HomeMy WebLinkAboutA-3 2.24.21ELECTRICAL DEMAND CALCULATION
GENERAL UGHTING@ 3 VA/FT= 3VA X 1881 5643VA
SMALLAPPLIANCE CIRCUITS 4500 VA
DRYER 5000 VA
WASHER 1500 VA
DISHWASHER 1500 VA
DISPOSAL 400 VA
REFRIGERATOR 1200 VA
WATER HEATER 4500 VA
RANGE 12000 VA
FANS 7 @ 240 (Calculated Load) 1680 VA
EXHAUST FANS 3@240 720 VA
OH GARAGE DOOR OPENER 600 VA
GRINDER PUMP (1800 Watts) 1800 VA
POOL & I IRRIGATION 0 VA
41043 VA
1ST 10,000 VA @ 100% 10000 VA
REMAINDER @ 40% 12417.2 VA
A/C - HEAT @65% 15000 VA
TOTAL 37417.2 VA
240 VOLTS
155,905 AMPS
ELECTRICAL CONTRACTOR
USE 200AMP SERVICE
TO VERIFY ELECTRIAL CALCULATIONS
AND SERVICE REQUIREMENTS
ELECTRICAL LEGEND
ELECTRICAL
COUNT
SYMBOL
Electric Meter
1
8
Electric Panel
1
miiZ]
Disconnect
b
Junction - 220V
am
Light - surface mount/pendant
{ }
Light - incandescent pull chain
Light - exterior flood/security
�Q
Light - Recesed can
Light -Recessed canvaporproof
®VP
Light -Ext.- Wall Mount- Coach
Light -Fluorescent
-
Light - Fluorescent - UC
Light - wall mount
Receptacle - 110v
Receptacle - I 1 Ov - switched
Receptacle GFI
1
Receptacle WP/GFI
�¢'NP/GFI
Receptacle dedicated
DED
Receptacle -dishwasher J110v
Vymllo.
Receptacle 4 Plex GFI
GFI
Receptacle 220V- Dryernov
Receptacle J 110V & 220V - Range
uawm11o.
Water heater junction 220v
moo
Prewire For GDO
GDO
Push button gdo
t
Switch
Switch - 3 way
3
Phonejack
ph
Cable TV
❑Tv
Smoke / CO detector
soco
Exhaust Fan
Ceiling Fan Light Combo Rough -In
n
Solid lines - install Fan/Light
II II
Dashed lines - pre wire only w/ cover
I I .' 7
CEILING
MOUNTED
n
tI
I I
II
C- USE FAN BOX
INSTALL LIGHT
,
(2) 3080 LEAD
w/SINGLE LIT
CLEAR GLASS
n
II
II
USEFANBOX
INSTALL LIGHT ,'/
nI
7
I I
C- - - FAN/LIGHT
PREWIRE
WEATHERHEAD 200 AMP OVERHEAD
PER FPL ELECTRIC SERVICE
REQUIREMENTS
i
THW-CU � 1 8 THW-CU GROUND
-----------------
I
� i I i s® 1 1/2" CONDUIT 2 "CONDUIT
FLOOR OUTLET 2 "CONDUIT
1 w/ COVER FLUSH® I
1 I 1 w/ FLOOR FINISH 1
13METER HOUSING
2 L PER FPL O 200A :B42
OA HVAC B.C. DISC
REQUIREMENTS FUSED CIR.
�� n n DISC. AKER16"AFF1 METER BY O NEL HVAC C.U. DISC
FPL
60"AFP tl 1 . � � - 1 `� tI II .?
1 HOUSE PANEL
I � $ 60"AFR
O ~¢ --
FANLIGHT6o'AFF --- FANLIGHT aa� FAN/LPREWIGHT
(1) #4-CU 200 AMP- 1P- 120/240V- 3 WIRE
O
I . PREWIRE 6¢"AFF I PREWIRE r-I $
i6'AFF i N nw / GROUND #14 AWG COPPER TO LIGHTS & OUTLETS
#10 AWG COPPER TO WATER HEATER
CONNECT GROUND TO #10 AWG COPPER TO DRYER
I I RECESSED L.V. CABINET FOUNDATION STL, AND
60"TO CENTER AFF # 8 AWG COPPER TO RANGE
I (1) GROUND ROD 6' AWAY
I 1 1 I PROVIDE DEDICATED
I 1 I 1 110 V SERVICE FOR
I 1 FLOOR OUTLET I
I I 1 w/ COVER FLUSH 1 (2) OUTLETS
5/8" DIA x 8'-0"
w/ FLOOR FINISH LONG COPPER
® I ® GROUND ROD
_-____SD CO 1 1 1
__J LL
-
----- - - - -- � L- ----- --------- ---- ----- - -- - -- o soco
a
® N b
31-8n sD co LONG DCIOPPER-0"
I 1 n GROUND ROD
rn I II
❑ ❑ i o .'
10 FUTURE - - ELECTRIC RISER
SINK �---
FAN/LIGHT{�
I r _____-•� PREWIRE Td N.T.S.
F,
x 22�
I
e � 1
e 1
1
I
u
\� I
I
u
u
i
TO FLOOD LIGHT
AT RIGHT FRONT u
CORNER
I IL O eq. eq.
-r-
i11.9t1 31_�1t 1t_9t1 , 5t_�tt ILL
i
I
0) TWO
EXTERIOR VENT HOOD I
i
SD CO
CFl ____
GFI
MP/GFI
I I
a I I
W I I
I I
I I
I I
a
W
I on tanE I wA I
�ATTIF �t`ESS
Ji)ELD LOCA4'E I
PLEX)
CRASH
POLE O
200 A PANEL
LOCATE IN FIELD
I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I
i
TO FLOOD LIGHT
AT LEFT FRONT
CORNER
METER, HOUSING
& MAIN 200 A
DISCONECT
LOCATE IN FIELD
ELECTRICAL NOTES:
1. ELECTRICAL CONTRACTOR TO VERIFY SERVICE REQUIREMENTS
2. 200 AMP SERVICE.
3. ALL MATERIALS AND INSTALLATIONS SHALL COMPLY W/
APPLICABLE PROVISIONS OF THE CURRENT NATIONAL ELECTRIC
CODE, STATE &LOCAL CODES AND ORDINANCES AND
REQUIREMENTS OF FLORIDA POWER & LIGHT.
4. SMOKE DETECTORS ARE REQUIRED.
5. CARBON MONOXIDE DETECTORS AS REQUIRED
6. FIELD VERIFY RECEPTACLE LOCATIONS
7. ALL CIRCUITS, RECEPTACLES (INCLUDING GFI RECEPTACLES),
AND DEVICES TO BE ARC FAULT PROTECTED IN ALL ROOMS
WHERE REQUIRED PER NEC 210,12
THE ARC -FAULT CIRCUITINTERRUPTER(S) SHALL BE INSTALLED
IN A READILY ACCESSIBLE LOCATION
8. ALL RECEPTACLES TO BE TAMPERPROOF WHERE REQ'D. BY NEC
406.11
9. RECESSED LIGHTING FIXTURES MUST COMPLY WITH FLORIDA
ENERGY CODE 606.1.ABC. 1.2.4, PRODUCT APPROVAL (TOTALY
ENCLOSED).
13. GARBAGE DISPOSAL TO BE ON SWITCH CONTROLLED OUTLET,
14. BOTH DISHWASHER AND GARBAGE DISPOSAL OUTLETS TO BE
LOCATED INSIDE CABINET BELOW SINK FOR ACCESS.
15. EXHAUST FANS IN BATHROOMS TO EXHAUST DIRECTLY TO
EXTERIOR OF STRUCTURE.
16. KITCHEN OUTLETS TO BE GFI AND ARCH FAULT PROTECTED.
17. FIELD VERIFY WELL PUMP AND AC EQUIPMENT LOCATIONS,
18. ALL LIGHTING FIXTURES, RECEPTACLES, AND LIGHT SWITCHES
MUST COMPLY WITH ART. 410 OF NEC..
19. PROVIDE W/P GFI OUTLET WITHIN 25' OF AC COMPRESSOR,
20. WIRE AND INSTALL OUTLET FOR GARAGE DOOR OPENER,
21. ALL SWITCHES TO BE DECORA ROCKER TYPE,
22. WIRE FOR VENTLESS MICROWAVE, OUTLET IN CABINET ABOVE
RANGE MUST BE HOME RUN TO HOUSE PANEL.
23. ALL SMOKE DETECTORS MUST BE A MINIMUM OF 3' FROM ANY
BATHROOM DOOR,
24. ELECTRICIAN TO SUPPLY AND INSTALL ALL SMOKE AND
SMOKE/CARBON DETECTORS.
25. ELECTRICIAN TO SUPPLY AND INSTALL DOOR BELL CHIMES,
TRANSFORMER, AND ACTIVATION SWITCH,
26. ALL CHANGES MUST BE DONE IN WRITING BY GROZA BUILDERS,
INC. HOME OWNERS DO NOT HAVE THE RIGHT TO CREATE OR
INSTRUCT CHANGES WITHOUT DOCUMENTS.
J
m
LU M
U Ln
J M
Z LL
LL
L
r)loWW' H
ce J
0
d �
(f1
r 0
tn a
V
Z=
Q
`JI
MJ�
W
O�
f�
DATE
09/11/20
DESIGN BY
CHECKED
BY
MODEL
HARBOURVIEW
OWNER
REV
DESCRIPTION
1
P1
11
SEP 20
2
P2
25
SEP 20
3
P3
23
OCT 20
4
P4
09
DEC 20
5
6
7
8
J �
W
N PE