FLORIDA ENERGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Envelope Leakage Test Report
Prescriptive and Performance Method
Project Name: 230 Camino Builder Name: ACS
Street: 230 SE Camino St. Permit Office: 607-22-2017
City,State,Zip: Port St. Lucie,FL,33056 Permit Number:1705-0380
Design Location: FL,ST_LUCIE_CO_INTL Jurisdiction: St. Lucie County
Cond.Floor Area:: 1600 sq.ft. Cond.Volume: 12800 cu ft.
Envelope Leakage Test Results Leakage Characteristics
Regression Data: CFM(50):
C: n: R:
ELA:
Single or Multi Point Test Data
HOUSE PRESSURE FLOW: EgLA:
ACH:
SLA:
ACH(50) "
* For prescriptive projects, tested leakage must be
<=7 ACH(50). For performance projects, tested
leakage must be <=the ACH(50) shown on Form
R405-2014 for this project.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air changes per hour
in Climate Zones 1 and 2.Testing shall be conducted with a blower door at a pressure of 0.2 inches w.g.(50 Pascals).Testing shall be conducted by
either individuals as defined in Section 553.993(5)or(7),Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f),(g),or(i)or an
approved third party.A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.Testing
shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other
infiltration control measures;
2.Dampers including exhaust, intake,makeup air,backdraft and flue dampers shall be closed,but not sealed beyond intended infiltration
control measures;
3. Interior doors, if installed at the time of the test,shall be open;
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed;
5. Heating and cooling systems, if installed at the time of the test,shall be turned off;and
6.Supply and return registers, if installed at the time of the test,shall be fully open.
�� ""`ppI I I}J �/ Testing shall be conducted by either
I herebk,�y I&&,� �dde envelope leakage '114E S7.
i individuals as defined in Section C) F
perfodn fie*r� t�tam *e compliance Qti
with l�i�a E er yi Code EGpiMments in 553.993(5)or(7), Florida Statutes or C,ci,
A,, individuals licensed as set forth in ,,,;
ac®r&6ce vlq e�tagn R40�.4=1.2.
* _ Section 489.105(3)(f), (g), or(i)or an .�
STATE F approved third party. A written report
of the results of the test shall be signed
SIGtiE;�� by the third party conducting the test
PRIN + and provided to the code official. COp`yE0
TL�',()I ����� CgtLDofv-A
BUILDING OFFICIAL:
DATE: _ Z = S—I�] _ _. DATE:
- 12/4/2017 4:51 PM EnergyGauge®USA-v5.1 -Section R405.4.1 Compliant Software Page 1 of 1
i R
FORM R405-2014 Duct Leakage Testoort Performance Method
FLORIDA ENERGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Form R405 Duct Leakage Test Report
Performance Method
Project Name: 230 Camino Builder Name: ACS
Street: 230 SE Camino St. Permit Office: 607-22-2017
City,State,Zip: Port St.Lucie, FL,33056 Permit Number: 1705-0380
Design Location: FL ST_LUCIE_CO_INTL Jurisdiction: St.Lucie County
Y
Duct Test Time: Post Construction
Duct Leakage Test Results
CFM25 Duct Leakage Test Values
Line System Outside Duct Leakage
1 System 1 cfm25(Out)
2 System 2 cfm25(Out)
3 System 3 cfm25(Out)
4 System 4 cfm25(Out)
5 Total House Sum lines 1-4
Duct System
Leakage Divide by
(Total Conditioned Floor Area)
(Qn,Out)
\���1111111/�
��\\\\�D C s RQ O//�li
I certify themeC �ea�Cageo�ojde, Qn, is Duct tightness shall be verified b T S7'
not greate); - the r duat*-c*ge Qn y O� = ATE'
specified e�1�of rr1 R0 -2014. testing to Section 803 of the RESNET ,,,.; ,_ 0,6
— * ; L - Standards by either individuals as
.n
,, sT defined in Section 553.993(5)or(7),-10
Florida Statutes, or individuals licensed
SIGNATUR��z O F _a
,c �� as set forth in Section 489.105(3)(t),
�SIOPa��� \\� (g), or(i), Florida Statutes. '♦
PRINTED NAME ��� �\\ +CpD WE
DATE: - S''- ( BUILDING OFFICIAL:
DATE:
12/4/2017 4:52 PM EnergyGauge®USA-v5.1 - Section R405.4.1 Compliant Software Page 1 of'1
I
FQRM R,402-2014 Duct Leakage Test ort Prescriptive Method .
FLORIDA ENE
RGY EFFICIENCY CODE
FOR BUILDING CONSTRUCTION
Duct Leakage Test Report
Prescriptive Method
Project Name: 230 Camino Builder Name: ACS
Street: 230 SE Camino St. Permit Office: 607-22-2017
City,State,Zip: Port St. Lucie,FL,33056 Permit Number: 1705-0380
Design Location: FL,ST_LUCIE_CO_INTL Jurisdiction: St. Lucie County
Duct Leakage Test Results
CFM25 Duct Leakage Test Values
Line System Total Duct Leakage
1 System 1 cfm25(Total)
2 System 2 cfm25(Total)
3 System 3 cfm25(Total)
4 System 4 cfm25(Total)
5 Total House Sum lines 1-4
Duct System
Leakage Divide by
(Total Conditioned Floor Area)
(Qn,Total)
Air Handler Installed at time of test?
(circle one) Yes No
To qualify as"substantially leak free" Qn Total
must be less than or equal to 0.04 if air handler
unit is installed. If air handler unit is not installed
Qn Total must be less than or equal to 0.03.
I hereby ce �\t `0sting Duct tightness shall be verified by q�iE S7
performans� it emkUfra 6mmiance O� AT8
testing to Section 803 of the RESNET �, = s 1 0
with the F6fa En%9yi 99gR requFe dents in Standards by either individuals as
accordali�e*mlh Section R403.2. * _
* = defined in Section 553.993(5)or(7), 41
T T F Florida Statutes,or individuals licensed s — o
SIGNAT as set forth in Section 489.105(3)(f),
p Rio,,- N (g), or(i), Florida Statutes,to be * '
�PRINTED N�i `SSj fl r asubstantially leak fre .
7�® -R AWD _ free.
Cpp �
DATE: Z- _11 BUILDING OFFICIAL:
DATE:
12/4/2017 4:52 PM EnergyGauge®USA-v5.1 - Section R405.4.1 Compliant Software Page 1 of 1
'1
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: 230 Camino Builder Name: ACS
Street: 230 SE Camino St. Permit Office: 607-22-2017
City,State,Zip: Port St. Lucie,FL,33056 Permit Number:1705-0380
Owner. ELI NISSIM JurlsdictiGm St.Lucie County
Design Location: FL,ST_LUCIE_CO_INTL
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings,drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/doorjambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped. .
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit,or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
airtight, IC rated,and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cat neatly to it around wiring and plumbing in
exterior walls, or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
12/4/2017 4:52 PM EnergyGauge®USA-v5.1 -Section R405.4.1 Compliant Software Page 1 of 1
Buil ing Input Summary Report
PROJECT
Title: 230 Camino Bedrooms: 3 Address Type: Street Address
Building Type: User Bathrooms: 0 Lot#
Owner: ELI NISSW Conditioned Area: 1600 sq.ft. BlocklSubDivision:
#of Units: 1 Total Stories: 1 PlatBook:
Builder Name: ACS Worst Case: No Street: 230 SE Camino St.
Permit Office: 607-22-2017 Rotate Angle: 0 County: St.Lucie
Jurisdiction: St.Lucie County Cross Ventilation: No City,State,Zip: Port Si.Lucie,
Family Type: Single-family Whole House Fan: Yes FL, 33056
New/Existing: Addition Terrain: Suburban
Year Construct: 2012 Shielding: Suburban
Comment: Garage Addition
CLIMATE
Design Design Temp Int Design Temp Heating Design Daily Temp
Location Tmy Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL,ST_LUCIE CO INTL FL_VERO BEACH_MUNICIPAL A 39 90 70 75 299 58 Medium
UTILITY RATES
Fuel Unit Utility Name Monthly Fixed Cost $/Unit
Electricity kWh Florida Average 0 0.1145
Natural Gas Therm Florida Average 0 1.82
Fuel Oil Gallon Florida Default 0 1.1
Propane Gallon Florida Default 0 1.4
SURROUNDINGS
Shade Trees Adjacent Buildings
Ornt Type Height Width Distance Exist Height Width Distance
N None Oft Oft Oft Oft Oft Oft
NE None Oft Oft Oft Oft Oft Oft
E None Oft Oft Oft Oft Oft Oft
SE None Oft Oft Oft Oft Oft Oft
S None Oft Oft Oft 0ft Oft Oft
SW None Oft Oft Oft Oft Oft Oft
W None Oft Oft Oft Oft Oft Oft
NW None Oft Oft Oft Oft Oft Oft
BLOCKS
Number Name Area Volume
1 Blockl 1600 12800
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Finished Cooled Heated
1 Main 1600 12800 Yes 4 3 Yes Yes Yes
FLOORS (Total Exposed Area= 1600 sq.ft)
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulation Main 190 ft 0 1600 ft2 ---- 0.2 0 0.8
12/4/2017 4:50 PM EnergyGauge@/USRCZB v5.1 Page 1 of 7
Buil ing Input Summary Report
ROOF
Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 1649 ft2 0 ff2 Medium 0.75 Yes 0.9 Yes 0 14
ATTIC
# Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Unvented 0 1600 ft2 N N
CEILING (Total Exposed Area= 1600 sq.ft.)
# Ceiling Type Space R-Value Ins.Type Area Framing Fraction Truss Type
1 Under Attic Q Main 38 Batt 1600 ft2 0 Wood
WALLS (Total Exposed Area= 1392 sq.ft.)
Wall orientation below is as entered. Actual orientation is modified by rotate angle shown in"Project'section above.
Adjacent Cavity Width Height Sheathing Framing Solar Below
# Ornt To Wall Type Space R-Value Ft In Ft In Area R-Value Fraction Absor. Grade%
1 S Exterior Concrete Block-Jnt JnsuJ Main 4.2 52 8 416.0 ft2 0 0.75 0
2 E Exterior Concrete Block-Int Insul Main 4.2 35 8 280.0 ft2 0 0.75 0
3 N Exterior Concrete Block-Int Insul Main 4.2 52 8 416.0 ft2 0 0.75 0
4 W Exterior Concrete Block-Int Insul Main 4.2 35 8 280.0 ft2 0 0.75 0
Total Exposed Gross Wall Area: 1392 sq.ft. Total Window Area: 434 sq.ft. Total Door Area: 21 sq.ft. Net Wall Area: 937 sq.ft.
DOORS (Total Exposed Area= 21 sq.ft.)
Width Height
# Ornt Adjacent to Door Type Space Storms U-Value Ft In Ft In Area
1 S Exterior Insulated Main None .4 3 7 21 ft2
WINDOWS (Total Exposed Area= 434 sq.ft.)
Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Storm Area Depth Separation Interior Shade Screening
1 S t Metal Double(Tinted) Yes 0.4 0.25 N 24.0 ft2 t ft 6 in 1 ft 4 in IECC Norte
2 E 2 Metal Double(Tinted) Yes 0.4 0.25 N 24.0 ft2 1 ft 6 in 2 ft 0 in IECC 2012 None
3 N 3 Metal Double(Tinted) Yes 0.4 0.25 N 8.0 ft2 1 ft 6 in 1 ft 8 in IECC 2012 None
4 W 4 Metal Double(Tinted) Yes 0.4 0.25 N 24.0 ft2 1 ft 6 in 3 ft 6 in IECC 2012 None
5 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 40.5 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
6 E 2 Metal Double(Tinted) Yes 0.55 0.6 N 32.0 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
7 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 36.0 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
8 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 13.5 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
9 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 8.0 ft2 1 ft 6 in 1 ft 8 in Drapes/blinds None
10 W 4 Metal Double(Tinted) Yes 0.55 0.6 N 10.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
11 E 2 Metal Double(Tinted) Yes 0.55 0.6 N 32.0 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
12 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 13.5 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
13 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 36.0 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
14 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 9.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 2 of 7
Builcting Input Summary Report
WINDOWS (Total Exposed Area= 434 sq.ft.)
Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Storm Area Depth Separation Interior Shade Screening
15 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 12.0 ft2 1 ft 6 in 1 ft 0 in Drapes(blinds None
16 S 1 Metal Double(Tinted) Yes 0.55 0.6 N 10.0 ft2 1 ft 6 in 1 ft 8 in Drapes/blinds None
17 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 36.0 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
18 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 9.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
19 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 12.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
20 W 4 Metal Double(Tinted) Yes 0.55 0.6 N 10.0 ft2 1 ft 6 in 1 ft 8 in Drapes/blinds None
21 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 13.5 ft2 1 ft 6 in 2 ft 4 in Drapes/blinds None
22 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 9.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
23 N 3 Metal Double(Tinted) Yes 0.55 0.6 N 12.0 ft2 1 ft 6 in 1 ft 0 in Drapes/blinds None
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 Space(s)
1 Wholehouse Proposed CFM(50) .00025 1050 57.64 108.41 .1876 4.9219 All
GARAGE
# Floor Area Roof Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 286 ft2 286 ft2 37 ft 8 ft 4.2
MASS
Mass Type Area Thickness Furniture Fraction Space
No Added Mass 0 ft2 0 ft 0.3 Main
HEATING SYSTEM
# System Type Subtype Efficiency Capacity ------Geothermal HeatPump----- Ducts Block
Entry Power Volt. Curr
1 Electric Heat Pump Split HSPF:8.2 21.3 kBtu/hr 0 0 0 s s#1 1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Ducts Block
1 Central Unit None SEER:15 21 kBtu/hr 630 cfm 0.75 s s#1 1
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Fixture Flow Pipe Ins. Pipe length
1 Electric None Main 0.94 50 gal 60 gal 120 deg Standard None 99.442719099991
Recirculation Recirc Control Loop Branch Pump DWHR Facilities Equal DWHR Other Credits
System Type length length power Connected Flow Eff
No NA NA NA NA No NA NA NA None
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 3 of 7
Builcting Input Summa Report
SOLAR HOT WATER
Collector Surface Absorp. Trans Tank Tank Tank Heat PV Pump
Collector Type Tilt Azimuth Area Loss Coef. Prod. Corr. Volume U-Value Surf Area Exch Eff Pumped Energy
DUCTS
DUCT --Supply----- ----------Return--------- Air CFM 25 CFM25 HVAC#
# Location R-Value Area Location R-Value Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Main 6 400 ft2 Main 6 6 ft2 Default Leakage Main Default (Default) 1 1
TEMPERATURES
Programable Thermostat:N Ceiling Fans: N
Cooling Jan Feb Mar Apr PX
May Jun X Jul ]Aug Sep Oct X Nov X Dec
Venting JXXJ
Jan jXXj
Feb JXXJ
Mar jXXj
Apr �May r
j Jun tXi Jul JX
X]Aug jxxj Sep jxxj
Oct �X Nov X Dec
Jun X Jul X Aug X Sep
Thermostat Schedule: FloridaCode 2014 Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 75 75 75 75 75 75 75 75 75 75 75 75
PM 75 75 75 75 75 75 75 75 75 75 75 75
Cooling(WEH) AM 75 75 75 75 75 75 75 75 75 75 75 75
PM 75 75 75 75 75 75 75 75 75 75 75 75
Heating(WD) AM 72 72 72 72 72 72 72 72 72 72 72 72
PM 72 72 72 72 72 72 72 72 72 72 72 72
Heating(WEH) AM 72 72 72 72 72 72 72 72 72 72 72 72
PM 72 72 72 72 72 72 72 72 72 72 72 72
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 4 of 7
I
_ Buil ing Input Summa Re pod
APPLIANCES & LIGHTING
Appliance Schedule: IECC 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Ceiling Fans(Summer) AM 0.65 0.65 0.65 0.65 0.65 0.65 .0.65 0.33 0.33 0.33 0.33 0.33
%Released: 100 PM 0.33 0.33 0.33 0.33 0.33 1 0.9 0.9 0.9 0.9 0.9 0.65
Annual Use: 0 kWh/Yr Peak Value: 0 Watts
Clothes Washer AM 0.105 0.081 0.046 0.046 0.081 0.128 0.256 0.57 0.849 1 0.797 0.872
%Released: 60 PM 0.779 0.698 0.605 0.57 0.581 0.57 0.57 0.57 0.57 0.488 0.43 0.198
Annual Use: 0 kWh/Yr Peak Value: 0 Watts
Dishwasher AM 0.139 0.05 0.028 0.024 0.029 0.09 0.169 0.303 0.541 0.594 0.502 0.443
%Released: 60 PM 0.377 0.396 0.335 0.323 0.344 0.448 0.791 1 0.8 0.597 0.383 0.281
Annuaf Use: 0 kWh/Yr Peak Value: 0 Watts
Dryer AM 0.2 0.1 0.05 0.05 0.05 0.075 0.2 0.375 0.5 0.8 0.95 1
%Released: 10 PM 0.875 0.85 0.8 0.625 0.625 0.6 0.575 0.55 0.625 0.7 0.65 0.375
Annual Use: 891 kWh/Yr Peak Value: 200 Watts
Lighting AM 0.16 0.15 0.16 0.18 0.23 0.45 0.4 0.26 0.19 0.16 0.12 0.11
%Released: 90 PM 0.16 0.17 0.25 0.27 0.34 0.55 0.55 0.88 1 0.86 0.51 0.28
Annual Use: 1735 kWh/Yr Peak Value: 567 Watts
Miscellaneous AM 0.48 0.47 0.47 0.47 0.47 0.47 0.64 0.71 0.67 0.61 0.55 0.53
%Released: 90 PM 0.52 6.5 0.5 0.5 0.59 0.73 0.79 0.99 1 b.96 0.77 0.55
Annual Use: 1896 kWh/Yr Peak Value: 348 Watts
Pool Pump AM 0 0 0 0 0 0 0 0 0 1 1 1
%Released: 0 PM 1 1 1 1 0 0 0 0 0 0 0 0
Annual Use: 0 kWh/Yr Peak Value: 0 Watts
Range AM 0.057 0.057 0.057 0.057 0.057 0.114 0.171 0.286 0.343 0.343 0.343 0.4
%/o Released: 100 PM 0.457 0.343 0.286 0.4 0.571 1 0.857 0.429 0.286 0.229 0.171 0.114
Annual Use: 447 kWh/Yr Peak Value: 165 Watts
Refrigeration AM 0.85 0.78 0.75 0.73 0.73 0.73 0.75 0.75 0.8 0.8 0.8 0.8
%Released: 100 PM 0.88 0.85 0.85 0.83 0.88 0.95 1 0.98 0.95 0.93 0.9 0.85
Annual Use: 775 kWh/Yr Peak Value: 106 Watts
Well Pump AM 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1 0.1 0.1 0.1 0.1
%Released: 0 PM 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Annual Use: 0 kWh/Yr Peak Value: 0 Watts
REFRIGERATORS
ID Type Screen Location Quantity Vol FrZ.Vol Make Model Schedule kWhPerYr
1 Default New Main 1 HERS2011 691
CLOTHES WASHERS
ID Type Screen Location Capacity Make Model Schedule LoadsPerYr
1 Cl.washe Default New Main HERS2011
CLOTHES DRYERS
ID Type Screen Location Capacity Fuel Type Make Model Schedule LoadsPerYr
1 Dryers Default New Main Electricity HERS2011
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 5 of 7
Builctng Input Summa Report
DISHWASHERS
ID Type Screen Location Capacity Vintage Make Model Schedule kWhPerYr
1 Dishwash Energy Guide Roomsln 12 EStarRef EStarRef HERS2011 142
RANGE OVEN
ID Type Screen Location Type Fueltype Make Model Cooktop Oven
1 Ranges Default New Roomsln CooktopOven C Electric Electric FI Not Conv
HARD WIRED LIGHTING
ID Type Screen Location Total# Qualify# Comp FI All Other FL txtBulbtype Schedule Watts per bulb
1 Hard-Wir By Count-Qualif Main 100 10 0 10 HERS201
2 Hard-Wir Default New Exterior HERS201
3 Hard-Wir Default New Garage HERS201
MISC ELECTRICAL LOADS
ID Type Screen Item Quantity Catagory Operating Location Schedule Off Standby
1 Misc Elec Simple Default 1 1 Main HERS2011 1
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 6 of 7
Builcting Input Summary Report
APPLIANCES & LIGHTING SCHEDULES
Appliance Schedule: HERS2014 Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Occupancy peak: 400 Btu AM 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.98 0.46 0.27 0.27 0.27
%Released: 100% PM 0.27 0.27 0.27 0.27 0.33 0.61 1 1 0.93 0.93 0.93 0.93
refrig peak: 94 W AM 0.824 0.804 0.784 0.764 0.744 0.734 0.744 0.754 0.764 0.794 0.814 0.854
/o
o a
Released: 100 /o PM 0.854 0.864 0.884 0.904 0.925 0.945 0.925 0.915 0.904 0.894 0.874 0.854
cWash peak: 27 W AM 0.2 0.1 0.05 0.05 0.05 0.075 0.2 0.375 0.5 0.8 0.95 1
%Released: 30% PM 0.875 0.85 0.8 0.625 0.625 0.6 0.575 0.55 0.625 0.7 0.65 0.375
E-cDry peak: 147 W AM 0.2 0.1 0.05 0.05 0.05 0.075 0.2 0.375 0.5 0.8 0.95 1
%Released: 15% PM 0.875 0.85 0.8 0.625 0.625 0.6 0.575 0.55 0.625 0.7 0.65 0.375
dWash peak: 52 W AM 0.139 0.05 0.028 0.024 0.029 0.09 0.169 0.303 0.541 0.594 0.502 0.443
%Released: 60% PM 0.376 0.396 0.334 0.323 0.344 0.448 0.791 1 0.8 0.597 0.383 0.281
E-rOven peak: 165 W AM 0.057 0.057 0.057 0.057 0.057 0.114 0.171 0.286 0.343 0.343 0.343 0.4
%Released: 80% PM 0.457 0.343 0.286 0.4 0.571 1 0.857 0.429 0.286 0.229 0.171 0.114
TVs peak: 226 W AM 0.1 0.05 0.05 0.05 0.1 0.2 0.4 0.45 0.4 0.2 0.1 0.1
%Released: 100% PM 0.05 0.05 0.15 0.45 0.85 1 0.95 0.8 0.5 0.25 0.15 0.1
cFan peak: 0 W AM 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.25 0.25 0.25 0.25 0.25
%Released: 100% PM 0.25 0.25 0.25 0.25 0.25 0.25 0.55 0.6 0.6 0.6 0.6 0.6
Igts-in peak: 561 W AM 0.16 0.15 0.16 0.18 0.23 0.45 0.42 0.26 0.19 0.16 0.12 0.11
%Released: 100% PM 0.16 0.17 0.25 0.27 0.34 0.55 0.6 0.88 1 .0.88 0.51 0.28
Igts-out peak: 48 W AM 1 1 1 1 1 0.75 0.75 0 0 0 0 0
%Released: 0% PM 0 0 0 0 0 0 0 0.5 0.75 0.75 0.75 1
Igts-gar peak: 37 W AM 0 0 0 0 0 0.5 0.75 1 0.75 0.5 0 0
%Released: 0% PM 0 0 0.5 0.5 0.75 1 0.75 0.5 0 0 0 0
MEL peak: 192 W AM 0.5 0.5 0.5 0.75 0.75 0.85 1 1 1 1 0.9 0.9
%Released: 90% PM 0.9 0.9 1 1 1 1 1 1 1 0.85 0.75 0.75
12/4/2017 4:50 PM EnergyGauge®/USRCZB v5.1 Page 7 of 7