Loading...
HomeMy WebLinkAboutAPPROVED 8505 Paso Robles Blvd - PlansDesign Parameters 1. Building Occupancy Category, Paragraph 1604.5 and Table 1604.5: Risk Category I. 2. Basic Wind Speed, Table 1609C, State of Florida Debris Region & Basic Wind Speed, Paragraph 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed, VuLT= 150 MPH 3. Exposure Category, Paragraph 1609.4.3 : C Applicable Codes, Regulation and Standards 1. The 7th Edition (2020) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and Specifications for Aluminum Structure, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association, Inc. Washington, D.C., 2010 Edition 3. ASCE 7-16 r_nnn..l Nlntnc 1. The contractor shall verify all dimensions prior to construction 2. All work shall comply with all local and regional ordinances. 3. Any deviation from this plan shall be reviewed by the engineer of record and is subject to approval. Specifications The following specifications are applicable to this projects 1. Where concrete specification are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable. 1.1. Concrete shall conform to ASTM C94 for following components: 1.1.1. Portland Cement Type 1, -ASTM C 150 1.1.2. Aggregate - Large Aggregate 3/4" max - ASTM C 33 1.1.3. Air entraining +/- 1 % - ASTM C 260 1.1.4. Water reducing agent - ASTM C 494 1.1.5. Clean Potable water 1.1.6. Other admixture not permitted 1.2. Metal accessories shall conform to: 1.2.1. Reinforcing Bars - ASTM A615, grade 60 1.2.2. Welded wire fabric - ASTM A185 1.3. Concrete slump at discharge per chute not less then 3" or more than 5". Water added after batching is not permitted. 1.4. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2 and 3 including hot weather recommendation 1.5. Moist cure or polyethylene curing required. 1.6. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. 1.7. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 1.8. Fiber reinforced concrete per ASTSM C1116 is an acceptable alternative tc 6X6 W1.4/W1.4 WWF. 2. Aluminum extrusions shall be 6005 T5 Alloy. 3. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plate to ASTM B633, or stainless steel series "300". 4. All Self Mating Beam Sections and PFB are to be stitched with either #14 screws 6" from end 24" on center or #12 screws 6" from end 12" on center. 5. Screened enclosures containing swimming pools shall comply with the applicable requirements of FBC R4501.17 and FBC 454.1.3.1.9. 6. Door location shall be determined by contractor in the field. 7. When installing pavers over concrete slab or footing which are supporting aluminum members, such as continuous screen tracks or upright, the anchors must extend past the pavers and reach proper embedment into the underlying foundation. 8. All flashing and waterproofing shall be provided by the contractor. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. 10. Vinyl and acrylic panels shall be removed when wind speeds exceed 75mph Foundation Design: New 8"x8" (1 #5 bar Cont.) thickened edge, 4" monolithic sl< Concrete shall be a minimum 2,500 psi FIBERCRETE. Reber 31" lap splice. Use 3" chairs. Per current edition of the FBC R401.4.1 or FBC 1806.2, soils testing is not required for design using the presumptive bearing pressure of 1,500 psf. Roof Type Screen Size Composite 18/14 ALUMINUM MEMBER DIMENSIONS HOLLOW SECTIONS SELF MATING BEAM (SMB) OTHER SELF MATING BEAMS 2 x 2: 2" x 2" x 0.046" 2 x 4 SMB: 2" x 4" x 0.044" x 0.100" 3.75 PFB: 2" x 3.75" x 0.05O" 2 x 3: 2" x 3" x 0.050" 2 x 5 SMB: 2" x 5" x 0.050" x 0.100" 5.75 PFB: 2" x 5.75" x 0.055" 2x4: 2"x4"x Oo5O" 2x6SMB: 2"x6"x 0.050"x 0.120" COLUMNS 2x 5: 2"x5"x 0.050" 2x7SMB: 2"x7"x 0.057"x 0.120" 2x 8 SMB: 2"x8"x 0.072"x 0.124" 2x 9SMB: 2"x9"x 0.072"x0.124" 3x3: 3"x3"x 0.125" 4x4: 4"x4"x O.125" 6x6: 6"x6"x 0.125" OPEN BACK SECTIONS 1 x 2: 1" x 2" x 0.040" 2 x 10 SMB: 2" x I ONO 092" x 0.398" 1 x 3: 1"x 3' x 0.045' MINIMUM FASTENER EDGE DISTANCE: 1/2" KB: KNEE BRACE MINIMUM FASTENER SPACING: 3/4" RC: REC. CHANNEL SNAP SECTIONS 2 x 2 Snap: 2" x 2" x 0.045" CONCRETE SCREW ANCHOR: SHEET MATEL SCREWS (SMS) : 2 x 3 Snap: 2" x 3" x 0.050" SIMPSON TITEN HD OR EQUIVALENT ITW BUILDEX OR EQUIVALENT 2 x 4 Snap: 2" x 4" x 0.045" NOTE: THIS DRAWING IS FOR ILLUSTRATIVE PURPOSES. DRAWING NOT TO SCALE. USE DIMENSIONS GIVEN. CABLE BRACING MAY TERMINATE AT SLAB IN DIFFERENT LOCATION. MAINTAIN ANGLE PER DETAIL. r- m n m r D O Z HOST FASCIA ATTACHMENT I I I I I CR-1 w 2 00 o w CD W Lu O co J N I I I CR-0 I 2 CD5.75 PFB END BEAM I I L------------------------------ j 21'-0"- 1'-0" ----J 1'-0" I -0� - 1X2 X o 2X2DJ 04 DJ-1 0 2 N 2X2DJ N O N � I i� 3.75 PFB X 04 N O 1� 1X2 MI 6'-0" 1,-C k7'-6" 3" 0.032" ALUM. SKIN 1-LB EPS FOAM CORE PANEL ROOF. MINIMUM SLOPE OF 1/4" PER FOOT, OR AS SHOWN IN DIMENSIONS. (Roof: FL7561.1) 1X2 (TYP) M LO m Lo m M O N co a- n CL N I I B-1 i 2 2X3 2X3 2X3 �TYP 7'-0" 7'-0"k ° 4 ° ° a a° d ° d ° \� + 4 d d °4 // 4 ° A N a ° i 4 j W / 0 d a° ed 4° A Z / ° d LU A _ A ° n e ° n / CL o- 0 MIN. ]500 PSI CONCREI SCREEN ENCLOSURE FOOTEN OUANTITYWIDTH PER NOTES REINFORCEMENT MEN eE of REINFORCEMENT PER FOUND RE FOR DESIGN NOTE SHOWNMAINTAIN HERE FOR ILLUSTRATION. MAINTNN ]' CLEM CONCRETE COVER. NOTES: 1. CONCRETE SLAB SHALL BE INSTALLED ONLY ON COMPACTED, WELL GRADED CLEAN SAND FILL. 2. CONCRETE SHALL BE PROPERLY AND ADEQUATELY CONSOUDATED TO REMOVE ALL VOIDS IN BLOCK CELLS AND AROUND REINFORCEMENT. 3. REBAR SHALL HAVE A 31" LAP SPLICE. USE 3" CHAIRS TO MAINTAIN 3' CLEARANCE FROM THE SOIL RIBBON FOOTING 1'-0" FRONT ELEVATION ALUMINUM COIL KICKPLATE. FASTEN WITH #12 x 3/4" SMS @ 12" O.C. INTO EACH MEMBER. (TYP) This item has been elers + aHyef r r�ray.! tronicalb signed and. sealed by Edward Roske E PE using a Digital Qigna- ture. Printed copies of No.'s ? iss ' this acc DC-t are not *" considered signed and sealed and the signature STATE OF mast be wri>:md ❑n any r +`tiJ lA4 �+`•+• .1-t-31. Copies- r+rlrar.e. Edward Rosk 2020.12. '00'05- 12:31: O U O d O y LO C" A! M Q M L O a _O i C N U. V L U d � `� CD O 0 a 00 d�a A+ Q O W LL V O a SHEET ***NOTE - NOT ALL DETAILS ARE USED FOR THIS PROJECT. SEE PLAN FOR DETAIL CALL OUTS*** 1/4" LAGS, 4" FROM ENDS & 18" O.C. MAX. 1" MIN LONGER THAN THE PANEL THICKENESS. W/� NEOPRENE WASHER ON EACH LAG 3" X 0.082 ALUM RECEIVING CHANNEL W/ #12 X 3/4" TOP AND BOTTOM AS END CAP (2) 3/8" DIA THRU BOLTS IF SCREEN WALL BENEATH COMPOSITE ROOF, 1"x 2" W/ (2) #10 x 2" SMS INTO SCREW BOSSES INTO UPRIGHT & (1) #14 X 2" SMS 6" FROM EACH SIDE OF UPRIGHT & @ 24" O.C. NOTCH UPRIGHT OR POST TO ACCEPT BEAM. SEE PLAN SHEET FOR MEMBER INFORMATION 2'k7k1/8" ANGLE EA SIDE (1) 3/8" DIA CONCRETE SCREW ANCHORS INTO EACH LEG COMPOSITE ROOF TO BEAM 2 SCALE:NTS — (1) 1/2" DIA THRU BOLT WITH NYLOCK JAM NUT (JAM NUT WITH THREADLOCKER MAY BE USED, IN LIEU). DO NOT OVER TIGHTEN. TIGHTEN ONLY UNTIL CONTACT. FOR 2X2 AND 2X3 UPRIGHTS, USE (4) #14 x 3/4" SMS INTO POST BRICK PAVERS. MAY NOT BE PRESENT. ENSURE MINIMUM CONCRETE EMBEDMENT. Z p W � Z ~ w �\ mZ O w TOP VIEW AT INTERMEDIATE FOUNDATION PER PLAN UPRIGHT PER PLAN 1X2 O.B. ANCHORED TO CONCRETE WITH 1/4" DIA. CONCRETE SCREW ANCHOR @ 24" O.C. MAX (4) #14 x 3/4" SMS INTO POST FOR CORNER CONNECTION FASTEN 1X2 WITH #12 x 3/4" 4 SMS @ 24" O.C. FLASHING - INSTALL UNDER EXISTING DRIP EDGE #14 X 3/4" SMS @ 6" O.C. TOP AND BOTTOM W/ 1-1/2" DIA. NEOPRENE WASHER @ TOP SCREW ONLY ROOF PANEL (2) 1/4" DIA. X 3" LAG SCREWS @ 6" O.C. 1" X 1" X 1/8" ALUM ANGLE W/ (3) #14 X 3/4" SMS IN COMPOSITE PANEL FLANGE INTO UPRIGHT. RECEIVING CHANNEL (BOTH SIDES OF UPRIGHT) SEAM. SEE PLAN SHEET FOR MEMBER INFORMATION III 9e 01X2 � n� UPRIGHT (4) #14 x 2" SMS THRU 1X2 INTO POST TOP VIEW FRONT VIEW AT CORNER B-1 UPRIGHT TO FOUNDATION CONNECTION 2 SCALE:NTS CR-1 COMPOSITE ROOF TO HOST 2 SCALE:NTS SHIM AS NECESSARY IF OTHER THAN A PLUMB \ / CUT FASCIA 1/8" x 2" x 2" ANGLE WITH �(4) #14 x 3/4" SMS INTO ® ® POST ® O RICK PAVERS MAY NOT BE PRESENT. FOLLOW ANCHOR MINIMUM CONCRETE EMBEDMENT z Z OW e e U Z w d m W N d SIDE VIEW J PER PLAN 1x2 O.B. ANCHORED TO CONCRETE WITH 1/4" DIA. - ANCHOR (MIN. 1-1/4" --- EMBED) @ 24" O.C. 1 #14 x 3/4" SMS INTO t d1) 3/8" DIA. CONC. d d m ANCHOR. EMBED MIN. c 2-1/2" a 6" < d d DOTING. SEE PLAN FOR FRONT VIEW DETAILS DJ-1 DOOR JAMB CONNECTION 2 SCALE:NTS (2) 1/4" x 3" LAG SCREWS, 6" FROM END & @ 16" O.C. CONC. (2) 1/4" DIA. x 2 1/4" CONCRETE SCREW ANCHOR, 6" FROM END & @ 16" O.C. OPTION 1: (4) #10 x 1-1/2" SMS INTO SCREW BOSSES (TYP) SNAP OR--"' SELF -MATING BEAM ONLY WOOD: #10 x 3" WOOD SCREWS @ 6" FROM ENDS & 12" O.C. CONC. 1/4" DIA. x 3" CONCRETE SCREW ANCHOR @ 6"FROM ENDS & 24" O.C. OPTION 2: 2" x 2" x 1/8" ANGLE WITH (2) #10 x 3/4" SMS IN EACH FLANGE, EACH SIDE (TYP) I URLIN / GIRT / CHAIR RAIL M-1 PURLIN / GIRT / 0.13 TO HOST CONNECTION 2 SCALE:NTS it W a O N_ ti N N r Q U O v, ♦� Lo O A! m a M �V i 7 L o N L c LU) O + C N U. V L U d O `� Lo CD a 00 dL0a A+ Q L ^W � Li V r O i IL SHEET