320
a. U-Factor: Dbl,U=0.54 99.23 ft2
SHGC: SHGC=0.25
b. U-Factor: Dbl,U=0.55 40.00 ft2 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 34.8 SEER:15.00
c. U-Factor: N/A ft2
SHGC: 13.Heating systems kBtu/hr Efficiency
. U-Factor: N/A ft2 a.Electric Heat Pump 34.8 HSPF:8.50
SHGC:
Area Weighted Average Overhang Depth: 3.586 ft.
Area Weighted Average SHGC: 0.250 14.Hot water systems
a. Electric Cap:40 gallons
8. Floor Types (1446.0 sqft.) Insulation Area
a.Slab-On-Grade Edge Insulation R=0.0 1446.00 ft2 b. Conservation features EF:0.970
b.N/A R= ft2 None
.N/A R= ft2 15.Credits Pstat
GI ass/Floor Area: 0.096 Total Proposed Modified Loads: 46.91 PASS
Total Baseline Loads: 48.19
I hereby certify that the plans and specifications covered by Review of the plans and Z$E ST.gT
this calculation are in compliance with the Florida Energy specifications covered by this r�ti►,� _ , �O�
Cotle. calculation indicates compliance
with the Florida Energy Code. rrr,,,.;..,�.,, j�•°.�� „ O
PREPA DY. Before construction is completed
DATE: this building will be inspected for
compliance with Section 553.908
I hereby certify that this building, as designed, is in compliance Florida Statutes. 5�
with the Florida Energy Code. G'OD W'E
OWNER/ T: BUILDING OFFICIAL:
DATE. DATE:
I I
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and an envelope leakage
test report in accordance with R402.4.1.2.
7/6/2017 9:01 AM EnergyGauge@ USA-FlaRes2014 Section R405.4.1 Compliant Software -- -'���� Page 1 of 5
I�
FORM R405-2014
i
PROJECT
Tiitie: THE GRAND CARLTON Bedrooms: 2 Address Type: Street Address
Building Type: User Conditioned Area: 1446 Lot#
Owner: Total Stories: 1 Block/SubDivision:
#!of Units: 1 Worst Case: Yes PlatBook:
Builder Name: WYNNE DEVELOPMENT Rotate Angle: 135 Street: WYNNE DEVELOPME
Permit Office: ST. LUCIE COUNTY Cross Ventilation: No County: ST.LUCIE COUNTY
Jurisdiction: Whole House Fan: No City,State,Zip: FT.PIERCE,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
IECC Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,ST_LUCIE_CO_INTL FL_VERO_BEACH_MUNI 2 39 90 70 75 299 58 Medium
BLOCKS
�INumber Name Area Volume
I
1 Entire House 1446 11568
SPACES
(Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 BEDROOM 234 1872 No 2 1 1 Yes Yes Yes
12 WIC 54 432 No 0 1 No Yes Yes
3 MASTER BATH 63 504 No 0 1 Yes Yes Yes
4 M.BATH 56 448 No 0 1 Yes Yes Yes
5 KITCHEN 172 1376 Yes 0 1 No Yes Yes
6 BATH 45 360 No 0 1 Yes Yes Yes
7 BEDROOM 2 204 1632 No 1 1 1 Yes Yes Yes
8 LAUNDRY 42 336 No 0 1 Yes Yes Yes
9 GREAT/DINING 526 4208 No 0 1 Yes Yes Yes
10 FOYER 50 400 No 0 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio BEDROOM 40 ft 0 234 ftZ ---- 0 1 0
I
2 Slab-On-Grade Edge Insulatio WIC 1 ft 0 54 ftz ---- 0 1 0
i
3 Slab-On-Grade Edge Insulatio MASTER BATH 9 ft 0 63 ft2 ---- 0 1 0
I
4 Slab-On-Grade Edge Insulatio M.BATH 8 ft 0 56 ftz ---- 0 1 0
5 Slab-On-Grade Edge Insulatio KITCHEN 1 ft 0 172 ftz ---- 0 1 0
6 Slab-On-Grade Edge Insulatio BATH 5 ft 0 45 ftZ ---- 0 1 0
I
7SIab-On-Grade Edge Insulatio BEDROOM 2 34.2 ft 0 204 ftz ---- 0 1 0
I
6/2017 9:01 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
I
�I
FORM R405-2014
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
8 Slab-On-Grade Edge Insulatio LAUNDRY 6 ft 0 42 ft2 ---- 0 1 0
I
9 Slab-On-Grade Edge Insulatio GREAT/DINING 47 ft 0 526 ft2 ---- 0 1 0
10SIab-On-Grade Edge Insulatio FOYER 7 ft 0 50 ft2 ---- 0 1 0
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
I I
I
1 Gable or shed Metal 1524 ft2 240 ft2 Light 0.6 No 0.9 No 0 18.4
I I
ATTIC
J # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 1446 ft2 N N
I I
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
i
1 Under Attic(Vented) BEDROOM 30 Blown 234 ft2 0.1 Wood
2 Under Attic(Vented) WIC 30 Blown 54 ft2 0.1 Wood
3 Under Attic(Vented) MASTER BATH 30 Blown 63 ft2 0.1 Wood
4 Under Attic(Vented) M.BATH 30 Blown 56 ft2 0.1 Wood
5 Under Attic(Vented) KITCHEN 30 Blown 172 ft2 0.1 Wood
6 Under Attic(Vented) BATH 30 Blown 45 ft2 0.1 Wood
7 Under Attic(Vented) BEDROOM 2 30 Blown 204 ft2 0.1 Wood
8 Under Attic(Vented) LAUNDRY 30 Blown 42 ft2 0.1 Wood
;I 9 Under Attic(Vented) GREAT/DINING 30 Blown 526 ft2 0.1 Wood
10 Under Attic(Vented) FOYER 30 Blown 50 ft2 0.1 Wood
,I
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
SpaceFt In Et in Area _ o
1 N=>SE Exterior Concrete Block-Ext InsiBEDROOM 4.1 9 0 8 0 72.0 ft2 0 0 0.5 0
2 S=>NW Exterior Concrete Block-Ext InsidEDROOM 4.1 18 0 8 0 144.0 ft2 0 0 0.5 0
_ 3 W=>NE Exterior Concrete Block-Ext Insfi3EDROOM 4.1 13 0 8 0 104.0 ft2 0 0 0.5 0
III
4 S=>NW Exterior Concrete Block-Ext Ins)JASTER BA 4.1 9 0 8 0 72.0 ft2 0 0 0.5 0
5 S=>NW Exterior Concrete Block-Ext InsuM.BATH 4.1 8 0 8 0 64.0 ft2 0 0 0.5 0
1 6 N=>SE Exterior Concrete Block-Ext Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0 0.5 0
7 N=>SE Exterior Concrete Block-Ext Ind3ffDROOM 2 4.1 16 0 8 0 128.0 ft2 0 0 0.5 0
8 E=>SW Exterior Concrete Block-Ext InQEDROOM 2 4.1 10 0 8 0 80.0 ft2 0 0 0.5 0
119 SE=>W Exterior Concrete Block-Ext In!UDROOM 2 4.1 4 3 8 0 34.0 ft2 0 0 0.5 0
10 S=>NW Exterior Concrete Block-Ext InfiffDROOM 2 4.1 4 0 8 0 32.0 ft2 0 0 0.5 0
11 S=>NW Exterior Concrete Block-Ext InsillAUNDRY 4.1 6 0 8 0 48.0 ft2 0 0 0.5 0
i
12 N=>SE Exterior Concrete Block-Ext InsGREAT/DINT 4.1 26 0 8 0 208.0 ft2 0 0 0.5 0
I
I
I
6/2017 9:01 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
ij
FORM R405-2014
WALLS
I
i
Adjacent A Ornt In Wall T-VpeSpace Cavity Width Height Sheathing Framing Solar Below
13 W=>NE Exterior Concrete Block-Ext InsGREAT/DINT 4.1 21 0 8 0 168.0 ft2 0 0 0.5 0
14 N=>SE Exterior Concrete Block-Ext Insul FOYER 4.1 1 0 8 0 8.0 ft2 0 0 0.5 0
15 E=>SW Exterior Concrete Block-Ext Insul FOYER 4.1 6 0 8 0 48.0 ft2 0 0 0.5 0
16 N=>SE Exterior Frame-Wood GREAT/DINT 11 23 5 8 187.3 ft2 0.23 0.5 0
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
II Ft In Ft In
l 1 E=>SW Insulated FOYER None .28 3 6 8 20 ft2
it
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 W=>NE 3 Metal Low-E Double Yes 0.54 0.25 32.4 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
2 S=>NW 5 Metal Low-E Double Yes 0.54 0.25 6.9 ft2 1 ft 0 in 1 ft 4 in None None
3 E=>SW 8 Metal Low-E Double Yes 0.54 0.25 23.2 ft2 1 ft 0 in 1 ft 4 in None None
4 N=>SE 12 Metal Low-E Double Yes 0.54 0.25 36.8 ft2 1 ft 0 in 1 ft 4 in None None
5 W=>NE 13 Metal Low-E Double Yes 0.55 0.25 40.0 ft2 10 ft 0 in 1 ft 4 in None None
I I
i
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 315ft2 315ft2 24ft 8ft 11
!I
INFILTRATION
I
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 1349.6 74.09 139.34 .2669 7
HEATING SYSTEM
V # System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump Split HSPF:8.5 34.8 kBtu/hr 1 sys#1
I I
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 15 34.8 kBtu/hr cfm 0.85 1 sys#1
I
i
I
i
I
i
i
7/6/2017 9:01 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
ii
I '
FDRM R405-2014
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.97 40 gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ft2
I I
DUCTS
---Supply---- ----Return---- Air CFM 25 CFM25 HVAC#
II # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 320 ftz Attic 80 ftZ Default Leakage Attic (Default) (Default) 1 1
TEMPERATURES
Piogramable Thermostat:Y Ceiling Fans:
Coolin Jan Feb Mar Apr [ ]May [X]Jun [X]Jul rl Au JXJ Se [ ]Oct [ ]Nov Dec
Heating Jan Feb f X�Mar f Apr [ ]May E ]Jun [ ]Jul Au SeP [ ]Oct [X]Nov X Dec
ntin Jan Feb X Mar [X)A r [ ]Ma ]Jun [ ]Jul Aug Se �X]Oct (X]Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
Scit�edule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cool ling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Co ling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
He I ting(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
II PM 68 68 68 68 68 68 68 68 68 68 66 66
I
i
i
I
� I
it
I
I
i
7/6/2017 9:01 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
FORM R405-2014
TABLE 402.4.1.1
i AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
i
Project Name: THE GRAND CARLTON Builder Name: WYNNE DEVELOPMENT
i Street: WYNNE DEVELOPMENT Permit Office: ST. LUCIE COUNTY
City,State,Zip: FT.PIERCE,FL, Permit Number:
Owner: Jurisdiction:
Design Location: FL,ST_LUCIE_CO_INTL
I�
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/door jambs and framing and skylights and
framing shall be sealed.
i
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated, and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls,or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
6/2017 9:01 AM EnergyGauge@ USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
I
-FORM R405-2014
!
ENERGY PERFORMANCE LEVEL (EPL)
DISPLAY CARD
i ESTIMATED ENERGY PERFORMANCE INDEX 97
The lower the EnergyPerformance Index, the more efficient the home.
WYNNE DEVELOPMENT, FT. PIERCE, FL,
1. INew construction or existing New(From Plans) 9. Wall Types Insulation Area
a.Concrete Block-Ext Insul, Exterior R=4.1 1250.00 ftz
2. Single family or multiple family Single-family b.Frame-Wood, Exterior R=11.0 187.33 ftz
3. Number of units,if multiple family 1 c. N/A R= ftz
4. Number of Bedrooms 2 d.N/A R= ftz
1 10.Ceiling Types Insulation Area
5. is this a worst case? Yes a. Under Attic(Vented) R=30.0 1446.00 ftz
6. Conditioned floor area(ftz) 1446 b. N/A R= ftz
7. Windows- Description Area c.N/A R= ft
z
a. U-Factor: Dbl, U=0.54 99.23 ftz 11.Ducts R ftz
a.Sup:Attic,Ret:Attic,AH:Attic 6 320
SHGC: SHGC=0.25
b. U-Factor: Dbl, U=0.55 40.00 ftz
11 SHGC: SHGC=0.25 12.Cooling systems kBtu/hr Efficiency
c. U-Factor: N/A ftz a.Central Unit 34.8 SEER:15.00
SHGC:
d. U-Factor: N/A ftz. 13.Heating systems kBtu/hr Efficiency
SHGC: a. Electric Heat Pump 34.8 HSPF:8.50
Area Weighted Average Overhang Depth: 3.586 ft.
,Area Weighted Average SHGC: 0.250
8. Floor Types Insulation Area 14.Hot water systems
z a. Electric Cap:40 gallons
'a.Slab-On-Grade Edge Insulation R=0.0 1446.00 ft EF:0.97
b.N/A R= ftz
c.N/A R= ftz b. Conservation features
None
15.Credits Pstat
it
I ce ify that this home has complied with the Florida Energy Efficiency Code for Building TgE Sr
Construction through the above energy saving features which will be installed (or exceeded) �y0� _ ATFo
in this home before final inspection. Otherwise, a new EPL Display Card will be completed yki',�''�%' r
based on installed Code compliant features.
i
BuilderSignature: Date: NsAz,
Address of New Home: �� ` City/FL Zip: a
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
j mortgage(EEM) incentives if you obtain a Florida EnergyGauge Rating. Contact the EnergyGauge Hotline at(321)
638-1492 or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For
information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support
staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
7/6/2017 9:01 AM EnergyGauge®USA-FlaRes2014 -Section R405.4.1 Compliant Software Page 1 of 1
I�
Project Summary pat.
!- - wlrightsoft Entire House By:
QUICK CALCS,INC.
1817 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax 772.466-6796, Email:QUICKCALCS@}\OL.COM;
i
i
Project • •
For THE GRAND CARLTON
WYNNE DEVELOPMENT, FT. PIERCE, FL
Notes:
Design Information
Weather: Fort Pierce, FL; US
Winter_Design Conditions. Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF - Inside db 75 OF
! Design TD 28 OF Design TD 15 OF
Daily range L
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 17848 Btuh Structure 17520 Btuh
Ducts 5654 Btuh Ducts 8536 Btuh
Central vent(0 cfm): 0 Btuh Central vent(0 cfm) 0: Btuh
Hum(none).
idification 0 .Btuh Blower e) 0 Btuh
Piping 0 Btuh
Equipment load 23503 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 24753 Btuh
j Method Simplified Latent Cooling Equipment Load Sizing
Construction quality- Average
j. Fireplaces 0 Structure 3203 'Btuh
Ducts 2318 Btuh
Central vent(0 cfm) 0' Btuh
Heat' Coolingg: (none).
Area(ft2) 1446 1446 Equipment latent load 5521 Btuh
Volume(ft3) 12511 12511
Air changes/hour 0.45 0.23. Equipment total load 30274 Btuh
Equiv.AVF(cfm) 94 48 Req. total capacity at 0.70 SHR 2.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade CARRIER AIR CONDITIONING Trade_ CARRIER AIR CONDITIONING
Model 25HBC536A*030 Cond 25HBC536A*030
AHRI ref 7914585 Coil FX4DN(B;F)037
AHRI ref 7914585
Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER
Heating input Sensible cooling 24360 Btuh
Heating output 34600 Btuh @ 47°F Latent cooling 10440 Btuh
Temp .erature rise 27 °F Total cooling 34800 Btuh
Actual air flow 1160 cfm Actual airflow 1160 cfm
Airflow factor 0.049 cfm/Btuh Airflow factor - 0.045 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat. Load sensible heat ratio 0.83
Capacity balance point=32 OF
Backup:
Input=7 kW, Output=23009 Btuh, 100 AFUE 1 cc r
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- - wrightsoft` 2017-Apr-11 09:29:38
{ACM Right-Suite®Universal 2.017 17.0.14 RSU08101, Page 1
...uick CalcslDocuments\THE GRAND CARLTON-1446.nup Calc=MJB Front Door faces: N
4 - wrightsofts Right-J®Worksheet ;lob:
Entire House Date:
QUICK CALCS, INC. BY:
j
317 ST LUCIE LN.,FT.PIERCE,FL 34946'Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@a,40L.COM_
1 Room name Entire House BEDROOM
2 Exposed wall. 156.2 ft 49.0 ft
3 Room height 8.7 ft d 8.0 ft heat/cool
4 Room dimensions 1.0 x 297.0 ft
5 Room area 1445.5 ft2 297.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft2-°F) (Btu 2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) .
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A�tocs 0 143 n 4:00 2 55 503 465 1862 1184 72 72 288 183.
4A5 2om.; O.T/0. n'`. 21:56 19:31 38' 0 815 Z30.` 0 0 p 0
13A-4ocs 0.143 a 4.00 2.55 128 83 333 212 0 0 0 0
1Ac1om 1.270 a 35.56 87.29 24 2 848 2082 0 0 0 0
11 �D 11DO 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0
W ';13A-4ocs 0:143 'se. 4:00 2.55 34 34 136 86 .0 0, 0, 0
13A-4ocs 0.143 s 4.00 2.55 360 353 1414 899 216 216 865 550
1Ac1om 1.270 s 35.56 34.77 7 7 247 241 0 0 0 0
13A-4ods 0.143 w. 4.00 2.55 310 -237 949 603 104 72 288 183
1Ac1om. :-1.270 w 35.56 55.21 32 2 1140 1770 32 ;2 1140 1770.
05-tom,. 0.770 w 21[56 19.31 41 41. : 880.;, '. 788 0 0_ 0 0
P 12C Osw. 0.091 - _ 2.55 . _ . 1.28 192 192 489 246 0 0_ 0 0
C 16A30rrtd`' 0.032 090' 2,32 1446 :1446 1295 3354 :;._ 297 _ '297 266 ;:;689
F 22A tpl_ 0.9.89 27.69 0.00 1446 156 4325 0 297 49 1357 0
i
I _
i
i
I
6 c)AED excursion 918 627
Envelope loss/gain 14961 13349 4204 4003
12 a) Infiftation 2887 791 848 232
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 6 1380 3 .690
Appliances/other 2000 0
Subtotal(lines 6 to 13) 17848 17520 5053 4925
Less e#emal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 17848 17520 5053 4925
15 Duct loads 32% 49% 5654 8536 32% 49% 1601 2400
Total room load 23503 26056 6653 7325
`Air required(cfm)' 1160 11601. 328 326
i
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
�.wrightsoft- 2017-Apr-11 09:29:38
' `~cA Right-Suite®Universal 2017 17.0.14 RSUD8101- Page 1
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
I
wrightsoft, Right-M Worksheet Job:
Entire House Date`
QUICK CALCS, INC. By.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-166-6799 Fax 772-466-6796 Email:OUICKCALCS ,AOL.COM
1 Room name WIC KITCHEN
2 •Bip ised wall O ft O ft
3 Room height 8.0 ft heat/cool 8.0 ft heaticool
4 Room dimensions 6.0 x 9.0 ft 1.0 x 172.0 ft
5 Room area 54.0 ft' 172.0 ft2
Ty Construction LI-value ) Or (BtuTM or�peri W) (ft) (Bad Area (ftZ) Load
number (Btuh/ftk-°F. perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A,4c s; 0 143 n j4-W 2.55 0 0 0 0 0 0 0 0
'4A5 tom M-70 n 21.56 .19;31 0 0 0 p a 0 0 0
13A4ocs 0.143 a 4.00 255 0 . 0 0 0 0 0 0 0
1Ac1om 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 l-D 11D0 0 90.3 a 10.92 11.31 0 0 0 0 0 0 0 0
W., 13A4ocs 0`143 se 4.00 255 0 0 0 0 0 0 0 _ 0
VI! 13A4ocs 0.143 s 4.00 255 0 0 0 0 0 0 0 0
�G 1Ac1om 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
13A-0ocs:: 0:143;; w 4.00' 255 0. .0 0 .0 0 0 0 0
1Ac1om: - : 1.270 w 35.56 : 55.21 0 ' 0 0 0 0 0 0- 0
,4A5 2orri:, _ .0.776 w 21.56: 19.31 . .0 . 0 0. .0 0 0.` 0,. 0
P 12C-Osw 0.001 - 2.55 1.28. 0 0 0 0 64 64 163 82
C 16A3
. ' ..
0:032.:•- ;',.0:90 .; 232 ; 54.. -54 :. ' 48:' : 125 ... :..172 172 154 :399
F 22A tpl 0.989 27.69 0.00 54 0 0 0 172 0 0 0
i
i
6 c)AED excursion -9 -170
I
Envelope loss/gain 48 117 317 311
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 2000
Subtotal(lines 6 to 13) 48 117 317. 2311
j Less extemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 48 117 317 2311
15 Duct loads 32% 490/( 15 57 32% 49%1 100 1126
Total room load 64 174 418 3437
Air required(cfm) 3 8 21 153
1E.
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
wrightsoft- 2017-Apr-11 09:29:38
A&k Right-Suite®Universal 2017 17.0.14 RSU08101 Page 2
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Cale=MJ8 Front Door faces: N
1
I
- wrighUoft- RighW@ Worksheet °b
Entire House Date:
QUICK CALLS, INC. By.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@/\OL.COM
1 Room name BATH BEDROOM 2
2 Exposed wall 5.0 ft 34.2 ft
3 Room height 8.0 ft heaticoot 8.0 ft heat/cool
i 4 Room dimensions 9.0 x 5.0 ft 1.0 x 203.5 ft
5 Room are 45.0 ft2 203.5 ft2.
Ty Construction U-value. Or HTM Area (ft2) - Load Area (ft2) Load
number (Btut✓ftz°F) (Btu 2) or perimeter (ft) (Btuh) or perimeter. (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V�/ 13A flocs -Q 143 n, 4:00 2;55 40 40 160 102 128 128 513 326
0 770 . ri .. 2156 . . 1931 0 0 0 0 0° _..0
11 VLZ13A-4ocs 0.143 a 4.00 2.55 0 0 0. 0 80 56 225 143
IA-c1om 1.270 a 35.56 87.29 0 0 0 0 24 2 848 2082
11D0 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W 13A-4ots 0:143 se 4:00 2:55 0 0 0 0 34 -34 136 86
13A-4ocs T—G0.143 s 4.00 2.55 0 0 0 0 32 32 128 81
1A-c1om 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
4 13A4ocs' 0143 w 4;00 255 0 0 0 0 0 0 0 0
1A-clom z1270 w 35:56 55:21 0 0 0 0 0 >0 0 0
4A5.2om 0 770 . w 21.5t 19:31 0 0 0 0` D 0 0 _. . 0:
P 12C-0sw 0.091 2.65 1.28 0 0 0 0 _ 0 0 0 0
C AQA 30md 0 032 .0.90 .2.32' 45 45 40 - 104 204-: 204 162 '472'
F. 22A tpl 0,989 27.69 0.00 45 5 138 . 0 204 34 446 0
!
i
I - _
j . .
I
61 c)AED excursion -16 -85
Envelope loss/gain 339 190 2978 3106
12 a) Infiltration . 87 24 593 162
b) Room ventilation 0 0 - 0 0
13 Internal gains: Occupants @ 230 0 0 1 230
Appliances/other 0 0
i Subtotal Qines 6 to 13) 425 214 3571 . 3498
j Less extemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 425 214 35,71 3498
15 Duct loads 32% 49% 135 104 32% 49%1 1131 1704
. Total room load 560 318 4702 5203
Air required(cfm) 28 14 232 232
I
Calculations approved bVACCA to meet all requirements of Manual J 8th Ed.
wci htsoft'
Right-Suite®Universa12017 17.0.14 RSU08101 2017-Apr-1109:29:38Page 3
.:.uick Calcs\Documents\THE GRAND CARLTON-1446.rup Cale=MJ8 Front Door faces: N
I
I
1
- wrightsofta Right�-J®Worksheet Job:
Entire House Date:
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6769 Fax 772-466-6796 Email:QUICKCALCS ,AOL.COM
1 Room name LAUNDRY GREAT/DINING
2 E)posed wall 6.0 ft 47.0 ft
3 Room height 8.0 ft heat/cool 9.8 ft heaUcool
4 . Room dimensions 7.0 x 6.0 ft 1.0 x 526.0 ft
5 Room area 42.0 ft2 526.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross WP/s Heat Cool
6 13A flocs 0143 n... 4 00 255 . 0 0 0 < p 255 217, 869 ;.552
1 1 4A5-tom: 0.770 n` 21:56 19:31' 0 ' 0 0 0 38 0 815 . 730.
13A-4ocs 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0
—G 1A-c1om 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 �—D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W 13A-4ocs 0143 se 4:00 255 0 0 0 0 0 0 A 0
Val 13A-4ocs 0.143 s 4.00 2.55 48 48 192 122 0 0 0 0
—C' IA-c1om 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
13Aflocs -0.143 w .4.00 2.55 0 0 0 0 206' '165 661 420.
1A-c1om.... 1p270:-w 35:56- ._55.21 0 p p. p p p p p
AA5 2om'-;-, "0 7J0>.w.:. .21.56 '19.31 zb. 0 0 '-0-. 41 41 . 880 78g'
P 12C-Osw. 0.091 .2.55 -1.28 56 56. 143 n 0 0 0 0
C ;76A 30riid ';'- 0`032 r ' :0;90 2 32 42 42"- 38:. 97 526 526 471 1220
F 22A tpl 0.989 27.69 0.00 42 6. 166 0 526 - 47 1302 0
j
i
i
6 c)AED excursion -22 668
Envelope loss/gain 539 270 4997 4379
12 a): Infiltration 104 28 997 273
b) Room ventilation 0 0 01 0
13 Internal gains: Occupants @ 230 0 0 2 460
Appliances/other 0 0
Subtotal(lines 6 to 13) . 643 298 5994 5112
i
Less e)demal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 643 298 5994 5112
15 Duct loads 32% 49% 204 145 32% 49% 1899 2490
Total room load 846 443 7892 7602
Air required(cfm) 42 20 390 338
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
4- wrightsci t- 2017-Apr-11 09:29:38
Right-Suite®Universal 2017 17.0.14 RSU08101 Page 4
...uick CalcslDocuments\THE GRAND CARLTON-1446.rup Cale=MJ8 Front Door faces: N
- wrightsoft Right4@ Worksheet ' Job:
Entire House Date:
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS AOL.COM
1 Room name FOYER M.BATH
2 =ed well 7.0 ft 8.0 ft
3 Room height 8.0 ft I heat/cool 8.0 ft. heat/cool
4 . Room dimensions 1.0 x 50.0 ft 7.0 x. 8.0 ft
5 Room area 50.0 ft2 56.0 ft2.
Ty .Construction U-value Or HTM Area (ft2) Load Area. (ft2) Load
number (Btuh/ftl-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter. (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-0ocs 0.143 n' 4s00` 2 55 8 8 32 20 0 :. 0 0 0
_4A5 tom 0.770 n`:. 21.56 19°31 0 0 0 0_ 0 0. 0 0
13A-400s 0.143 a 4.00 Z55 48 27 108 69 0 0 0 0
1A-c1om 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 11DO 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0
W >13A40cs 0.143 se 4.00 2.55 0 0 0.. 0 0 0 4 1 0
\2/ 13AAocs 0.143 s 4.00 2.55 0 0 0 0 64 57 228 145
---G IA-c1om 1.270 s 35.56 34.77 0 0 0 0 7 7 247 241
13AAocs 0.143 w- 4.00 2.55 0 0 0 0 0- 0 0 0.
1A c1om 1'.270 w` 35.56 55.21; 0 0 0 :'0' 0
4A52om .0.770 .w;" 21:56 19.3t `:::0 0. 0 0 0= b ,0.. . r"A
P 12C-Osw. 0.091-. ,:- . _ 2.55 1.28 72 72 163 92 0 0 0 0
C ;16A30md: 0:032 0 90, . 2 32 60 50` - 45: 11fi..:: 55 56: %50 130
F 224tpl 0.9.89 - 27.69 0.00 50 7 194.. 0 56 8 222 0
I
I .
I
1
6 c)AED e)xursion -39 -38
Envelope loss/gain 792 496 747 478
12 a) Infiltration 121 33 138 38
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
j
Subtotal pines 6 to 13) 913 529 M . 516
Less eMemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 913 529 885 516
15 Duct loads 32% 49% 289 . 258 32% 49% 280 251
Total room load 1202 787 1166 768
Air required(cfm) 59 35 58 34
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft'; Right-Suite®Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page 5
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
i
I'
�- 1 wrightsoft0 Duct System Summary Job,:
Entire House.. By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:.772 466�799:Fax 772 466 6796 Email:QUICKCALCS a�10L.COM
Project
• - • •
I For: THE GRAND CARLTON
WYNNE DEVELOPMENT, FT. PIERCE, FL
i
Heating. Cooling
Extemal static pressure 0.50 in H2O 0.50. in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0.50 in H2O 0.50 in H2O
Supply!return available pressure 0.250/0.250 in H2O 0.250/0.250 in H2O
Lowest friction rate 0.285 in/100ft 0.285 in/100ft
Actual air flow 1160 cfm 1160 cfm
Total effective length(TEL) 176 ft
SupplyDetail Table
i
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln (ft) Trunk
BATH h 560 28 14 0.364 4.0 Ox0 VIFx 22.4 115.0 st1
BEDROOM 2 h 4702 232 232 0.360 7.0 Ox0 VIFx 23.9 115.0 st1
BEDROOM-A h 3327 164 163 0.300 6.0 Ox 0 VIFx 31.8 135.0 st2
BEDROOM-B h 3327 164 163 0.285 6.0 Ox 0 VIFx 40.6 135.0 st2
FOYER h 1202 59 35 0.505 4.0 Ox0 VIFx 4.0 95.0
GREAT/DINING h 3946 195 169 0.300 7.0 ox0 VIFx 31.8 135.0 st2
GREAVDINING-A h 3946 195 169 0.300 7.0 Ox0 VIFx 31.8 135.0 st2
KITCHEN C 3437 21 153 0.379 6.0 Ox0 VIFx 17.0 115.0 st1
LAUNDRY h 846 42 20 0.361 4.0 NO VIFx 23.3 115.0 st1
M.BATH-A h 768 58 34 0 0 OxO . VIFx 0 0
WIC C 174 3 8 0.309 4.0 Ox0 VIFx 27.0 135.0 st2
Supply Trunk Detail Table
i
Trunk Htg Cig Design Veloc Diam H x W Duct
Name Type (Cfm) (Cfm) FR (fpm) (in) (in) Material Trunk
st2 Peak AVF 721 672 0.285 918 12.0 0 x 0 VinlFlx Sid
st1 Peak AVF 1043 1091 0.285 1020 14.0 0 x 0 VinlFlx
i
2017-Apr-11 09:29:38
wrightsoftg Right-Suite®Universal 2017 17.0.14 RSU08101
Page 1
i
Zc ...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
i
I
I
TableReturn Branch Detail
Grille Htg Clg TEL Design Veloc Diam. H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) . (in) Opening (in). Matl Trunk
rb1 OxO . 1160 1160 0 0 0 0 Ox 0 VIFx
I
I
I
i
I
I
I
l
i .
I
I
j
j
i
F
W19 htSOft@ 2017-Apr-11 09:29:38
Right Suite®Universal 2017 17.0.14 RSU08101 Page 2
ACCX ...uick Calcs\Documents%THE GRAND CARJON-1446.rup Calc=MJ8 Front Door faces: N