HomeMy WebLinkAboutRev Carports Anywhere - B Troska - 303010-Rev1 - Digital Sealed (2)PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
I•
3'-0"'-11.�
SWINGING
---------------------------------------------------------------------------------------------------------------------------------------
1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND CLADDING, AND
BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY
SET —BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON —HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF SUPPORTING DEAD
LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY ADDRESSED HEREIN, INCLUDING
DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS LIST, AND NOT PROVIDED AND INSTALLED
BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS
ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE
APPLICATION OF ADDITIONAL LOADS.
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2.
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15.
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET —BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE
RESPONSIBILITY OF THE OWNER.
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS WITH SEAL WASHERS CAD 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-14x3/4" SELF —DRILLING SCREWS.
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED WELDER.
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,50OLB TENSILE STRENGTH.
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
SUB —GRADE SOILS:
—TO BE TERMITE TREATED AND COVERED WITH 6 MIL VAPOR RETARDANT PER SECTION
R318 AND 1816 OF THE 2020 FLORIDA BUILDING CODE, 7TH EDITION
—BOTTOM OF CONCRETE FOOTING SHALL BE MINIMUM OF 12" BELOW UNDISTURBED OR
ENGINEERED GRADE
CONCRETE:
—MINIMUM 2,500 PSI COMPRESSIVE STRENGTH AT 28 DAYS
—ALL OPEN AREAS OF CONCRETE OUTSIDE OF THE PROPOSED STRUCTURE SHALL BE
i
DESIGNED TO SLOPE AWAY FROM THE STRUCTURE
REINFORCING STEEL (REBAR) REQUIREMENTS:
—MINIMUM GRADE 40 STEEL
—REBAR MAY BE BENT IN SHOP OR FIELD PROVIDED:
—THE REBAR IS BENT COLD
—THE DIAMETER OF THE BEND MEASURED ON THE INSIDE DOES NOT EXCEED
6—BAR DIAMETERS: AND
—REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT
EXCEPT IN CASES WHERE DOWELS NEED TO BE BENT TO ALIGN WITH A VERTICAL
CELL. THESE REBAR MAY BE BENT NOT TO EXCEED TO SLOPE OF 1"
HORIZONTALLY TO 6" VERTICALLY.
—COVER:
—3" COVER MINIMUM WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY
IN CONTACT WITH SOIL OR WEATHER, AND 11" ELSEWHERE. REBAR EMBEDDED IN
GROUTED CELLS SHALL HAVE A MINIMUM CLEAR DISTANCE OF 4" FOR FINE
GROUT, AND I" FOR COARSE GROUT BETWEEN REBAR AND ANY FACE OF A CELL.
REBAR USED IN MASONRY WALLS SHALL HAVE A MASONRY COVER (INCLUDING
GROUT) OF NOT LESS THAN 2" FOR MASONRY UNITS WITH FACE EXPOSED TO
EARTH OR WEATHER, AND 14" FOR MASONRY UNITS NOT EXPOSED TO EARTH OR
i
i WEATHER.
i
GALVANIZATION:
—METAL ACCESSORIES FOR USE IN EXTERIOR WALL CONSTRUCTION AND NOT DIRECTLY
EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A 153,
i
CLASS B-2. METAL PLATE CONNECTORS, SCREWS, BOLTS, AND NAILS EXPOSED
DIRECTLY TO WEATHER SHALL BE STAINLESS STEEL OR HOT DIPPED GALVANIZED.
4%54" EXPANSION ANCHOR WITHIN 6"
OF EACH POST/TRUSS ALONG SIDES
AND EVERY OTHER END —WALL POST
2" MIN.—{ H- ABASE RAIL
GRADE
I I I� � I I I I I I I 1111 6,>
�12"—
MINIMUM SOIL BEARING
CAPACITY 500 PSF(TYP.)
L2,500 PSI 4" CONCRETE
SLAB WITH 10GA. W.W.F.
OR FIBER MESH
(2) #5 REBAR ® 6" O.C.
CONTINUOUS WITH MINIMUM
25" OVERLAP SPLICE
CONCRETE FOUNDATION/BASE RAIL
ANCHOR DETAIL
2 5" PLAN VIEW DOOR FRAMING
J" RECESS
4 DOOR WIDT" I
ELEVATION VIEW
DOOR FRAMING
" RECESS
.75"T L-4„ DOOR WIDT
OPTIONAL ROLL -UP DOOR
CONCRETE SPLASH -GUARD RECESS
1 I r• r 1 111, 6 to, � ,
0
ZOLL4 U P
DOOR
O
I
o
OI
O
o
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II-B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/- 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
10PSF
ROOF LIVE LOAD
20PSF OR 30011D P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
900 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
BY
1
2020FBC
2/26/21
MTB
DRAWN sY: MTB
DATE: 9/29/20
LOCATION:
7106 Banyon St., Ft. Pierce
SIZE: 30'L X 30'W X 10'H
m
\>,E .........e 9
L\CENSF
Q�.: • i
NO. 64608 : 2
i •: STATE OF i 411
S .. Q>
�1011111-\_- ````
Digitally signed
by Matthew
Baldwin
1
Date:2021.02.26
MIN. 2,500 PSI 4" CONCRETE SLAB WITH 10GA. W.W.F. (OR
FIBER MESH) AND 12"x12" REINFORCED FOOTER PERIMETER 12"x12" REINFORCED FOOTER 1 9:45:57-051001
-----------------------------------------------------------
z Matthew T. Baldwin P.E.
Q Florida License #64608
uj
pJ Sheet:
CA-1 OF 4
0'
O'
FRONT END WALL
O.0
ROLL -UP
DOOR
12
Q3
o'
i
D.C. MAX.
a
SWINGING
DOOR
E[1
O.C.
LEFT SIDE WALL
RIGHT SIDE WALL
-DREAR END WALL
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SHA AUTHENTICATION CODE MUST BE VERIFIED
ON ANY ELECTRONIC COPIES
GWOMANYMEW
CODE INFORMATION
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
900 SQ. FT.
REVISIONS
REV
DESCRIPTON
DATE
I BY
1
12020FBC
1 2/26/21
1 MTB
" ".. MTB
DATE: 9/29/20
LOCATION: 7106 Banyan St., Ft. Pierce
SIZE: 301 X 30'W X 1O'H
U)
W
0
Z
Q
ry
LL_
z
w
Matthew T. Baldwin P.E.
LLJ Florida License #64608
Sheet: CA-2 OF 4
FRONT END
SWINGING
DOOR
o o
LEFT SIDE WALL
RIGHT SIDE WALL
19
m
PRINTED COPIES OF THIS DOCUMENT ARE NOT
CONSIDERED SIGNED AND SEALED AND THE
SHA AUTHENTICATION CODE MUST BE VERIFIED
ON ANY ELECTRONIC COPIES
CODE VERSION
MANUFACTURER
r 1-1-
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
UTILITY, U
WIND SPEED
Vult-150mph
EXPOSURE
B
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
1OPSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
900 SQ. FT.
REVISIONS
REVI
DESCRIPTON
DATE
I BY
1
12020FBC
1 2/26/21
1 MTB
—".. MTB
DATE: 9/29/20
LOCATION: 7106 Banyan St., Ft. Pierce
SIZE: 30'L X 30'W X 1O'H
w
z
w
Matthew T. Baldwin P.E.
LLJ Florida License #64608
cn Sheet: CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH SECURED TO WALL POST WITH
(4)#12-14xj" SELF —DRILLING (4)#12-14xi" SELF —DRILLING
SCREWS SCREWS
�/ NIPPLE TO 2"x2"x2" 16 GA. ANGLE CLIP
V \ BASE RAIL NIPPLE >1i TO " SECURED WITH (4) #12-14x "
BASE RAI SELF —DRILLING SCREWS
11-
POST TO BASE RAIL
CONNECTION
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14x4"
SELF —DRILLING SCREWS
NON—STRUCTURAL HEADER OR
WINDOW RAIL TO POST DETAIL
I INTERIOR
#12-14xi" SELF —DRILLING
SCREWS ® 10" O.C. MAX.,
3" MAX. FROM CORNERS
HORIZONTALLY/ 4" MAX.
FROM CORNERS VERTICALL'
EXTERIOR
DOOR FRAME TO POST
CONNECTION
END POST TO BASE RAIL
CONNECTION
18
It
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi"
SELF —DRILLING SCREWS
SINGLE OR DOUBLETS
HEADER
INTERMEDIATE POST TO
HEADER/BASE RAIL/OR HEADER CONNECTION
WINDOW RAIL DETAIL DETAIL OPTION 1
2"x2"x2" 16 GA. ANGLE CLIP SECURED
WITH (4) #12-14xi" SELF —DRILLING
ARIES
MAX. SPACIN
F--3" MIN.
.Ell A STD. MAX. SPACING
RZT)VARIES
SIDE WALL ROLL —UP
DOOR/FRAME OUT
HEADER DETAIL
INSTALL PER MANUFACTURERS INSTRUCTIONS
#14x1" SELF —DRILLING
SCREWS ® 6" O.C. MAX.
& 6" MAX. FROM CORNERS
ROLL —UP DOOR TO
POST CONNECTION
26 GAUGE ROOF SHEATHING SECURED WITH
(1)#12-14xi" SELF —DRILLING SCREWS
'2-1-2-1' (6" O.C. (9" O.C. MAX.))
AR" 0AX
1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH
(2)#12-140" SELF —DRILLING
SCREWS TO EACH RAFTER.
ROOF PANEL CONNECTION
VERTICAL SHEATHING OPTION
TO
1 "x2j" 16 GA.
U—CHANNEL BRACE, MIN.
_�R&24" UP TO 7' POST, 0
r6.-48" OVER 7' POST. MIN.
45' TO MAX. 60' FROM
HORIZ. (EXCLUDE
END —WALLS). SECURED
WITH (4)#12-14xj"
SELF —DRILLING SCREWS.
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
(4)#12-14xj" SELF —DRILLING
SCREWS
BOX EAVE RAFTER TO
POST CONNECTION DETAIL
Design Pressures - 150 mph Basic Wind Speed
Zone
Roof
Wall
1
2n
2r
2e
3r
3e
4
5
9.6
9.6
9.6
9.6
13.8
13.8
13.8
16.6
-10.6
-33.9
-27.1
-10.6
-59.1
-49.7
-15.4
-20.9
N
TO 1
IPPLE
ASE
MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
12-14xj" SELF —DRILLING
EWS
SINGLE OR DOUBLETS
HEADER
HEADER CONNECTIO
OPTION 2
MINIMUM 6" TS NIPPLE.
NIPPLE SECURED TO WALL
POST WITH (4)#12-14xi"
SELF —DRILLING SCREWS
POST TO TRUSS
CONNECTION
NIPPLE
TRUSSED RAFTER
CONNECTION DETAIL
DETAIL
APPROVED PRODUCTS
APPROVAL NO.
ROOF SHEATHING
Carports Anywhere
FL27402.1 — R 1
Hampton Rib Roof Panel
WALL SHEATHING
Carports Anywhere
FL27403.1
Hampton Rib Wall Panel
SWINGING DOOR
ELIXER DOOR AND METAL COMPANY
FL17996.5
407 STEEL DOOR
ROLL —UP DOOR
JANUS INTERNATIONAL CORPORATION
FL21450.3
SERIES 3100
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES
CODE VERSION
FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER
CARPORTS ANYWHERE
BUILDING TYPE
UTILITY STRUCTURE
CONSTRUCTION TYPE
II—B
RISK CATEGORY
I
FIRE PROTECTION
NONE
FIRE SUPPRESSION SYSTEM
NONE
OCCUPANCY
JUTILITY, U
WIND SPEED
Vult-150moh
ENCLOSURE
ENCLOSED
INTERNAL PRESSURE COEFF.
+/— 0.18
IMPORTANCE FACTOR
1.0
ROOF DEAD LOAD
1OPSF
ROOF LIVE LOAD
20PSF OR 3001b P.L.
FLOOR DEAD LOAD
10PSF
FLOOR LIVE LOAD
50PSF
"R"RATING OF WALLS, FLOOR, ROOF
N/A
MODULES PER BUILDING
1
HURRICANE PROTECTION USAGE
NO
HURRICANE SHELTER USAGE
NO
SQUARE FOOTAGE
900 SQ. FT.
REVISIONS
2020FBC
uw+wN er: MTB
DATE: 9/29/20
LOCATION: 7106 Banyan St., Ft. Pierce
SIZE: 30'L X 30'W X 10'H
cn
J
Q Matthew T. Baldwin P.E.
Florida License #64608
0 Sheet:
CA-4 OF 4