HomeMy WebLinkAboutFPR MRO Hanger T&B ReportACCURATE BALANCING & COMMISSIONING, INC
1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 NEBB Certification #3429
Robert@tabfirm.com Expires 3/31/2022
CERTIFIED TEST; ADJUST; BALANCE REPORT
Project: Treasure Coast International Airport
3191 Jet Center Terrace
Fort Pierce, FL 34982
Contractor: Climax Mechanical Corp
661 W Rambling Dr
Wellington, Florida 33414
Office 561.328.7365
Engineer: Avcon Engineers & Planners
5555 E Michigan St, Suite 200
Orlando, Fl 32822
Phone: 407-599-1122
Project 2017.259.01 drawings dated December 2018
Technicians: Robert Shorr & Zachary Shorr
Test Dates: 2/2/21 thru 2/17/21
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB
PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS.
ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE
TEST-ADJUST-BALANCE REPORT PROJECT SUMMARY. DUCT SMOKE DETECTOR TESTING AND
CERTIFICATION VERIFIES THE DIFFERENTIAL PRESSURE ACROSS THE DETECTOR PICK UP TUBES ONLY
AND DOES NOT TEST ANY ELECTRICAL OR DETECTOR OPERATION.
Firm Certification Number: 3429
Firm Name: Accurate Balancing & Commissioning
Certification: Testing, Adjusting and Balancing of Environmental Systems
Certified Professional Name: ROBERT D. SHORR
Expiration Date: 3/31/22
ACCURATE BALANCING & COMMISSIONING, INC
1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 NEBB Certification #3429
Robert@tabfirm.com Expires 3/31/2022
Equipment Calibration Schedule
Definitions
FPM – feet per minute CFM – cubic feet per minute
RPM – Revolutions per minute DP – Differential Pressure
RH – Relative Humidity S/A – Supply Air
R/A – Return Air E/A – Exhaust Air
O/A – Outside Air FL – Full Load
HP – Horsepower SP – Static Pressure
EDH – Electric Duct Heater PSI – Pounds per square inch
GPM – Gallons per minute VAV – Variable Air Volume Terminal Box
AHU – Air Handling Unit N/A – No Design Value on Drawings
“ wc – Inches Water Column CHW – Chilled Water
TBD – To Be Determined ft – Feet Head
Instrument Serial #
Model Application
Dates of use Calibration
Date
Evergreen Hydronic
Manometer 1900151 S-DP-250 Hydronic Pressure
Not Used 10/12/20
AEMC Electrical Meter 48129SHCT 503 Voltage, Amperage
2/2/21 thru
2/17/21
12/15/20
Evergreen DP Meter with
8” & 15” Flow Hoods 2000321 S-PVF-1 FPM, CFM, DP 2/2/21 thru
2/17/21 7/16/20
Evergreen Temp Probe 2000120 PR-T-1 Temperature Not Used 9/10/20
Evergreen Temp Meter 14001141 RM-T-1 Temperature Not Used 9/11/20
Evergreen Temp/RH
Meter 2000297 S-H-3-5 Temperature & Humidity
Not Used 9/11/20
ACCURATE BALANCING & COMMISSIONING, INC
1742 E Rd, Loxahatchee, FL 33470 TAB/Cx Supervisor Robert Shorr
Phone 561-351-0245 NEBB Certification #3429
Robert@tabfirm.com Expires 3/31/2022
Project Summary
Test and balance air flows for new MRO hanger with office/shop spaces, restrooms, locker
rooms and pump building.
Deficiencies
No deficiencies noted.
Table of Contents
Description Page Number
AHU, supply and return grill Report 1
Duct Smoke Detector DP Report 2
Electric Heater Report 3
Exhaust Fan Reports 4-7
Air Handling UnitPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: AHU-01
AREA: Office
Unit Data
Unit Manufacturer Trane
Unit Model Number TWE09044BAA
Unit Serial Number 20091567BA
Test Data
R/A Damper Position 100 %
O/A Damper Position 100 %
Outside Air Duct Size 8x10 in
AHU-01/Supply Fan
Motor Volts T1-T2 478 Volts
Motor Volts T2-T3 480 Volts
Motor Volts T1-T3 478 Volts
Motor Amps T1 2.0 Amps
Motor Amps T2 1.9 Amps
Motor Amps T3 1.8 Amps
Compressor Test Data
# of Compressors 2
Compressor Full Load Amps 6.1
Motor Data
AHU-01/Supply Fan
Motor HP 2 HP
Motor Rated Volts 460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 2.9 Amps
Sheave Data
AHU-01/Supply Fan
Fan Sheave MFG Direct Drive
Air Test Data
S/A Scheduled Design 3200 CFM
Total S/A Outlet Design 3200 CFM
Total S/A Outlet Actual 3163 CFM
R/A Scheduled Design 2950 CFM
Total R/A Inlet Design 2950 CFM
Total R/A Inlet Actual 2954 CFM
Outside Air Design Max 250 CFM
Outside Air Actual Max 227 CFM
Pitot Traverse Total 2990 CFM
Pitot Duct Size 22x24 RA
Condenser Data
Condensing Unit Model #TWA09044DAB
Condensing Unit Serial #20081402YA
Refrigerant Type R410a
# of CU Fans 1
System/Unit Area Served Design
Reading
Prelim
Reading
% Prelim
Deviation
Final Reading % Final
Deviation
Outlet-01 110 Office 2755 2681 97 2720 99
Outlet-02 111 Womens
RR
35 51 146 34 97
Outlet-03 112 Mens RR 35 33 94 37 106
Outlet-04 114 Electric
Room
375 364 97 372 99
Totals:3200 3129 98 3163 99
AHU-01 Supply Outlet Summary
System/Unit Area Served Design
Reading
Prelim
Reading
% Prelim
Deviation
Final Reading % Final
Deviation
Inlet-01 110 Office 2575 2596 101 2562 99
Inlet-02 114 Electric
Room
375 358 95 358 95
Totals:2950 2954 100 2920 99
AHU-01 Return Inlet Summary
Accurate Balancing and Commissioning Page 1 of 7
Duct Detector DP ReportPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: Duct Smoke Detector-01
AREA: AHU-1
Unit Data
Manufacturer Potter
Model PAC-100
Max DP 1.200 in wc
Min DP 0.010 in wc
Actual DP 0.011 in wc
Detector #1-07
Duct Type Supply
SYSTEM/UNIT: Duct Smoke Detector-02
AREA: AHU-1
Unit Data
Manufacturer Potter
Model PAC-100
Max DP 1.200 in wc
Min DP 0.010 in wc
Actual DP 0.070 in wc
Detector #1-08
Duct Type Return
Accurate Balancing and Commissioning Page 2 of 7
Electric CoilPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: Electric Coil-01
AREA: AHU-1
Unit Data
Coil Location Supply Duct
Coil Type Electric Resistance
Coil Manufacturer Trane
Coil Model Number BAYHTR415AA
EDH Rated KW 15.0 KW
EDH Stages 1
Test Data
EDH Design Volts 480 Volts
EDH Design Amps 18.0 Amps
All Stages On Act. Volts 1 478 Volts
All Stages On Act. Volts 2 481 Volts
All Stages On Act. Volts 3 479 Volts
All Stages On Act. Amps 1 20.6 Amps
All Stages On Act. Amps 2 19.7 Amps
All Stages On Act. Amps 3 20.3 Amps
Entering Air Temp 69.7 deg F
Leaving Air Temp 95.4 deg F
Accurate Balancing and Commissioning Page 3 of 7
Fan UnitPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: EF-01
AREA: Lockers
Unit Data
Fan Manufacturer Acme
Fan Model Number XD120EC
Fan Serial Number 20A1810-1
Test Data
Total Fan Design Airflow 650 CFM
Total Actual Airflow 686 CFM
Total Grill Design Airflow 675 CFM
Motor Data
Motor HP 1/2 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 6.8 Amps
System/Unit Area Served Design
Reading
Prelim
Reading
% Prelim
Deviation
Final Reading % Final
Deviation
Inlet-01 103 Womens
Locker
100 45 45 101 101
Inlet-02 103 Womens
Locker
75 121 161 79 105
Inlet-03 104 Womens
Shower
150 118 79 164 109
Inlet-04 105 Mens
Lockers
150 128 85 142 95
Inlet-05 105 Mens
Lockers
75 68 91 76 101
Inlet-06 106 Mens
Shower
100 121 121 98 98
Inlet-07 107 Janitor 25 72 288 26 104
Totals:675 673 100 686 102
EF-01 Exhaust Inlet Summary
Accurate Balancing and Commissioning Page 4 of 7
Fan UnitPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: EF-02
AREA: Restroom
Unit Data
Fan Manufacturer Acme
Fan Model Number XD100EC
Fan Serial Number 20A1810-3
Test Data
Total Fan Design Airflow 125 CFM
Total Actual Airflow 136 CFM
Total Grill Design Airflow 125 CFM
Motor Data
Motor Manufacturer Acme
Motor HP 1/4 HP
Motor RPM 1800 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 3.6 Amps
System/Unit Area Served Design
Reading
Prelim
Reading
% Prelim
Deviation
Final Reading % Final
Deviation
Inlet-01 111 Womens
RR
50 119 238 55 110
Inlet-02 112 Mens RR 50 121 242 54 108
Inlet-03 113 Janitor 25 84 336 27 108
Totals:125 324 259 136 109
EF-02 Exhaust Inlet Summary
SYSTEM/UNIT: EF-03
AREA: Hangar
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCWP-48BTC-9
Test Data
Total Fan Design Airflow 21500 CFM
Total Actual Airflow 20640 CFM
Volts 486 Volts
Motor Volts T2-T3 485 Volts
Motor Volts T1-T3 483 Volts
Motor Amps T1 3.9 Amps
Motor Amps T2 4 Amps
Motor Amps T3 3.9 Amps
Motor Data
Motor Manufacturer Teco
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1745 RPM
Motor Rated Volts 460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 6.1 Amps
Accurate Balancing and Commissioning Page 5 of 7
Fan UnitPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: EF-04
AREA: Hangar
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCWP-48BTC-9
Test Data
Total Fan Design Airflow 21500 CFM
Total Actual Airflow 21780 CFM
Volts 477 Volts
Motor Volts T2-T3 476 Volts
Motor Volts T1-T3 478 Volts
Motor Amps T1 4.1 Amps
Motor Amps T2 3.7 Amps
Motor Amps T3 4.1 Amps
Motor Data
Motor Manufacturer Teco
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1745 RPM
Motor Rated Volts 460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 6.1 Amps
SYSTEM/UNIT: EF-05
AREA: Hangar
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCWP-48BTC-9
Test Data
Total Fan Design Airflow 21500 CFM
Total Actual Airflow 19950 CFM
Volts 477 Volts
Motor Volts T2-T3 476 Volts
Motor Volts T1-T3 479 Volts
Motor Amps T1 4.1 Amps
Motor Amps T2 3.8 Amps
Motor Amps T3 4.2 Amps
Motor Data
Motor Manufacturer Teco
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1745 RPM
Motor Rated Volts 460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 6.1 Amps
SYSTEM/UNIT: EF-06
AREA: Hangar
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCWP-48BTC-9
Test Data
Total Fan Design Airflow 21500 CFM
Total Actual Airflow 20860 CFM
Volts 485 Volts
Motor Volts T2-T3 487 Volts
Motor Volts T1-T3 484 Volts
Motor Amps T1 3.8 Amps
Motor Amps T2 4.2 Amps
Motor Amps T3 4 Amps
Motor Data
Motor Manufacturer Teco
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1745 RPM
Motor Rated Volts 460 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 6.1 Amps
Accurate Balancing and Commissioning Page 6 of 7
Fan UnitPROJECT:
LOCATION:
Treasure Coast Airport MRO Hangar
Ft Pierce, FL
2017.259.01PROJECT #:
DATE:
CONTACT:
2/22/2021
Robert Shorr
SYSTEM/UNIT: EF-07
AREA: FPER
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCPE-142AE
Fan Serial Number A20-0300724
Test Data
Total Fan Design Airflow 1450 CFM
Total Actual Airflow 1558 CFM
Motor Data
Motor Manufacturer McMillan
Motor HP 1/2 HP
Motor RPM 1725 RPM
Motor Rated Volts 115 Volts
Motor Phase 1
Motor Hertz 60 Hz
Motor FL Amps 6.8 Amps
Motor Service Factor 1.2
SYSTEM/UNIT: EF-08
AREA: Pump Bldg
Unit Data
Fan Manufacturer Twin City Fan
Fan Model Number TCWP-48BTC-9
Fan Serial Number 20-763749-2-1
Test Data
Total Fan Design Airflow 17200 CFM
Total Actual Airflow 18120 CFM
Volts 208 Volts
Motor Volts T2-T3 210 Volts
Motor Volts T1-T3 209 Volts
Motor Amps T1 5.4 Amps
Motor Amps T2 5.5 Amps
Motor Amps T3 5.6 Amps
Motor Data
Motor Manufacturer Teco
Motor Frame 184T
Motor HP 5 HP
Motor RPM 1745 RPM
Motor Rated Volts 208 Volts
Motor Phase 3
Motor Hertz 60 Hz
Motor FL Amps 12.2 Amps
Motor Service Factor 1
Sheave Data
Motor Sheave Model 1VP50
Fan Sheave Model AX104
Number of Belts 1
Belt Model #A42
Accurate Balancing and Commissioning Page 7 of 7