ENGINEERS NARRATIVE TO PLAN REVIEWERS COMMENTS
September 11,2017
Building Official
Port St. Lucie County
Building Department
RE: Project Address: 230 Camino
Owner: ELI/AYALA NISSIM
Project: 230 CANIINO
Permit: 1705-0380
Contractor: All Construction Systems,Inc.
Dear Building Official:
Following are the narrative answers to the Plans Reviewers Comments and where to find them in the
subject Plans:
1. Energy Calculation attached to set of plans in cut sheets, I have used the EMS approved
software to determine the BTU and CFM in any air outlets and the ENERGY GAUGE
Software program as you required
2. Window and Door Buck details in page S-01,per product approval specs.
3. CFM'S As per Calculations and equipment Schedule in Page M-01,
4. A scale section showing the air supply and return distribntion ;,n page M-01 for the existing
Combo air-conditioning Unit. The strapping noted to suF,port J60 mph Wind per FBC
5. Shower detail in page P-01 shows the ASTM testing criteria number and attachment fasteners
6. Door and Windows Buck and Flashing as per NOA's in Page S-01 and attached cut NOA
Sheets
7. EMS Calculations originally Signed and sealed and new ENERGY GAUGE Calculations
attached signed and sealed.
8. The scope of work in page CP stated that "THE AREA IN THE BACK YARD WAS EXISTING,
THE CHANGES WERE SPECIFICALLY TO MODIFY THE LAUNDRY AND STORAGE AREA TO
HAVE AN INDEPENDENT BATHROOM AND THE LAUNDRY ROOM.
THE GARAGE WAS CONVERTED IN INTO A NEW DEN/HOBBY/PLAYROOM AREA
THE EXISTING SCREENED AREAS WERE INTO A CBS WALLS AND WERE REPLACED BY
NEW CBS WALLS AROUND NEW WINDOWS AND SLIDING DOOR
NO BASIC STRUCTURAL WORK WAS PERFORMED"
2500 Parkview Dr.Apt.1221,
Hallandale Beach,Fl.33009
Ph:(786)252 2131 PA
albertocardonape@gmail.com
4, • •
AC CONSULTING ENGINEERS.
Cert. Of Auth.: 31780
9. Original two set of plans, Calculations,NOA7 S, and required documents are attached to this
answer
If there is anything else we need to clarify,please don't hesitate to contact our office,and if everything
is satisfactory,we respectfully ask you to approve the project.
CARS//i�i
0 7
,
7
?J STATE OF 13- I
% 'ejrtoFCardona R# 17138
C."'ONAL
2500 Parkview Dr.Apt.1221,
Hallandale Beach,Fl.33009
Ph:(786)252 2131 �µ�E Z
albertocardonape@gmail.com
RECEIVE
CONSULTOMS EMOUMEERS P- aa . FEB 09 20
Permitting Departi,
Certificate of Authorization #31780 St. Lucie Count,
2500 Parkview Drive,ApIL 2414
Hallandale Beach, Fl 33009
------------
.Ph:17-86) 252 2131
January 26, 2018
ENGINEERING ELECTRICAL INSPECTION
Mr. Joe Cicio
Building Official
County of Port St. Lucie
RE: Project Address: 230 SW Camino, Port St. Lucie, Fl. 33056
Owner: ELI NISIM
Project: GARAGE-COt4VERSION-
Permit: 1705-0380
Contractor: All Construction Systems
Dear Mr. Cicio:
As FOR I have completed the inspection related to the areas under the requirements of
the FBC 2014, 5th Edition, ELECTRICAL in the reference address with the following
comments:
1. The permit card was exposed in working place
2. Notice of commencement in field
3. Electrical panel Clearance 36 inch wide and 6'-6" high, per code (E 330.5)
4. Receptacles spaces in wall no more that 12' apart within 6' of a door
5. Minimum 20 Amps circuits in kitchen, Laundry and batrooms, wired 12
Gauge wire size
6. Kitchen Countertop receptacles spacing.every.Z feet-on,center
7. Wiring protected from abrasion and physical damage
8. Smoke detectors hard wired in each bedrooms and corridor and
interconnected with batteries backup. Separation of walls and ceilings per
code as the separation of min. Tfeet from air movement.
I re�R�c}tfWNfp/quest your approval of the ELECTRICAL Final Inspection
C A
--�GENS 0
17138
-;3', STATE OF ,,4t/
%J Car fmaA
ONAL
COPY
0 •
Certificate of Authorization #31780
' - 2500-Parkview Drive, Apt. 2414
Hallandale Beach, F133009
----- ---------------------
Ph: (786) 252 2131
January 25, 2018
ENGINEERING ELECTRICAL INSPECTION
Mr. Joe Cicio
Building Official
County of Port St. Lucie
RE: Project Address: 230 SW Camino, Port St. Lucie, FI. 33056
Owner: ELI NISIM
Project: GARAGE CONVERSION
Permit: 1705-0380
Contractor: All Construction Systems
Dear Mr. Cicio:
As FOR I have completed the inspection related to the areas under the requirements of
the FBC 2014, 5' Edition, ELECTRICAL in the reference address with the following
comments:
1. The permit card was exposed in working place
2. Notice of commencement in field
3. Electrical panel Clearance 36 inch wide and 6'-6" high, per code (E 330.5)
4. Receptacles spaces in wall no more that 12' apart within 6' of a door
5. Minimum 20 Amps circuits in kitchen, Laundry and batrooms, wired 12
Gauge wire size
6. Kitchen Countertop receptacles spacing-every 2' feet on center
7. Wiring protected from abrasion and physical damage
8. Smoke detectors hard wired in each bedrooms and corridor and
interconnected with batteries backup. Separation of walls and ceilings per
code as the separation of min. 3' feet from air movement.
t your approval of the ELECTRICAL Final Inspection
E1Is 0
\��'ordtally � '•T,
No 17138
ZZ
Cdrs I n � eer. FILE
C.
� 1� 1�'
FO-i AZ & :RUSSELL;
CONSTRUCTION COMPANY
A/C Lic.: CAC 1815659, Roofing Lic.CCC 132 7760, Plumbing Lic. CFC 142 7602,General Lic. : 1512006
Date: JANUARY 0812018
County of Port St. Lucie
Building Official
Mr. Joe Ciccio
Subject: Duct Sealing Certification Letter
Permit No: 1705-0380
Property Address: 230 SW CAMINO, PORT ST. LUCIE, FL. 33056
hereby affirm and certify that all accessible joints and seams in the air distribution
system have been inspected and sealed where needed using reinforced mastic or code
approved equivalent in accordance with FBC 2010—Energy Conservation Table
503.2.7.2 —As prescribed in FBC 2010 — Energy Conservation 101.4.7.1.1
The system was tested and repair as necessary
Company Name: DIAZ AND RUSSEL CORP.
Contractor License Number: CAC 181 5659
Contractor/Qualifier Name: ELSON RICARDO DIAZ
Contractor/Qualifier
The contractor shall attach to the air handler unit a signed certification in substantially this for the
final inspection.
F C 0 P Y
6992 NW 42"d. Street
Miami, FI. 33166
Ph: 305 439 8257,email: argricardodiaz@yahoo.com
t, L
MAY 17 29113
PER 0iTTil\'G
St. Lucie County, FL
s _---- All Construction Systems, Inc.
845 Vanda Terrace
DATE: 24-Apr-17
Weston,R.33327
PH:(954)385 8504 FAx:(954)385 7261 Cell:(954)663 2078
CONSTRUCTION
uSTOMER: ELI MSSIM ESTIMATE
,Ioe: INTERIOR IMPROVEMENTS-VIOLATION Based on 3 Weeks construction schedule
ADDRESS 230 SE.CAMINO STREET,,PORT ST_LUCIE
Div/Code DESCRIPTION Units Quantityl Unit Price Total Price Percent
T783 90 5647?%
15-410 New Drywall-Ceilings SgFt 840.00 0.80 672.00
15-440 New tile on floor and walls SgFt 420.00 1.55 651.00
15-440 Painting Ceiling,Doors and walls SgFt 840.00 $ 0.67 610.90
15-440 New Kitchen LF 20.00 260.00 5,250.00
15-440 Bathroom Appliances Unit 3.00 200.00 600.00
16-000 ELECTRICAL 1,250.00 9.07716'
16-050 Basic Electric Materials&Labor Outlet 14.00 77.50 685.00
16-510 Light Fixtures Unit 8.00 122.50 565.00
15-001 IPLUMBING 3,506.00 25.39%
15-001 1 KITCHEN AND BATHROOM INSTALATION Fixtures 5.00 250 1,250.00
15-001 MECHANICAL . 1,260.001 9.07%
15-001 NEW A/C GRIDS Fixtures 4.00 250 1,000.00
TOTAL 1 13,783.90
OWNER ACCEPTANCE A