HomeMy WebLinkAboutbuilding plans (2)Gulf Coast Supplg and MPG 5v Crimp Metal roofing FL 411451.12 26 ga. 5v crimp metal roofing attached to plgwood deck using #9 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D (tgpe 2) 30 lb felt underlayment installed with min. 4' aide laps and L" end laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails s aced L" o.c. at all laps and two sta gered rows 12" o.c. in field. Attach 12" 12" H. H. �5/8" thick light textured O - stucco on typical concrete block construction 0' Finish Columns with 5/8" thick x 8% cut 5/8" thick cut coral coral finished stucco bands finished stucco bands RIGHT ELEVATION SCALE: 1/4" = 1'-0" Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12 26 ga. 5v crimp metal roofing attached to plgwood deck using #9 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D (type 2) 30 lb felt underlayment installed with min. 4' side laps and 6" end laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails spaced 6" o.c. at all laps and two staggered rows 12" o.c. in field. Attach deck to trusses using attachment detail on this sheet 12 4 1 SLOPE Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11451.12 26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D (type 2) 30 lb felt underlagment installed with min. 4' side laps and 6" end laps fastened with corrosion resistant tin caps and with 1.25" ring shank nails na ced ^L'J+o.c. at all laps and two staggered rows 12" o.c. in freld. Attach o/ v 6111UN t.UL wl-ai stucco on typical concrete finished stucco bands block construction 17/0­XI/a new UM rolj-r Y FT II^ V C Ply. I_ EWED FOR L NCE 'WED E _ MUST BE WPT O INSPECTION WILL BE MADE.ON JOB /8" thick x 8"W cut oral finished stucco bands CONCEALED FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OF RECORD REARELEVATION ,EMMSANDALLPROPOSEDWORKELEVATIONNOTES: TlLpSCALE: 1/4= 1-0" ppgf N6 0TOR,THAT IIN aR0111111 TO - Overhangs at i'-O" unless otherwise noted on Roof Plan oMpLywIT`�i 9A*i"1°'#00"' - Roof Itch at p 4:12 unless otherwise noted GulfCoastSupply and MFG 5v Crimp Metal roofing FL WILS1.12 - ,4 n y e h a n g e s t o this plan shall b e submitted t 0 the architect wood ascrewscwith selfmetal sealingroofing wa her at12' to olc. maxwood dscacingnover9 ASTM (tgpe 2) 30 Ib D N,LMANUiADRJIIIiLAAI�aIO�INQ or approval in writing prior to starting construction. felt underlayment installed with min. 4P side laps and L" laps fastened with corrosion resistant tin caps and with 1.25" ring shank ,aced 6" o.c. at all laps and two staggered rows 12" o.c. in field. Attach end ll FAOT MAND*10110 COMPLIANCE nails WmIFmENERGY CODEmusT - Return ALL Stucco III Sands Into l I n d O W Or Door. eck to trusses using attachment detail on this sheet REMAIN ON ALL DOORS AND WINDOWS LJ ONiiL INSPECTIONS ARE APPROVED TERMITE TREATMENT REQUIRED 1/8" Thick cut coral stucco over paper backed wire lath nailed to substrate through one layer of 15 lb felt using 8d nails. Substrate to be 19/32" COX Plywood nailed at 6" o.c. 12 in field and edges with IOd ring shank galvanized nails into truss webbing. 4 SLOPE e'-I" T.O.B. 12" - H ®®®® 2 „ 12" H. O.H, 2., 5/8" thick x 8"w cut 0H. 5/8" thick x 8"W cut coral finished stucco bands coral finished stucco bands � 3 ® e. 3 ®I1 ® /8„ t 8„W 5 hick x cut ®®®® coral finished stucco bands 5/8" thick light textured EB stucco on typical concrete block construction = Finished Floor - ar a Finished Floor ------------------------------------------------------------ -0'-4" A.F.F. 7�,��thick light textured Pinish Columns Wlth stucco on typical concrete 5/8" thick cut coral L E F T ELEVATION block Construction finished stucco bands FRONT ELEVATION SCALE: 1/4" = 1'-0" SCALE: 1/4" = 1'-0" Product Approval Submittal Affidavit Opening Schedule Swing Doors, Overhead Doors, Sliding Doors, Windows & Skylights Opening Type NOA/FL NUMBER Product Model # Manufacturer Glass Attachment method T� Fixpiration Data Design Pressure of Approved Tests 1,2,3 $4 FL# 11499.2 Single Hung g g Series 195 MI Windows and doors . x elyeons mi p n t net m ion sac corner and I o.c. Nerea�ter througi T �uck Into amid Ailed CMU well mamtainm min 2.5" edge distance m strict adherence to the product a provaLg g ± 60 per A 16-0330.02 Overhead Garage Door Model 824/811 9'-4" max. width 6'-0" max height DAB a.ta ,! to cornets m Ya. . ce mt o ss ber wart. uY a 3/9' x P Ww HLc ais.v. anchn. at a' ox. with i.a5• dL aaahen ash a. 1' edapppae datanee. IaNalla track to buck manor I �. I S/8'%1i thrGC to atr'mq' ed i I pkc.t approval rovd. /IL' L Yaeh.r an roll" shafts. 10-9-21 50.0/-60.0 psf B FL# 16414.1 Fiberglass 9 Deal n Pro/ ® Smooth Pro Jeld-Wen Elco 1/4" dia. tapcon with min 1.25" embedment at 3" max from corners and 11.5" o.c. max thereafter in head and jambs. + _ 50.0 PSF C FL# 153 52.2 511d1n Glass g Door Series 420 MI Windows and doors i • x cone w mi . penet anon at max. PTm Buck into":ol dnfllledpC HUele ado"mbainten rig horn 2L5" edge gdietence n strict adherence to the roduct approval. + 48.2 PSF - Product NOA/FL NUMBER Model # Manufacturer Attachment Method T•�'�� LOT Date Design Pressure of Approved Teats Mullions FL# 15353.8 CM-18531 vertical mullion Mi Windows and doors For CMU use (2) 1/4' x 2 3/4" tapeona with min 1 1/4" embedment penetration into each Mull Clip. Attach mull to clip using (4) #10 x 1.251, aeif tapping screws per clip as shown in product approval. + 118.9 PSF_ Roof FL# IIL51.12 SV Crimp Metal Roofing Gulf Coast Supply and manufacturing 2G ga. Ev crimp metal roofing attached to plywood deck using #9 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D R a 2) 30 Ib felt underia ment installed with min. 4� aide laps and V end sP s p laps Fastened with at corrosion reactant tin caps and with c. ring shank Walla apecad G" o.c, at all laps and two staggered rows 12" o.c. In field. Attach deck to trusses using attachment detail on roof plan - I08.5 PSF Siding stucco on Block Soffit FL# 12198.3 Model T4 12" vented Vinyl Soffit Kagdan Install using 2" x 2" battens at 6" o.c. screwed to soffit framing using 98 x 3" wood screws at each truss. Install soffit to battens using 0.12" die. x LF)" ioniona rina &hank nails with S/S" dia. +55.0/-35.0 PSF Hurricane Panels FI# 15014.2 24 Gauge Storm Panels Global Protection Products LLC Install using 1/2" die. solid set lead anchors with 1/4" dia.-20 x 1.5" long 55 screw head combo. with Neoprene washer at 12 1/2' o.c. along the bottom and 13" ox. at the top ± 45.0 PSF I have reviewed the above and approved it by my seal below. ( Architect or Engineer of Record ALL CONTRACTOR WARRANTIES BEGIN WHEN THE CLOSING OCCURS BETWEEN THE BUYER AND WYNNE BUILDING CORP I/2" drywall ceiling on truss bottom cord AND WILL CONTINUE FOR ONE YEAR FROM THAT DATE 2" x 4" top plate 1/2" drywall on 2" x 4" studs at IC o.c. base -board 1 11 / 2" x 4" P.T. bottom plate \ 4" concrete slab with fibermesh OR 6"xC #10/10 WWM on 6 mil Vlsqueen over clean compacted termite treated fill Interior Non -Bearing Partition nts PERMITTING INFORMATION (FORM 100) Florida Building Code Residential: 5th Edition and ASCE 1-10 for Wind Loading Building Design is: Enclosed Risk Category: II Wind Velocity: 165 mph ultimate Mean Roof Height: II'-0" Roof Pitch: 4:12 Internal Pressure Coefr(tcent: ±O_I8 SubJectibility to damage from: Weathering: Negligible Termites: Very Heavy Width of Roof End Zone: 3'-4" Wind Speed: 165 mph ultimate Wind Exilrit f forClassification: C 1.21 x 0.4 = 0.126 ASO desi n Adjuatmsnt factor for Exposure Height: gg Load C'Imbination: ASCE 1-10 Section 2.4 DL+LL; DL+O.6WL; 0.6DL+0.61UL Components t Cladding Wind Pressure (NET) Roof Zone: I. +20.6/-32.6 psf Roof Zone: 2. +20.6/-51.0 psf Roof Zone: 3. +20.6/-84.0 psf Components t Cladding Wall End Zone Width: 3'-11" Components t Cladding Wind Pressure (NET) Wall Zone: 4.+35.8/-38.1 psf Wall Zone: 5. +35.e/-41.8 par Components t Cladding Wind Pressure (NET) on Garage Door: +32.0/-40.3 per Shear Ualls Considered for Structure? Yes Continuws Load Path Provided?Yee - Are Conponents an Cladding Detai s Provided? Yes Minimum Soil Bearing Pressure:2.500 psi, Presumptive: X Bg Test: psi This Belding Shall Have the Following: APIROVED SHUTTERS.­X IMPACT GLASS: BOTH: NEITHER: ROOF AVE.LOAD: 3'1 psf ROOF DEAD LOAD: 10 psf FLOOR LIVE LOAD: -A-5- pat FLOOR DEAD LOAD 10 par JOB ADDRESS: TCH = Roof Zone I Walls Zone 4 EM = Roof Zone 2 Walls Zone 5 END ZONE = Corner Zones Roof Zone 3 I FLOOR FLAN CRASH POST DETAIL TYPICAL NOTES: SCALE 1/4" = I'-O" I. Contractor to verify ALL notes and dimensions prior to Ste high by 4" diameter s proceeding with Work. Flange with 4teel crash post. Floor - 3/8" 2. Contractor to STRICTLY enforce ALL OSHA Requirements. ex analor bolts into 3. ALL Lumber to be used as Beam, Rafters, etc... to have Slag (3/8"t 50 ksi steel plate) a minimum 1,400 P.S.I. fiber stress. 41, 4. No dissimilar metals to touch. 2%," 2 S. ALL Concrete used for slabs shall be min. 2,500 PSI concrete. ALL Concrete used for vertical filled cells, cont. tie beams etc.. to shall be 3,000 P.S.I. concrete and/or 4,000 P.S.I. groat mix 6. Drywall at ceilings shall be leveled and attached to bottom chord of trusses with screws per FBC R-102.3.5. 7. ALL wood in contact with concrete shall be pressure treated, ° 8. ALL wall dimensions are nominal and not finished wall or stud dimensions. 9. ALL plumbing fixtures to be low flow. 10, Contractor to Provide Drain at water heater in accordance with the current edition of the Florida Plumbing Code. 11. Contractor to Provide a 2'-8" wide door at one bathroom for handicap accessibility requirements. 12. Lowest finished floor to be set by Governing Building Department surveyor to set in field. 13. Separation between residence and garage shall be per FBC R302.( 14. Door between garage and residence shall be 1-3/4"t 20 min, rated door w.H. = Water Heater 15. Wall and Ceiling shall have a flame -spread classification of not greater than 200 er FBC R302.9.1 I6. Wall and ceiling finishes shall have a smoke -developed Index of not greater than 450 per FBC R302.9.2 11. All exposed attic insulation materials installed on attic floors shall have a critical radiant 1" x 6" P.T. Buck nailed to flux not less than 0.12 watt per square centimeter. Exposed foam plastic insulation block with case hardened nails materials exposed on the underside of the roof deck or on the attic walls shall comply prior to door attachment with F.B.C. R316 - see permit info box of code edition 18. Gyypsum board material shall conform to ASTM C3L, C19, C415, C514, C00, C931 C91o0, C1002, C1041,C1177, C1118, C1218, C1395, or C1396 and shall be installed according to the following: (FBC R702.3.5) Drywall Thickness Location Orientation Framing Member Max, spacing of fasteners Nail sizing options for of drywall into Spacing Maximum installation wood framing members Nails FScrujs 2" x min. thickness Ceiling Perpendicular 24" 1" 12" 13ga 1 3/8" lloong with 19/64" head O 0.098" diameter x I I/4" long annular -ringed or 5d cooler nail �2 OR 0.080" dia. xx 1 5/8" long with Walls Either 16" e' 1V Direction 15/64" head OR G psum board nail 0.084" dia. x 5/8 with 9/32" head. Ceiling Perpendicular 24" 1" 12" 13ga 15/8" long with 19/44" head OR 0.098" diameter x 1 3/8" long annular -ringed or 6d cooler nail a OR 0.092" dia. x 1 1/8" long with Walls Either 141, 8" I61, Direction 1/4" head OR Gypsum board nail 0.0916" dia. x 1 1/8" with 19/44" head. Install SGD thru buck into block with 3/16" tap -con with 1 1/2" penetration at 6" o.c. max. from each corner and 20." o.c_ max thereafter at head per product approval Use 3/14" tap -con with 1 1/2" penetration at 6" o.c. max. from each corner and 20" o_c, max thereafter at sill per product approval 19. ALL ceramic tile surfaces installed shall conform to ASTM A108.1 thru A108.6, A108.1, A118.1, A118.3, A136.1 and A13-1_1 20. Cement, fiber -cement or glass mat gypsum backers in accordance with ASTM C1288, C1325, OR C11718 and installed I.A.W. manufacturers recommendations shall be used as backer for the wall tile in tub areas and wall panels in shower areas. 21. Insulation including facings such as retarders or vapor permeable members installed within floor -ceiling assemblies, roof -ceiling assemblies, wall, crawl spaces and attics shall have a flame spread index not to exceed 25 with an accompanging smoke developed index not to exceed 450 when tested in accordance with ASTM E 84. Insulation shall comply with F.B.C. R316. Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11651.12 26 ga. 5v crimp metal roofing attached to plywood deck using #9 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D (type 2) 30 lb felt underlayment installed with min. 4' side laps and 6" end laps fastened with corrosion resistant tin caps and with L25" ring shank nails spaced 6" o.c. at ell laps and two staggered rows 12" o.c. in field. Attach deck to trusses using attachment detail on this sheet Simpson HETA 20 or equal hurricane anchor at each truss with (10) IOd x 1 1/2" nails ( 24" o.c.) supporting Max. 18101bs. uplift Aluminum Drip - Edge t Fascia 2" x 6" Kaycan full o vent vinyl soffi usingg 1/8" dia shank x 1.5" for rooFing nails with 3/8" die. he product approval - see chart 5/8" thick light textured stucco on typical concrete block construction #5 bar vert. w/ 30" overlap at each filled cell Grade 12 PRE-ENGINEERED TRUSSES 4 �- at 24"o.c. TYPICAL (shop drawings by manufacturer) "\R-30 blown fiberglass in bottom chord of trusses I/2" drywall with smooth finish Two rows of beam block filled with concrete and !U #5 bar cont. in each row. Substitute ed precast lintel filled with concrete and (l) #5 bar cont. for bottom row over openings #1 1/2" dr wall over 1" x furring strips at IC o.c, with R4.1 fi-foll insulation on typical 8" Block walls All drywall to be installed per FBC R102.3.1 -1 and shall meet all pertaining ASTM codes. co Mortar to be Type "M" only proportioned per FBC R601.1 and Mortar Jonts shall comply with FBC R601.2J. Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...) Fill cell with concrete and (D #5 bar vert. (typical)_ Max. spacing shall not exceed Wood 48" unless otherwise noted Base see foundation plan notes for J spacing at openings .4" concrete slab with fibermesh OR 6"xO #10/10 WWM on 6 mil Visqueen over / clean compacted termite treated rill i i Fi i i I i ii i iI i ii i i I- lll II 14" x 14' Concrete footing If with (2) #5 bars cont. and #5 TY P I C A L SECTION transverse bars at 48" o.c. 0 Masonry Beam Sliding Door At Masonry Wall N.T.S. Head fixed door sliding door 1 1/2" Sill Detail NTS AREA CALCULATIONS Lving A/C = 1446 sq. ft. F°ont Porch = 141 sq, ft. Rear Porch = 200 sq. ft. Garage = 321 sq. ft. Total Under Roof= 2108 sq. ft. Total Cubic Ft = 11,968 2' VTR JAL I I I 21' VTR /'i Master Bath I s• I Lay. I 2" Lev. I 4' I 2" VTR W.C. J1L 2' 3' Shur. I Kit. Sink I I Kitchen 2 I I I Lay. J 3' W.C. Bath ,sT o Septic PLUMBiNG RISER 1" x 6" P.T. Buck nailed to block with case hardened nails prior to door attachment ` Masonry Wall gpical Flooring It - Install SGD thru buck into block with 3/16" tap -con with 1 1/2" penetration at 6" o.c. max. from each corner and 20." o.c. max thereafter at Jambs per product approvaiJamb Window Schedule Mark Size Rough Open. Window Description PRESSURE ZONE 1. 4'-S4"x 5'-3 %a' 54%"x 63/4" Single Hung ZONE 4 2, 4'-2A"x 5'-3 %' l5" x 43 %4" Single Hung ZONE 4 3. 2'-2" x V-2 1/2" 21%2"x 38%" Single Hung ZONE 4 4. 1 4'-5All x 4'-2%a' 54/e°x 54%" Single Hung ZONE 4 ALL Windows to be aluminum windows w/ tint and mullions per elevations. ALL windows to withstand pressures in permit info box on sheet I ALL windows in bathrooms to be tempered All rough opening dimensions to be verified bg contractor with manufacturer s specs prior to construction Door Schedule Mark Size Rough Opening Door Description PRESSURE ZONE A 9'-0" X 7'-0" 108" x 84" Overhead Garage Door ZONE 4 B 3'-0" X 6'-8" 41 %4"x 83N" Fiberglass Panel - Inswing ZONE 4 C 6'-O" X 6'-8" 14" x 81 1/2" or r. e"tw.tO" Sliding Glass Door ZONE 4 D 2'-0" X 6'-8" Solid Core - Wood - 6-Panel -Bi-Fold Finished 24" x 81 %2" E X-till X C-8" Solid Core - Wood - 9-Panel F 5'-0" X 6'-8" Solid Core - Wood - 6-Panel - Bi-Fold G 2'-8" x G'-8" x 1 %;' Solid Core Wood, Steel, or Masonite Door H 2'-8" X 6'-8" Solid Core - Wood - 6-Panel J 2'-6" X C-8" Solid Core - Wood - 9-Panel - Bi-Fold K 2'-8" X 6'-8" Solid Core - Wood - 6-Panel - Bi-Fold ALL Exterior doors to withstand pressures stated in permit info box on sheet 41 GARAGE DOOR SPECIFIED IN PRODUCT APPROVAL FORM AND SHALL WITHSTAND THE PRESSURES STATED IN PERMIT INFO BOX ON SHEET 41 All rough opening dimensions to be verified bg contractor with manufacturer s specs prior to construction 34'-0" 14'-0" 9'-6" 12" 8'-till .12" ❑° ❑° �° ❑° Lola E E (V EGRESS E 12" x 12" concrete column block filled with concrete and (2) #1 bars vert. tied Into lintels above p Covered Porch o a E E (N I OS O E° F)l I I I I imiSO c O MASTER uom BEDROOM 9 8'-0" to 9'-8" A.F.F. aov mU1111P Vaultedl Ceiling LLN Flat Ceiling o E GREAT R0�1'1 I � O Rod t helf I I � - H B `� Vanity to be 1 I s l r Nry 34 /2„hig I to N I I O Ln E O E I o 2" x 6" knee -wall 8'-O" to 9'-8" A.F.F. `� pC below top O rr r I counter I Vaulted Ceiling DiNING LINEN CAB NE Rod t Shelf 8" /'S,� ;F I R O O M E Q E \�`� W A T H /\ I Vanity be O ° o to H I 34 /2"high OO I -m KITCHEiII High Wall O I � Ven Dryer thro h wall L 1-1/2" I _ _ 8'-O" A.F.F. Uver-hang J O (V U. ILJI - Flat Ceiling o pper cabinets to D O ext nd over Ref. cryv 2" filler 4'-01, I N ^ I E n , a G an BATH - O g rowaDv i amn 1�tat _ Rod t Shelf O E R-II Beets nwleGon W H. N E -I ® N_ E O a /C I � #1 4"� Steel Ballard i See detail orb �ia-shseJ< - 6 F lfl I�" I > cn O I 22i x Access � O I rose de auto I Atmith tight~ N �r 22' _ _ J V-O" A.F.F. ' Flat Ceiling 150 Amp 4,, - on J Meter a 1r-6° Panel -o„ 0D n; C) m SECOND - o GARAGE E BEDROOM EGRE55Y S O -4" A.F.F. E MT EE ry Flat Ceiling E E O P- o„ � OE O r----------------- 1 EGRESS E Block wall in ° `r i garage to be I = E E �Wd ao S E struck block O E - I C \/ER D 6 12" x 12" concrete column block filled I 4 6 IRORCH with con rete and (2) 1 bars vert. tied IO into lintels above Ln I 6' 2" II' -till till 1 ® 11. o E E lslhr�EE OE N Elml 2'-8" 2'-8" 4'-2" 5'-4" Install windows thru buck into block with 3/IL" tap -con with 1 1/2" penetration at 6 o.c. max. from each corner and 20." o.c. max thereafter at jambs and 20" o.c. max. Exterior face at head and sill per product approval of wall -- / \ Buck to be I" x 4" PT I"x4" P.T. Buck nailed to block with case hardened nails D e t a l l a t W i n d OW S prior to window attachment NTS INSTALL VULKEM BLOCK SEALANT ON ALL JAMB, HEADER, AND SILL BLOCK PRIOR TO BUCK INSTALLATION Exterior face Attach buck to block wall with 1/4" dia. Elco conic screws with min. 1 1/4" penetration at 12" o.c. max and 4" max from each corner thru 2" x 6" PT Buck Detail at Door crews thru jamb into buck ige and 15" o.c. max and prior to door attachment NTS Scale : 1/2" = I'-O" 3+ -0" TFU L NQ L ALL FOOTING ARE DESIGNED FOR A MINIMUM OF 2,500 PSF SOIL 9. BEARING CAPACITY. IF ANY SUB -SOIL, MUCK OR NON -UNIFORM CONDITIONS EXIST, REPORT TO ARCHITECT AND OBTAIN PROPER ENGINEERING DATA FOR DESIGN. 2. ALL SLABS AND FOOTINGS TO BE A MINIMUM 2,500 PSI AT 28 DAYS IC ALL COLUMNS, FILLED CELLS, AND BEAMS SHALL BE MIN. 3000 PSI BE 3000 PSI OR 4,000 PSI GROUT MIX AT 28 DAYS 3. POISON SOIL AND COVER W/ L MIL. VISQUEEN WITHIN 24 HOURS. NO SOIL POISONING TO BE ACCOMPLISHED OUTSIDE OF FOUNDATION. II. 4 GROUND FLOOR SLAB TO BE A MINIMUM 4" THICK W/ 6X6 10/10 WELDED WIRE MESH REINFORCING ON 6 MIL. POLYETHYLENE VAPOR 12 BARRIER ON TERMITE TREATED, CLEAN MACHINE COMPACTED FILL (MINIMUM 95% DENSITY). LAP POLYETHYLENE 12" MINIMUM. FIBERMESH MIX MAY BE SUBSTITUTED FOR WELDED WIRE MESH. 5. LOT TO BE CLEARED OF ALL SMALL PLANT GROWTH AND DEBRIS BEFORE FILL IS BROUGHT IN. FILL TO BE SPREAD IN 12" LAYERS AND 13 MACHINE COMPACTED TO A MINIMUM OF 2500 PSI IN AREA OF BUILDING CONSTRUCTION 6. TEST FOR FILL COMPACTION MINIMUMS PRIOR TO FORMING SLAB. 14 GENERAL CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS. BRING ANY DISCREPANCIES OR OMISSIONS TO THE 15 ATTENTION OF THE ARCHITECT. 16 8. GARAGE FLOORS TO BE SMOOTH TROWEL FINISH (SLOPPED PER FOUNDATION PLAN). PROVIDE 1-1/2" RECESS FOR OVERHEAD DOOR Il FCLAD,470N fLi4N SLOPE ALL PORCH SLABS, COVERED WALK, ETC. AWAY FROM HOUSE TO DRAINS (IF PROVIDED) PER PLANS DESIGN LOADS ARE AS FOLLOWS: ROOF (DL+LL) = 41 PSF WIND VELOCITY = PER PERMIT INFO BOX ON SHEET #1 EXPOSURE ="C" ALL REINFORCING STEEL SHALL BE GRADE 60, MEETING ASTM A-16, t A-35 SPECIFICATIONS. ALL ANCHOR TO BE A - 301 STEEL. ALL DOWELS, SLEEVES, CONDUITS, INSERTS, BLOCKOUTS, ANCHOR BOLTS AND FRAMES SHALL BE IN PLACE PRIOR TO POURING CONCRETE. FOR OPENINGS AND SPECIAL FEATURES OMITTED ON THESE PLANS, SEE ARCHITECTURAL OR MECHANICAL PLANS WHERE APPLICABLE. MINIMUM CONCRETE PROTECTION FOR REINFORCING BARS: FOOTING: 3" BEAMS: 1-1/2" LAP ALL REINFORCING STEEL A MINIMUM OF 48 BAR DIAMETERS. USE STRUCTURAL GRADE WOOD WITH A MINIMUM Fb OF 1600 PSI ALL STANDARD LUMBER SHALL BE SYP WITH A MINIMUM Fb OF 1000 PSI OF NO.2 SOUTHERN PINE, UNLESS NOTED OTHERWISE. ALL LUMBER IN CONTACT WITH ANY CONCRETE OR MASONRY SHALL BE PRESSURE TREATED. FASTENERS TO HAVE MIN. G185 RATING. I. Any changes to plans must be submitted to the architect for approval before proceeding With construction. 2. Contractor shall be responsible for verlf [cation of all notation and dimensions before starting construction. 3. Soil conditions assumed to be 2800 psf. Should any other conditions be encountered, the architect shall be notified in writing for revision 4. Verify all recess thickness at showers, tile, etc.... S. Contractor to provide filled cell with concrete and I #8 bar vert. at 48" O.C. max. Provide (1) filled cell on each side of openings upp to 5'—I1" wide. Provide (2) filled cells on each side of openings from 6'—O" to 9'—II" and Provide (3) filled cells on each side of openings from 10'-0" and up Contractor to see plans for any other condition used. Foundation walls shall have filled cells at 24" o.c. unless otherwise noted (see section) 6. Contractor to provide for Form Board Survey — Form Board Survey to be provided to Truss Company prior to truss construction 1. Contractor to provide for soil test prior to construction and provide a copy of soil test to architect for review prior to construction 8_ ALL Reinforcing steel shall be grade (0, meeting ASTM A—I(o and A-38 specifications. ALL Anchors to be A-301 Steel. 9. Provide a minimum of 3" concrete protection at footings and 1-1/2" concrete protection at beams for ALL reinforcing bars. tt5 bar vert. w/SEE TYPICAL ea ch overlap ECTIONS at each filled cell f' 4" concrete slab with fibermesh OR 6"xb" #10/10 WWM on 10 mil Visqueen over clean compacted termite treated fill It cal _ _IIII III IIII_ 14"w x 14"d concrete monolithic footing with (2) #5 bars cont. 14" „ l= j TYPICAL FOOTING DETAIL J 5CALE 1/2" = I'-U 4" concrete slab with fibermesh OR 6 x6 #10/10 WWM on 10 mil Visqueen over clean compacted termite treated fill #5 bar cont. Step per foundation plan (2) #5 bars cont. bottom steel DETAIL AT GARAGE STEPDOWN SCALE 1/2" = 1'-0" 12" x 12" concrete column block filled with concrete and (2) #1 bars vert. tied into lintels above Verifg house slab height in field Top of footer 16" below finished flo it 11l ff 01111M sn1_�a rE 30 rl COLUMN FOOTING DETAIL 30"x30"xl6" concrete column footing with (4) #S bars each way Thicken edge to 8"x8" with concrete and one #5 bar continuous 45 bar vert. w/ 30" overlap at each filled cell Adjust curb height based on gar. floor slope. #5 bar in curb \ SCALE: 114" = 1'-0" Termite Protection for New Construction. Soil treatment used for subterranean termite prevention inside the foundation perimeter shall be done after all excavation, backfilling and compaction is complete. If soil area is disturbed after initial chemical soil treatment area shall be re -treated with a chemical soil treatment including spaces boxed or framed. Treatment must be in accordance with the rules and laws established by the Florida Department of Agriculture and consumer services. Protective sleeves around metallic piping penetrating concrete slab on grade floors shall not be of cellulose containing materials and shall receive application of termicide in annular space between sleeve and pipe. 4" concrete slab with fibermesh OR 6"x6" 410/10 WWM on 10 mil Visqueen over fill EE TYPICAL iECTIONS 4" concrete slab with fibermesh OR Vxb" #10/10 WWM on 10 mil Visqueen over clean compacted termite treated fill 0'-0" a F.F. AIL _�Ir / — I '!�14"w x 14"d concrete monolithic footing with (2) 45 bars cont. GARAGE CURB DETAIL 2" x 6" PT wood secured with \ 3/8"dia. x 6" anchor bolt at 18" o.c. overhead door track secured to wood jamb per manufacturer's product approval Garage Door Jamb Detail GARAGE DOOR TO WITHSTAND PRESSURES STATED NTS IN PERMIT INFO BOX ON SHEET #I. SEE PRODUCT APPROVAL FORM FOR MANUFACTURER MAKE AND MODEL. Filled Cell Masonry Column With One #5 From Footing To Tie Beam Conc. Fill To Be 3000 PSI See Floor Plan For Location O Single Filled Cell Column NTS Filled Cell Masonry Column With One #5 From Footing To Beam Each. Conc. Fill To Be 3000 PSI See Floor Plan For Location Double Filled Cell Columr NTS 14' -O" 20'-0" — — EE °O EE ° ---- ,E--------I --------t- ° I FI I Filled der der above girder I 24" I I o Rear Patio/Slab r I O r J to be poured separate from the house slab. EI �_ I E m I Thicken footing to �E I FI 24"w x 14"d x 24"L under filled cell I I a under girder bearing. E E 111 4 10 1 1 1 1 01 1 1 1 E E E --- —;=N— ———— —— — — — — —- w tj o c I Rear Patio/Slab to be flush with bottom of ° is a-u w H I sliding door recess. Slope 1/2" I F_ a`n I E I I IF- I I I h- to IE ° 32'-8" I H.B. I I^ 4" concrete slab with fiber ash OR I E ° 6,,XC 410/10 WWM on 6 mil V squeen over I O " clean compacted termite tr ated fill I _I —i ell E V I I � t I CV I O ° Q H.B. a T RMITETREATME�.t r— -------- I 4"m Steel Ballard FI #I FS w filled w/ Concrete 0 � OI �O= I Imo Nvv .� I I �__�J I N2r Will E ? I i5 (� m I `Et! I I IE y�E I L--a FI Oil I °� EEC I moo'' I I O\\ I E E o �E3E UOO I \ FI I I u �a� N I F5 - tx IjJ I ° O CDE EE x L— F5 Recess for J 8 N I E 00 °E Garage Door ---- E 00 00 --- °° --------- J F � 3'-5" 6'-2" II'-6" 6' � with concrete and�(2) #1 bars vert. tir.Z into lintels above A b FOOTING SCHEDULE Mark Sae Description FI 14"W x 14"D MONOLITHIC FOOTING WITH 2 #5 BARS CONTINUOUS F 1211W X 12"0 MONOLITHIC FOOTING WITH (2) #5 BARS CONTINUOUS F 30" x 30" x 16"D COLUMN FOOTING WITH (4) #5 BARS EACH WAY 8"111 x 8"D THICKEN SLAB EDGE WITH I #5 BAR CONTINUOUS F5 114"W With x 14"D Curb at Garage MONOLITHIC FOOTING WITH 2 45 BARS CONTINUOUS - CURB 9 0'-0" / ����MPA ��� ������������ Q RA MR 04 1 1 r.! �WWW�����'���������� Ke Area Bilge Field Fastener Pressure Zone I 6" 6" 8d ring shank 45 psf Zone 2 4" L" 8d tin shank 7(. psf Zone 3 x{" q" 8d ring shank 84 psf ** Zone 3a (o" 6" 48 wood screw 112.5 psf Provide 45 liars with min. 48 bar diameters overlap Into beam. Tie felled cell steel Into continuous beam block steel, n Provide 45 bar set in pre -cast lintel Into beam where length of the opening calla for it. Provide Cast -Crete ,= � � � '?�.�•• T ; SUB-OB/OT precast - - � -} I - lintel set in mortar \ Min. 8" Bearing ovide PT Buck :ached per iamb 11 I F �� Poured Felled Cell ads into filled cell 4" Pre -cast Sill \ 11111 Provide #5 bars with min. 48 bar diameters overlap In filled cell. Tie filled cell steel Into continuous Footer steel. CBS WALL Scale: I/2" = I'-O" SINGLE PLY REAR GIRDER TRUSS 2" x 4" blocking to vart. leg of truss with IOd x 1.5' Wads at 4" O.C. Verify with Plan V- Install Simpson MGT Into wall usln Concret Llnt le 12"x 12" Into "wet bthreaded em a d (2set 2) IOd neils�into trues Column Block f- 7 Reber Reber 48 Bar Dia. , min. Overlap TRUSS BLOCKING DETAIL Column to LIntel �4ttac�7&nt AT GIRDER STRAPPING ,4T CENTER BE,4RINC,, POINT NTS 1/8" thick Ilght textured stucco installed per ASTM C 926 over ASTM D type 2 paper backed wire lath nailed to substrate through one layer of ASTM D Tyype 2 felt paper using 8d nails. Substrate to be 19/32' COX Plywood nailed at 6" o.c. in field and edges with IOd ring shank nails into studs. Gulf Coast Supply and MFG 5v Crimp Metal roofing FL #11G51.12 26 ga. 5v crimp metal roofing attached to plywood deck using 49 x 1.5" wood screws with self sealing washer at 12" o.c. max spacing over ASTM D (tgpe 2) 30 lb felt underlagment installed with min. 4' aide laps and 6" end laps fastened with corrosion resistant tin caps and with 1,25" ring shank nails spaced 6 o.c. at all laps and two staggered rows 12" o.c, in field. Attach deck to trusses using attachment detail on this sheet \ none Additional Precast Lintel x5 bars Lintel Bar Clear "A" "B" Length Len th 9 Sp, n Bars Bars 2'-10" 2'-8" I'-6" 2,#3 none 3'-6" 3'-4" 2'-2" 2,#3 -none BFB-OB/IT BF8-IB/IT BF8-IB/2T Additional 4'-0" 3'-10" 2'-8" 2,43 none tt5 bare •.• CLEA ;` 2,#3 Nall SCHEDULE Mork Window or Door Unit Width Lrntel Size Cast-Crete SpeciPlcaUon Rowe of "H" Block Above Boteom Steal Size Top Steel Size Mept Gravity Load (pLF) Max. Uplift Load (PLF) Max. Lateral Load (PLF) L22 2'-2" 3'-L' 8F8-OB/IT I tt5 300 I549 1024 L31 2'-0 4'-O" 8F8-OB/IT I #5 25L1 1363 10 L45 4'-5" 5'-10" BFB-08/IT I #5 1105 909 339 L50 5'-0' G'-G' 8F8-OB/IT I #5 1238 835 121 LLO 6'-8" 1'-4" 8111118-OB/IT I #5 1011 121 534 L80 8'-O' 9'-40 8F8-IB/2T I tt5 2 u5 l52 591 512 L90 9'-0" 10'-4" BPS-IB/2T I #5 2 tt5 L43 530 401 L90B 9'-0" 10'-G" BFI4-IB/2T ONE i #5 2 45 1533 1183 401 1_I00 10'-0" II'-4" 8F8-IB/2T I #5 2 tt5 582 494 452 LIOOB 10'-0" II'-4" eFIL-IB/2T ONE I u5 2 #5 134G 1028 452 LI20 12'-O" 13'-4' 8F8-IB/2T I tt5 2 tt5 411 428 324 LI206 12'-0" 13'-4" BFIL-IB/2T ONE I its 2 tt5 1015 110 324 LI40 14'-0" I5'-4" 81sIL-IB/21r ONE I #5 2 #5 1250 609 259 LILO IL'-O" IT-4' 8F8-IB/2T I tt5 2 tt5 300 192 194 LILOB IV -Or I'1'-4" BFIL-0/2T ONE I #5 2 #5 950 500 194 - ALL LINTELS SHALL BE MADE BY CAST-CRETE. - LINTELS SHALL BE FILLED SOLID WITH 3000 P51 CONCRETE - REFER TO CAST-CRETE CATALOG FOR ALL INFORMATION REGARDING LINTEL CONSTRUCTION, HANDLING INFORMATION, AND SAFE LOAD REQ. REQUIREMENTS - LINTELS OVER 14'-0" LONG ARE TO BE PRESTRESSED Simpson HETA 20 or equal hurricane anchor at each truss with (10) IOd x I I/2" Halle — ( 24" o.c.) supporting Max_ 18101ba. uplift Aluminum Drip ------- Edge t Fascia 12" 2" x 6" Sub-Fasci Kaycan full o vent vmgl soffit metalled tieing I/e" ilia shank x 15" long gale. rooting nails with 3/e" ilia. heed per product approval -see chart sheet ttl 12" x 12" concrete column block filled with concrete and (2) ire bare vert. tied�� Into lintels above thicken edge to 8"x8" with concrete and one tt5 bar continuous BEYOND Top of faoter 16" below finished floor 4 Aluminum Drip Edge 6 Fascia Co crate Anchors Per Ma ufacturers specs Poured Concrete or / concrete black well N 1I/4"Max. Aluminum Panel Sizes per manufacturer - See Tua cal Stud Detal I ' v l/a° x 3/32" Wing Nut w/ I v_ appropriate washer and spacing I u `v per manufacturer's Details d 4 .ocs' I � � I ' =m I " I d I x 1 � I I I I I I 11115. I Stud Detail Poured Concrete or Stud w/ Die Caat Zinc era concrete block wall � I Nickel Plated Wing Nut vl° Concrete Anchors Per =. Manufacturers Specs Flash and Counter v flash Nail ledger to gable end truQilr\ with (2) IOd at each web I/2" thick stucco on 3/6" hi -rib lath attached to horizontal and vertical wood Framing with Halls or staples to provide no lees than I-3/4" penetration Into horizontal wood framing and 3/4" penetration into vertical wood Pramina members 5/8" thick fight textured stucco on typical concrete block construction Varies - see plan #5 bar vert, w/ 30" overlap at each filled cell Rear Patio/Slab to be flush with bottom of sliding door recess. Step per foundation plan a Slope per Foundation plan Brace Gable end with 2" x 4" SYP #2 8ft back Walled to bottom of top chords using (2) IOd Halls at each truss LLI PRE-ENGINEEiiED WOOD TRUSSES � e 24"o.c. TYPICAL ( shop drawings by manufacturer ) R-30 blown fiberglass Flush Mounted Shutter Detail nts N N � X s O� rn N � 4�0� Q L O 93 U o0 a ems_ °p O �N d Brace Gable end with 2" x 4" SYP #2 min. 8Ft back Walled to bottom — of top chords using (2) IOd Halls at each truss a 0 in bottom chord or trusses m -1/2" drywall with smooth finish o = Two rows of beam block filled with concrete -and (1) #5 bar cont, in each row. Substitute u precast lintel filled with concrete and (1) #5 bar cont, for bottom row over openings m I/2" drggwall over I" x furrinN gg strips of 16" o.c. with R4.1 f`I-foil Insulation on typical 8" Block walls All drywall to be installed per FBC R102.3.1 Strap 5/e' truss to wall ilia. threaded using Simpson MGT with rod with min 12" embedment Simpson HETA 20 Into beam either wet set or In epoxy with hurricane anchor at each truss (22) truss IOd leg Halls Into per detail truss. Add blocking to on this sheet ( 24" O.C.) supporting Max. IBI/l IL_ ._Lr" and shall meet all pertaining ASTM codes, HETA 20 Mortar to be Type "M" oney proportioned per FBC R601.1 and Mortar points shall comply with FBC RbOl.2.1. Provide Our-O-Rock at all wet areas (ex. showers, tubs etc...) PIII cell with concrete and ROOF O O � }�"� � J/�\ I\`IL h * I (1) US bar vert. (typrcaD. I}� Max. spacing shall not exceed 48" unless otherwise noted see foundation plan notes for — OVERHANGS AT I'—O" UNLESS OTHERWISE NOTED ON THIS SHEET spacing at openings 4" concrete slab with fibermesh OR - ROOF PITCH AT 4:12 UNLESS OTHERWISE NOTED ON THIS SHEET 6"x6" #10/10 WWM on 6 and Vlsqueen over - TRUSS SHOP DRAWINGS TO BE PROVIDED BY MANUFACTURER lclean compacted termite treated fill - ANY CHANGES TO THIS PLAN SHALL BE SUBMITTED TO THE Tf1=fT�1T ARCHITECT FOR APPROVAL IN WRITING PRIOR TO STARTING CONSTRUCTION. =IIII=IIII— — ALL TRUSS TO TRUSS CONNECTIONS BY =IIII=IIII=IIII=IIIIIIII—IIII—IIII— I. Ili' TRUSS MANUFACTURER III i�II ;,.IIII=IIII=IIII=III IIII IIiI- =F1 - ARCHITECT TO REVIEW TRUSS SHOP DRAWINGS PRIOR TO CONSTRUCTION FOR LAYOUT AND UPLIFT VERIFICATION li 3 Typical Section at Front Porch — CONTRACTOR TO PROVIDE FOR FORM BOARD SURVEY AND TO PROVIDE Scale ; " _ " FORM BOARD SURVEY TO TRUSS COMPANY PRIOR TO TRUSS CONSTRUCTION Braden $ Braden AI A, FA Wynne Building Corp. Date Drawn :Revisions Sheet Comm :4Architects - Planners 5-9--I1 Tel S.E. Coconut Avenue The Grand Carlton LEFT E Drawn by: w4" l 2 — 2 b Tel (712) 287-8258 commast .net C.C.U. E-mail: braden Fax (rat) 28 Spanish Lakes Checked bg: Stuart FL 3ala comcaSt. Lucie Count Florida OF 5 Vile Ali co;!) r "4996 #AAC000032 D_R? S. Wood Base Cr7 PANEL "A" arc# Description Wire Load BR Poles Poles BR Load Wire Description circ# 2 40 1.0 kw #8 A/C comp 1 2 AHU #Io 3.5 kw 30 2 3 q 2 30 4.5 kw #l0 40 gal. water HTR 5 6 Range #L 12.0 kw 50 2 1 8 1 20 1.8 kw #12 Pump 9 10 Dr er #10 5.0 kw 30 2 11 12 1 20 1.5 kw 31:12 13 14 Dishwasher #12 1.2 kw 20 1 1 20 1.5 kw #12 Microwave i5 14 Refrigerator #12 1.2 kw 20 1 I 20 1.5 Ike #12 Kitchen S.A.C. I� 18 Recepts #12 20 1 1 20 1.5 kw #12 Kitchen S.A.C. 19 20 Recepts #12 20 1 1 20 1.2 kw 412 Clothes Washer 21 22 Recepts #12 20 1 1 20 0.81 kw #12 Garage Door Opener 23 24 Recepts #12 20 1 I 120 1.4 kw #12 25 2L Recepts #12 20 1 1 20 1.92 kw #12 21 28 Recepts 412 #12 20 1 1 20 #12 General Lighting 29 30 Recepts 20 1 1 20 #12 General Lighting 31 32 Recepts 912 20 1 1 20 912 General Lighting 33 34 Exterior GFCI #12 20 1 1 20 912 General Lighting 35 36 Bathroom GFI #12 20 1 I 20 #12 Smoke Detectors 31 38 General Lighting #12 20 1 I 20 #12 Bathroom GFI 39 40 General Lighting 412 20 1 s are 41 42 Spare PANEL "A" LOAD CALCULATION SHEET Load Description Qt . Watts Total(Watts) General .Lighting. (3. watts sq. ft.) $mall. A.ppha.n.ce. C.ircuit(s) . . ... . . . . . . .. . . . . ................. Rprige........................................... ............. Refrigerator Microwave .......... ............... Dish, Washer ............. _.................................. Clothes Washer .............................................. Clothes -Dryer ................................................ Water Heater Water Pump ................................................... ............. Garage. Door. Opener. 1135 3 5,205 2 1,500 3.000 1 12,000 12,000 I 1,200 1 500 1,200 1,200 5,000 1,200 1 1,500 1 1,200 -- 1 1,200 1 5.000 1 4,500 1,800 4,600 1 1,800 1 810 810 Total Watts 31,415 First 10000 Watts $100% 1 10,000 10,000 Remainder 21.415 e40% 1 O 10,944 Electric Heat or A/C 10,000 50% 1 10,000 Watts 10,000 Calculated Load 30,946 Voltage 240 Calculated Wattage Divided bg Voltage = Total Amps 129.03 Panel Size Required = 150 Amps Electrical S mbol LeOrd S Single Pole Switch ® Recessed Can Light S3 Double Pole Switch ® Eyeball Recessed 1 PB Push Button Switch Exhaust Fan Duplex Outlet Ceiling Mounted Light Special Receptacle o- Wall Mounted Light ==ec L.P. rr Waterproof ground fault circuit interrupter w Light with Pull Chain (attic) ® Floor Duplex Outlet @ Computer Connection Jack Fc-ri-1 Carbon Monoxide Detector Flood Light QT Thermostat m Electrical Panel ® Central Vac cE:-::b Electrical Meter Q Smoke Detector Ceiling fan Q Television Jack Telephone Jack AC DISo A/C Disconnect ® I x 4 Florescent Light ® 2 x 4 Florescent Light sr'KR Speaker Hook -Up Intercom 143 CFM IOxiox6 MASTER BEDROOM 143 CFM IOxlOxb 12xl2x9 B/A F 1 F' IL - _ _ - - - - - - 4\ i 12xl2x9 B/A CLOSE x4 Yent_thru ____ Soffit �- H I �\I I 101, IN I GR IAT ROM I I 169 CFM I Center Registers on ceiling fan 169 CFM IOxio I \�IOxloxl 12" L------T - DINING ROOM " i FM j ��A� Sx 4- Lce7i�; A T H 111 N i - - - A'I$/I C 150 I - 10 UT- CT2• II0 JII1II 20 IL"_2_2" _x _54"_ > Attic Access ---23-2 C- FM c - - - - - I 12xdxl i� Meter Panel Amp ex4xSECOND 35 CBEDROOMGARAGE 12x12x8hl \- B/A r----------------- I I I I I I I I I I I I I I I I I I I I I I I I ®= JUNCTION BOX TO SUPPORT A FAN � � � O = THERMOSTAT LOCATION B/A = BALANCED AiR SCALE: 1/4" = 1'-0" Electric Notes: I. 2. Use copper wire only, no aluminum. Provide and wire all required smoke detectors. 11. It is not the intent of these plans to show every minor detail 3. Contractor to verify location of electrical of construction. The contractor shall furnish and install all items for a complete electrical system and provide all 4. service and provider. ALL paddle fans shall be on a rheostat. the requirements necessary for the equipment to be placed in 5. ALL bath and kitchen receptacles to be GFI protected. proper working order. Ig All work shall be done 1n accordance with the N.E.C. and 6. ALL exterior outlets be WP/GFI protected. shall comply with all local codes and ordinances, and shall be stalled per NFPA requirements. in Recessed cans n meet all standard requirements of the local electric utility 8. . AFCI receptacles are regwired in all rooms except es and telephone company. Kitchen, Bathrooms, and Garage. 9. 10. A/C Return Air Balance Must comply w/ FBC RM1402 A/C Refrigerant lines that are run thru slabs must be 19. The electrical system shall be completely and effectively sleeved in PVC rounded as required b g q y the latest edition of the N.E.C. 11. ALL A/C Equipment shall comply with energy calculation 20. All material shall be new and shall bear underwriters' 12. All work shall be performed bg a licensed electrical labels where applicable. contractor, the completed system shall be fullU operative. 13. Contractor shall pay for all fees, permits, testing, and 21. All equipment and panel sizes shall be verified before inspections including blower testing where required. ordering. The contractor shall provide circuit routings to 14. All work shall be coordinated with other trades to avoid suit the job conditions. interference with the progress of construction. 15. All required insurance shall be provided for protection 22. Furnish and install all fixtures as called for on the plans against the public liability and property damage for the or as selected bg others. duration of the work. 16. Contractor shall guarantee all materials and workmanship 23. All raceways and pipes placed in or through any concrete free of defects for a period of not less than two years from slab shall be spaced a minimum of three diameters of the the date of acceptance or certificate of occupancy, or one largest conduit or pipe from any other service. year from closing sale of house. Correction of defects shall be completed without additional 24. All exposed wire below 9'-I" shall be installed in metal EMT charge and shall include replacements or repair of any conduit. other phase of installation that may have been damaged. 25. Dryer Vents to be installed per FBC RM1502 Z COVERED PORCH 4H.B. Vent thru Soffit A/C disc. ISO #2/0 Aluminum feed AM I %` Conduit PANEL M TE AHU 2" PVC ( FPL 2" rigid service PPL Bare #6 copper wire to #5 cont. rebar in slab ELECTRICAL RiSER - Contractor shall use AL-CU Landing lugs. NTS - Contractor shall torque lugs I.A.W. manufacturers recommendations which shall be verified prior to construction Braden t Braden AIIA, FA Architects - Planners 411 S.E. Coconut Avenue Tel : (112) 281-8258 Fax : (112) 281-8283 E-mail: bradenaia8comcast.net Exhaust Duct Thru Soffit 4" Exhaust Duct Thru Wall wP GF Install owleAoru) under disc - not not shown clarity A/C Meter PATiO/SLAB ,'Covered Porch\\ T \ 1 \ \ I UP GFCI \ 1 Tv S I TV I Smoke / Carbon R I AT Monoxide Detector R C� O M Combo s I CM I I I =8 II II II II DINING �\ GFCI I I I_ 4\\\GFCI GFCI1® KITCHEN L Smoke LCgrbon-- - Monoxide Detector Combo \ CM CFGFCI` /I 50 CFM fGFS712 F NFGF;CIII'/ n 42" GFCI 22" x 54" 17" I I F /W® I Attic Aecess O Cents \ 1 with light L M J 150 Am? 1° Optional Panel \ I Pull chain panel location \ light in attic 42" GFCI GARAGE II Garage `/fjJj J� Doa Opener r----------------- i I I I I I I I I I I I I I I I I I I I I I I I I , MASTER BEDROOM LZ� O EC7RiC/4/4 \`\SECONO BEDROOM \ / 1 WP GFCI \ I-I-CPOdRRH C� SCALE: 1/4" =" i'-0 Post Light with / o o Attic Venting Calculations FBC 2309.1 Total Attic Space = 212,4 sq. ft. Venting Ratio I/iSO = 14.16 sq. ft. required fi rovlde A Continuous Vented Soffit Wynne Building Corp. The Grand C arltor Spanish Lakes St. Lucie County Florida Photo cell am+ r� H.B. Exhaust Duct Thru Soffit Wire For Front Post Light Date Drawn Revisions : Sheet Comm 4 5-9-1'1 GARAGE Drawn by: LEFT C.C.U. E -1 12 - 2 � Checked by: ED.R.E3- OF 6 LIFE SAFETY WARNING s ymbol identifies Life Safety Warnings that should be read e special attention by all persons installing trusses. 5-PAGING NOTE ALL TRUSSES ARE TO BE SET AT 2.-0: ON CENTER EXCEPT AS NOTED MULTIPLE PLY TRUSSES MUST BE STENED TOGETHER PER ENGINEERING BEFORE SETTING. REFER TO TGINEERING DRAWING TO DETERMINE IF MULTIPLE PLY. M DON'T LIFT TRUSSES WITH SPANS LONGER THAN 30' BY THE PEAK. Pnkl Cl II T RCCI ` Span or less ® 30' to 60' Span Spree er Bar 60 degrees or less ag �_ Approx 2/3 to �___ 1 /2 .— _� T g ',Line spon approx. one I/2 of span REFER TO BCSI REFER TO BCSI Tr s-s must be set this way if crane used. Truss must be set this way if crane used. tr Ins, s t on example. ycw ass may not match. rone operator sets truss this woy- This is an example, truss may not match. Insist crane operator sets truss this way. All load bearing walls, headers, beams & lintels must be in place at indicated height before trusses A are installed. A .IFS HArV9::�I F=FR NOTE UNLESS NOTED ELSEWHERE ON THIS LAYOUT, THESE TRUSSES ARE NOT DESIGNED FOR AIR HANDLERS IN THE ROOF OR FOR ANY OTHER A/C REQUIREMENTS. THIS MAY BE IN CONFLICT WITH BUILDING CODE AND A/C DESIGN REQUIREMENTS. CONSULT WITH BUILDING DEPARTMENT AND A/C CONTRACTOR. U REPRESENTS A HANGER For Truss to Truss Connections see hanger/connector schedule in engineering package. Carrying Girder Truss )s l. EAT PLATES BY CHAMBERS N INDICATES LOAD BEARING WALL REQUIRED BY TRUSSES SUPPLIED BY BUILDER AT A HEIGHT OF 8'-1" ABOVE FINISHED FLOOR 12 4.00 ­__ M I 181 upset=1/4" heel=315/16" PLUMB CUT END 1 2 x 4 Top Chord WALL HEIGHT 8'-l" TYPICAL END DETAIL 12 4.00 F_ upset=1/4" heel=315/16" PLUMB CUT END 2 x 4 Top Chord WALL HEIGHT 8'-l" END DETAIL: A L► ARRANGE WITH CRANE OPERATOR IN ADVANCE FOR A SPREADER BAR OF 17' - 23' IN LENGTH Do not stand on trusses until they are braced per BCSI & properly nailed to straps & hangers GARAGE LEFT GARAGE RIGHT FABRICATION AGREEMENT MW8= CMaWT WOTMM tWM TMa Agin g== i REnMM TiielsWldesalptmdlMproprlywMn4ntrussesMaleteYdho TM admaw og"and apeer f. Tmlm WE be mess In atft eaoonwbe was eIb bop pbomlent fall, � !1#"Ufefobatft*trdeEa"***wAowsfitebrkatlondteillu" . Z AldmenWaahthbWjaRlrwbaatwl0edpy0>.ubalalp,d .S, uMiev<a watfrl noft b Provldsd by ail~ na1 b playa Tlow wail fm (10) 4104 of eeatwry ate laldratornd spew V as M row.d..b ow ant arh was llotoa b lmllelnd plwMre M Ml a days b W h bbadnnv�anmi+4orbwthad•M�titdaaa.atglmbraaa• • 6Tha ltldelelpind dooa'YdOwlwabt d'amiZamiabaalby MRpl 'a pMy b b 1eb Mb. I In 4r buyaf'a'�Nb Mien on lob ap w�abla for dew ChambwaTnwahrMdaaualpbrb IWNA *dewjobaed,a poitbndewjob see axesrrwy. O ftntbu we bereepawsb brdwreddreryaMy. Tlr buy. b rpPo nbb br ado1r1wW deteery etrpwwK rpinl Men TAw has b ndelwr bece. job eb b fiot ppaappewreadd it deMry or hW Is nd l3tryerM Iwlpombbbgrmbefa Trimbrbelk4mebduefteft �gGple' 'yd9nosw, 0. aMb n shown h peaepeph 7 wow b etApct b qrp r eny dtwase an,ada hi - tWifiyait.ASEoparnalrtt.al.erlu,enwbed,.asdb)r�ab@MTn*& 7: 7Nt 4 a PURCHASE ORDER to CtuMen,Tnr of to an speed 4 or Ir • ia'=. t a 11111111101011111 plloe. bwblce WE be nee an deMry wd Pdd wthh tines d bo dltery. btwla rpey, b. made el .aa:alted Ibb'br ddmy r buyer areld dellry d teteloeiad tnaeaa Tho wderdpnsd spoils b DaY prnbrs.Trya lenrrMa ehomsyh foil 1bt caFsldelr ti went dpgnsant llat Lady reds 9-12 %per IlbrAl aNtQaa . dleiesad�rarYwamnolpddttldir brl„s• a. sWowle orrrywlwa on tis sheet aoletblba aPeemrdbof.errs hash • W'In oamidrdim d pwMwn Truce erdrdlrtt aadt for tlb MdUM to ladWOWad • womdlawy p,,rwwee PE when due ofetlyr and d bdshbbnw owed b graben These by.arr orley ire ff= and Ow redwsomd,wpen to Pry arch Ydegbbdnsss Indu ft sl1Orneys bill, r ddm* b peymere for weds wlet be anby to ' 1 in en.veft d amr moron oawnlnu agile yr.rlwR, tl. aril t1mM.a br.ndr or afted b hwWN tlaPWGK Ogles tlet tw WO Vasa tw rly wxh aodmwa be 8iM 60ob Counb. tiarlda. 11. Daabn roWnsUM" wa Px'rMCorW Mwdad And RR%ff awwedaddekW on RsipraalWn nbp Far Cotlm UehV Mdd Plate Calmeced Wood Tnssn ANSYlPUNRCA 4-2001r' . DAYW rors TrtaF --.. AapnAdwbwmavbo"per'BCSlwrbperwtr*xyad®,raps . M011101e pry tresses moat be fastened bwdwr per eaapinoerin8 before they are 804 fallure to do so can rekaln roof fxaapq& Temporary and pemwwnt bracing are required aW can sen Oft and properly and Is the nispafrwW41W of the truss emiatom Study the contents of the �l n packet on dellwry Truni smwtbeaatoridbowedbpraat"admrpew Trusses ¢alit be met plumb and egwn Do notlilt bunt or stw* of plywood, rooiblg marbal /eof wry ' rARrcenbsted loads on trusses, this can axes. t)t?NOT SET TRUSSES USING THIS LAYOUT .. -tom LAYOUT D8NMW rtrw TRUSM To Sd TRUSSO CHAMBERS TRU96 INC 3105 Oleander Avenue Fort'Plerr* Florida 34982.8423 800.551-5932 . FmtPlerm r..�. 14611l-el71 .%rAr0Vr''I2, r. y�ect'S , rt�aart .e('GroF'es va s a "double check" of the contractor. The contractor shall remain responsible - for checking field measurements and _ other construction criteria. Architect's approval covers general roof shape, review of truss strapping, and loading on structure from gravity and uplift loads and their reNaI've locations. Approved By. Date: Braden a Braden A.I.A. P.A. 92-0/93-2 MITEK 4.2 DESIGN CRITERIA County SAINT LUCIE Building Department SAINT LUCIE COUNTY Wind Design Criteria ASCE 7-2014 Wind Design Method Main Wind Force Resisting Roofing Material Shingle or Shake 0 — m' Loading in PSF Roof R.D.L. Top Chord Live 20 Q0 I Top Chord Dead 7 4.2 o Bottom Chord Live 10 Non -Concurrent o Bottom Chord Dead 10 3 TOTAL Load 37 7.2 2 — c Duration Factor 1.25 m Wind Speed 165mph Top Chord C.B. Sheeting by builder. Bottom Chord C.B. Sheeting by builder. Highest Mean Height 14'-0" Building Type ENCLOSED Building Category II:Non Restrictive Exposure Category C Barrier Island No Conforms to FBC 2014 W F-- Q Verify DESIGN CRITERIA shown above with the building department and your engineer. Design Criteria is the responsibility of the Chambers Truss Inc. Drawing Name: M11323 Scale: 1 /4 = 1' 72 total trusses, 13 different trusses. MI 4: SAE ACAD: SAE Reviewed Date:04/24/12 Revised:10/07/15 FOR WYNNE BUILDING CORP. DESCRIPTION: 62' GRAND CARLTON III PAGE 1 of 1 CUSTOMER INITIALS EACH PAGE f 13 TRUSS DRAWINGS ARE ATTACHED TO LAYOUT M 11323 ''k,, . 7q&,o 3 4L &WO 48Al