HomeMy WebLinkAboutEnergy Efficiency Code & Project InformationFORM R405-2020
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the
Residential Simulated Performance Alternative shall include:
❑ This checklist
❑ Form R405-2020 report
❑ Input summary checklist that can be used for field verification (usually four pages/may be greater)
❑ Energy Performance Level (EPL) Display Card (one page)
❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
❑ Mandatory Requirements (five pages)
Required prior to CO:
❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page)
❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4
allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to
comply with Section C402.5
❑ If Form R405 duct leakage type indicates anything other than "default leakage", then a completed
2020 Duct Leakage Test Report - Performance Method (usually one page)
12/22/2020 6:45:10 AM EnergyGauge® USA 7.0.00 - RaRes2020 FBC 71h Edition (2020) Compliant Software Page 1 of 1
MANDATORY REQUIREMENTS - (Continued)
R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage
between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls.
❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system.
❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways
for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or
(7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent
of the design airflow rate when tested in accordance with ASHRAE 193.
❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods:
1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system,
including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise
sealed during the test.
2. Posiconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire
system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building
thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section
R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn =
duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the
compliance report for the proposed design.
A written report of the results of the test shall be signed by the parry conducting the test and provided to the code official.
❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C)
or below 55°F (13°C) shall be insulated to a minimum of R-3.
R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that
caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are
installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with
Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall
❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for
circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The
controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no
demand for hot water.
❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall
automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the
times when heated water is used in the occupancy.
3/l/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5
MANDATORY REQUIREMENTS - (Continued)
❑R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have
heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3'/z inches (89 mm) in the hot water distribution line and cold water line located as close as possible
to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from 100°F to 140°F (38°C to 600C).
❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to
electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of
combustion types of service water -heating systems to be turned off.
❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed.
Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate
water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1.
❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water -heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the
Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation
including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical
ventilation, the air handler shall be powered by an electronically commutated motor.
R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation
shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10
otherwise.
R403.7 Heating and cooling equipment.
R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based
❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation
methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the
outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design
conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other
factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical
ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have
an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is
installed.
TABLE R403.6.1
WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIRFLOW RATE MINIMUM
(CFM)
MINIMUM EFFICACY a
(CFM/WATT)
AIRFLOW RATE MAXIMU
(CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In -line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
<90
Bathroom, utility room
90
2.8 cfm/watt
Any
For SI: 1 cfm = 28.3 Umin. a. When tested in accordance with HVI Standard 916
3/1/2021 7:21 AM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 71h Edition (2020) Compliant Software Page 3 of 5
MANDATORY REQUIREMENTS - (Continued)
R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the
equipment shall not be less than the calculated latent load.
The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's
expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature.
Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the
calculated total sensible load but not less than 80 percent of that load.
2.
When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of
equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design
requirements calculated according to the procedure selected in Section R403.7.1.
❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners
shall not be less than the design load calculated in accordance with Section R403.7.1.
❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections
❑ C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403.
❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building,
shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.80C).
❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas
shall be in accordance with Sections R403.10.1 through R403.10.5.
❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots.
❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operation.
2. Pumps that operate solar- and waste -heat -recovery pool heating systems.
3. Where pumps are powered exclusively from on -site renewable generation.
3/1/2021 7:21 AM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5
❑R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on oral
the water surface or a liquid cover or other means proven to reduce heat loss.
Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered
energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required.
R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal
❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance
with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
❑R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the
requirements of APSP-14.
R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements:
1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house
is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day.
2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air.
3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2.
4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential.
R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13,
conform to the following requirements:
1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft
damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct.
2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system,
a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct.
3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the
central cooling evaporator coil.
4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an
efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt.
R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights.
3/1/2021 7:21 AM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5
2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: Olivia Model - LH - XXX TBD Builder Name: A Great Home
Street: XXX TBD Permit Office: Martin County
City, State, Zip: Martin County , FL , Permit Number:
Y
U
Owner: Jurisdiction: 531000
w
x
Design Location: FL, Fort Pierce
c>
COMPONENT
AIR BARRIER CRITERIA
INSULATION INSTALLATION CRITERIA
General
A continuous air barrier shall be installed in the building envelope.
Air -permeable insulation shall
requirements
The exterior thermal envelope contains a continuous air barrier.
not be used as a sealing material.
Breaks or joints in the air barrier shall be sealed.
Ceiling/attic
The air barrier in any dropped ceiling/soffit shall be aligned with
The insulation in any dropped ceiling/soffit
the insulation and any gaps in the air barrier shall be sealed.
shall be aligned with the air barrier.
Access openings, drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls
The junction of the foundation and sill plate shall be sealed.
Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be
shall be insulated by completely filling the cavity
sealed.
with a material having a thermal resistance of R-3
Knee walls shall be sealed.
per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows, skylights
The space between window/door jambs and framing, and
and doors
skylights and framing shall be sealed.
Rim joists
Rim joists shall include the air barrier.
Rim joists shall be insulated.
Floors
The air barrier shall be installed at any exposed edge of
Floor framing cavity insulation shall be installed to
(including
insulation.
maintain permanent contact with the underside of
above -garage
subfloor decking, or floor framing cavity insulation
and cantilevered
shall be permitted to be in contact with the top side
floors)
of sheathing, or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls
Exposed earth in unvented crawl spaces shall be covered with
Where provided instead of floor insulation, insulation
a Class I vapor retarder with overlapping joints taped.
shall be permanently attached to the crawlspace wall
.
Shafts, penetrations
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be out to fit, or narrow
Narrow cavities
cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation
Air sealing shall be provided between the garage and conditioned spa
s.
Recessed lighting
Recessed light fixtures installed in the building thermal envelope
Recessed light fixtures installed in the building
shall be sealed to the finished surface.
thermal envelope shall be air tight and IC rated.
Plumbing and wiring
Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls, or insulation that on
installation readily conforms to available space shall
Shower/tub
The air barrier installed at exterior walls adjacent to showers and
Exterior walls adjacent to showers and tubs shall
on exterior wall
tubs shall separate them from the showers and tubs.
be insulated.
Electrical/phone box or
The air barrier shall be installed behind electrical or communication
exterior walls
boxes or air -sealed boxes shall be installed.
HVAC register boots
HVAC supply and return register boots that penetrate building
thermal envelope shall be sealed to the sub -floor, wall covering or
Concealed
When required to be sealed, concealed fire sprinklers shall only be
sprinklers
sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
a. in addition, inspection or log wa is snap oe in accordance with the provisions of ICU-4u1J.
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2020 Florida Building Code, Energy Conservation, 7th Edition
Jurisdiction: 531000
Permit #:
Job Information
Builder: A Great Home Community: Lot: NA
Address: XXX TBD
City: Martin County State: FL Zip:
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method
0 PRESCRIPTIVE METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding 7 air
changes per hour at a pressure of 0.2 inch w.g. (50 Pascals) in Climate Zones 1 and 2.
0 PERFORMANCE or ERI METHOD -The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding
the selected ACH(50) value, as shown on Form R405-2020 (Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50.
ACH(50) specified on Form R405-2020-Energy Ca/c (Performance) or R406-2020 (ERI): 6.000
x 60 — 32448 — Method for calculating building volume:
CFM(50) Building Volume ACH(5O)
0 Retrieved from architectural plans
❑ PASS 40 Code software calculated
When ACH(50) is less than 3, Mechanical Ventilation installation 0 Field measured and calculated
must be verified by building department.
R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals)
Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section
489.105(3)(f), (g), or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and
provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration
control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control
measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Compa
Company Name: Phone:
I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: Date of Test:
Printed Name of Tester:
License/Certification #: Issuing Authority:
3/l/2021 7:22:10 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1
Job: Olivia Model-LH-XXX T.
Manual S Compliance Report ..
E -Caks Date: Mar 01, 2021
r' Inc Entire House By: E-Calcs Plus, Inc.
PI'mE-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalcsplus.com Web: www.ecalcspluscom License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
Design Conditions
Outdoor design DB: 90.4°F
Sensible gain: 42721 Btuh
Entering coil DB: 76.9°F
Outdoor design WB: 77.4°F
Latent gain: 8402 Btuh
Entering coil WB: 63.8'F
Indoor design DB: 75.0°F
Total gain: 51122 Btuh
Indoor FIR 50 %
Estimated airflow: 1883 cfm
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Goodman Mfg.
Model: GSZ140601K+ASPT61D14A
Actual airflow: 1883 cfm
Sensible capacity: 47136 Btuh
110'/ of load
Latent capacity: 9337 Btuh
111°/o of load
Total capacity: 56473 Btuh
110'/ of load SHR: 83/
Design Conditions
Heating Equipment
Outdoor design DB: 41.0°F
Heat loss: 43953 Btuh
Entering coil DB: 70.0°F
Indoor design DB: 70.0°F
Manufacturer's Performance Data at Actual Design Conditions
Equipment type: Split ASHP
Manufacturer: Goodman Mfg.
Model: GSZ140601K+ASPT61D14A
Actual airflow: 0 cfm
Output capacity: 59000 Btuh
1341/o of load
Capacity balance: 34 °F
Supplemental heat required:
0 Btuh
Economic balance: -87 °F
Backup equipment type: Elec strip
Manufacturer: Goodman Mfg.
Model: AFUE 100
Actual airflow: 0 cfm
Output capacity: 7.5 kW
58 / of load Temp. rise: 12 OF
Meets all requirements of ACCA Manual S.
ttv 2021-Mar-0107:29:23
r .,... Rig ht-Suite®Universa1202121.0.03 RSU27537 Pagel
r
...H - XXX TBD\Olivia Model - XXX TBD 3.1.2021.rup Calo = MJ8 Front Door faces: E
Project Summary
E-Calcs Entire House
Plus, Inc. E-Calcs Plus, Inc.
Job: Olivia Model- LH -XXX T...
Date: Mar 01, 2021
By: E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalcsplus.com Web: www.ecaicsplus.com License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
Notes:
Weather: St Lucie Co Intl, FL, US
Winter Design Conditions
Summer Design Conditions
Outside db 41 OF
Outside db
90 OF
Inside db 70 OF
Inside db
75 OF
Design TD 29 OF
Design TD
15 OF
Daily range
L
Relative humidity
50
Moisture difference
57 gr/lb
Heating Summary
Sensible Cooling Equipment Load Sizing
Structure 37330 Btuh
Structure
30333 Btuh
Ducts 6623 Btuh
Ducts
12388 Btuh
Central vent (0 cfm) 0 Btuh
Central vent (0 cfm)
0 Btuh
(none)
(none)
Humidification 0 Btuh
Blower
0 Btuh
Piping 0 Btuh
Equipment load 43953 Btuh
Use manufacturer's data
y
Rate/swing ltiplier
1.00
Infiltration
Equipment senmusible load
42721 Btuh
Method Simplified
Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0
Structure
3926 Btuh
Ducts
4476 Btuh
Central vent (0 cfm)
0 Btuh
Heating Cooling
(none)
Area (ft2) 3080 3086
Equipment latent load
8402 Btuh
Volume (ft3) 32358 32358
Air changes/hour 0.28 0.15
Equipment Total Load (Sen+Lat)
51122 Btuh
Equiv. AVF (cfm) 151 81
Req. total capacity at 0.75 SHR
4.7 ton
Heating Equipment Summary
Cooling Equipment Summary
Make Goodman Mfg.
Make Goodman Mfg.
Trade GOODMAN
Trade GOODMAN
Model GSZ140601K
Cond GSZ140601K
AHRI ref 201652594
Coil ASPT61 D14A
AHRI ref 201652594
Efficiency 8.5 HSPF
Efficiency 11.5 EER, 14 SEER
Heating input
Sensible cooling
42375 Btuh
Heating output 59000 Btuh @ 47-F
Latent cooling
14125 Btuh
Temperature rise 0 OF
Total cooling
56500 Btuh
Actual air flow 0 cfm
Actual air flow
1883 cfm
Air flow factor 0 cfm/Btuh
Air flow factor
0.044 cfm/Btuh
Static pressure 0.50 in H2O
Static pressure
0.50 in H2O
Space thermostat
Load sensible heat ratio
0.84
Capacity balance point = 34 o F
Backup: Goodman Mfg. AFUE 100
Input = 8 kW, Output = 25591 Btuh, 100 AFUE
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
w!1511I tIDo1't-
2021-Mar-0107:29:23
--•,•,—. Right -Suite® Universal 202121.0.03 RSU27537
Pagel
Aft_f�l•-•-••
...H-XXX TBD\Olivia Model- XXX TBD 3.1.2021.rup Calc=MJ8 Front Door faces:
E
Load Short Form Job: Olivia Model- LH -XXX T...
E-Calcs Date: Mar 01, 2021
Plus, Inc. Entire House By: E-Calcs Plus, Inc.
E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalcsplus.com Web: www.ecalcsplus.com License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
Htg Clg Infiltration
Outsidedb (°F) 41 90 Method Simplified
Inside db (°F) 70 75 Construction quality Average
Design TD (°F) 29 15 Fireplaces 0
Daily range - L
Inside humidity (%) 50 50
Moisture difference (gr/lb) 24 57
HEATING EQUIPMENT
Make Goodman Mfg.
Trade GOODMAN
Model GSZ140601K
AHRI ref 201652594
Efficiency
8.5 HSPF
Heating input
Heating output
59000 Btuh@47-F
Temperature rise
0 OF
Actual air flow
0 cfm
Air flow factor
0 cfm/Btuh
Static pressure
0.50 in H2O
Space thermostat
Capacity balance point = 34 ° F
Backup: Goodman Mfg. AFUE 100
1n 0 _ A LAA1 r).a—f _ ggga1 Pt.,h
inn 4GI IF
COOLING EQUIPMENT
Make Goodman Mfg.
Trade GOODMAN
Cond GSZ140601K
Coil ASPT61 D14A
AHRI ref 201652594
Efficiency 11.5 EER, 14 SEER
Sensible cooling
42375 Btuh
Latent cooling
14125 Btuh
Total cooling
56500 Btuh
Actual air flow
1883 cfm
Air flow factor
0.044 cfm/Btuh
Static pressure
0.50 in H2O
Load sensible heat ratio
0.84
ROOM NAME
Area
(ft2)
Htg load
(Btuh)
CIg load
(Btuh)
Htg AVF
(cfm)
CIg AVF
(cfm)
M BR
425
7779
6348
0
280
His WIC
42
700
354
0
16
Her WIC
54
59
335
0
15
MT
16
432
259
0
11
M BA
282
5200
3245
0
143
Laundry
96
1006
1314
0
58
BR4
226
3347
2719
0
120
BA2
72
2128
1255
0
55
BR2
256
2242
2530
0
112
BR3
182
4184
3470
0
153
WIC3
24
462
227
0
10
BA3
90
1460
814
0
36
LivDin
609
9469
12646
0
557
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
} WI'�h1:70iri 2021-Mar-0107:29:23
r .,... .��..�� Right -Suite® Universal 202121.0.03 RSU27537 Pagel
H -XXX TBD\Olivia Model- XXX
TBD 3.1.2021.rup Calc=MJ8 Front Door faces: E
Entire House d
3080
43953
42721
0
1883
Other equip loads
0
0
Equip. @ 1.00 RSM
42721
Latent cooling
8402
r�rni n
I nnnn
I .nncn
I r.. nn
I n
l .nnn
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
- !tr!T 2021-Mar-01 07:29:23
r !�75 i
Paget
...H-XXX TBD\Olivia Model- XXX TBD 3.1.2021.rup Calc=MJ8 Front Door faces: E
FORM R405-2020
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Project Name: Olivia Model - LH - XXX TBD
Builder Name: A Great Home
Street: XXX TBD
Permit Office: Martin County
City, State, Zip: Martin County , FL ,
Permit Number:
Owner:
Jurisdiction: 531000
Design Location: FL, Fort Pierce
County: Martin (Florida Climate Zone 2 )
1. New construction or existing New (From Plans)
10. Wall Type$3092.2 sqft.)
Insulation Area
2. Single family or multiple family Detached
a. Concrete Block - Int Insul, Exterior
R=4.2 2852.20 ft2
b. Frame - Wood, Adjacent
R=13.0 240.00 ft2
3. Number of units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 4
d. N/A
R= ft2
11. Ceiling Types (3257.0 sqft.)
Insulation Area
5. Is this a worst case? No
a. Under Attic (Vented)
R=30.0 3089.00 ft2
6. Conditioned floor area above grade (W) 3089
b. Knee Wall (Vented)
R=30.0 168.00 ft2
Conditioned floor area below grade (W) 0
c. N/A
R= ft2
7. Windows(476.8 sqft.) Description Area
12. Ducts R W
a. Sup: Attic, Rol: Laundry, AH: Laundry 6 414
a. U-Factor: Dbl, U=0.69 240.00 ft2
SHGC: SHGC=0.22
b. U-Factor: Dbl, U=0.57 136.00 ft2
13. Cooling systems
kBtu/hr Efficiency
SHGC: SHGC=0.24
a. Central Unit
56.5 SEER:14.00
c. U-Factor: Dbl, U=0.70 68.00 ft2
SHGC: SHGC=0.20
Area Weighted Average Overhang Depth: 6.161 ft.
14. Heating systems
kBtu/hr Efficiency
Area Weighted Average SHGC: 0.226
a. Electric Heat Pump
56.5 HSPF:8.50
8. Skylights Area
c. U-Factor:(AVG) N/A ft2
15. Hot water systems
SHGC(AVG): N/A
a. Electric
Cap: 40 gallons
9. Floor Types (3089.0 sqft.) Insulation Area
EF: 0.950
a. Slab -On -Grade Edge Insulation R=0.0 3089.00 ft2
b. Conservation features
b. N/A R= ft2
None
c. N/A R= ft2
16. Credits
Pstat
Glass/Floor Area: 0.154 Total Proposed Modified Loads: 93.96
PASS
SS
Total Baseline Loads: 97.97
r/��7�7
1 hereby certify that the plans and specifications covered by
Review of the plans and
F•{HE SrgJ,
this calculation are in compliance with the Florida Energy
Code.
specifications covered by this
indicates
�1� ` - 4P
calculation compliance
K E-Calcs Plus, Inc.
with the Florida Energy Code.
o
PREPARED BY:
DATE: March 1.2021
Before construction is completed
this building will be inspected for
compliance with Section 553.908
d a
r, y
°
*�Q
I hereby certify that this building, as designed, is in compliance
Florida Statutes.
with the Florida Energy Code.
COD 1 �O
OWNER/AGENT:
BUILDING OFFICIAL:
DATE: -
DATE:
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory -sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 6.00 ACH50 (R402.4.1.2).
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 71h Edition (2020) Compliant Software Page 1 of 6
Building Analysis Job: Olivia Model-LH-XXXT
g ...
E-Calcs Date: Mar 01, 2021
Entire House By: E-Calcs Plus, Inc.
qZ1 Plus, Inc. E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalcsplus.com Web: www.ecalcsplus.com License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
Design
C•
Location:
Indoor:
Heating
Cooling
St Lucie Co Intl, FL, US
Indoor temperature (°F)
70
75
Elevation: 26 ft
Design TD (°F)
29
15
Latitude: 28°N
Relative humidity (%)
50
50
Outdoor: Heating
Cooling
Moisture difference (gr/Ib)
24.4
56.9
Dry bulb (°F) 41
90
Infiltration:
Dailyrange (°F) -
15 (I
) Method
Simplified
Wet bulb (°F) -
77
Construction quality
Average
Wind speed (mph) 15.0
7.5
Fireplaces
0
Component
Btuh/It2
Btuh
% of load
Walls
4.0
10420
23.7
Glazing
18.6
8869
20.2
Doors
11.3
241
0.5
Ceilings
0.9
2858
6.5
Floors
3.3
10129
23.0
Infiltration
1.7
4813
10.9
Ducts
6623
15.1
Piping
0
0
Humidification
0
0
Ventilation
0
0
Adjustments
0
Total
43953
100.0
Component
Btuh/It2
Btuh
% of load
Walls
2.5
6430
15.1
Glazing
17.2
8205
19.2
Doors
7.3
155
0.4
Ceilings
1.7
5204
12.2
Floors
0
0
0
Infiltration
0.5
1369
3.2
Ducts
12388
29.0
Ventilation
0
0
Internal gains
8970
21.0
Blower
0
0
Adjustments
0
Total
42721
100.0
Latent Cooling Load = 8402 Btuh
Overall U-value = 0.121 Btuh/ft2-°F
Data entries checked.
Dols
V�klls�
I filb26m
emn,'
Raps
aril �
NHIS Irterrt Gins
Gairg
Clie piZ
CBlirgs
HIMc l
{11i" Wrigl'1>Ct�irL"• 2021-Mar-01 07:29:23
.....r..+... Right -Suite® Universal 202121.0.03 RSU27537 Pagel
...H - XXX TBD\Olivia Model - XXX TBD 3.1.2021.rup Calo = MJ8 Front Door faces: E
First Floor
0
Job #: Olivia Model - LH - XXX TBD
1 : 135
E-Calcs PlusInc.ale:
, .
Performed by E-Calcs Plus, Inc. for:
Page 1
Olivia Model - LH - XXX TBD
9250 Corkscrew Rd, Suite B
9
Right-Suite®Universa12021
XXX TBD
Estero, FL 33928
21.0.03 RSU27537
Martin County, FL
Phone: 239.810.6106
2021-Mar-01 07:29:45
www.ecalcsplus.com eric@ecalcsplus.com
...via Model - XXX TBD 3.1.2021.rup
Duct System Summary Job: Olivia Model-LH-XXXT...
E-Calcs Date: Mar 01, 2021
Plus, Inc. Entire House By: E-Calcs Plus, Inc.
E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalcsplus.com Web: www.ecalcaplusAom License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
External static pressure
Pressurelosses
Available static pressure
Supply / return available pressure
Lowest friction rate
Actual air flow
Total effective length (TEL)
Heating
0.50 in H2O
0.16 in H2O
0.34 in H2O
0.187 / 0.153 in H2O
0.099 in/100ft
0 cfm
342 ft
Cooling
0.50 in H2O
0.16 in H2O
0.34 in H2O
0.187 / 0.153 in H2O
0.099 in/100ft
1883 cfm
Name
Design
(Btuh)
Htg
(cfm)
Clg
(cfm)
Design
FR
Dian
(in)
H x W
(in)
Duct
Matl
Actual
Ln (ft)
Ftg.Egv
Ln (ft)
Trunk
BA2
c 1255
0
55
0.105
6.0
Ox 0
VIFx
47.4
130.0
st2
BA3
c 814
0
36
0.109
5.0
Ox 0
VIFx
41.3
130.0
st2
BR2
c 2530
0
112
0.110
7.0
Ox 0
VIFx
39.5
130.0
st2
BR3
c 3470
0
153
0.109
8.0
Ox 0
VIFx
41.3
130.0
st2
BR4
c 2719
0
120
0.123
7.0
Ox 0
VIFx
22.0
130.0
st4
Her WIC
c 335
0
15
0.110
4.0
Ox 0
VIFx
45.0
125.0
st3
His WIC
c 354
0
16
0.106
4.0
Ox 0
VIFx
46.6
130.0
st3
Kitchen Nook
c 3603
0
159
0.119
8.0
Ox 0
VIFx
27.0
130.0
st4
Kitchen Nook -A
c 3603
0
159
0.118
8.0
Ox 0
VIFx
29.0
130.0
st4
Laundry
c 1314
0
58
0.119
6.0
Ox 0
VIFx
26.6
130.0
st4
LivDin
c 4215
0
186
0.125
9.0
Ox 0
VIFx
24.1
125.0
st1
LivDin-A
c 4215
0
186
0.126
9.0
Ox 0
VIFx
23.1
125.0
st1
Livoin-C
c 4215
0
186
0.125
9.0
Ox 0
VIFx
25.1
125.0
st1
M BA
c 3245
0
143
0.103
8.0
Ox 0
VIFx
51.2
130.0
st3
M BR
c 3174
0
140
0.106
8.0
Ox 0
VIFx
46.7
130.0
st3
M BR -A
c 3174
0
140
0.099
8.0
Ox 0
VIFx
58.1
130.0
st3
MT
c 259
0
11
0.103
4.0
Ox 0
VIFx
52.4
130.0
st3
WIC3
c 227
0
10
0.107
4.0
Ox 0
VIFx
45.3
130.0
st2
WI't9tltifi�}t' 2021-Mar-0107:29:24
.,... ...�..�� Right -Suite® Universal 202121.0.03 RSU27537 Pagel
...H - XXX TBD\Olivia Model - XXX TBD 3.1.2021.rup Calo = MJ8 Front Door faces: E
Trunk
Htg
Clg
Design
Veloc
Diam
H x W
Duct
Name
Type
(cfm)
(cfm)
FIR
(fpm)
(in)
(in)
Material
Trunk
st3
Peak AVF
0
465
0.099
592
12.0
0 x 0
VinlFlx
st1
Peak AVF
0
557
0.125
521
14.0
0 x 0
VinlFlx
st2
Peak AVF
0
366
0.105
466
12.0
0 x 0
VinlFlx
st4
Peak AVF
0
495
0.118
631
12.0
0 x 0
VinlFlx
Grille
Htg
Clg
TEL
Design
Veloc
Diam
H x W
Stud/Joist
Duct
Name
Size (in)
(cfm)
(cfm)
(ft)
FIR
(fpm)
(in)
(in)
Opening (in)
Matl
Trunk
rb4
Ox 0
0
167
152.2
0.101
378
9.0
Ox 0
VIFx
rt1
rb5
Ox 0
0
163
154.1
0.099
369
9.0
Ox 0
VIFx
rt1
rb2
Ox 0
0
120
98.9
0.155
448
7.0
Ox 0
VIFx
rb1
Ox 0
0
465
108.5
0.141
592
12.0
Ox 0
VIFx
rb3
Ox 0
0
969
71.0
0.216
694
16.0
Ox 0
VIFx
Name
Trunk
Type
Htg
(cfm)
Clg
(cfm)
Design
FIR
Veloc
(fpm)
Diam
(in)
H x W
(in)
Duct
Material
Trunk
rt1
Peak AVF
0
330
0.099
420
12.0
0 x 0
VinlFlx
vrri9ht5wiY- 2021-Mar-01 07:29:24
.... ...�..�� Right -Suite® Universal 202121.0.03 RSU27537 Paget
...H - XXX TBD\Olivia Model - XXX TBD 3.1.2021.rup Calo = MJ8 Front Door faces: E
Static Pressure and Friction Rate Job: Olivia Model-LH-XXXT...
E-Gales Date: Mar 01, 2021
Plus, Inc. Entire House By: E-Calcs Plus, Inc.
E-Calcs Plus, Inc.
9250 Corkscrew Rd, Suite 8, Estero, FL 33928 Phone: 239.810.6106 Email: eric@ecalosplus.com Web: www.ecalc5plus.00m License: HERS Rater ID 0757810
For: Olivia Model - LH - XXX TBD, A Great Home
XXX TBD, Martin County, FL
Heating
Cooling
(in H2O)
(in H2O)
External static pressure
0.50
0.50
Pressurelosses
Coil
0
0
Heat exchanger
0
0
Supply diffusers
0.03
0.03
Return grilles
0.03
0.03
Filter
0.10
0.1 C
Humidifier
0
0
Balancing damper
0
0
Other device
0
0
Available static pressure
0.34
0.34
Total Effective Length
Supply
Return
(ff)
(ff)
Measured length of run -out
21
23
Measured length of trunk
37
36
Equivalent length of fittings
130
95
Total length
188
154
Total effective length
342
Friction
Heating
Cooling
(in/100ft)
(in/100ft)
Supply Ducts
0.099 OK
0.099 OK
Return Ducts
0.099 OK
0.099 OK
Fitting Equivalent Length Details
Supply 4AD=60, 11A=20, 11G=5,
1A=35, 11G=5, 11G=5: TotalEL=130
Return 6M=20, 11M=20, 11G=5, 5D=40, 11G=5, 11G=5: TotalEL=95
WI't9tltifi�}t' 2021-Mar-0107:29:24
.,... ...�..�- Right -Suite® Universal 202121.0.03 RSU27537 Pagel
...H - XXX TBD\Olivia Model - XXX TBD 3.1.2021.rup Calo = MJ8 Front Door faces: E
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
PROJECT
Title:
Olivia Model - LH - XXX TBD
Bedrooms: 4
Address Type:
Street Address
Building Type:
User
Conditioned Area: 3089
Lot #
Owner Name:
Total Stories: 1
Block/Subdivision:
# of Units:
1
Worst Case: No
PlatBook:
Builder Name:
A Great Home
Rotate Angle: 0
Street:
XXX TBD
Permit Office:
Martin County
Cross Ventilation: No
County:
Martin
Jurisdiction:
531000
Whole House Fan: No
City, State,
Zip:
Martin County,
Family Type:
Detached
FL,
New/Existing:
New (From Plans)
Comment:
CLIMATE
/
Design Temp
Int Design Temp
Heating
Design Daily Temp
V Design Location TMY Site 97.5 %
2.5 %
Winter
Summer Degree Days Moisture
Range
FL, Fort Pierce FL_VERO_BEACH_MUNI 39
90
70
75
299
62
Low
BLOCKS
Number
Name Area
Volume
1
Entire House 3089 32448
SPACES
Number
Name Area
Volume Kitchen Occupants
Bedrooms
Infil ID
Finished Cooled
Heated
1
M BR 425
4590 No
2
1
1
Yes
Yes
Yes
2
His WIC 42
420 No
0
1
Yes
Yes
Yes
3
Her WIC 54
540 No
0
1
Yes
Yes
Yes
4
MT 16
160 No
0
1
Yes
Yes
Yes
5
M BA 282
2820 No
0
1
Yes
Yes
Yes
6
Laundry 96
960 No
0
1
Yes
Yes
Yes
7
BR4 226
2260 No
1
1
1
Yes
Yes
Yes
8
BA2 72
720 No
0
1
Yes
Yes
Yes
9
BR2 256
2560 No
1
1
1
Yes
Yes
Yes
10
BR3 182
1820 No
1
1
1
Yes
Yes
Yes
11
WIC3 24
240 No
0
1
Yes
Yes
Yes
12
BA3 90
900 No
0
1
Yes
Yes
Yes
13
LivDin 609
7308 No
0
1
Yes
Yes
Yes
14
Kitchen 715
7150 Yes
0
1
Yes
Yes
Yes
FLOORS
#
Floor Type Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood Carpet
1 Slab -On -Grade Edge Insulatio
M BR 53 ft 0
425 ft2
----
1 0
0
2 Slab -On -Grade Edge Insulatio
His WIC 6 ft 0
42 ft2
----
1 0
0
3 Slab -On -Grade Edge Insulatio
Her WIC 1 ft 0
54 ft2
----
1 0
0
4 Slab -On -Grade Edge Insulatio
MT 3 ft 0
16 ft2
----
1 0
0
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 71h Edition (2020) Compliant Software Page 2 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
FLOORS
# Floor Type
Space Perimeter Perimeter R-Value
Area
Joist R-Value
Tile Wood Carpet
5 Slab -On -Grade Edge Insulatio
M BA 44 ft
0
282 ft2
----
1 0
0
6 Slab -On -Grade Edge Insulatio
Laundry 3 ft
0
96 ft'
----
1 0
0
7Slab-On-Grade Edge Insulatio
BR4 14 ft
0
226 ft2
----
1 0
0
8Slab-On-Grade Edge Insulatio
BA2 18 ft
0
72 ft'
----
1 0
0
9 Slab -On -Grade Edge Insulatio
BR2 16 ft
0
256 ft2
----
1 0
0
10Slab-On-Grade Edge Insulatio
BR3 27 ft
0
182 ft2
----
1 0
0
11Slab-On-Grade Edge Insulatio
WIC3 4 ft
0
24 ft2
----
1 0
0
12SIab-On-Grade Edge Insulatio
BA3 9 ft
0
90 ft2
---_
1 0
0
13SIab-On-Grade Edge Insulatio
LivDin 44 ft
0
609 ft2
----
1 0
0
14SIab-On-Grade Edge Insulatio
Kitchen 31 ft
0
715 ft2
----
1 0
0
ROOF
/
Roof
Gable
Roof
Red
Solar
SA Emitt
Emitt Deck
Pitch
V # Type Materials Area
Area
Color
Barr
Absor.
Tested
Tested Insul.
(deg)
1 Hip
Metal 3454 ft2
0 ft2 Medium
N
0.75
No 0.9
No 0
26.57
ATTIC
v # Type
Ventilation Vent Ratio (1 in)
Area
RBS
IRCC
1 Full attic
Vented
150
3089 ft2
N
N
CEILING
# Ceiling Type
Space
R-Value
Ins Type
Area
Framing Frac Truss Type
1 Under Attic (Vented)
M BR
30
Batt
425 W
0.1
Wood
2 Under Attic (Vented)
His WIC
30
Batt
42 ft'
0.1
Wood
3 Under Attic (Vented)
Her WIC
30
Batt
54 ft'
0.1
Wood
4 Under Attic (Vented)
MT
30
Batt
16 ft2
0.1
Wood
5 Under Attic (Vented)
M BA
30
Batt
282 ft2
0.1
Wood
6 Under Attic (Vented)
Laundry
30
Batt
96 ft'
0.1
Wood
7 Under Attic (Vented)
BR4
30
Batt
226 ft2
0.1
Wood
8 Under Attic (Vented)
BA2
30
Batt
72 ft2
0.1
Wood
9 Under Attic (Vented)
BR2
30
Batt
256 ft2
0.1
Wood
10 Under Attic (Vented)
BR3
30
Batt
182 ft2
0.1
Wood
11 Under Attic (Vented)
WIC3
30
Batt
24 ft2
0.1
Wood
12 Under Attic (Vented)
BA3
30
Batt
90 ft2
0.1
Wood
13 Under Attic (Vented)
LivDin
30
Batt
609 ft2
0.1
Wood
14 Under Attic (Vented)
Kitchen
30
Batt
715 ft2
0.1
Wood
15 Knee Wall (Vented)
M BR
30
Batt
64 ft2
0.11
Wood
16 Knee Wall (Vented)
LivDin
30
Batt
104 ft2
0.11
Wood
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacant
Cavity
Width
Height
Sheathing Framing
Solar
Below
#
Ornt
To
Space
Wall Type
R-Value
Ft
In
Ft In
Area
R-Value
Fraction
Abs-
1
N
Exterior
Concrete Block - Int Insul M BR
4.2
11
0
10 10
119.2 ft�
0
0
0.45
0
2
S
Exterior
Concrete Block - Int Insul M BR
4.2
25
0
10 10
270.8 ft=
0
0
0.45
0
3
W
Exterior
Concrete Block - Int Insul M BR
4.2
17
0
10 10
184.2 ft2
0
0
0.45
0
4
S
Exterior
Concrete Block - Int Insul His WIC
4.2
6
0
10 0
60.0 ft2
0
0
0.45
0
5
S
Exterior
Concrete Block - Int Insul MT
4.2
3
0
10 0
30.0 ft2
0
0
0.45
0
6
N
Exterior
Concrete Block - Int Insul M BA
4.2
12
0
10 0
120.0 ft2
0
0
0.45
0
7
E
Exterior
Concrete Block- Int Insul MBA
4.2
18
0
10 0
180.0 ft2
0
0
0.45
0
8
S
Exterior
Concrete Block- Int Insul MBA
4.2
14
0
10 0
140.0 ft2
0
0
0.45
0
9
E
Exterior
Concrete Block - Int Insul Laundry
4.2
2
0
10 0
20.0 ft2
0
0
0.45
0
10
S
Exterior
Concrete Block - Int Insul Laundry
4.2
1
0
10 0
10.0 ft2
0
0
0.45
0
11
E
Garage
Frame - Wood Laundry
13
5
0
10 0
50.0 ft2
0
0.23
0.01
0
12
N
Exterior
Concrete Block - Int Insul BR4
4.2
14
0
10 0
140.0 ft2
0
0
0.45
0
13
E
Garage
Frame - Wood BR4
13
19
0
10 0
190.0 ft2
0
0.23
0.01
0
14
N
Exterior
Concrete Block - Int Insul BA2
4.2
6
0
10 0
60.0 ft2
0
0
0.45
0
15
W
Exterior
Concrete Block - Int Insul BA2
4.2
12
0
10 0
120.0 ft2
0
0
0.45
0
16
N
Exterior
Concrete Block - Int Insul BR2
4.2
16
0
10 0
160.0 ft2
0
0
0.45
0
17
S
Exterior
Concrete Block - Int Insul BR3
4.2
13
0
10 0
130.0 ft2
0
0
0.45
0
18
W
Exterior
Concrete Block - Int Insul BR3
4.2
14
0
10 0
140.0 ft2
0
0
0.45
0
19
W
Exterior
Concrete Block - Int Insul WIC3
4.2
4
0
10 0
40.0 ft2
0
0
0.45
0
20
S
Exterior
Concrete Block - Int Insul BA3
4.2
9
0
10 0
90.0 ft2
0
0
0.45
0
21
E
Exterior
Concrete Block - Int Insul LivDin
4.2
22
0
12 0
264.0 ft2
0
0
0.45
0
22
S
Exterior
Concrete Block - Int Insul LivDin
4.2
3
0
12 0
36.0 ft2
0
0
0.45
0
23
W
Exterior
Concrete Block - Int Insul LivDin
4.2
19
0
12 0
228.0 ft2
0
0
0.45
0
24
N
Exterior
Concrete Block - Int Insul Kitchen
4.2
23
0
10 0
230.0 ft2
0
0
0.45
0
25
S
Exterior
Concrete Block - Int Insul Kitchen
4.2
8
0
10 0
80.0 ft2
0
0
0.45
0
DOORS
#
Ornt
Door Type Space
Storms
U-Value
Width
Height
Area
Ft
In
Ft In
1
N
Insulated M BR
None
.2
.1
.1
.0 ft'
WINDOWS
Orientation shown is the entered,
Proposed orientation.
/
Wall
Overhang
V
#
Ornt ID
Frame Panes NFRC
U-Factor
SHGC
Imp
Area
Depth
Separation
Int Shade
Screening
1
N 1
Metal Low-E Double Yes
0.69
0.22
N
48.0 ft2
19 ft 0 in
0 ft 6 in
None
None
2
S 2
Metal Low-E Double Yes
0.57
0.24
N
9.0 ft2
2 ft 0 in
0 ft 6 in
None
None
3
W 3
Metal Low-E Double Yes
0.57
0.24
N
15.0 ft2
2 ft 0 in
0 ft 6 in
None
None
4
S 5
Metal Low-E Double Yes
0.57
0.24
N
6.0 ft2
2 ft 0 in
0 ft 6 in
None
None
5
E 7
Metal Low-E Double Yes
0.46
0.26
N
8.8 ft2
2 ft 0 in
0 ft 6 in
None
None
6
N 12
Metal Low-E Double Yes
0.57
0.24
N
15.0 ft2
2 ft 0 in
0 ft 6 in
None
None
7
W 15
Metal Low-E Double Yes
0.57
0.24
N
6.0 ft2
2 ft 0 in
0 ft 6 in
None
None
8
N 16
Metal Low-E Double Yes
0.57
0.24
N
15.0 ft2
2 ft 0 in
0 ft 6 in
None
None
9
S 17
Metal Low-E Double Yes
0.69
0.22
N
48.0 ft2
4 ft 0 in
0 ft 6 in
None
None
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 71h Edition (2020) Compliant Software Page 4 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall
Overhang
V # Ornt ID Frame Panes NFRC
U-Factor SHGC Imp Area Depth Separation Int Shade
Screening
10 W 18 Metal Low-E Double Yes
0.57 0.24 N 10.0 ft2 2 It 0 in 0 It 6 in
None
None
11 S 20 Metal Low-E Double Yes
0.7 0.2 N 20.0 ft2 4 It 0 in 0 It 6 in
None
None
12 E 21 Metal Low-E Double Yes
0.46 0.26 N 12.0 ft2 6 It 0 in 0 It 6 in
None
None
13 E 21 Metal Low-E Double Yes
0.46 0.26 N 12.0 ft2 6 It 0 in 0 It 6 in
None
None
14 E 21 Metal Low-E Double Yes
0.57 0.24 N 30.0 ft2 6 It 0 in 0 It 6 in
None
None
15 E 21 Metal Low-E Double Yes
0.7 0.2 N 48.0 ft2 6 It 0 in 0 It 6 in
None
None
16 N 24 Metal Low-E Double Yes
0.57 0.24 N 30.0 ft2 2 It 0 in 0 It 6 in
None
None
17 S 25 Metal Low-E Double Yes
0.69 0.22 N 48.0 ft2 19 ft 0 in 0 It 6 in
None
None
18 E 21 Metal Low-E Double Yes
0.69 0.22 N 96.0 ft2 0 It 0 in 0 It 0 in
Drapes/blinds
None
GARAGE
# Floor Area Ceiling Area
Exposed Wall Perimeter Avg. Wall Height Exposed Wall Insulation
1 500 ft2 500 ft2
64 ft 8 ft
1
INFILTRATION
# Scope Method SLA
CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .0004
3244.8 178.02 334.21 .1207
6
HEATING SYSTEM
# System Type Subtype
Speed Efficiency Capacity
Block
Ducts
1 Electric Heat Pump/ Split
Singl HSPF:8.5 56.5 kBtu/hr
1
sys#1
COOLING SYSTEM
# System Type Subtype
Subtype Efficiency Capacity Air Flow
SHR Block
Ducts
1 Central Unit/ Split
Singl SEER: 14 56.5 kBtu/hr cfm
0.75 1
sys#1
HOT WATER SYSTEM
# System Type SubTpe Location
EF Cap Use SetPnt
Conservation
1 Electric None Garage
0.95 40 gal 70 gal 120 deg
None
SOLAR HOT WATER SYSTEM
FSEC
Collector
Storage
Cart # Company Name
System Model # Collector Model # Area
Volume
FEF
None None
ft�
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 71h Edition (2020) Compliant Software Page 5 of 6
FORM R405-2020 INPUT SUMMARY CHECKLIST REPORT
DUCTS
---- Supply ----
--
Return
--
Air
CFM 25 CFM25
HVAC #
V # Location R-Value Area
Location
Area
Leakage Type
Handler
TOT
OUT ON
RLF
Heat Cool
1 Attic
6 414 ft-
Laundry
103 ft-
Default Leakage
Laundry
(Default) (Default)
1 1
TEMPERATURES
Programablre
Cr[eiling Fans:
1Thermostart:'JY
Heat ng Jan Feb
Mar
r
APr
May
r[l J]
Jun
r[l ]1
Jul
f[l J]
Aug
f[` J]
Sep
[ ]
L 1 Oct
fDC1�
Venting [ 1 Jan [ 1 Feb
l l l l
X Mar
X
l
I
I Jun
lXl
[ Jul
lXl
I Aug
lXl
l Sep
lXl
lxl
[X] Nov
Dec
Thermostat Schedule: HERS 2006 Reference
Hours
Schedule Type
1
2
3
4
5
6
7
8
9 10
11
12
Cooling (WD) AM
78
78
78
78
78
78
78
78
80 80
80
80
PM
80
80
78
78
78
78
78
78
78 78
78
78
Cooling (WEH) AM
78
78
78
78
78
78
78
78
78 78
78
78
PM
78
78
78
78
78
78
78
78
78 78
78
78
Heating (WD) AM
66
66
66
66
66
68
68
68
68 68
68
68
PM
68
68
68
68
68
68
68
68
68 68
66
66
Heating (WEH) AM
66
66
66
66
66
68
68
68
68 68
68
68
PM
68
68
68
68
68
68
68
68
68 68
66
66
MASS
Mass Type
Area
Thickness
Furniture Fraction
Space
Default(8 Ibs/sq.ft.
0 W
0 ft
0.3
Great Rm Entry
Default(8 lbs/sq.ft.
ft�
ft
0.3
Laundry
Default(8 lbs/sq.ft.
ft�
ft
0.3
BA1
Default(8 lbs/sq.ft.
ft2
ft
0.3
BR3
Default(8 lbs/sq.ft.
ft2
ft
0.3
BR2
Default(8 lbs/sq.ft.
ft2
ft
0.3
BA2
Default(8 lbs/sq.ft.
ft2
ft
0.3
BA3
Default(8 lbs/sq.ft.
ft2
ft
0.3
Loft
Default(8 lbs/sq.ft.
ft2
ft
0.3
OTB
Default(8 lbs/sq.ft.
ft2
ft
0.3
Hall
Default(8 lbs/sq.ft.
ft2
ft
0.3
Den
Default(8 Ibs/sq.ft.
ft2
ft
0.3
M BA
Default(8 lbs/sq.ft.
ft2
ft
0.3
MT
Default(8 Ibs/sq.ft.
ft2
ft
0.3
M BR
Default(8 Ibs/sq.ft.
ft2
ft
0.3
Her WIC
Default(8 lbs/sq.ft.
ft2
ft
0.3
His WIC
Default(8 Ibs/s .ft.
ft2
ft
0.3
Kit Din
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 6 of 6
FORM R405-2020
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE
INDEX* =
96
The lower the EnergyPerformance Index, the more efficient the home.
XXX TBD, Martin County, FL,
1. New construction or existing New (From Plans)
10. Wall Type and Insulation
Insulation Area
2. Single family or multiple family Detached
a. Concrete Block - Int Insul, Exterior
R=4.2 2852.20 ft2
b. Frame - Wood, Adjacent
R=13.0 240.00 ft2
3. Number of units, if multiple family 1
c. N/A
R= ft2
4. Number of Bedrooms 4
d. N/A
R= ft2
11. Ceiling Type and insulation level
Insulation Area
5. Is this a worst case? No
a. Under Attic (Vented)
R=30.0 3089.00 ft2
6. Conditioned floor area (W) 3089
b. Knee Wall (Vented)
R=30.0 168.00 ft2
7. Windows" Description Area
c. N/A
R= ft2
U-Factor: Dbl, U=0. 69 240.00 ft2
12. Ducts, location & insulation level
R W
a.
a. Sup: Attic, Ret: Laundry, AH: Laundry 6 414
SHGC: SHGC=069
.22
b. U-Factor: Dbl, U=0.57 136.00 ft2
SHGC: SHGC=0.24
13. Cooling systems
kBtu/hr Efficiency
c. U-Factor: Dbl, U=0.70 68.00 ft2
a. Central Unit
56.5 SEER:14.00
SHGC: SHGC=0.20
d. U-Factor: other (see details) 32.83 ft2
14. Heating systems
kBtu/hr Efficiency
SHGC: other (see details)
a. Electric Heat Pump
56.5 HSPF:8.50
Area Weighted Average Overhang Depth: 6.161 ft.
Area Weighted Average SHGC: 0.226
8. Skylights Description Area
15. Hot water systems
Cap: 40 gallons
a. U-Factor(AVG): N/A ft2
a. Electric
El 0.95
SHGC(AVG): N/A
b. Conservation features
9. Floor Types Insulation Area
None
a. Slab -On -Grade Edge Insulation R=0.0 3089.00 ft2
Credits (Performance method)
Patel
b. N/A R= ft2
c. N/A R= ft2
certify that this home has complied with the Florida Energy Efficiency Code for Building �g11E sT4j,
Construction through the above energy saving features which will be installed (or exceeded) 11 Fo
in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: Date:
�o
Address of New Home: City/FL Zip:
COD WE tg0
*Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient
mortgage (EEM) incentives if you obtain a Florida Energy Rating. For information about the Florida Building Code,
Energy Conservation, contact the Florida Building Commission's support staff.
**Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
3/1/2021 7:21 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 71h Edition (2020) Compliant Software Page 1 of 1
Florida Building Code, Energy Conservation, 7th Edition (2020)
atory Requirements for Residential Performance, Prescriptive and ERI Methods
ADDRESS: XXXTBD Permit Number:
Martin County , FL
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
R401.3 Energy Performance Level (EPL) display card (Mandatory).The building official shall require that an energy performance level (EPL)
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. The building official shall verity that the EPL display card completed and signed by the builder accurately reflects the plans
and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD.
SECTION R402 BUILDING THERMAL ENVELOPE
❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of
Sections R402.4.1 through R402.4.5.
Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to
comply with Section C402.5.
R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and
R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction.
R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance
with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required
by the code official, an approved third party shall inspect all components and verify compliance.
R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or
an approved third party. A written report of the results of the test shall be signed by the parry conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
❑R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where
using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907.
❑R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm
per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or
AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Exception: Site -built windows, skylights and doors.
3/1/2021 7:21 AM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5