6 ISLOPE
12
6 SLOPE
5/8" thick light textured
stucco on typical concrete
block construction
-------------------------------------------------------
LEFT ELEVATION
SCALE: 1/4" = 1'-0"
12
6 SLOPE
Southeastern Metals 24 ga. 5v Crimp metal roofing installed
over Owens coorning Titanium PSU 30 self adhered
underlayment over 19/32" COX plywood attached to
trusses per sheeting attachment diagram on roof plan
12
SLOPE 16
Southeastern Metals 24 ga. 5v Crimp metal roofing installed
over Owens coorning Titanium PSU 30 self adhered
underlayment over 19/32" CDX plywood attached to
trusses per sheeting attachment diagram on roof plan
stucco retui
ach window to block wall with
dia. x 3.25" tap -cons with min.
2" penetration at 12" o.c. max
6' o.c. max from each corner thru
4" PT Buck
wall return
ble sill
jail
Section 5 Window Head it SIII
NTS
#5 bar vert. Typical Masonrg Wall
at filled cell r „
❑❑ L11=1$L17TI
6"
Control Joint Extend joint reinforcing
at 30'-O" max. into concrete column
PLAN VIEW PLAN VIEW
0 0-
Tgpical Masonrg Wall _
m
32„
32"
El
Provide Prefabricated
Provide Prefabricate
L" Jant Reinforcing
T" Jant Reinforcing
at ALL Corners
at ALL T-intersections
PLAN VIEW
AT ALI , m_ __
PLAN VIEW
.T ALL <aR«
TYPICAL CONCRETE BLOCK WALL REINFORCING
TO BE OUR-O-WAL DAS200 LADUR JOINT
I2 REINFORCEMENT IN STANDARD WEIGHT (9GA) WITH A
HOT DIPPED GALVANIZED FINISH. REINFORCING SHALL
12 BE PLACEDIN ALL CONCRETE BLOCK WALLS AT
SLOPE
SLOPE 6 14" O.C. VERTICAL OR EVERY OTHER COURSE OF BLOCK
6
TYFICAL 1`1ASONRY WALL
REINFORCING DETAILS
NTS
o
5/8" thick light textured
stucco on typical concrete
------------------ — — — — block construction
EKI
6" wide stucco banding /
RIG, T ELEV,47I0N
Bond Beam
S
(1) 45 bar
in filled cell
TO Hook
Bond Beam l '
4h::'..............
1c I s
I I,
I .
I "
vert.
T
D Hook
(1) 45 bar vert.
in filled cell
Changes In Bond seam Helght
Scale: NTS
Strap double top plate to
each stud using Simpson
SP straps. Adjust the
strap size to match stud width
2"x studs - see well
sections for applicable widths
and stud spacing zZ..
Stud along block wall to
be PT
2"x blocking as req. by
Florida Building Code -
Residential.
29
Beam - see typical
section at block wall.
SCALE: 1/4" = 1'-0"
Contractor to fill last cell 7
solid with concrete and (U
u5 bar vert, for frame wall
attachment.
Tapcon Screws #10 x 3" is 2" x C PT wood secured with overhead door track secured to wood
16" o.c. or 1/2" dim. x5/12" Lg. I/2"dia. x 6" expansion anchors jamb per manufacturer's product approval
"Red Heads" w/ 2"dim.x 1/8" washer with 2" sq. washer at 18" O.C.
ALL GARAGE DOORS AS SPECIFIED IN PRODUCT
APPROVAL ON THESE PLANS. DOORS TO MEET
See typical
block way WIND PRESSURE STATED IN PERMIT INFO BOX ON
Section THESE PLANS
con crate, footer
Frame to Block Wall 4nchor Detail
Scale: NTS
Gdraae Door Jamb Detail
NTS
E
(
w N`
� NU,
O �
N Z
N.�
CIZ
.. w
FL
� t
E00
M M
�o 00
� rn
w ^FM
Uv'(az,
U�U
U��
0 L4
Y�cG
N N
.ZW��u
LLI W � 0 O
O
o
Q
<C
00� u
r- r-u
4
I z (�v N s*
O �
�
V O
�Wu
"`M m
~
LUv;�LL
ul ��
X-1
0( N
(V Q)
3
Q =3 .�
N
DATE DRAWN :
2-23-21
DRAWN BY:
C.c.u.
Dowel (1) 45 bar
CHECKED BY:
1D.R.B_
w/ 25" min lap
MODEL:
OLIVIA
and 6" embed
GARAGE
Fir.
Floor
[7�
I,-,J)
F—I
SHEET
Cont.
Concrete Footing
OF 8.
JOB NUMBER:
M I SSG d T I G D OUJ r R G b a I r 20-2302
QO.DD,OOO
n t S o�p0oo .. o00
0 °
Digitally signed by o ®�e
Daniel R. Braden po° M770 0�
t_. Date:2021.02.25
14:43:56-05'00'�3CDo °p�np04
66'-O"
1 30'-2" 19'-2" 16'-8" 1
H.B.
---
++
`PR
` +
1
©
O I----,
I
I
F-ILCaa1
Fill
cell with concrete and
(0 fU tt5 bar vert. ftypicaU. ul
I F-I
cess 3.5"
N Max. spacing shall not exceed TI
II
of $bower
32" unless otherwise noted LLI
foundation notes for
$loppe 51ah1
I
see plan
spacing at opening& I
p,5" foil
I drainage)
ICI
I
ICI
I
1
I
I
I
I
I
I
I
I
� I
SB-2 1
0 1 I
I
C I
I I
I
I SS-1
j I
I
I
I
i
�
i N
I
lol
I
rJ
1
i I
I
I
� AO
I ---
Ipl
I
I
I
I
ICI
I
I
I
I
I
C
I
I�1
4.lo
4" concrete slab with fibermesh OR
L"xL" #10/10 WWM on 6 mil Visqueen over
clean compacted termite treated fill
I _;I
I _;I
I _;I
I 'I
IDI
I I �
I II
Ipl i i
I I I D` JI
I I
I I SS -I
I b0
° 1100
I I
I I
Ipl
I I
I I
A/C I D Fill call with concrete and
#I I I U #5 bar Vert. ftypicaU.
I I Max spacing shall not exceed
I I 32" unless otherwise noted
see foundation plan notes for
&pacing et openings
I i I Strap post to foundation
using Simpson ABU 44
Post base with (U 5/8"
I i I threaded rod set in predrilled
clean epoxy filled hole with min.
8" embedment and fill all nail holes
I I A with IGd x 3 5" nails.
I I v I
T C-III
3 N
F-3L�- - L-
---------------------
------------ -'-'-'-'- -
I r- ------------------+
T-8
F-IL I
I I T
I I N
I I I �
I
� o O 4• $ I I
I a I
`sl
I
I
I SB-2
;-
LL�
u
a
I
LLl 11
i_
I
p
b
I
I
1'-
I
I
j
I
F.
________
_
a
_ ________
_
p1LL
I f�O
'-----------
�f�0
.t------^
-
f7 OD
----�
I
I
F-ILM
I
�
I
m
I
I�
N
10
� l-
I
I '-
110
vl
I
2'
4" concrete slab with Flbermeah OR -O"
L"x1" 410/10 WWM on L mil Visqueen over C-3
LLI
I
I
clean compacted termite treated fill
B-5
I
Strap post to foundation
using Slmpson ABU 44
Poet base with (U 5/8"
threaded rod set in h predrilled
clean epoxy filled hole with min.
8" embedment and Pill all Heil holes
with ILd x 3.5" pads.
I
r
I
I
FiQHU,
I
I
I
I
�
Ell
II "�I
6'-8"�
SB-51
I
4b `ov�e I
o ILM
Ih------- - - - - - - -----tea --
H.B. I
I .H.
I°I
I I
I I
I
I®I
I I
METER
JT
N
o - -
_ _ F_-IL_ _ o ry
=o ---©o-----------o ---ooj
B - - - T-8 �- C
r
Y SB-4
I � T-
p I -
C IRS
concrete sia with fibermesh OR LL L"xL' 410/10 WWM n L mil Visqueen over I
clean compacted termite treated fill
0
---------------
U.
ODI
0
o `o
per;
O
O I NFL
HI
m
I
SLOPE 2"
I
W
I
SB-4
I
��
a
I
I
I
I
u
K
O Iv
I
I
-
v 1
I
m
of
of
I
I
I
m I
DI
o I
jP_i
F-24 I
I
I
OI
1
00
v
I
SLOPE 2" 1
0�
Ir>
i�iLL
Ni
Rm0
�
I
22'-6" I
j -
F-24
I P
I m
-
-
CD
�_T_T_
- r_T_ -- ---0 ---0------- E7- OD
O T- i 1
I (V
23-10"
-C
42'-2"
' r iU tt5 bar vert. iypicab.
I ILL --
Max' spacing shall not exceed - I
32" unless otherwise noted - I
I I we foundation plan notes f p l
I I spacing at openings I I
o I I
a I ° °
w 1 I SB-4 TUBo I D
I I
o I I F ecess
n I 'a T for Shower ill I
ILL mI
� I I
F-IL J I
I E3 tJ O u.w I so OO p 3
o r
�I O T " fJ---r-r-T_r_
L_-_1-1-I-I-i-I--_ J
Footing Schedule
Mark
size and Description
T-8
Thicken slab edge to 8" x 8" with (1) #5 bar cant.
F-12
SEE STEP DETAIL ON THIS SHEET
F-IL
I("w x IL"d concrete monolithic footing with (2) #5 rebar continuous
and #5 transverse bars at 32" o.c.
F-ILM
gbottom)
SEEXSTEPcDETAILmON THIS SHgETh (2) #5 rebar continuous
F-24
Thicken slab to 36"w x 34"1 x IL"d concrete pad footing with #5 rebar at
8" o.c. each bottom steel.
F-3(
St.% S 4"I x IL"d concrete pad footing with #5 rebar at 8" o.c. each
F-48
48"w x 48"1 x IL"d concrete pad footing with #5 rebar at 8" o.c. each
bottom
Slab Bar
Schedule
Mark
size
x
r
z
Tgpe
Spacing
Notes
65-1
#4
48"
—
—
Standard
40" o.c.
Tie to vert. wall steel
Upturn Bar
SB-2
#4
—
48"
24"
"Z" Bar
40" o.c.
SB-3
#4
—
48"
48"
"Z" Bar
40" o.c.
SB-4
#4
12"
—
—
Standard
40" o.c.
Tie to vert. wall steel
Upturn Bar
SB-5
#4
1 48"
FLAT
40" O.C.
x
x
STANDARD SLAB BAR
-
STANDARD HOOK BAR
Y Z
ie House Slab
x
Ve" Slab
each loca
Ztion
"" BAR EQUAL OR UNEQUAL LEG
STANDARD UPTURN HOOK BAR
x
I A
DA BAR
B-SFlatN
(Where applicable bar allso a00P
ALL SLAB BARS SHALL BE INSTALLED IN THE MIDDLE OF THE SLAB
TIE ALL STANDARD HOOKS TO VERT.
STEEL IN WALLS UPTURN.
BARS CAN ALSO BE LAID SIDEWAYS AND TIED TO HORIZONTAL
FOOTING STEEL IN THICKENED EDGES AT STEM WALLS WHERE
APPICABLE.
Termite Frotectlon for New
Construction as per F.B.C. F318.1
CONTRACTOR TO REFERENCE F.B.C—R
FOR FURTHER REQUIREMENTS
Soil treatment used for subterranean termite prevention
inside the foundation perimeter shall be done after all
excavation, backfilling and compaction is complete.
If soil area is disturbed after initial chemical soil treatment,
area shall be re -treated with a chemical soil treatment
including spaces boxed or framed.
Treatment must be in accordance with the rules and laws
established by the Florida Department of Agriculture and
consumer services.
Protective sleeves around piping penetrating concrete
Slab on grade floors shall not be of cellulose -containing
materials and shall have a min. wall thickness Of 0.010"
and shall be sealed within the slab using a non -corrosive
clamping device to eliminate the annular space between
pipe and sleeve. NO TERMICIDES shall be applied
Inside the sleeve per FBC Plumbing 305.1
Thicken edge to 8"x8"
with concrete and
one 45 bar continuous
4" concrete slab with fibermesh OR
4"x6" #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
GRAD
T-8 FOOTING DETAIL
SCALE 1/2" = 1'-0"
4" concrete slab with fibermesh OR SS-5 - see slab bar
L'xb" 410/10 WWM on 10 mil Visqueen over schedule on foundation
clean combatted termite treated fill
6" (2) #5 bars
coot.
F-I1 FOOTING DETAIL
SCALE 1/2" = I'-O"
4" concrete slab with fibermesh OR SB-3 - see slab bar
6"xV 410/10 WWM on 10 and Visqueen over schedule on foundation
clean compacted termite treated fill
lie 48" L" 48'
6" ma
0111111
INNEEMM
2"
I6"
F-16M STEPDOWN FOOTING DETAIL
SCALE 1/2" = 1'7O"
45 bar vert. w/
30" overlap
c at each filled ell
Optional I" recess for
waterproofing at slab
verify with owner prior
to construction
L" min. clear for termite
protection
o
SEE TYPICAL
SECTIONS
SB-I - see slab bar
schedule on foundation
4" concrete slab with fibermesh OR
L"xb" #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
F-IL footing - see schedule
C
F-16 FOOTING DETAIL
tt5 bar vert. w/
30" overlap
at each Filled cell
FOUNDATION FLAN Optional i recess for
waterproofing at slab
verify with owner prior
FOUNDATION NOTES: SCALE: 3/16" = 1'-0" to construction
1. Any changes to plans must be submitted to the architect L" min. clear for termite
for approval before proceeding with construction. protection Grade
2. Contractor shall be responsible for verification of all notation and dimensions ry
prior to start of construction.
3. ALL Concrete used for slabs shall be 2,500 PSI concrete min., andtrt7
—
ALL Concrete used for vertical filled cells, continuous. tie beams etc.. to
shall be 3,000 P.S.I. concrete and/or 4,000 F.B.I. grout mix min.
4. Soil conditions assumed to be 2500 psf and stable. This shall be confirmed
by soil borings which shall be provided in writing to this firm by owner/contractor
prior to start of any construction.
5. Verify all recess thickness at shower floors, all floor finishes as selected by
owner, door sills � thresholds etc.... prior to placing any slabs.
6. Contractor to provide filled cell with concrete and I #5 bar vert. at 40"
O.C. Max. Provide (1) filled cell on each side of openings up to 5'—I1" wide.
Provide (2) filled cells on each side of openings from ('—O" to 9'—II"
and Provide (3) filled cells on each side of openings from 10'-0" and up
Contractor to see plans for any other condition used. Foundation walls
shall have filled cells at 24" o.c. unless otherwise noted (see section)
7- Contractor to provide for Form Board Survey — Form Board Survey
to be provided to Truss Company prior to truss construction
8. ALL Reinforcing steel shall be grade 6O, meeting ASTM A—I6 and
A-35 specifications. ALL Anchors to be A-307 steel.
9. Provide a minimum of 3" concrete protection at footings and
1-1/2" concrete protection at beams for ALL reinforcing bars.
10. Contractor to provide the Architect with truss shop drawings including
ALL truss cut sheets showing ALL truss reactions prior to START
OF FOUNDATION WORK for strap and footing size verification.
11. Contractor to compact clean fill to 95% of the dry density prior to placing slab.
12. All Concrete stoops shall slope away from building for drainage
SCALE 1/2" = I'-O"
SEE TYPICAL
SECTIONS
Provide 8" wide curb - verify height with
step down and slope shown on foundation plan
513-1 - see slab bar
schedule on foundation
4" concrete slab with fibermesh OR
L"x(" #10/10 WWM on 10 mil Visqueen over
clean compacted termite treated fill
16 footing - see schedule
F. C
F-16 AT GARAGE CURB
SCALE 1/2" = I'-C"
N N
W LU o O
W 73 " O
z W tf) CD U O
O �
N N cr
�VO�r3 Cr
W U m
~LU b x -1
(pu_ )
tri � N
r—� N to
< D ,+
L
DATE DRAWN
2-22-21
DRAWN BY:
C.C.U.
CHECKED BY:
D.R.B.
MODEL:
OLIVIA
GARAGE
LEFT
Q
SHEET
OF 8.
w
JOB NUMBER:
20-2302
DpOO.D.o-boo
p
�ao�
�000pa�,or�"
Digitally signed by
o"
Daniel R. Braden °o•p*" M770
��
Date: 2021.02.25 00
14:43:01-05'00' ��'�. )
Attic Venting Calculations EBC R806.2
Total Attic Space = 4,816 sq. ft.
Venting Ratio 1/150 = 32.50 sq. ft. required
q. evenly spaced
ion
an
Strap Gi
MG T atr
embeded
(22) IOd
strap ti
using (2.
one eac
SF-,4M
SCHEDuL
Mark
Size and Description
B1
Two rows of
beam
block filled with concrete and 1 #5 bar
continuous in
each
row. Provide precast lintel filled with
concrete and
(1) 45 bar cont over openings and use #6
bar cont. in
lintels loacted at rear porch
B2
(2) 1 3/4" x
IL"
2.OE LVL laminated wood beam
attach beam
plies
together using (,4) IOd x 3" nails at
12" o.c. staggered
each side
B3
�(2) 2" x 12"
SYP 32 wood beam
Additional Precast Lintel
a5 bare
CLEAR
,,: i• CLEA `,.�.^x'•'}:
i - CLEAR \ CLEA
8/8-OVAL 8/8-IU/IL 8/8-IU/2L °r ya,
Additional i.'%%.<,' Additional
= a5 here :.a . ``;�., 25 bars
CLEA +'•: :;;`: v(C':"
t;.
One Row or "H" One Row of "H" %'�'�•
Block Above Block Above
r - Precast Lintel r-=;"i;-' r'' 4,!';'(� Precast Lrntel
Additional • -'t 1 Additional
\ CLEA — tt5 bars — \ CLEAR a5 bare cLeA —
8/I6-IUAL 8/I6-IU/2L 8/24-IU/IL 8/28-ILIAL
NOTES: NOTES:
I. m veraga of atee®=1.5"
2. min. cbearun reemred ea. end=a"
3. standard for r mf. steel=ASTM A415
TYPICAL LINTEL SECTION
( PRECAST CONCRETE )
LINTEL SCHEDULE
Window
Max
Max
Max
or Door
Gravitg
Upldt
Lateral
Mark
Unit
Lintel
Height
Bottom
s—
s—
Width
Specification
Stee
Seel
(PLF)
(PLF)
(PLF)
L22
2-2"
T-0
24"
8/24 IUAL
1
a5
1
a5
10000
Isis
1250
L31
2'-L"
4'-O'
24'
8/24 IUAL
1
a5
1
a5
10000
718.4
933
2 _8"
3'-1.
L45
4-5"
5-10"
24"
8/24 IUAL
1
a5
1
a5
1414
4014
L51
LLO
I 6'-8'
I T-V
24"
1 8/24 IUAL
I
1 a5
1 1
a5
14013
12434
804
LLOB
L'-8"
1'-L
12'
8/12 IUAL
1
a5
1
tt5
1021
534
LLOC
C-8'
1'-1'
L'
8/L IU/IL
1
a5
1
a5
538
804
LLOD
6'-8'
1'-0
24'
8/24 IUAL
1
a5
1
tt5
2434
8o4
L10
1'-0"
8'-4"
24"
8/24 IUAL
1
a5
1
a5
g20,41
1192
L4L
L70B
1'-0"
8'-4'
28'
8/28 IU/IL
1
a5
1
a5
1992
446
LI00
10'-0'
II'-4"
24"
8/24 IUAL
1
a5
1
a5
1138
415
L120
12'-0'
13'-4"
24"
8/24 IUAL
1
a5
1
a5
8L6
340
LILO
IL'-O"
11'-4'
24'
8/24 IU/IL
I
a5
I
a5501
33L
- ALL LINTELS SHALL BE MADE BY LOTTS LINTELS
- LINTELS SHALL BE PILLED SOLID WITH 3000 PSI CONCRETE
- REFER TO CATALOG FOR ALL INFORMATION REGARDING
LINTEL CONSTRUCTION. HANDLING INFORMATION, AND SAFE LOAD REQ.
REQUIREMENTS
- LINTELS OVER 14'-0" LONG ARE TO BE PRESTRESSED.
- CONTRACTOR TO VERIFY ALL LINTEL SIZES BASED ON FINAL MASONRY
OPENING SIZES AND ADJUST LINTELS ACCORDINGLY PRIOR TO ORDERING
ANY/ALL LINTELS
Simpson HGUS 26-2
hanger at girder truss = = 5/8" dia. x 6" exp. anchors
filling all nail holes with n bolts to be A325 Steel
Ibd nails
Han er Ca acit 10" 3"
STR.4FFING SCHEDULE
HETA 2
SIMPSON HETA 20 hurricane
anchor at each truss supportin(
Max. 1810 lbs. uplift. Strap sl
have (9) IOd x 1 1/2" nails.
BOTTOM CHORD TRUSS BRACING NOTES
Contractor to race all bottom chords in floor
and roof trusses in the following manner:
install first row of truss bracing 34" from exterior walls
and spaces 12" o.c. thereafter.
- install bracing on any bottom chord which is longer
than 12" in clear span.
All truss bracing to be 2" x 4" wood and shall be attached to
bottom chord of trusses.
nwermw•mam�
lases spaced per truss
iufactures plans
>ical splice
.tech bracing to truss chord
ng (2) IOd nails in all
aUons
x 4" wood bracing
d bracing shall lap one truss
ALL BRACING SHALL COMPLY WITH BCSI-B3 SUMMARY
IGe
Area
Edge
Field
Fastener
Pressure
Zone I
6"
6"
8d ring shank
45 psf
Zone 2
�"
6"
8d ring shank
�6 psf
Zone 3
�"
Sd ring shank
84 psf
** Zone 3a
6"
6"
1tS wood screw
112.b psf
g p 12 Simpson HUB 26
Max. Gravityy 5, 30 lb
hanger at each truss
Max. Uplift 2,IS5 Ibs
See truss engineering b • • filling all nail holes with
others for acival loads y ® • • Ibd nails
24"
N
Install (4) 5/8" exp. anchors N Install (2) 2" x 8" SYP #2 PT wood
as shown near girder COSG ledger with 5/8" COX plywood pplate between
LEDGER DETAIL attached to wall to wall using 5/8" dia. x 6"
expansion anchors per detail on this sheet.
Scale: 1/2" = 1'-0"
ROOF PLAN
TYPICAL ROOF NOTES: Scale 3/16" = 1'-0"
- Overhangs shall be 2'-0" unless otherwise noted on this sheet
- Roof pitch shall be 6:12 unless otherwise noted on this sheet
- Truss shop drawings to be provided by manufacturer
- Any changes to this plan shall be submitted to the
architect for approval in writing prior to starting construction.
- ALL TRUSS TO TRUSS CONNECTIONS BY
TRUSS MANUFACTURER
- Architect to review Truss Shop Drawings Prior
to construction for layout and uplift verification
- Contractor to provide for Form Board Survey and to provide
Form Board Survey to Truss Company prior to truss construction
- Contractor to provide the Architect with truss shop drawings including
ALL truss cut sheets showing ALL truss reactions prior to TART
OF FOUNDATION WORK for strap and footing size verification.
- TRUSS DEFLECTION SHALL NOT EXCEED 0.5" ON ANY TRUSS.
GARAGCD
E
LET
DATE DRAWN
2-22-21
DRAWN BY:
c.c.u.
CHECKED BY:
D.R.B.
�
MODEL:
OLIYIA
Digitally signed by Q�o'�®�'�L�`�0�
Daniel R. Braden Mrro
Date: 2021.02.25 goo
14:42:36-05'00'
Southeastern Metals 24 ga. 5v Crimp metal roofing installed
over Owens coorning Titanium PSU 30 self adhered
underlayment over 19/32" COX plywood attached to
trusses per sheeting attachment diagram on roof plan
Simpson HETA 20 or e
hurricane anchor at each
with (10) IOd x 1 1/2" r
( 24" o.c.) supporting
S10lbs. uplift
Galt' -Alum Metal drip on
I" x 4" Drip on -
1" x 8" Fascia on `o
2" x 6" Sub -Fascia
5/8" thick stucco on 3/8" h1-rib lath
attached to horizontal and vertical wood
framing with nails or staples to provide
no less than 1-3/4" penetration into
horizontal wood framing and 3/4" penetration
into vertical wood framing members
Provide 1" x 24" aluminum
screen vents - spaced evenly.
5/8" thick light textured
stucco on typical concrete
block construction
45 bar vert. w/
30" overlap
at each filled cell
12 PRE-ENGINEERED TRUSSES
6 at 24"o.c. TYPICAL
( shop drawings by manufacturer )
R-30 Batts
5/8" drywall with smooth finish
1/2" drygwall over I" x furring
BI strips ai 14 o.c. with R4.2 fyfoll
insulation on typical 8" Block walls
All drywall is per FBC 102.3.1 and
shall meet all pertainingASTM codes.
Mortar to be Tye "M" onlg.
Provide Dur-O-Rock at all wet
areas (ex. showers, tubs etc...)
Typical Wall Reinforcement
see detail on sheet D-2
base
board
Attach door to block wall with 1/4" dia.
tap -cons with min. 1 1/4" embedment to be
spaced per product approval. Contractor shall
adhere to min. edge distance of C from corner
and 14" o.c. max
Exterior face
of wall
Varies
c
iy
1"x8" P.T. Buck
2 sides d header
Detail at
Exterior SGD Doors
NTS
Verify all stucco banding and
trim per elevations
Stucco return
Attach door to block wall with
1/4" dia. x 3" tap -cons with min.
1 1/2" penetration at 12" o.c. max
and 6" o.c, max from each corner thru
I" x 8" PT Buck
Exterior
See door schedule and
floor plan for size and locations
install door per product approval by mfg
Drywall return
Fill cell with concrete and Interior
(1) #5 bar vert. (typical). See typical wall sections for interior
Max. spacing shall not exceed drywall finish notes
32" unless otherwise noted
see foundation plan notes for verify filled cell count per
spacing at openings floor plans at window jambs
4" concrete slab with ribermesh OR Exterior D co r Jamb D e t a i l
CxC 410/10 WWM on 6 mil Visqueen over
f
— clean compacted termite treated ill N T S
Grade
I IIIIIIII-IIII , III I
IIIIII�IIIIII����IIIIII,;�,,,_ IIII=j111
F-IL
See detail on sheet 4.
TYfi ICAL SECTION
Southeastern Metals 24 ga. 5v Crimp metal roofing installed
over Owens coorning Titanium PSU 30 self adhered
underlayment over 19/32" COX plywood attached to
trusses per sheeting attachment diagram on roof plan
Simpson HETA 20 or equal
hurricane anchor at each truss
with (10) 10d x 1 1/2' nails
( 24" o.c.) supporting Max.
8101ba. uplift
Galt' -Alum Metal drip on
I" x 4" Drip on
I" 8" Fascia on
2" x x 6" Sub-Fascia`o -
L(.0D
5/8" thick stucco on 3/8" hi -rib lath
attached to horizontal and vertical wood
framing with nails or staples to provide
no less than 1-3/4" penetration into
horizontal wood framing and 3/4" penetration
into vertical wood framing members
Provide 1" x 24" aluminum
screen vents - spaced evenly.
5/8" thick light textured
stucco on typical concrete
block construction
Scale 1/2" = 1'-0"
5/8" thick stucco over
17.1
on 3/8" high rib lath on
15/32" CDX Plywood
UT
nailed to trusses with IOd
ring shank nails at
12" o.c. field and C o.c.
edges. Install per ASTM
C926-I1a and ASTM C1043
O
O
i
in
Door and transom
see schedule and install
per product approval
Verify step height
on foundation plan
Simpson HETA 20 or equal
hurricane anchor at each truss
with (10) IOd x 1 1/2" nails
( 24" o.c.) supporting Max.
1810lbs. uplift
.60B
N
L60C
_��II����—IIII—IIII-IIII IIII ,, I -
F-16M
O
iv
Ex
Int
Window Jamb Detal
Drywall
Verify all stucco banding and
trim per elevations
Stucco return
Attach window to block wall with
1/4" dia, x 3" tap -cons with min.
1 1/2" penetration at 12" o.c. max
and 6" o.c. max from each corner thru
I" x 4" PT Buck
See window schedule and
floor plan for size and locations
install window per product approval by mfg
Drywall return
See typical wall sections for interiordrywall finish notes
verify filled cell count per
floor plans at window jambs
Lintel - see plans for
size and steel req.
Attach window to block wall with
1/4" dia. x 3" tap —cons with min.
11/2" penetration at 12" o.c. a-
s
nd G" c. max from each corner thru
1" x 4" PT Buck
NTS
Sill - verify final stucco return
material and size
with owner prior
to ordering
See window schedule and
floor plan for size and locations
Seal ALL concrete block jambs prior Stucco finish over sill
slope for drainage
to buck per FBC R703.8 using an(g
approved sealant Pour concrete sill
over tin cap
VERIFY ALL SILL MATERIAL Section Window Head Sill
WITH OWNER PRIOR TO ORDERING NTS
VERIFY ALL ROUGH OPENING
SIZES WITH THEIR RESFECTIVE
MANUFACTURER FR10R TO
INSTALLING MASONRY
Southeastern Metals 24 ga. 5v Crimp metal roofing installed
over Owens coorning Titanium PSU 30 self adhered
underlayment over 19/32" COX plywood attached to
trusses per sheeting attachment diagram on roof plan
PRE-ENGINEERED TRUSSES
at 24"o.c. TYPICAL
( shop drawings bg manufacturer )
R-30 Batts
5/8" drywall with smooth finish
See window schedule
for sizes
1/2" drygwall over I" x furring
strips at 14" o.c. with R4.2 fyfoll
insulation on typical 8" Block walls
All drywall is per FBC 102.3.1 and
shall meet all pertaining ASTM codes.
Mortar to be Type "I`1, onlg.
Provide Dur-O-Rock at all wet
areas (ex. showers, tubs etc...)
See door schedule
for sizes
4" concrete slab with ribermesh OR
6"xb" #10/10 WWM on 6 mil Visqueen over
—clean compacted termite treated fill
ENTRY FORC�H SECTION
Scale 1/2" = l'-O"
Simpson HETA 20 or equal
hurricane anchor at each truss
with (10) IOd x 1 1/2' nails
( 24" o.c.) supporting Max,-
18101bs. uplift
GalvI"Alum Metal drip on
I" x 4" Drip on
I" x 8" Fascia on _p
2" x 6" Sub -Fascia
5/8" thick stucco on 3/8" hi -rib lath J
attached to horizontal and vertical wood
framing with nails or staples to provide
no less than 1-3/4" penetration into
horizontal wood framing and 3/4" penetration
into vertical wood framing members
2" cont screen vent
12// PRE-ENGINEERED TRUSSES
6 at 24"o.c. TYPICAL
( shop drawings by manufacturer )
5/8" thlck stucco over
� BI on 3/8" high rib lath on
15/32" CDX Plywood
nailed to trusses with IOd
L192 ring shank nails at
12" o.c. field and 6" o.c.
edges. Install per ASTM
C926-I1a and ASTM C1063
WALL BEYOND
Typical Wall Reinforcement
see detail on sheet 1--)-2
5/8" thick light textured
stucco on typical concrete -
block construction
45 bar vert. w/
30" overlap
at each filled cell
Verify step height
on foundation plan
=
u—III
1 I I1 -I 1=1-III 11 11 III 11
RE/4 R fi ORCH SECTION
BI
base
board
Simpson HTS-20 at each truss
with (24) IOd x 1 1/2" nails
�truss
in each strap
5/8" drywall
Strap studs to plate using Simpson
ceiling
SP4 strap with (6) IOd x 1 I/2"
Z
nails 1n each strap
O (2) 2" x 4" toy
plate
H
U
w
1/2" drywall on
n
2" x 4" studs at 14" o.c.
U2"
x 4" Blocking
H
w m
w
Strap studs to plate using Simpson
SP4 strap with (() IOd x 1 1/2"
w
nails 1n each strap
J(
e
2" x 4" p.t. bottom pprate with
I/2" anchor bolt at 32" o.c. and
min. 1" embedment with 2" washer
N N
Typical basebo
rd
4" concrete slab with ribermesh OR
6"xC 410/10 WWM on 6 mil Visqueen over
clean compacted termite treated fill
;; <;footmg see foundation plan
for size and steel req.
T(Qplcal Interior Bearing Partition
Scale: 1/2" = I'—O"
Filled Cell Masonry Column With One
tt5 From Footing To Beam.
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
Single Filled Cell Column
NTS
6/8" drywall with smooth finish
R-30 Batts
1/2" drywall over I" x furring
strips at 14" o.c. with R4.2 fyfoil
insulation on typlcal 8" Block walls
All drywall is per FBC 102.3.1 and
shall meet all pertaining ASTM codes.
Mortar to be Type "M" onlg.
Provide Our-O-Rock at air wet
areas (ex. showers, tubs etc...)
FIII cell with concrete and
(1) 45 bar vert. (typical).
Max. spacing shall not exceed
40" unless otherwise noted
see foundation plan notes for
spacing at openings
4" concrete slab with fibermesh OR
CxC 410/10 WWM on 6 mil Visqueen over
—clean compacted termite treated fill
` F-16M
See detail on sheet 4.
Scale 1/2" = 1'-0"
Filled Cell Masonry Column With One
45 From Footing To Beam Each.
Conc. Fill To Be 3000 PSI
See Floor Plan For Location
u7 e
N
o•�
N Z
N.�
CIZ
FL
t
E00
M
�o 00 00
t
w ^�M
U�w
0U��
FFU-- a
0UF,
"��h
Y^�
N N
(LIV w E o
z W 00
No No O
U
— 4 oou
Double Filled Cell Column a- � rr q
NTS
I z NN #
Lo O
(3r�� IT-
V
L_
~ LI �m�
C)0) IL T)
41
IK
3
Q,u
to
Contractor to provide
proper foundation chairs
for proper steel installation
E
Q
t�l
30" min.
Corner Steel La
J-I.J
DATE DRAWN
2-23-21
DRAWN BY:
c.c.u.
CHECKED BY:
D.1Z.B.
-
MODEL:
CLIVIA
—
GARFAGE
LE
SHEET
OF 8.
w
JOB NUMBER:
nts
20-2302
QD.DD,OOO
0
0
Digitally signed by
O p`®�FOg' so
Daniel R. Braden
Ar9770
Date: 2021.02.25
S �a°°"
p.
14:42:07-05'00'
.Q......... n'
H.B.
Inal
15" a.f.f.
ME
A/C disc. Pool disc. Grinder disc.
1,2) fta /7 copper feed 200
lit AMP
PANEL
2 Copper
servic
,ground to rebar in slab
TRICAL RISER
NTS
2" VTR
JIL
I
2" I
I
LAV-1 i
-1
2"
AAv JIL 3
BATH
LIAV-1 tt3
3"
2" BT-1
WC-11
:R
ELECTRICAL PL,4N
ELECTRIC NOTES:
PANEL
"A"
Poles
BR
Load
Wire
Description
circa
circa
Description
Wire
Load
BR
Poles
2
60
12.0 kw
ttb
A/C comp
1
2
AHLI
u10
6.0 kw
30
2
3
4
2
30
4.5 kw
#10
40 gal. water HTR
5
6
Range
ttb
12.0 kw
50
2
�
8
I
20
1.8 kw
u12
Water Pump
9
10
Dr er
#10
5.0 kw
30
2
11
12
1
20
1.5 kw
#12
Range Hood
13
14
Dishwasher
#12
1.2 kw
20
1
1
20
1.2 kw
tt12
Clothes Washer
IS
16
Refrigerator
#12
1.2 kw
20
1
1
20
.81 kw
#12
Garage Door Opener
11
18
General Lighting
912
20
1
1
20
1.5 kw
W2
Kitchen S.A.C.
19
20
General Lighting
412
20
1
1
20
1.5 kw
#12
Kitchen S.A.C.
21
22
General Lighting
u12
20
1
1
20
tt12
General Lighting
23
24
General Lighting
912
20
1
1
20
tt12
General Lighting
25
26
General Lighting
31:12
20
1
1
20
#12
General Lighting
2-1
28
Bathroom GPI
u12
20
1
1
20
#12
General Lighting
29
30
Put. Pool Equip.
#10
2.8 kw
30
1
1
20
#12
General Lighting
31
32
Grinder Pump
u10
1.8 kw
20
1
I
120
412
1 Bathroom GFI
33
1 34
1
20
#12
Smoke Det
35
36
Disposal
u12
1.0 kw
20
1
1
20
#12
Smoke Det
31
38
spare
spare
39
40
0 tional Stub -panel
(3) u8
9.6 kw
50
2
s are
41
92
PANEL "A" LOAD CALCULATION SHEET
Load Description
Qt .
Watts
Total(Watts)
General Lighting (3 watts sq. ft.)
Small„A.pphance.Cir,cuit(s), ,,,, ,,,,,,,,, ,,,,,,,,, ,,,,,,,,,,,
.Range .....................................................................
Range..Hood.............................................................
Refrigerator.............................................................
Dish Washer
D.Isposal...................................................................
Clothes -Washer. ........................................................
Clothes„Dryer..........................................................
Water Heater..........................................................
....................
Water Pump.............................................................
Pool Egwpment....................................................... -
Csara9e Door Opener ....
Grinder. Pump...........................................................
..............................................................................
..............................................................................
3923
3
8,328
2
1,500
3,000
1
12,000
12,000
1
1,100
1,100
1
1,200
1,200
1
1,200
1,200
1
1,000
1,000
1
1,200
1,200
1
5,000
5,000
1
4,500
4,500
1
1,800
1,800
1
2,800
2,800
1
810
810
I
1,800
1,800
Total Watts
49,179
First 10000 Watts 8100%
1
10,000
10,000
Remainder 39.119 1140%
1
O
15,612
Electric Heat or A/C 10,000 865%
1
18,000
18,000
Calculated Load
Watts
43,612
Voltage
240
Calculated Wattage Divided bg Voltage = Total Amps 181.91
Panel Size Required = 20OAmps
Sanitary Riser Legend
Sanitary line
;r
Bath Tub "P" trap
---
Vent Line
�
shwa, "P" trap
rr'
Lavatory Trap
r"
Washing Machine Drain
r'
Sink Trap
r
Urinal
LL
Water Closet
Water Fountain Drain
LL
Floor Drain
11r,
Grinder Pump
T'
Clean Out
!� n
2" Vent thru Roof
''--
2" Vent thru wall
2"
Pipe Diameter Designation (2" die)
NOTES:
- ALL sanitary pipe to be Schedule 40 PVC
- Slope hall be no leas than 1/8" per foot and no more than 1/4" per foot
SCALE: 3/16" = 1'-0"
I. Use copper wire only, no aluminum.
nts 2. Provide and wire all required smoke detectors.
3. Contractor to verify location of electrical service and provider
4. ALL paddle fans shall be on a rheostat.
S. Recessed cans to be installed per NFPA requirements.
6. ALL Branch Circuits that supply 125v Single phase 15 amp or 20 amp outlets
shall be protected by Combination -Type AFCI Circuit Breakers.
1. Tamper resistant AFCI receptacles to be installed in ALL rooms
Kitchen, Bathrooms, and Garage.
8. ALL bath, laundry, kitchen and garage receptacles to be GFCI protected.
9. ALL exterior outlets to be WP/GFCI protected.
10. A/C Return Air Balance Must comply w/ F.B.C. Mechanical lth ed. and
current version of any supplements to the Ith ed.
11. A/C Refrigerant lines that are run thru slabs must be sleeved in PVC
12. Provide Disconnects at ALL appliances (water heater, A/C units, and
ALL other equipment as required by N.E.C.)
14. A/C Ducts in Garage shall be metal or I" thick minimum rigid nonmetallic Class 0 or
Class I duct or other approved material and shall have no openings into the garage.
15. Smoke Alarms shall be installed in the following locations:
W LU 0 0
ua = O
Z LU OD (0 O
< Q 00
OD OD U
i z 00 NCA It
O �
�VO�r3cr
W U a cal
x -1
io a;
LLN
4 =
-tt+r ED
co
73
DATE DRAWN
2-22-21
DRAWN BY:
C.C.U.
CHECKED BY:
D.R.B.
MODEL:
OLIVIA
GARAGE
LEFT
SHEET
OF 8.
w
JOB NUMBER:
20-2302
DpOO.D.0000
a) In each sleeping room. Digitally signed by
b) Outside each separate sleeping area in the immediate vicinity of the bedrooms.
c) On each additional story of the dwelling Daniel R. Braden
** ALL Smoke Alarms shall be interconnected and hardwired ** Date:2021.02.25
14:39:25-05'00'