HomeMy WebLinkAboutHoffman Tank SpecificationWHY CHOOSE QUALITY STEEL UNDERGROUND TANKS? • 120 - 1,990 WG CAPACITY • General Specifications • Conforms to the latest edition of ASME Rules for Construction of Pressure Vessels, Section Vill, Division 1. • Complies with NFPA 58. • Rated at 250 psig from -20" F to 125" F. All vessels registered with National Board. • Two service options available: • Option 1: Ready -to -bury underground option, coated with either powder coated phenolic epoxy finish or liquid applied epoxy primer coat followed by urethane top coat, supplied with composite AGIUG dome • Option 2: Aboveground option, coated with either powder coated TGIC polyester finish or liquid applied epoxy primer coat followed by urethane top coat, supplied with steel AGIUG dome • Family & employee owned • Financing and leasing available • Customized delivery programs available HOW DO I FIND MY SALES REP? Visit our website, www.propanetank.com to view a list of our reps. Once on our site you'll be able to choose the Commercial options and from there you'll be taken to a list of US states where you can choose your location and view the contact information for your local sales rep. If you don't see your sales rep. please give us a call at 800-345-2495. Our manufacturing locations are strategically located to help serve your tank needs. OHIO LOCATION 721 Graham Drive Fremont, OH 43420 . , - - , -- -. . UTAH LOCATION 5601 Axel Park Rd. West Jordan, UT 84081 801-280-1133 HOME OFFICE 2914 U.S. 61 Cleveland, MS 38732 800-345-2495 Consult our dimension and specification chart below to find the tank that best fits your needs. Visit our website at www.propanetank.com for more information. 16144111INIININe3d:i OVERALL HEIGHT LEG SPACING LEG WIDTH �j \= +-- LEG WIDTH APPROXIMATE ABOVEGROUND/UNDEGROUND (AG/UG) VESSEL DIMENSIONS AND SPECIFICATIONS WATER CAPACITY DIAMETER (OD) HEAD TYPE OVERALL LENGTH OVERALL HEIGHT LEG* WIDTH LEG** SPACING WEIGHT (Ibs.) **QUANTITY FULLLOAD PERSTACK *120 w 24" Ellip. 5'-8" 3' V-1 1/2" 2'-10 1/2'Ig. or 3'-11" 260 108 196 16 1 12 *250 wg. 30" Hemi. 7'-10" 3'-8" 1'-5" 4'-11" 480 54 9 *320 wg. 30" Hemi. 9'-7" 3'-8" 1'-5" 5' 620 45 9 500 wg. 37 1/2" Hemi. 10, 4'-2" 1'-8" 5' 950 37 30 8 6 1000 wg. 41" Hemi. 16' 4'-5" 1'-8" 10'-1" 1,800 17 15 6 5 1 1450 wg. 46 1/2" Ellip. 17'-4" 4'-11" 1'-9" 11'-7" 2,650 12 4 1990 w . 46 1/2" Ellip. 23'-11" 4'-11" 1'-9" 16' 3,520 8 4 Dimensions and specifications shown are approximate. Individual vessels may vary . Leg spacing +1- 2 Leg widths and spacing may vary based on mfg. location. Check with your salesperson for details. 120, 250, 320 wg. standard tanks - no holes in legs (one center hole on request). 500 and 1000 wg. standard tanks - 2 holes 16" on center. 1450 wg. and up as shown above. ** Full load and stack quantities vary by shipping location. Check with your salesperson for details. QUALITY STEEL Because quality Steel Means oudily Tanks *I h3ni; You for Snlllfon3ng uSA ManulaLlurrrs * HOME OFFICE 2914 U.S.61 Cleveland, MS 38732 800-345-2495 OHIO LOCATION 721 Graham Drive Fremont, OH 43420 419-334-2664 UTAH LOCATION 5601 Axel Park Rd. West Jordan, UT 84081 801-280-1133 Quality Steel 6/2017 S2 STORAGE TANK IS ADEQUATELY ANCHORED TO PREVENT FLOATATION, COLLAPSE OR LATERAL MOVEMENT DURING THE BASE FLOOD EVENT. ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 54-58, NATIONAL FUEL GAS CODE AND FLORIDA FUEL GAS CODE 2020 dt FLORIDA BUILDING CODE 2020. TANKS INSTALLED IN TRAFFIC AREAS SHALL BE PROTECTED WITH GALV. STEEL SCHED. 80 PIPE BOLLARDS (4"0) 6' LONG X 3' BURY DEPTH WITH CAP ® 3' O.C. PROPANE TANK BUOYANCY MAX BUOYANCY = pn*g*VtwA = 1.94 slug/ft' * 32.2 ft/s= * 66.84 ft' = 4176 LBS NET BUOYANCY = MAX BUOYANCY — WEIGHT OF EMPTY TANK = 4176 LBS — 871 LBS = 3305 LBS FORCE ON J' CABLE = 3305 / 2 = 1653 LBS TENSILE STRENGTH OF J" CABLE = 9800 LBS / 5 = 1960 LBS FORCE ON AUGER ANCHOR = 1653 / 2 = 827 LBS MIN. PULL—OUT RESISTANCE OF AUGER ANCHOR = 1360 LBS LP TANK J" 709 GALV. AIRCRAFT CABLE 2 TOTAL (IN POLY. SLEEVE) AUGER ANCHOR, 36' LONG W/ 6.0 HELIX 4 TOTAL SIDE ELEVATION SCALE 1/4" - P—O" GRASS Ferrellgas 3232 SE Dixie Hwy. Stuart, FL 34997 n 0 rs �r N OF 7 i Foil Pierce Engineering, Ina Dependable Meahaad=l, elacUlaal & Plumbing Dedga C.A. No. 28173 315 Soulh7th Street Fact Pieeae, FL. 34950 Phone: 772 672-4636 Fnx 772 672-4637 nl6 Lu li u+pdn,. LP TANK EXCAVATION SIZE a 1 121 x 4'W x 4.5'D VI116aa a Siitbodd;"?$ 17LB. ANODE C0004L — Ew a"QP.E. No. " 7x19 GALV. �,;31 sw>° a' AIRCRAFT CABLE `a • _ s RtA'WN�i $TRAPPING BOLT � vavTy"„-�,W APPROVED: E.13 DRAWING NUMBER AUGER ANCHOR, 36" DigitalysignedbyeBcsveL.d, Date 2Ae LONG W/ 60 HELIX Aobekt.m.iz lo:nsz-osoo• robaf version: �uu FRONT ELEVATION zozo,msaoma T- SCALE 1/4" = 1--0" LP500