Loading...
HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 124 Block 5 Waterston... wrightsoft, Date: Entire House By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Project• • For: ADAMS HOMES 5358 San Benedetto Place, Fort Pierce, FL 34951 Cooling Equipment Design Conditions Outdoor design DB: 90.4°F Sensible gain: 24849 Btuh Entering coil DB: 76.4°F Outdoor design WB: 77.4 OF Latent gain: 4767 Btuh Entering coil WB: 63.2°F Indoor design DB: 75.0 OF Total gain: 29616 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 27841 Btuh 112%of load Latent capacity: 5462 Btuh 115% of load Total capacity: 33303 Btuh 112%of load SHR: 84% Heating Equipment Design Conditions design DB: 41.0 OF Heat loss: 28493 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31708 Btuh 111 % of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 91 % of load Temp. rise: 20 °F Meets all requirements ofACCA Manual S. Entering coil DB: 69.5OF Capacity balance: 36 OF Economic balance: -99 OF ,` * wrightsoft" 2021-Jan•1414:52:01 �M,•N ,ti. ���m Rig ht-Sdte®Universal 202121.0.02RSU23828 Pagel terstore1820AGL\Lot124BIk5Waterstone1820AGL.rLp Calc=MJB Front Door faces: NW :--wrightsoft® Component Constructions Job: . Lot 124 Block 5 Waterston... Entire House By. DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM •�ct intormation. For: ADAMS HOMES 5358 San Benedetto Place, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD. (OF) 29 15 Latitude: 28 ON Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft= Bto1vftz1F ftzcFratuh Bwhift= Bwh Btuh/ft2 Btoh Walls 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh 12C-Osw. Fan wall, stucco ext, 3/8" wood shth, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud Partitions 12C-Osw: Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'k4" wood frm, 16" o.c. stud ne 20 0.049 19.0 1.42 28 2.59 52 se 20 0.049 19.0 1.42 28 2.59 52 sw 20 0.049 19.0 1.42 28 2.59 52 nw 20 0.049 19.0 1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 ne 534 0.201 4.1 5.83 3113 4.06 2168 se 317 0.201 4.1 5.83 1846 4.06 1286 sw 611 0.201 4.1 5.83 3561 4.06 2481 nw 102 0.201 4.1 5.83 595 4.06 414 all 1564 0.201 4.1 5.83 9115 4.06 6349 nw 24 0.091 13.0 2.64 64 2.21 54 270 0.091 13.0 2.64 713 1.31 354 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 ft window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" ne thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang se (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht sw all 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" se thk; NFRC rated (SHGC=0.70); 11.83 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" se thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.83 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht 7 0.330 0 9.57 66 17.7 123 49 0.330 0 9.57 469 17.7 868 33 0.330 0 9.57 313 15.6 509 49 0.330 0 9.57 469 15.6 763 131 0.330 0 9.57 1251 16.4 2140 18 0.550 0 16.0 285 16.2 289 33 0.330 0 9.57 313 8.52 279 - wrightsoft® 2021-Jarr1414:52,01 �."ot• o. ti.• •«.•.��••. Right-Stite®Un1versa1202121.0.02RSU23828ACCA Pagel terstore1820AGL1Lot124Blk5Waterstone1820AGL.nQ CaIc=MJB Front Door faces: NW 2A-2ov: 2 glazing, cir low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" nw 7 0.330 0 9.57 67 26.3 184 ' thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft ' sep.); 6.67 ft head ht 2B-2fv: 2 glazing, cir low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" nw 14 0.330 0 9.57 130 26.3 358 thk; NFRC rated (SHGC=0.31); 9 ft overhang (6.8 ft window ht, 2 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, cir innr, 1/4" gap, 1/8" nw 33 0.330 0 9.57 313 16.6 543 thk; NFRC rated (SHGC=0.21); 50%drapes, medium; 1 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type nw 20 0.600 6.3 17.4 355 17.6 359 Ceilings 1613-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1 /2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 0 28.7 6080 0 0 wrightscvft- 2021 -Jan- 14 14:52:01 Right-Sute®UNversal2021 21.0.02 RSU23828 Page 2 terstone1820AGULot124BIk5Waterstone1820AGL.nQ Calc=W8 Front Door faces: NW +-wrightsoft® Project Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Proiect Information Job: Lot 124 Block 5 Waterston... Date: By- DCS For: ADAMS HOMES 5358 San Benedetto Place, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2116/16 S. Finch L. S. 1-13-21 VWK Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 24273 Btuh Structure 19072 Btuh Ducts 4220 Btuh Ducts 5777 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 28493 Btuh Use manufacturer's data y Rate/swin multipplier 1.00 Infiltration Equipmen1sensible load 24849 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh Area Heatingg Cooling (none) (ft2) 1820 1820 Equipment latent load 4767 Btuh Volume (ft3) 18350 18350 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 29616 Btuh Equiv. AVF (cfm) 116 61 Req. total capacity at 0.75 SHR 2.8 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC537AP03 Cond 25HBC537AP03 AHRI ref 204837926 Coil FX4DNF037L00 AHRI ref 204837926 Efficiency 8.5 HSPF Efficiency 12.5 EER,16 SEER Heating Input Sensible cooling 26250 Btuh Heating output 34600 Btuh @ 470F Latent cooling 8750 Btuh Temperature rise 27 OF Total cooling 35000 Btuh Actual airflow 1167 cfm Actual airflow 1167 cfm Air flow factor 0.041 cfm/Btuh Air flow factor 0.047 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 36 OF Backup: Input = 8 kW, Output = 25800 Btuh,100 AFUE Calculations approved byACCAto meet all requirements of Manual J 8th Ed ` wriglttsoft- 2021-Jarr1414:52:01 Right-SLAe®Uriversal 2021 21.0.02 RSU23828 Page 1 '�...terstone1820AGL\Lot124BIk5Waterstone1820AGL.nQ CaIc=MJB Front Door faces: NW -�' gvrightsoft® Right-M Worksheet Job: Lot 124 Block 5 Waterstone 1... Entire House Date: By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CO DISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W WW.DELAIR.COM 1 Room name Entire House BDRM2 2 Exposed wall 212.0 ft 36.0 ft 3 Room height 10.0 ft d 10.0 It heattcool 4 5 Room dimensions Room area 1835.0 ftz 13.0 x 13.0 ft 169.0 ftz Ty Construction number U-value (Btuh/ftz Or HTM (Btuh/ftz) Area 011) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W V�1 <16B 19ad_..._ _ Bik wall, stucco ext 2A-2ov 0.049 0.201 0.330 .. ne_.; ne ne 1.42s 5.83 9.57 2.59 4.06 17.70 ., ,_�, 20 590 7 s _20 534 0 _.. ,< 28 3113 66 2168 123 100 0 _.,_:0 100 0 _.0 583 0 406 0 II�G 2A-2ov _ Blk wall, stucco ext 1OC-v 2A-2ov 0.330 0.201 0.550 0.330 ne se se se 9.57 5.83 15.95 9.57 17.70 4.06 16.20 15.57 49 400 18 33 k� 0 317 18 8 _�. 469 1846 285 313 r 868 1286 289 509 0 130 0 16 0 114 0 4 0 663 0 156 _ 0 461 0 254 _ ,1N.� �.`..1.68.19ad�:� �1 _ -G W . W 2A-2ov - �..ti_.._.� Blk wall, stucco ext 2A-2ov 12C Osw _ 2A=2ov 2B=2fv _11J0_ _ _: _._ _._._ 16B 19ad Blk wall stucco ext ^ «^ 2A=2ov_ " 12C-Osw 0.330 00.49 0.201 0.330 0.091 0 330 0:330 .-_,_ _._0.600 0.049 0201 0330 0.091 se. M sw,v sw sw nw nw nw _nw. nw nw ._nw_ _..4 _- _�_ _ 9.57 _� u1.42; 5.83 9.57 2 64 -. 9 57 9 57 _�u__17.40:.,.._ 1.42 5..83 ..,_.-9.57. 2.64 x �Q,93- , 28.68 8.52 _ 2:59 M 4.06 _ 15.57 2.2i 26 32 26 32 1.7.58 259 4D6 v�_16.61 1.31 �,169 0.00 33 �.. _._ _•�20 660 49 65 7 14 a.�__.__.20 20 , 135 __ 33 270 1835 1835 33 _._._.r,.>:_20 611 13 24 0 0 _. a20 : 20 �102 �_ ,. 0 270 _. _1835 212 r 313 ��,�.__.28 3561 _.X 469 64 67 130 _._, -',355 28 595 _.._ '313-,-` _. 713. , ._. 1703. .�_ 6080 279 .__52 2481 _ 763 ' 54 184 358 __-...-359 _ 52 414 _543 __ 354 _3100 0 0 ;� . rt-0 130 _ w� 0 0 : ` 0 Ij ___:0 _0 p 0 __. 0 w_,_ _169, 169 0 _.��.._.`._v0 130 0 0 0 _ ___.._ 0 0 0 -- 169 _ ; 36 0 --_ �u_._��. 0. 758 0 0 0 _. _...:_-0. 0 0 _, 157 1033 0 _ __:.�_�0 528 0 0 0 0 0 0 P C F. _ J,6f3_30ad _. __. 22A ipl .__ _ 0.032 M 0.989 �i..,_....__.__-..+.........�. ___...u...._...._.. _.. .__._.� _ .__.._ ,.....V.memrP ,.._.._., pn.: ems-_. _... ._R.�...._ M�..�. ... r._...._..... a_�_._. ..... __ .._�-.-__ _.�,...__ ..s..._,..__ X _ _..._._..,.._. .__.,_,...�.,r..-.__...=,w:.-.._......e:. 'e..__....., -..__. ... .._: -.t.__..._«._.._... F....:.:. ...«.. _._ _L�._.. _...�. _.....-.._+. _, -_.> _a_�....tP.,._..: ......+..�i..-....._.. .....«.=...-L.,.._..._...�....._._: ._..._-.__........... � _....�...-:'..cur... 6 c) AED excursion 149 25 Envelope loss/gain 20569 14487 3349 1 1961 12 a) Infiltration b) Room ventilation 3704 0 1035 0 691 0 193 0 13 Internal gains: Occupants @ 230 Appliances/other 5 1150 2400 0 0 0 Subtotal (lines 6 to 13) 24273 19072 4040 2154 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 1700 30% 0 0 0 24273 4220 0 0 0 19072 5777 170/. 30% 0 0 0 4040 702 0 0 0 2154 652 Total room load Air required (dm) 28493 1167 24849 1167 1 4742 194 2806 132 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rw wr➢ghtsoft- 2021-Jan-1414:52:01 �C" LA Right-Sute®Udversal2021 21.0.02 RSU23828 Page 1 terstone1820AGL1Lot124BIk5Waterstone1820AGL.nQ CaIc=MJB FrontDoor faces: NW -- wrightsoft9 Right-J® Worksheet Job: Lot 124 Block 5 Waterston 1... Date: Entire House Da DaDcs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 Room name BATH 2 BDRM3 2 Exposed wall 6.0 ft 13.0 it 3 Room height 10.0 ft heaUcool 10.0 It heaticoal 4 5 Room dimensions Room area 13.0 x 6.0 ft 78.0 ft2 13.0 x 13.0 ft 169.0 ft2 Ty Construction U-value Or HTM Area 012) Load Area (ft2) Load number (Btuh/ft2-Cq (Btuhflt2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk wall, stucco ext 2A-2ov 0.201 0.330 ne ne 5.83 9.57 4.06 17.70 0 0 0 0 0 0 0 0 0 0 0... 0 0 _ _Q 0 0 0 0 yyyJJJ 2A-2ov _ r Blkwall,slu000e)d 10C-v 2A-2ov 0.330 0.201 0.550 0.330 ne se se se 9.57 - 5.83 15.95 9.57 17.70 -- 0 0 0 0 0 0 0 0 0 0 0 0 0 _ 0 0 0 _ 0 _ --_ 0 0 0 _ 0 0 0 0 0 0_ _ a 0 0 0 _ 0 0 0 0 4.06 1620 15.57 _ 2A-2ov Blk wall, stucco e)d 2A-2ov 12G Osw 2A=2ov 26-2fv 0.330 0201 0.330 0 091 Ownw 0 330 se sw sw _ nw , nw „ 957 42, 5.83 9.57 2 64 9.57 9 57 8.52 � _2,59 4.06 _15.57 2 21 26 32 26:32 -0 , 0 60 y 0 0 0 0 ,. .0 0 _n� - �0 350 0 0 0 0 __ - � 0 244 0 0 0 0 _ .gip 130 16 0 0 0 _ ---0 114 4 0 0 0 F . 0, 663 156 0 0 0 _ 0 � Q 461 254 �m 0 0 0 60 0 0 0 W V)!' I--G P C.= _._ - 166-19ad Blk wall stucco ext 2A-2ov._ _._ _ 12C-Osw, ,1.66 30adY ; -_._.-0.600 0.049 0201 .a �0.330 0.091 _Q:032 __nw_ nw nw, _nw: ._ __.1.7.40, 142 - 5.83 - 9.57' 2.64 0.93- __ 1.7.58 259 7174.66 .- _16.6:1 , 1.31 -�. _1,69 _ _ L_0 0 . _ _ w0 0 ` �__ 78, .__-...__ _0 0 v_0 0 __. 78 _.._ __ 0 _0 _:._=,.0 _ 0 ___ _- 72 �. �_-_0 0 -- -- 0 0.-- 132 0, _.._ 0 0 .. _ 169 0 �--0 _169 0 _ _ �0 - _ . 15,7 0 76 _.�_ �0 286 F 22A tpl 0.989 _ _ 28.68 d , M0,.00 78 6 172 0 169 13 373 _ 0 6 c) AED excursion -21 67 Envelope loss/gain 594 354 1349 1068 12 a) Infiltration 115 32 249 70 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 AppliancesUher 0 0 Subtotal (lines 6 to 13) 709 386 1598 1138 14 Less external load Lesstransfer Redistribution Subtotal 0 0 0 709 0 0 0 386 0 0 0 1598 0 0 0 1138 15 Ductloads 17% 30% 123 117 179/6 30% 278 345 Total room load Air required (cfm) 134 833 503 24 1876 77 1483 70 Calculations approved bvACCA to meet all reauirements of Manual J 8th Ed. - wrYgHtsoft� 2021-Jarr141452:01 ACCP. Right-SUte@Uriversal 2021 21.0.02 RSU23828 Page 2 terstone1820AGL1Lot124Blk5Waterstone1820AGL.rg7 Calc=MJB Front Door faces: NW -r- wrightsoft° Right-JO Worksheet Job: Entire House Date: By: DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Lot 124 Block 5 Waterston 1... DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area DININGIFOYER 25.0 ft 10.0 ft heattcool 1.0 x 276.0 ft 276.0 ft2 DENBDRM4 31.0 ft 10.0 ft heat/cool 13.0 x 13.0 ft 169.0 82 Ty Construction number U-value (Btuh/ t2-co Or HTM (Btuh/ftz) Area (ft) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N(P/S Heat Coal 6 11 .W a _- W _1.6B.19ad Blk wall, slu000 ext 2A-2ov 2A-2ov _ BIk wall, si ext 10C-v 2A-2ov 2A-2ov 19ad. . .. _ _. BIk wall, stucco ext 0.201 0.330 0.330 ne ne ne 5.83 9.57 9.57 4.06 17.70 17.70 0 0 0 0 0 0 0 0 0 0 0 0 50 0 0 50 0 0 291 0 0_ 203 0 0 ---G W�,�_..16B_19ad...��__�...._:.._......�0:049 -G yJ _� __G`..2A-2ovOsW W V7l P C . _ F. 0.201 0.550 0.330 0.330 _ _. 0049 0.201 0.330 _.::ser se se se se . ...sw sw sw _�1_:42 5.83 15.95 9.57 - 9.57 __1,42:..._. 5.83 9.57 _.:.u,.:2.59 4.06 16.20 15.57 8.52 259 4.06 15.57 ,.�.�.._.�.a 0 0 0 0 0 ____ 0 110 33 :_._.___v.�0 ._.��_,�t4 0 0 0. 0 451 313 _.�.,x_ ;..._0 0 0 0 0 314 509 54 184 358 __ .__.359 0 19 __.:_--0 92 '. 466 0 _ ;: �w._.....�Q 0 0 0 0 130 0 0 0 0 _ _.__.._0 0 130 .:r�....____33 . 0 _� 169. 169 ,:.__._.._: � 0 0 0 0 130 0 0 0 6 .. .__._._0 0 7 97 ���0 0 _ _.169 31 .�_ �. •w_� 0 0 0 0 758 0 0 0 0 . _, --0 _...�,.�:A. 0 0 0 0 77 8 0 0 0 0 528 0 _ :0 0 _-.0 0 395 w._543 0 �_ _.286. 0 126 2A-2ov 26-2fv .11J0___1_. _ _._ 1613-19ad Blk wall stuoo ex[ . 12C-Osw _-�•p _ �1.6B 30ad: , �_ 22A tpl _ _ _ 0 091 0 330 0.330 _-.__.0.600 0.049 0201 .0`.330 0.091 :0.032 0.989 _ - nw . nw nw _nw nw nw ...nw_ _ ._ _ :: _ _ 2.64 ' 9.57 9.57 ... J7.40:..___1.7..58 _ 142 5 83. -._9.57., 2.64 _ 0.93 28.68 . ._ 2 21 26 32 26 32 2.59 4.06 _ifi.6i _ 1.31 0.00 - 65 7 14 __.__.._--20 �0 5 _.__ 0 _ _ 70 27_6 276 24 0 0 _,_._____20 0 5 ._ . -.0 64 67 130 ..___,._355 0 27 _A 185 _ -256 , 717 _ 0 - 567 ,� _ _31-3 0, _ R.___1.57 889 _ _ 70 M276 . 25 _ - -- • _.,r - - -- - - - - 6 c) AED excursion 327 161 Envelope loss/gain 2565 2681 2975 2115 12 a) Infiltration b) Room ventilation 345 0 97 0 595 0 166 0 13 Internal gains: Occupants@ 230 AppliancesUher 1 230 0 0 0 0 Subtotal (lines 6 to 13) 2910 3008 3570 2281 14 15 Less external load Less transfer Redistribution Subtotal Dud loads 1700 30 % 0 0 0 2910 506 0 0 0 3008 911 17% 30% 0 0 0 3570 621 0 0 0 2281 691 Total room load Air required (dm) 3416 1401 3919 1841 1 4191 1721 2973 140 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -�'{�- wr➢gtitsolFt� "" Right-StDteC�Uri2021-Jan-1414:52:01 ACCA Universal Page terstone1820AGLNLot124BIk5Waterstone1820AGL.rLp Calc=MJ8 Front Door faces: NW wrightsoft® Right-J® Worksheet Job: Lot 124 Block 5 Waterston 1... Entire House Date: By: DCS DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 Room name FAMILY RM MSTR BDRM 2 Exloosed wall 13.0 It 41.0 It 3 Room height 10.0 it heat/cool 10.0 ft heattcool 4 5 Room dimensions Room area 13.0 x 22.0 It 286.0 ft2 14.0 x 17.0 It 238.0 ft? Ty Construction U-value Or HTM Area (ftz) Load Area (it) Load number (Btuh/R2-T) (Btu h/RZ) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W .16B 19ac1: _. 0,049 nea.' 142 _._ _M 2:.5.9 .__ . _M20 _ h. _.n20 . _..28 _. _ . 52 _ __. 0 _ . _ ._. �0 Vu Blk wall, stucco ext 2A-2ov 0.201 0.330 ne ne 5.83 9.57 4.06 17.70 0 0 0 0 0 0 0 0 170 0 154 0 896 0 624 0 II�G 2A-2ov _ W _ Blk wall, stucco ext 10C-v 2A-2ov 0.330 0.201 0.550 0.330 ne se se se 9.57 5.83 15.95 9.57 17.70 4.06 16.20 15.57 0 130 18 0 0 0 0 323 289 0 _ 16 140 0 16 0 124 0 4 156 721 0 156 289 502 0 254 79 18 0 28 463 285 0 2A-2ov _ 0.330 0.049.. se sw_ » 9.57 :._ w 1:42 8.52 L 2.59 33 _n ; :20 33 .. _20 313 28 - 279 �: -._ 52 _ 0 _ _._.: 0 0 ..� 0 _µ 0 0 _.. yJ _-G Blk wall, slucm ext 2A-2av 12C-Osuv 2A=2ov 26d2(v 0.201 0.330 0 091 0 330 0.330 sw sw nw nw nw, 5.83 9.57 2 64' 9 5T 9.57 4.66 15.57 221 2682 26 32 0 M.-_--- 0 0 0 0 0 -- Q 0 0 0 0 0 0" 0 0 0 _ Q 0,- 0 0 100 _ 0. 0 •,, 0 0 100 _ _ 0 0 '0 0 583 ___� 0" 0 0 406 . 0. 0 0 0, _...._._._0.600 _.nw_ .:..,_1.7.40:... 1Z.58 _ _0 -:._0 _w� 0 0 _0 W 161319ad Blk;wall stucco ext 0.049 0.201 .� V __0.330 nw nw . _hw.. 1.42 5.83, _.9.57 259 4 06 '__16.61 20 0 _ .,�. 1-6 20 0 .�___ �0 y 28 0 _ _ _,0 52 0 _ __�_.0 0 p ., __�_:0 0 0 -_-_�_-0: 0 ' 0• ,_�_4__�0 P _ _ F 0 286 13 12C Osw ._ 1,68 30ad _� T 22A tpl, _ 0.091 _ �0,032 0.989 _ av _ 2.64 w 0.93..� 28.68 _._. 1.31 -w1,69 0 00 m- 0 .__-w285 286 _._. - _.� 0 _ T26.5 373 w _.__.._._ 0 ,a 483 0 0 a 4.238 __ 0 � _ _238 Y_ W 0__ ;--221 0 _,,_ _-„ .. .(,.-._.._..-•-- _-..a,_... _. _-.: -yam ...._, ....__ _ _ �..r. 6 c) AED exarsion -124 -74 Envelope lose/gain 1813 1457 3909 2404 12 a) Infiltration 403 113 787 220 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 1 230 Appliances(other 0 600 Subtotal (lines 6to 13) 2216 2259 4696 3453 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 2216 0 0 2259 0 0 4696 0 0 3453 15 Ductloads 17% 30% 385 684 17% 30% 816 1046 Total room load Air required (cfm) 2601 107 2944 138 1 1 5512 226 4499 211 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _ -rid- wrigtitsoft- 2021-Jan-1414:52:01 ACCP. "'" R ght-Sute®Uruversal 2021 21.0.02 RSU23828 Page 4 terstone1820AGLLot124Blk5Waterstone1820AGL.np Calc=MJ8 Front Door faces: NW - wrightsoft' Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 124 Block 5 Waterston 1... Date: By: DCS 1 Room name M BATH M WIC 2 3 Exposed wall Room height 12.0 It 10.0 ft heaUcool 0 It 10.0 It heat/cool 4 5 Room dimensions Room area 1.0 x 119.0 It 119.0 ftz 7.0 x 7.0 It 49.0 ftz Ty Construction number U-value (Btuhr_,n Or HTM (BtuhRtz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 :W 'V!1 y166-19ad �•�,_�k Blk wall, stucco ext 2A-2ov 2A-2ov 6Br19ad. _. Blk wall, stu000 ext 1OC-v 2A 2ov s�,�0.049 0.201 0.330 0.330 __. 2Q49 0.201 0.550 0.330 .�.rie:.. ne ne ne wsea se se se � 1.42 5.83 9.57 9.57 : 142. 5.83 15.95 9.57 2.59 4.06 17.70 17.70 _ F259 4.06 1620 15.57 _��_.,�_ 0 120 7 0 .._. R 0 0 0 _-..1�:,_ 0 113 0 0 0 0 0 0 _..�.�0 659 66 0 _ 0 �0 0 0 __� :_�,Q 459 123 0 0 0 0 0 _: ____��0 0 0 0 ;` � , 0 0 0 0 ___ ____0, 0_.__._. 0 0 _ �.�_ 0 0 0 0 _.__ 0. 0 0 0 W _ 0 0 0 0 ___..-,_:._0. 0 0 0 =, U 0 0 0 _.- 1R/ �-( W y! L-G P 'Caw.._.16f3-30ad�°��_�::�w.,a�.���0.032.w�..:_:....,_v093,>__1:69 F 2A-2ov Blk wall, stucco ext 2A-2ov 12C Osw 2A 2ov 28-2fv 161319ad _ Blkall alu00oek . 2A2ov._._._= 12C Osw 22A tD1 0.330 0.201 0.330 0 091 0 330 0 330 0.049 0.201 Y ._ -'0.330 0.091 _ 0.989 se sw sw nw, .' nw nw nw hw, _nw- f _ 9.57 5.83 9.57 2 64. 9 57 9 57 _._17..40. 142 5.83; __ --:9.57-= 2.64 28.68 8.52 4.06 15.57 221 26 32 26 32 ,.. w],Z.58 259 4.06 �..,.._16.6.1 1.31 0.00 0 µ 0 0 0 0 0+ w...� _ .0 0 - 0 ----,--0 0 119 0 0 0 0 0 0 . _0 0 V 0 _ « _-0 0 12 - 0 0 0 0 0 0 .__. w A 0 0 _ ._, 0 0 344 0 0 0 0 0 0 _ d 0 0 0 _ w,0 0 0 0 0 0 �_ 0 0 0 e_ . 0 0 ' ;0O - _. 0 0 _ 49 0 0 0_ 0 A 6 �, 0 0 __ 0 0 - 0 _ 0 ' 0 0 _ _. 0 0 0 __ __:, .>0 0 ..T. : .O --0.._.,_.� _ 0 0 0 ._. 0 0 0 0 0 0 o -.._0. 0 0 77 .........-. .er. ::.u...»„a ..,, .� r..:wd....,.,.,.......nmw.:.....3.__...�.,._. ..... ..,...,4n.wo.............. .... .'vw�. .._.. :.. .-. ..... a_. _ H.R.,..;...::_-....w,......�.,..::.»m. - ,..,.- ..�,r...:.z,...,.t..».s...,.r..._..4....z:�.. :: w....4.�.,. w.t ..w,.., ....,,.....:.m. ,....«._:.d.._....._.. ,. __.... _......,...:.».r.. _c...»...:....:._,:,.5, _ .._....,-__ .-.L.a_� .___.�.e....�..,..__ ................ ....w3,. ......._...... � �-_....__ 77 __�..»_..._w _.._.__ _ _.� ,..._.s._.._.. tea_.._._ ,..,._..__ .«......_�. 71 6 c) AED excursion _44 _4 Envelope loss/gain 1180 739 45 78 12 a) Infiltration b) Room ventilation 230 0 64 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines6 to 13) 1410 803 45 78 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 17% 30% 0 0 0 1410 245 0 0 0 803 243 17% 30% 0 0 0 45 8 0 0 0 78 24 Total room load Air required (dm) 1656 68 1046 49 53 2 102 5 Calculations approved byACCA to meet all requirements of Manual J 8th Ed -�- wrigHtsof!- 2021-Jan-1414.52:01 Right -Sate® Universal 2021 21.0.02 RSU23828 Page 5 terstone1820AGULot124Blk5Waterstone1820AGL.np Calc=MJ8 Front Door faces: NW * wrightsoft° Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 124 Block 5 Waterston 1... Date: By: DCS 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area KITCHEN/NOOK 29.0 ft 10.0 ft heaUcool 1.0 x 246.0 ft 246.0 ftz LAUNDRY 6.0 ft 10.0 ft heat/cool 6.0 x 6.0 ft 36.0 ft2 Ty Construction number U-value (Btuh/tzf) Or HTM (BtuhAt2) Area (ftz) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 _ _W VI/ �-G I�-CG _.., W VN W P F e_.B 1_ -- - 169ad:_,; Blk wall, stucco ext 2A 2ov 2A 2ov Blk wall, stucco ext 1OC-v 2A-2ov 2A-2ov m16819ad ." ww:.: Blk wall, stucco ext 2A-2ov 12C Osw 2A-2ov 2&2fv 166-19ad Blk wall stucco ext 12C Osw 0_ 22A:pcl __ _ --- 0..049 0.201 0.330 0.330 0.201 0.550 0.330 0.330 _ > do 0.201 0.330 0 091 0 330 0.330 0.600 _0.049 0201 _0.330 0.091 0.989 .:ne':, ne ne ne se se se se_ .,sw". sw _ sni nw nw nw; .. nww nw nw, --'nw-,',.____9.57 __i'42.�___0 5.83 9.57 9.57 42 5.83 15.95 9.57 _ 957 142 5.83 9.57 2.64 9 57 , 9 57 . ._17.4D. _ 1.42 5.83, 2.64 28.68 4.06 17.70 17.70 7=2.59 4.06 16.20 15.57 8.52 _. �2 59 4.06 15.57 21 2 26:32 29 32 iZ.58 2_59 4.06 _,�_._1.6.61 1 31 .__.. 0,00 150 0 33 117 0 0 0 0 0 0 w _._0 0 0 70 0 0 0 0 .__._0 146 _ 29 684 0 _ 313 0 0 0 _ 0 _. _ 0 0 0 0. 0 0 - 0 0 0 __ 0 369 832 0 0 0, 0 0 0 _ 0 � �.0 0 _ _0 0 0 0 0 __._= 0 60 36 __ � 0 0 0 0 0 0 0 ,a_. _ »._ 0.=-O 0 0 4 0 0: 0,' 0_ 158 y32 172 0 0 _ 0 0 0 0 0 0 0 "p t 0. 0 0 79 h, 0 476 0 M 579 0 0 0 .�� 0 � .0 0 0 _ 0 0 0 �.__,._. 0 0 ____ _0 183 4 0 00 0 0 0 0 0 �� 0 . �W:'_ 0 0 0 0 0 0 0_ 60 6 0 0 0 0 . v.� 0 0 _0 0 0 0 .,. :_0 0 0 ._� _._0 140 241i ........... _..............._.._w ._ _�..._ --.._..,....._._...__ ....._.z,a.....� __..._.:._. _........... _..__ _._._..._.........« ...._._.,,..____ _.....-�_: >...._..,._�..._...6.. .�._�_ _max ._ _ �-...� _ �.�_� __.c .���.._._� 6 c) AED excursion -125 -39 Envelope loss/gain 2426 1629 364 101 12 a) Infiltration b) Room ventilation 288 0 80 0 0 0 0 0 13 Internal gains: Occupants@ 230 Appliances/other 0 0 1200 0 0 600 Subtotal (lines 6 to 13) 2714 2809 364 701 14 15 Less external load Less transfer Redistribution Subtotal Ductloads 179/. 30 % 0 0 0 2714 472 0 0 0 2809 851 17% 30% 0 0 0 364 63 0 0 0 701 212 Total room load Air required (cfm) 3186 130 3660 172 1 117 427 913 43 Calculations approved bVACCAto meet all requirements of Manual J 8th Ed -� wr_ ightsoR� ^� Rigtd-SLiteO Universal 2021 2l .O.O2 RSU23828 2021-Jan-1414:52:01 Page 6 terstone1820AGL\Lot124Blk5Waterstone1820AGL.np Calc=MJ8 Front Door faces: NW Duct System Summary Ube Lot 124 Block 5 Waterston wlrightsoft® ... Entire House By: DCs DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY,,SANFORD,FL32771Phone: 407-333-2665Fax: 407-333-3853 Web:WWW.DELAIR.COM Project• • For: ADAMS HOMES 5358 San Benedetto Place, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm 113 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.300 in/100ft 1167 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 833 34 24 0.394 4.0 Ox 0 VI Fx 16.3 70.0 BDRM 2 h 4742 194 132 0.366 8.0 Ox 0 VI Fx 22.9 70.0 BDRM 3 h 1876 77 70 0.433 6.0 Ox 0 VIFx 8.6 70.0 DENBDRM4 h 4191 172 140 0.409 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER c 3919 140 184 0.444 7.0 Ox 0 VIFx 6.5 70.0 FAMILYRM c 2944 107 138 0.330 7.0 Ox 0 MFx 17.9 85.0 st1 KITCHENMOOK c 3660 130 172 0.323 8.0 Ox 0 VIFx 20.1 85.0 sti LAUNDRY c 913 17 43 0.316 4.0 Ox 0 VIFx 22.7 85.0 st1 M. BATH h 1656 68 49 0.317 5.0 Ox 0 M Fx 22.2 85.0 sti KWIC c 102 2 5 0.318 4.0 Ox 0 M Fx 21.9 85.0 sti MSTR BDRM h 5512 226 211 1 0.300 8.0 Ox 0 VI Fx 28.2 85.0 st1 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 550 618 0.300 578 14.0 0 x 0 VinlFlx - wrightsoft® 4•/tl•.Wirellmn.nq�� ny Right-SUte®Ureversal 2021 21.0.02 RSU23828 terstonel820AGL\Lotl24Blk5Waterstorel820AGL.rLp CaIc=W8 Front Door faces: NW 2021-Jarr1414:52:02 Page 1 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rb1 Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx ti * wrightsoft® 2021-Jan14145202 ZcaAM,r•'".1-11.11 ��.,.•>� pP Right-Sute®Universal2021 21.0.02 RSU23828 Page t terstone1820AGL\Lot124BIk5Waterstone1820AGL.rp Calc=MJ8 Front Door faces: NW . 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 124 Block5 Waterstone 1820 AGL Builder Name: ADAMS HOMES Street: 5358 San Benedetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 W Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind poperia and worena. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only Tbesprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voidbetween fire sprffioklpr cover plates and walls or cellina a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage'; then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 1/14/2021 2:55:18 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information. Builder: ADAMS HOMES Community: Lot: NA Address: 5358 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Air: Leakage Test Re'su lts Passing results: must meet either the `PerforrhAnce, Prescriptive; or ERI Method O -PRESCRIPTIVE METHOD -The buildindior dwe_Iling,un tshall be tested and ver,'ified;as having an air leakage rate of not exceeding 7 air chan es{ er hour at a ressure; of 0.2.inch w. 50 Pascals m Climate Zones 1 and 2. , 9 P P p. ) Q PERFORMANCE or'ERI METHOD -The building -or dwelling,unitshall be tested grid `verified as having an air` leakage rate of not exceeding the selected ACH(50)'value, as shown on Form R405-2620 (Performance) or R4Q6-2020.(ERI), section labeled as%infiltratiop, sub -section ACH50. ACH(50) specified on Form,17405 2020-Energy Galc (Performance) or R406-2020, (ERI). 7.000 x 60 - 18200 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans 1-1 PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company' Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/14/2021 2:55:54 PM EnergyGaugeO USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5358 San Benedetto Place Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. FA SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 Us/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. 0 R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. El R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 ' MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. El R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 �-R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS ❑ R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 1/14/2021 2:55 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5