HomeMy WebLinkAboutProject Information FORM R405-2014
,FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of.Business and Professional Regulation - Residential Performance Method
Project Name: THE GRAND CARLTON Builder Name: WYNNE DEVELOPMENT
Street: WYNNE DEVELOPMENT Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT.PIERC FL, - Permit Number:
Owner: v���,`� `�'�� Jurisdiction:
Design Location: FL,ST_LUCIE_CO_INTL County:: ST. LUCIE COUNTY(Florida Climate Zone 2)
1. New construction or existing New(From Plans) 9. Wall Types(1437.3 sqft.) Insulation Area
2. Single family or multiple family Single-family a.Concrete Block-Ext Insul, Exterior R=4.1 1250.00 ftZ
b. Frame-Wood,Exterior R=11.0 187.33 ftZ
3. Number of units,if multiple family 1 c.N/A R= ftz
4. Number of Bedrooms 2 d.N/A R= ftz
5. Is this a worst case? Yes 10.Ceiling Types (1446.0 sqft.) Insulation Area a.Under Attic(Vented) R=30.0 1446.00 ftZ
6. Conditioned floor area above grade(ftZ) 1446 b.N/A R= ftz
Conditioned floor area below grade(ftZ) 0 c. R= ftZ
11.Duct
s R ftZ
7. Windows(139.2 sqft.) Description Area a.Sup:Attic,Ret:Attic,AH:Attic 6 320
a. U-Factor: Dbl, U=0.54 99.23 ftZ
SHGC: SHGC=0.25
b. U-Factor: Dbl, U=0.55 40.00 ftZ 12.Cooling systems kBtu/hr Efficiency
SHGC: SHGC=0.25 a.Central Unit 34.8 SEER:15.00
c. U-Factor: N/A ftZ
SHGC: 13.Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ftZ a.Electric Heat Pump 34.8 HSPF:8.50
SHGC:
Area Weighted Average Overhang Depth: 3.586 ft.
Area Weighted Average SHGC: 0.250 14.Hot water systems
8. Floor Types (1446.0 sqft.) Insulation Area a.Electric Cap:40 gallons
a.Slab-On-Grade Edge Insulation R=0.0 1446.00 ftZ b. Conservation features EF:0.970
b.N/A R= ftZ None
c. N/A R= ftZ 15.Credits Pstat
Glass/Floor Area: 0.096 Total Proposed Modified Loads: 46.91 PASS
Total Baseline Loads: 48.19
JJP
I hereby certify that the plans and specifications covered by Review of the plans and 4Z14E SZ,q?,
this calculation are in compliance with the Florida Energy specifications covered by this �0�,
Code. calculation indicates compliance �i„���'r''
with the Florida Energy CQd,�If
PREPARWB Before construction is comfA
�t�d�°
DATE: this building will be inspected for I°
compliance with Section 553.908 * fN
I hereby certify that this building, as designed, is in compliance Florida Statutes.
with the Florida Energy Code. ===1WE
OWNER& BUILDING OFFICIAL:
DATE: DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.2.2.1.
-Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 apofn ep�elope leakage
test report in accordance with R402.4.1.2. �� +? J
7/6/2017 8:51 AM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 5
FOkM R405-2014
PROJECT
Title: THE GRAND CARLTON Bedrooms: 2 Address Type: Street Address
Building Type: User Conditioned Area: 1446 Lot#
Owner: Total Stories: 1 Block/SubDivision:
#of Units: 1 Worst Case: Yes PlatBook:
Builder Name: WYNNE DEVELOPMENT Rotate Angle: 135 Street: WYNNE DEVELOPME
Permit Office: ST. LUCIE COUNTY Cross Ventilation: No County: ST.LUCIE COUNTY
Jurisdiction: Whole House Fan: No City,State,Zip: FT.PIERCE,
Family Type: Single-family FL,
New/Existing: New(From Plans)
Comment:
CLIMATE
/ IECC Design Temp Int Design Temp Heating Design Daily Temp
v Design Location TMY Site Zone 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL ST LUCIE CO INTL FL VERO BEACH MUNI 2 39 90 70 75 299 58 Medium
BLOCKS
Number Name Area Volume
1 Entire House 1446 11568
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated
1 BEDROOM 234 1872 No 2 1 1 Yes Yes Yes
2 WIC 54 432 No 0 1 No Yes Yes
3 MASTER BATH 63 504 No 0 1 Yes Yes Yes
4 M.BATH 56 448 No 0 1 Yes Yes Yes
5 KITCHEN 172 1376 Yes 0 1 No Yes Yes
6 BATH 45 360 No 0 1 Yes Yes Yes
7 BEDROOM 2 204 1632 No 1 1 1 Yes Yes Yes
8 LAUNDRY 42 336 No 0 1 Yes Yes Yes
9 GREAT/DINING 526 4208 No 0 1 Yes Yes Yes
10 FOYER 50 400 No 0 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio BEDROOM 40 ft 0 234 ft2 ---- 0 1 0
2 Slab-On-Grade Edge Insulatio WIC 1 ft 0 54 ft2 ---- 0 1 0
3 Slab-On-Grade Edge Insulatio MASTER BATH 9 ft 0 63 ft2 ---- 0 1 0
4 Slab-On-Grade Edge Insulatio M.BATH 8 ft 0 56 ft2 ---- 0 1 0
5 Slab-On-Grade Edge Insulatio KITCHEN 1 ft 0 172 ft2 ---- 0 1 0
6 Slab-On-Grade Edge Insulatio BATH 5 ft 0 45 ft2 ---- 0 1 0
7 Slab-On-Grade Edge Insulatio BEDROOM 2 34.2 ft 0 204 ft2 ---- 0 1 0
7/6/2017 8:51 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 2 of 5
F06 R405-2014
FLOORS
r
# Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet
8 Slab-On-Grade Edge Insulatio LAUNDRY 6 ft 0 42 ft2 ---- 0 1 0
9 Slab-On-Grade Edge Insulatio GREAT/DINING 47 ft 0 526 ft2 ---- 0 1 0
10SIab-On-Grade Edge Insulatio FOYER 7 ft 0 50 ft2 ____ 0 1 0
ROOF
/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
V/ # Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Gable or shed Metal 1524 ft2 240 ft2 Light 0.6 No 0.9 No 0 18.4
ATTIC
V # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 1446 ft2 N N
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) BEDROOM 30 Blown 234 ft2 0.1 Wood
2 Under Attic(Vented) WIC 30 Blown 54 ft2 0.1 Wood
3 Under Attic(Vented) MASTER BATH 30 Blown 63 ft2 0.1 Wood
4 Under Attic(Vented) M. BATH 30 Blown 56 ft2 0.1 Wood
5 Under Attic(Vented) KITCHEN 30 Blown 172 ft2 0.1 Wood
6 Under Attic(Vented) BATH 30 Blown 45 ft2 0.1 Wood
7 Under Attic(Vented) BEDROOM 2 30 Blown 204 ft2 0.1 Wood
8 Under Attic(Vented) LAUNDRY 30 Blown 42 ft2 0.1 Wood
9 Under Attic(Vented) GREAT/DINING 30 Blown 526 ft2 0.1 Wood
10 Under Attic(Vented) FOYER 30 Blown 50 ft2 0.1 Wood
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
9 ()rnt 10 IA/mil Type Spacen Et n Area le Ahsor
1 N=>SE Exterior Concrete Block-Ext InsfilEDROOM 4.1 9 0 8 0 72.0 ft2 0 0 0.5 0
2 S=>NW Exterior Concrete Block-Ext InstflEDROOM 4.1 18 0 8 0 144.0 ft2 0 0 0.5 0
_ 3 W=>NE Exterior Concrete Block-Ext InstdEDROOM 4.1 13 0 8 0 104.0 ft2 0 0 0.5 0
4 S=>NW Exterior Concrete Block-Ext Ins)AASTER BA 4.1 9 0 8 0 72.0 ft2 0 0 0.5 0
5 S=>NW Exterior Concrete Block-Ext InsuM. BATH 4.1 8 0 8 0 64.0 ft2 0 0 0.5 0
6 N=>SE Exterior Concrete Block-Ext Insul BATH 4.1 5 0 8 0 40.0 ft2 0 0 0.5 0
_ 7 N=>SE Exterior Concrete Block-Ext In9EDROOM 2 4.1 16 0 8 0 128.0 ft2 0 0 0.5 0
_ 8 E=>SW Exterior Concrete Block-Ext InREDROOM 2 4.1 10 0 8 0 80.0 ft2 0 0 0.5 0
9 SE=>W Exterior Concrete Block-Ext InQEDROOM 2 4.1 4 3 8 0 34.0 ft2 0 0 0.5 0
10 S=>NW Exterior Concrete Block-Ext InA3ffDROOM 2 4.1 4 0 8 0 32.0 ft2 0 0 0.5 0
11 S=>NW Exterior Concrete Block-Ext InsillAUNDRY 4.1 6 0 8 0 48.0 ft2 0 0 0.5 0
12 N=>SE Exterior Concrete Block-Ext InsGREAT/DINT 4.1 26 0 8 0 208.0 ft2 0 0 0.5 0
7/6/2017 8:51 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 3 of 5
r r
rOItM R405-2014
WALLS
Adjacent Cavity Width Height Sheathing Framing Solar Below
()cot To Mlnll Type Space
R_Va11e Ft n Ft n Area lie qor13 W=>NE Exterior Concrete Block-Ext InsGREAT/DINT 4.1 21 0 8 0 168.0 ft2 0 0 0.5 0
14 N=>SE Exterior Concrete Block-Ext Insul FOYER 4.1 1 0 8 0 8.0 ft2 0 0 0.5 0
15 E=>SW Exterior Concrete Block-Ext Insul FOYER 4.1 6 0 8 0 48.0 ft2 0 0 0.5 0
16 N=>SE Exterior Frame-Wood GREAT/DINT 11 23 5 8 187.3 ft2 0.23 0.5 0
DOORS
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 E=>SW Insulated FOYER None .28 3 6 8 20 ft2
WINDOWS
Orientation shown is the entered orientation => changed to Worst Case.
/ Wall Overhang
V/ # Ornt ID Frame Panes NFRC U-Factor SHGC Area Depth Separation Int Shade Screening
1 W=>NE 3 Metal Low-E Double Yes 0.54 0.25 32.4 ft2 1 ft 0 in 1 ft 4 in Drapes/blinds Exterior 5
2 S=>NW 5 Metal Low-E Double Yes 0.54 0.25 6.9 ft2 1 ft 0 in 1 ft 4 in None None
3 E=>SW 8 Metal Low-E Double Yes 0.54 0.25 23.2 ft2 1 ft 0 in 1 ft 4 in None None
4 N=>SE 12 Metal Low-E Double Yes 0.54 0.25 36.8 ft2 1 ft 0 in 1 ft 4 in None None
5 W=>NE 13 Metal Low-E Double Yes 0.55 0.25 40.0 ft2 10 ft 0 in 1 ft 4 in None None
GARAGE
# Floor Area Ceiling Area Exposed Wall Perimeter Avg.Wall Height Exposed Wall Insulation
1 315ft2 315ft2 24ft 8ft 11
INFILTRATION
# Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 1349.6 74.09 139.34 .2669 7
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Heat Pump Split HSPF:8.5 34.8 kBtu/hr 1 sys#1
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit Split SEER: 15 34.8 kBtu/hr cfm 0.85 1 sys#1
7/6/2017 8:51 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 4 of 5
' I
e
FORM R405-2014
HOT WATER SYSTEM
# System Type SubType Location EF Cap Use SetPnt Conservation
1 Electric None Garage 0.97 40 gal 60.9 gal 120 deg None
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
None None ftz
DUCTS
/ --Supply— —Return-- Air CFM 25 CFM25 HVAC#
V # Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 320 ft2 Attic 80 ftz Default Leakage Attic (Default) (Default) 1 1
TEMPERATURES
Programable Thermostat:Y Ceiling Fans:
CoolingJan Feb Mar Apr May X Jun X Jul rl Au �Xl Se Oct Nov DecHeatin Jan Feb f X�Mar Apr May Jun Jul AuSep Oct X�Nov X DecVentin Jan Feb X Mar [X]A r [ Ma [ Jun [ Jul Aug Se [X]Oct [X Nov [ Dec
Thermostat Schedule: HERS 2006 Reference Hours
Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78' 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
7/6/2017 8:51 AM EnergyGaugeO USA-FlaRes2014 Section R405.4.1 Compliant Software Page 5 of 5
� I
4
P
FORM R405-2014
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: THE GRAND CARLTON Builder Name: WYNNE DEVELOPMENT
Street: WYNNE DEVELOPMENT Permit Office: ST.LUCIE COUNTY
City,State,Zip: FT. PIERCE, FL, Permit Number:
Owner: Jurisdiction:
Design Location: FL,ST_LUCIE_CO_INTL
COMPONENT CRITERIA CHECK
Air barrier and thermal barrier A continuous air barrier shall be installed in the building envelope.
Exterior thermal envelope contains a continuous barrier.
Breaks or joints in the air barrier shall be sealed.
Air-permeable insulation shall not be used as a sealing material.
Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the
insulation and any gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
Corners and headers shall be insulated and the junction of the foundation
Walls and sill plate shall be sealed.
The junction of the top plate and the top or exterior walls shall be sealed.
Exterior thermal envelope insulation for framed walls shall be installed in
substantial contact and continuous alignment with the air barrier.
Knee walls shall be sealed.
Windows, skylights and doors The space between window/door jambs and framing and skylights and
framing shall be sealed.
Rim joists Rim joists are insulated and include an air barrier.
Floors (including above-garage Insulation shall be installed to maintain permanent contact with underside
and cantilevered floors) of subfloor decking.
The air barrier shall be installed at any exposed edge of insulation.
Crawl space walls Where provided in lieu of floor insulation, insulation shall be permanently
attached to the crawlspace walls.
Exposed earth in unvented crawl spaces shall be covered with a Class I
vapor retarder with overlapping joints taped.
Shafts, penetrations Duct shafts, utility penetrations, and flue shaft openings to exterior or
unconditioned space shall be sealed.
Narrow cavities Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled
by insulation that on installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spaces.
Recessed lighting Recessed light fixtures installed in the building thermal envelope shall be
air tight, IC rated,and sealed to the drywall.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in
exterior walls, or insulation that on installation readily conforms to available
space shall extend behind piping and wiring.
Shower/tub on exterior wall Exterior walls adjacent to showers and tubs shall be insulated and the air
barrier installed separating them from the showers and tubs.
Electrical/phone box on The air barrier shall be installed behind electrical or communication boxes or
air sealed boxes shall be installed.
HVAC register boots HVAC register boots that penetrate building thermal envelope shall be
9 9 P 9 P
sealed to the sub-floor or drywall.
Fireplace An air barrier shall be installed on fireplace walls. Fireplaces shall have
gasketed doors
7/6/2017 8:51 AM EnergyGauge®USA-FlaRes2014 Section R405.4.1 Compliant Software Page 1 of 1
S
i
i,r®ject 'Summary Date:
wrightsoft° Entire House
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT..PIERCE,FL 34946 Phone:.7 72116 6-6 79 9 Fax 772-466-6796. Email:QUICKCALCS@AOL.COM
Rmject Information%
For: THE GRAND CARLTON
WYNNE�D� (°EVELLO\PMENT, FT. PIERCE, FL
Notes: O.i O "� �o��Cl 9c�\
Design
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db - 75 OF
Design TD 28 OF Design TD 15 OF
Daily range L
Relative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 17848 Btuh Structure 17520 Btuh
Ducts 5654 Btuh Ducts 8536 Btuh
Central vent(0 Cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) I (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 23503 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 24753 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 3203 Btuh
Ducts 2318 Btuh
Central vent(0 cfm) 0 Btuh
Heatingg Cool ingg (none)
Area(ft?) 1446 1446 Equipment latent load 5521 Btuh
Volume(ft3) 12511 12511
Air changes/hour 0.45 0.23 Equipment total load 30274 Btuh
Equiv.AVF(cfm) 94 48 Req. total capacity at 0.70 SHR 2.9 ton
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make Carrier
Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING
Model 25HBC536A"030 Cond 25HBC536A*030
AHRI ref 7914585 Coil FX4DN(B,F)037
AHRI ref 7914585
Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER
Heating input Sensible cooling 24360 Btuh
Heating output 34600 Btuh @ 47°F Latent cooling 10440 Btuh
Temperature rise 27. OF Total cooling 34800 Btuh
Actual airflow 1160 cfm Actual air flow 1160 cfm
Air flow factor 0.049 cfm/Btuh Air flow factor 0.045 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.83
Capacity balance point=32 OF
Backup:
Input=7 kW, Output=23009 Btuh, 100 AFUE
Ma CCalculations approved byACCA to meet all requirements of Manual J 8th Ed.
.� wrightsoft` 2017-Apr-11 09:29:38
.� Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
'� ...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
i -
� i
wrightsoft' Right-M Worksheet °b
Entire House Date:
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@(AOL.COM
1 Room name Entire House BEDROOM
2 ,Exposed wall. 156.2 ft 49.0 ft
3 Room height 8.7 ft d 8.0 ft heat/cool!
4 Room dimensions 1.0 x 297.0 ft
5 Room area 1445.5 ft2 297.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (13tuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) .
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13Allacs•; ;0.143 n' 4:00 2,65 '509 465 ;1862 1184 '72 72 2M 183
,4A5 tom ' 0.770 n ` 21.56 19:31. .'.38 0 815 . 730 :• 0 0 :0 0
13AAocs 0.143 a 4.00 2.55 128 83 333 212 0 0 0 0
' -G 1Aclom 1.270 a 35.56 87.29 24 2 848 2082 0 0 0 0
11 ' D •11D0 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0
, A Aocs 0:143. se 4..00 255 34 34 136 86 0 _ 0 0 b
V�1 13A-4ocs 0.143 s 4.00 2.55 360 353 1414 899 216 216 865 550
I--G 1Ac1om 1.270 s 35.56 34.77 7 7 247 241 0 0 0 0
13A-4ocs" .0.143 .w 4.00 2.55 3.10 237 949 603 104 .72. 288 183
1Ao1om.' 1.270 :w. 35.56. 55.21: 32 :. 2 1140 1770 32 2 1140 1770
4AS2om`. 0:770 •:-w 21.56. 19.31 41 41 880 788: 0
P 12C-Osw 0.091 - 2.56 1.28 192 192 489 246 0 0 0 0
C 16A 30md 0 032 0 90: ." :.2.3-2 1446 1446 1295 3354 -297 297. 266 `;;689
F 22A tpl 0.9.89 - 27.69 0.00 1446 156 4325 0 297 49 1357 0
6 c)AED excursion 918 627
Envelope loss/gain 14961 13349 4204 4003
12 a): Infiltration 2887 791 848 232
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 6 1380 3 690
Appliances/other 2000 0
Subtotal pines 6 to 13) 17848 17520 5053 4925
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 17848 .17520 5053 4925
15 Duct loads 32% 49% 5654 8536 32% 49% 1601 2400
Total room load 23503 26056 6653 7325
Air required(cfm) 1160 1160 328 326
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
.wrightsoft- 2017-Apr-11 09:29:38
. P. Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
...uick CaIcs1Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
i.
;
+F wrigntsoft° Right-J®Worksheet Job:
Entire House Date:
By.
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@a,40L.COM
1 Room name WIC KITCHEN
2 Eiposed wall O ft O ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 6.0 x 9.0 ft 1.0 x 172.0 ft
5 Room area 54.0 ftz 172.0 ft'
Ty Construction LI-value Or HTM Area (ft-) Load Area (ft2) Load
number (Btuh/ftz'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 T m4ocs - 0:143 n 4.00..: 2.55 0 0 0 0 0 0 0 0
4A5-20m 0.770 n 21.56 19.31 0 0 0 .0 0 0 0 '0
13A-4ocs 0.143 a 4.00 2.55 0 . 0 0 0 0 0 0 0
-G IA-clom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 L-D 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W : 13A-0ocs 0.143 se 4.00 2.55 0 0 0_ 0 0 0 0 0
Vu 13A4ocs 0.143 s 4.00 2.55 0 0 0 0 0 0 0 0
Y-G 1Aclom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
13A-4ocs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
1A-clom 1.270 w 35.56 55.21 0 0 0 0 0 0 0 0
4A5-2om .0.770 w 21.56 19.31 0 . 0 0 0 0 .0 0 0
P 12C-0sw 0.091 - 2.55 1.28 0 0 0 0 64 64 163 82
C, 16A30md 0.032 - 0:90 2.32 54 54 48 - 125 172 172 .154 .399
F 224 tpl 0.989 27.69 0.00 54 0 0 0 172 0 0 0
6 c)AED excursion -9 -170
Envelope loss/gain 48 117 317 311
12 a) Infiltration 0 0 0 0
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 2000
Subtotal(lines 6 to 13) 48 117 317 2311
Less extemal load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 48 117 317 2311
15 Duct loads 32% 49% 15 57 32% 49% 100 1126
Total room load 64 174 418 3437
Air required(cfm) 3 8 1 1 211 153
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
- ,Wcightsott Right-Suite®Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page 2
...ulck CaIcslDocumOnts\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N
i
- -wrigntsoft Right-JO Worksheet Job:
Entire House Date:
` QUICK CALLS, INC. By.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-46"M Fax 772466-6796 Email:QUICKCALCS AOL.COM
1 Room name BATH BEDROOM-2
2 FVosed wall 5.0 ft 34.2 ft
3 Room height 8.0 ft heat/cool 8.0 ft heat/cool
4 Room dimensions 9.0 x 5.0 ft 1.0 x 203.5 ft
5 Room area 45.0 ft2 203.5 W
Ty Construction U-value Or HTM Area :
number (Btuh/ft'°F) (Btuh/ft2 or ft Load Area
perimeter (ft) (Btuh) or perimeter. (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 VU 13A�ocs. 0143 n:. 400 255 40 -: 40 160. 102 .128 - 128 =513 326
�C •;4A5 tom ':, . 0.770 n =, 21 56. .19.31 0 0 0 0:_ 0' 0. 0 ;:;`0
13A4ocs 0.143 a 4.00 2.55 0 0 0 0 80 56 225 143
1Aclom 1.270 a 35.56 87.29 0 0 0 0 24 2 848 2082
11 11DO 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
UU `13A4oes 0.143 se 4s00 2.55 0 0 0 0 34 .34 136 1 86
V�/ 13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 32 32 128 81
-G IA-clom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
13A4ocs' .0143 w- 4.00 2.55 0 0 0 0 0 0 0 0
1Ac1om 1270 w . 3556 55.21 -0 0 0 0 0 0 U p
;4A572om ;; O T/O .w _ 21.56 19:31` . 0 0 0 0 0." 0 0 0;
P 12C-0sw , 0.091" - 2.55 1.28" 0 0 0 0 0 0 0 0
C ;: 16A 30md '- A032 `,0.90 2.32 45 45 40 . 104, 204: 204:.. 18'2 -472
F 22A-tPl 0.989 27.69 0.00 45 5 138 0 204 34 . 946 0
_ -
p
6 c)AED excursion -16 -85
Envelope loss/gain 339 190 2678 3106
12 a) Infiltration 87 24 593 162
b) Room ventilation- 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 1 MO
Appliances/other 0 0
Subtotal nines 6 to 13) 425 214 3571 1.3498 -
Less exfemal load 0 0 0 i -0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 425 214 3571 3498
15 Duct loads 3201. 49% 135 104 32% 49% 1131 1704
Total room load F560 318 4702 5203
Air required(cfm) 28 14 1 2321 232
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
.� � wrig!i"aft' 2017-Apr-11 09:29:38
A"�� Right-Suite@ Universal 2017 17.0.14 RSU08101 Page 3
...uick Calcs\Documents%THE GRAND CARLTON-1446.rup Cale=MJ8 Front.Door faces: N
i
+b-wrightsoft' Right-J®Worksheet Job:
Entire Mouse Date:
QUICK CALCS, INC. By:
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@,AOL.COM
1 Room name LAUNDRY GREAT/DINING
2 Exposed wall 6.0 ft 47.0 ft
3 Room height 8.0 ft heat/cool 9.8 ft heat/cool
4 Room dimensions 7.0 x 6.0 ft 1.0 x 526.0 ft
5 Room area 42.0 ft2 526.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft2-OF) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
5 13A flocs: 0.143- :n. -4 00 2.55 0 0 0 0... 255 - 217 R. 552
-G 4A5 2orri.' 0.770 n 29:56 19.31 0 0 i- - 0 0 38 0 815 730
.13A4ocs 0.143 a 4.00 255 0 0 0 0 0 0 0 0
1A-c1om 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 11D0 0.390 a 10.92 11.31 0 0 0 0 0 0 0 0
W - .13A4ocs 0.143 se 4:00 2.55 0 0 0 0 0 0 0 0
V�/ 13A4ocs 0.143 s 4.00 2.55 48 48 192 122 0 0 0 0
Y-G 1Aclom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
13A-4ccs• 0.143 w 4.00 255 0 0 0 0 206 165. 661 420
-G 1Aclom 1,270 w 35:56. 55.21 0 0 0 0 0 0 0 0
G 4A5.2om= 0.770 w 21.56 19.31 0 0 0. 0 41 41 880 788
P 12C-0sw 0.091 - 2.55 1.28 56 56 143 72 0 0 0 0
C 16A 30md., '0032 :0.90 232' 42 42 _ 38, 97 -526 526, 471 1220
F 22A tpI 0.989 - 27.69 0.00 42 6 166 0 526 47 1302 0
6 c)AED excursion -22 668
Envelope loss/gain 539 270 4997 4379
12 a). Infiltration 104 28 997 273
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 2 460
Appliances/other 0 0
Subtotal(lines 6 to 13) 643 298 5994 5112
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 643 298 5994 5112
15 Duct loads 32% 49% 204 145 32% 49% 1899 2490
Total room load 846 443 7892 7602
Air required(cfm) 42 20 390 338
.Calculations approved bVACCA to meet all requirements of Manual J 8th Ed.
wrightsoft' 2017-Apr-11 09:29:38
RCCP. Right-Suite®Universal 2017 17.0.14 RSU08101 Page 4
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=WS Front Door faces: N
-�-wrigntsoft, Right-J®Worksheet Job:
Entire House Date:
QUICK CALCS, INC. By.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name FOYER M.BATH
2 .Exposed wall 7.0 ft 8.0 ft
3 Room height 8.0 ft heaticool 8.0 ft heat/cool
4 Room dimensions 1.0 x 50.0 ft 7.0 x 8.0 ft
5 Room area 50.0 ft2 56.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2)
number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A4ocs. 0.143 n' 4.00 255 8 8 32 20 0 0 0 0
�! 4A5-tom- 0.770 ri 21:56 19.31 0 0 0 0 0 0 0. 0
G.
13A-4ocs 0.143 a 4.00 2.55 48 27 108 69 0 0 0 0
1A-clom 1.270 a 35.56 87.29 0 0 0 0 0 0 0 0
11 11D0 0.390 a 10.92 11.31 21 21 229 238 0 0 0 0
W - .13A4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0
13A-4ocs 0.143 s 4.00 2.55 0 0 0 0 64 57 228 145
t-G 1A-c1om 1.270 s 35.56 34.77 0 0 0 0 7 7 247 241
13A-400s 0.143 _ w 4:00 2.55 0 0 0 0 0 0 .0 0
Ttg 1Acicm 1.270 w 3556 55.21 0 0 0 0 0 0 0 0
4A5.2om . 0.770. w 21.56: 1931 0 0 0 0 0 0. 0 0
P 12C-Osw 0.091 2.55 1.28 72 72 183 92 0 0 0 0
C 16A30md 0:032- 0:90 -2.32 50 50 45 116 56 56 50 130
F 22A tpl 0.9.89 - 27.69 0.00 50 7 194 0 56 8. 222 0
6 c)AED excursion -39 -38
Envelope loss/gain 792 496 747 478
12 a) Infiltration 121 33 138 38
b) Roam ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 913 529 885 516
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 0 0
14 Subtotal 913 529 885 516
1151 Duct loads 1 32% 49% 289 258 32% 49% 280 251
Total room load 1202 787 1166 768
Air required(cfm) 59 35 _T758 34
Calculations approved byACCA to meet all requirements of Manual J 8th Ed.
A - wrightsoft' Right-Suite@ Universal 2017 17.0.14 RSU08101 2017-Apr-11 0 Page
ae 5
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N 9
Duct S stem Summary Job:
+�- WAghtsofto Date:
Entire House By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:.772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
Project Information
For: THE GRAND CARLTON
WYNNE DEVELOPMENT, FT. PIERCE, FL
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0 in H2O 0 in H2O
Available.static pressure 0.50 in H2O 0.50 in H2O
Supply/return available pressure 0.250/0.250 in H2O 0.250%0.250 in H2O
Lowest friction rate 0.285 in/100ft 0.285 in/100ft
Actual air flow 1160 cfm 1160 cfm
Total effective length.(TEL) 176 ft
Supply Branch Detail • '
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln(ft) Ln (ft) Trunk
BATH h 560 28 14 0.364 4.0 Ox0 VIFx 22.4. 115.0" st1
BEDROOM 2 h 4702 232 232 0.360 7.0 OxO VIFx 23.9. 115.0 st1
BEDROOM-A h 3327 164 163 0.300 6.0 Ox 0 VIFx 31.8 135.0 st2
BEDROOM-B h 3327 164 163 0.285 6.0 Ox 0 VIFx 40.6 135.0 st2
FOYER h 1202 59 35 0.505 4.0 Ox 0 VIFx 4.0 95.0
GREAT/DINING h 3946 195 169 0.300 7.0 Ox0 VIFx 31.8. 135.0 st2
GREAT/DINING-A h 3946 195 169 0.300 7.0. Ox0 VIFx 31.8 135.0 st2
'KITCHEN c 3437 21 153 0.379 6.0 Ox0 VIFx 17.0 115.0 st1
LAUNDRY h 846 42 20 0.361 4.0 OxO VIFx 23.3 115.0 st1
M.BATH-A h 768 -58 34 0 0 Ox 0 VIFx 0 0
WIC I c 174 3 8 1 0.3991 4.01 Ox 0 1 VIFx 1 27.0 . 1 135.0 1 st2
Supply Trunk Detail Table
Trunk Htg. Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st2 Peak AVF 721 672 .0.285 918 12.0 0 x 0 VinlFlx st1
SO Peak AVF 1043 - 1091 0:285: 1020 14.0 0 x 0 VinlFbx
.` wa htsoft° 2017-Apr-1109:29:38
9 Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
ACZK:...uick Calcs\Documents\THE GRAND CARLTONA446.rup Calc=MJ8 Front Door faces: N
i
� j
ii
!.i
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam. H x W Stud/joist Duct
Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) . (in) Opening(in) Matl Trunk
rb1 OxO . 1160 1160 0 0 0 0 Ox 0 VIFx
WPI9 htSOft` 2017-Apr-1109:29:38
ZCARight-Suite®Universal 2017 17.0.14 RSU08101 Page 2
...uick Calcs\Documents\THE GRAND CARLTON-1446.rup Calc=MJ8 Front Door faces: N