ENGINEERING MECHANICAL INSPECTION
Mr. Joe Cicio
Building Official
County of Port St. Lucie
RE: Project Address: 230 SW Camino, Port St. Lucie, FI. 33056
Owner: ELI NISIM
Project: GARAGE CONVERSION
Permit: 1705-0380
Contractor: All Construction Systems
Dear Mr. Cicio:
As FOR I have completed the inspection related to the areas under the requirements of
the FBC 2014, 5th Edition, Mechanical in the reference address with the following
comments:
1. The permit card was exposed in working place
2. Energy Calculation according with the equipment installed
3. Notice of commencement in field
4. The duct sealing inspection was done by the Sub-Contractor DIAZ AND
RUSSEL, who certified in a written document attached.
5. The condensate drain and pipes and refrigerant lines, working properly
6. No vibration of the equipment and well insulated
7. Temperature remains daily in 750 Fahrenheit Degrees
8. Mounting compressor fastened accordingly
9. Bathrooms fan per approved fan schedule
10. Smoke detectors interconnected , typical units Kidde hardwire
11. Equipment as per equipment schedule sizes and calculations
12. Thermostat working properly after Battery replacement
I respectfully request\XNI ppprpval of the Mechanical Final Inspection
Cordially \�� RT 0 Cq
\\\\ ��--�x G E W
No17 8 117
ST TE OF
�S*F�O
Alberto Cardona �t ,01V
Consulting Engineer.////I111II11���
F_
ALBERTO CARDONA P.E.P.A.
-` Consulting Engineers
it --
--------------
Miami, FI. Dec. 05/2017
County of Port St Lucie
Building Department
Building Inspector
Mr. Joe Ciccio
Ref
Address: 230 S.E. Camino Street, Port St. Lucie
Folio: . 3419-515-0228-000-0
Permit No. 1705-0380
Owner: ELIIAYALA NISIM
Answers per comments done by Joe Ciccio dated 09/25/2017
1. Envelope leakage testing, duct leakage testing and air barrier inspection
report attached
2. Full Energy calculations Signed and stamped attached
3. Insulation Factor corrected per CBS Exterior walls
4. Window and door flashing shown in page S-01
5. New Mechanical sub-contractor lost form attached
The referred documents to attach to the permit that was is!s e CA,Q���i,
No 17138 7
Very truly yours, r E OF
Alberto ��E����``
Consulting Njirh# rl���
2500 Parkview Dr.Apt.1221,Hallandale Beach,Fl.33009
Ph:(786)252 2131
albertocardonape@gmall.com
Permit`1 `A�10 �h
CONSULTING ENGINEERS5 P.A. ti �c1e
' Certificate of Authorization #31780
- -- 2500 Parkview Drive, Apt. 2414
Hallandale Beach, Fl 33009
-------- --- Ph: (786) 252 2131
JgMN'�"$�18
January 8, 2018 $ nt
Pe
ENGINEERING BUILDING INSPECTION �Sid
Mr. Joe Cicio
Building Official
County of Port St. Lucie
RE: Project Address: 230 SW Camino, Port St. Lucie, Fl. 33056
Owner: ELI NISIM
Project: GARAGE-CONVERSION
Permit: 1176i-
Contractor: All Construction Systems
Dear Mr. Cicio:
As FOR I have completed the inspection related to the areas under the requirements of the FBC
2014, 5th Edition, Building in the reference address with the following comments:
1. The permit card was exposed in working place
2. Notice of commencement in field
3. Slab in concrete of+/- 3000 psi, is existing and looks well poured of 6" supporting
masonry, interior partitions and it was open to install the plumbing pipes
4. Concrete Columns and CBS cells fill with concrete @ max. 48" O.C. per the plans
approved
5. Termite treatment done by SHIP SHAPE PEST CONTROL and a certificate about it
attached to this inspection report, in the slab opening,for a new bathroom.
6. The Drywall was attached with drywall screws to 1"X2" wood_furring on top of CB
walls @24" O.C. basically as sill of new windows.
7. The CB walls in blocks 16"X8"X8"with reinforced ladder typical @ 8" O.C.
8. The Insulation on CB walls was done with Batt R-5 between furring strips on the
interior side of the exterior walls.
9. Windows and doors were not changed and I requested to the General contractor to
install metal storm panels in new windows. A new sheet will be submitted for
approval.
10. Windows and doors flashing as part of the aluminum windows installation shows on
plans
11. Windows and doors as per plans
I respectfully request your ap`�rfulglr?I/he Building Final Inspection
Cordially \���� 10 CARo/i�i
No 1713
017��11 STATE OF �'E ° P
��p �•• L
Alberto Cardona P. F c�OR10P GN
AL
Consulting Engineer. ���js�TON
�/lllllllll\
CONSULTING ENGINEERS, P.A.
Certificate of Authorization #31780
--f 2500 Parkview Drive, Apt. 2414
'i'_' Hallandale Beach, FI 33009
-----------------
Ph: (786) 252 2131
January 8, 2018
ENGINEERING PLUMBING INSPECTION
Mr. Joe Cicio
Building Official
County of Port St. Lucie
RE: Project Address: 230 SW Camino, Port St. Lucie, FI. 33056
Owner: ELI NISIM
Project: GARAGE CONVERSION
Permit: 1705-0380
Contractor: All Construction Systems
Dear Mr. Cicio:
As FOR I have completed the inspection related to the areas under the requirements of
the FBC 2014, 5th Edition, Plumbing in the reference address with the following
comments:
1. The permit card was exposed in working place
2. Notice of commencement in field
3. Drainages working properly.
4. No piping leaks detected
5. Vent pipe on top of roof well installed (6" above roof per FBC-R 3103.1) and
as per plans
6. Fixtures well installed and working as expectations —Minimum clearances
7. Clean out outside adequate in size and separation of the property and
accessible
8. Shower with proper slope
9. Anti —scald shower diverters
10. Water heater drain pan line/size termination point
11. Accessible valves installed
12. Correct minimum pipes sizes of water lines
13. Proper grade of pipes
I respectfully re q�pMV6Ur/aq oval of the Plumbing Final Inspection