Loading...
HomeMy WebLinkAboutFPR MRO Hanger T&B ReportACCURATE BALANCING & COMMISSIONING, INC 1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 NEBB Certification #3429 Robert@tabfirm.com Expires 3/31/2022 CERTIFIED TEST; ADJUST; BALANCE REPORT Project: Treasure Coast International Airport 3191 Jet Center Terrace Fort Pierce, FL 34982 Contractor: Climax Mechanical Corp 661 W Rambling Dr Wellington, Florida 33414 Office 561.328.7365 Engineer: Avcon Engineers & Planners 5555 E Michigan St, Suite 200 Orlando, Fl 32822 Phone: 407-599-1122 Project 2017.259.01 drawings dated December 2018 Technicians: Robert Shorr & Zachary Shorr Test Dates: 2/2/21 thru 2/17/21 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST-ADJUST-BALANCE REPORT PROJECT SUMMARY. DUCT SMOKE DETECTOR TESTING AND CERTIFICATION VERIFIES THE DIFFERENTIAL PRESSURE ACROSS THE DETECTOR PICK UP TUBES ONLY AND DOES NOT TEST ANY ELECTRICAL OR DETECTOR OPERATION. Firm Certification Number: 3429 Firm Name: Accurate Balancing & Commissioning Certification: Testing, Adjusting and Balancing of Environmental Systems Certified Professional Name: ROBERT D. SHORR Expiration Date: 3/31/22 ACCURATE BALANCING & COMMISSIONING, INC 1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 NEBB Certification #3429 Robert@tabfirm.com Expires 3/31/2022 Equipment Calibration Schedule Definitions FPM – feet per minute CFM – cubic feet per minute RPM – Revolutions per minute DP – Differential Pressure RH – Relative Humidity S/A – Supply Air R/A – Return Air E/A – Exhaust Air O/A – Outside Air FL – Full Load HP – Horsepower SP – Static Pressure EDH – Electric Duct Heater PSI – Pounds per square inch GPM – Gallons per minute VAV – Variable Air Volume Terminal Box AHU – Air Handling Unit N/A – No Design Value on Drawings “ wc – Inches Water Column CHW – Chilled Water TBD – To Be Determined ft – Feet Head Instrument Serial # Model Application Dates of use Calibration Date Evergreen Hydronic Manometer 1900151 S-DP-250 Hydronic Pressure Not Used 10/12/20 AEMC Electrical Meter 48129SHCT 503 Voltage, Amperage 2/2/21 thru 2/17/21 12/15/20 Evergreen DP Meter with 8” & 15” Flow Hoods 2000321 S-PVF-1 FPM, CFM, DP 2/2/21 thru 2/17/21 7/16/20 Evergreen Temp Probe 2000120 PR-T-1 Temperature Not Used 9/10/20 Evergreen Temp Meter 14001141 RM-T-1 Temperature Not Used 9/11/20 Evergreen Temp/RH Meter 2000297 S-H-3-5 Temperature & Humidity Not Used 9/11/20 ACCURATE BALANCING & COMMISSIONING, INC 1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr Phone 561-351-0245 NEBB Certification #3429 Robert@tabfirm.com Expires 3/31/2022 Project Summary Test and balance air flows for new MRO hanger with office/shop spaces, restrooms, locker rooms and pump building. Deficiencies No deficiencies noted. Table of Contents Description Page Number AHU, supply and return grill Report 1 Duct Smoke Detector DP Report 2 Electric Heater Report 3 Exhaust Fan Reports 4-7 Air Handling UnitPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: AHU-01 AREA: Office Unit Data Unit Manufacturer Trane Unit Model Number TWE09044BAA Unit Serial Number 20091567BA Test Data R/A Damper Position 100 % O/A Damper Position 100 % Outside Air Duct Size 8x10 in AHU-01/Supply Fan Motor Volts T1-T2 478 Volts Motor Volts T2-T3 480 Volts Motor Volts T1-T3 478 Volts Motor Amps T1 2.0 Amps Motor Amps T2 1.9 Amps Motor Amps T3 1.8 Amps Compressor Test Data # of Compressors 2 Compressor Full Load Amps 6.1 Motor Data AHU-01/Supply Fan Motor HP 2 HP Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 2.9 Amps Sheave Data AHU-01/Supply Fan Fan Sheave MFG Direct Drive Air Test Data S/A Scheduled Design 3200 CFM Total S/A Outlet Design 3200 CFM Total S/A Outlet Actual 3163 CFM R/A Scheduled Design 2950 CFM Total R/A Inlet Design 2950 CFM Total R/A Inlet Actual 2954 CFM Outside Air Design Max 250 CFM Outside Air Actual Max 227 CFM Pitot Traverse Total 2990 CFM Pitot Duct Size 22x24 RA Condenser Data Condensing Unit Model #TWA09044DAB Condensing Unit Serial #20081402YA Refrigerant Type R410a # of CU Fans 1 System/Unit Area Served Design Reading Prelim Reading % Prelim Deviation Final Reading % Final Deviation Outlet-01 110 Office 2755 2681 97 2720 99 Outlet-02 111 Womens RR 35 51 146 34 97 Outlet-03 112 Mens RR 35 33 94 37 106 Outlet-04 114 Electric Room 375 364 97 372 99 Totals:3200 3129 98 3163 99 AHU-01 Supply Outlet Summary System/Unit Area Served Design Reading Prelim Reading % Prelim Deviation Final Reading % Final Deviation Inlet-01 110 Office 2575 2596 101 2562 99 Inlet-02 114 Electric Room 375 358 95 358 95 Totals:2950 2954 100 2920 99 AHU-01 Return Inlet Summary Accurate Balancing and Commissioning Page 1 of 7 Duct Detector DP ReportPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: Duct Smoke Detector-01 AREA: AHU-1 Unit Data Manufacturer Potter Model PAC-100 Max DP 1.200 in wc Min DP 0.010 in wc Actual DP 0.011 in wc Detector #1-07 Duct Type Supply SYSTEM/UNIT: Duct Smoke Detector-02 AREA: AHU-1 Unit Data Manufacturer Potter Model PAC-100 Max DP 1.200 in wc Min DP 0.010 in wc Actual DP 0.070 in wc Detector #1-08 Duct Type Return Accurate Balancing and Commissioning Page 2 of 7 Electric CoilPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: Electric Coil-01 AREA: AHU-1 Unit Data Coil Location Supply Duct Coil Type Electric Resistance Coil Manufacturer Trane Coil Model Number BAYHTR415AA EDH Rated KW 15.0 KW EDH Stages 1 Test Data EDH Design Volts 480 Volts EDH Design Amps 18.0 Amps All Stages On Act. Volts 1 478 Volts All Stages On Act. Volts 2 481 Volts All Stages On Act. Volts 3 479 Volts All Stages On Act. Amps 1 20.6 Amps All Stages On Act. Amps 2 19.7 Amps All Stages On Act. Amps 3 20.3 Amps Entering Air Temp 69.7 deg F Leaving Air Temp 95.4 deg F Accurate Balancing and Commissioning Page 3 of 7 Fan UnitPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: EF-01 AREA: Lockers Unit Data Fan Manufacturer Acme Fan Model Number XD120EC Fan Serial Number 20A1810-1 Test Data Total Fan Design Airflow 650 CFM Total Actual Airflow 686 CFM Total Grill Design Airflow 675 CFM Motor Data Motor HP 1/2 HP Motor RPM 1725 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 6.8 Amps System/Unit Area Served Design Reading Prelim Reading % Prelim Deviation Final Reading % Final Deviation Inlet-01 103 Womens Locker 100 45 45 101 101 Inlet-02 103 Womens Locker 75 121 161 79 105 Inlet-03 104 Womens Shower 150 118 79 164 109 Inlet-04 105 Mens Lockers 150 128 85 142 95 Inlet-05 105 Mens Lockers 75 68 91 76 101 Inlet-06 106 Mens Shower 100 121 121 98 98 Inlet-07 107 Janitor 25 72 288 26 104 Totals:675 673 100 686 102 EF-01 Exhaust Inlet Summary Accurate Balancing and Commissioning Page 4 of 7 Fan UnitPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: EF-02 AREA: Restroom Unit Data Fan Manufacturer Acme Fan Model Number XD100EC Fan Serial Number 20A1810-3 Test Data Total Fan Design Airflow 125 CFM Total Actual Airflow 136 CFM Total Grill Design Airflow 125 CFM Motor Data Motor Manufacturer Acme Motor HP 1/4 HP Motor RPM 1800 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.6 Amps System/Unit Area Served Design Reading Prelim Reading % Prelim Deviation Final Reading % Final Deviation Inlet-01 111 Womens RR 50 119 238 55 110 Inlet-02 112 Mens RR 50 121 242 54 108 Inlet-03 113 Janitor 25 84 336 27 108 Totals:125 324 259 136 109 EF-02 Exhaust Inlet Summary SYSTEM/UNIT: EF-03 AREA: Hangar Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCWP-48BTC-9 Test Data Total Fan Design Airflow 21500 CFM Total Actual Airflow 20640 CFM Volts 486 Volts Motor Volts T2-T3 485 Volts Motor Volts T1-T3 483 Volts Motor Amps T1 3.9 Amps Motor Amps T2 4 Amps Motor Amps T3 3.9 Amps Motor Data Motor Manufacturer Teco Motor Frame 184T Motor HP 5 HP Motor RPM 1745 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.1 Amps Accurate Balancing and Commissioning Page 5 of 7 Fan UnitPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: EF-04 AREA: Hangar Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCWP-48BTC-9 Test Data Total Fan Design Airflow 21500 CFM Total Actual Airflow 21780 CFM Volts 477 Volts Motor Volts T2-T3 476 Volts Motor Volts T1-T3 478 Volts Motor Amps T1 4.1 Amps Motor Amps T2 3.7 Amps Motor Amps T3 4.1 Amps Motor Data Motor Manufacturer Teco Motor Frame 184T Motor HP 5 HP Motor RPM 1745 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.1 Amps SYSTEM/UNIT: EF-05 AREA: Hangar Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCWP-48BTC-9 Test Data Total Fan Design Airflow 21500 CFM Total Actual Airflow 19950 CFM Volts 477 Volts Motor Volts T2-T3 476 Volts Motor Volts T1-T3 479 Volts Motor Amps T1 4.1 Amps Motor Amps T2 3.8 Amps Motor Amps T3 4.2 Amps Motor Data Motor Manufacturer Teco Motor Frame 184T Motor HP 5 HP Motor RPM 1745 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.1 Amps SYSTEM/UNIT: EF-06 AREA: Hangar Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCWP-48BTC-9 Test Data Total Fan Design Airflow 21500 CFM Total Actual Airflow 20860 CFM Volts 485 Volts Motor Volts T2-T3 487 Volts Motor Volts T1-T3 484 Volts Motor Amps T1 3.8 Amps Motor Amps T2 4.2 Amps Motor Amps T3 4 Amps Motor Data Motor Manufacturer Teco Motor Frame 184T Motor HP 5 HP Motor RPM 1745 RPM Motor Rated Volts 460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.1 Amps Accurate Balancing and Commissioning Page 6 of 7 Fan UnitPROJECT: LOCATION: Treasure Coast Airport MRO Hangar Ft Pierce, FL 2017.259.01PROJECT #: DATE: CONTACT: 2/22/2021 Robert Shorr SYSTEM/UNIT: EF-07 AREA: FPER Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCPE-142AE Fan Serial Number A20-0300724 Test Data Total Fan Design Airflow 1450 CFM Total Actual Airflow 1558 CFM Motor Data Motor Manufacturer McMillan Motor HP 1/2 HP Motor RPM 1725 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 6.8 Amps Motor Service Factor 1.2 SYSTEM/UNIT: EF-08 AREA: Pump Bldg Unit Data Fan Manufacturer Twin City Fan Fan Model Number TCWP-48BTC-9 Fan Serial Number 20-763749-2-1 Test Data Total Fan Design Airflow 17200 CFM Total Actual Airflow 18120 CFM Volts 208 Volts Motor Volts T2-T3 210 Volts Motor Volts T1-T3 209 Volts Motor Amps T1 5.4 Amps Motor Amps T2 5.5 Amps Motor Amps T3 5.6 Amps Motor Data Motor Manufacturer Teco Motor Frame 184T Motor HP 5 HP Motor RPM 1745 RPM Motor Rated Volts 208 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 12.2 Amps Motor Service Factor 1 Sheave Data Motor Sheave Model 1VP50 Fan Sheave Model AX104 Number of Belts 1 Belt Model #A42 Accurate Balancing and Commissioning Page 7 of 7