HomeMy WebLinkAboutProject InformationProt SJob: -�+ Wrightsoft° Project Summary Date: AUG 23, 2018 Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM •Pronect Information F�9-GRUGE; F A1EjUSkRESIDENCE, PACE 2000, INC 6509•HICWRY DRNE, FORT PIERCE, FL Note : OCT 11 2' ST. Lucie County, Permitting Desi•n Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 24814 Btuh Structure 22796 Btuh Ducts 6351 Btuh Ducts 4103 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 31165 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 25555 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3654 Btuh Ducts 2485 Btuh - Area (ft2) Heating Coolingg 2263 2263 Central vent 0 cfm) Equipment latent load 0 6139 Btuh Btuh Volume (W) 22032 22032 Air changes/hour 0.32 0.16 Equipment total load 31694 Btuh Equiv AVF (cfm) 118 59 Req. total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trane Trade Trade TRANE Model Cond 4TTB6036A1 AHRI ref Coil "AM7AOC36H31 AHRI ref 5884597 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 9.5 kW Sensible cooling 24920 Btuh Heating output 32337 Btuh Latent cooling 10680 Btuh • Temperature rise 25 OF Total cooling 35600 Btuh Actual air flow 1187 cfm Actual air flow 1187 cfm Air flow factor 0.038 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 FILE C®PY Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wri htsoft° 2018-Aug-2312:22:56 .�• 9 RightSuiteO Universal 2017 17.0.08 RSU08101 Page 1 A'C'1�1 ...SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E - wrightsoft9 Right-J® Worksheet Entire House • QUICK CALCS, INC. .31j ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: OUICKCALCS@AOLCOM Job: Date: AUG 28, 2018 By: 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 210.6 it 9.7 it d 2262.5 ft2 MASTER BEDROOM 34.2 it 10.3 it heat/cool 1.0 x 244.5 it 244.5 ftz Ty Construction number U value (BtuhRtz-°F) Or HTM (Btuhrtt2) Area 0t2) or perimeter (it) Load (Btuh) Area (ft2) or perimeter (11) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool .. 11 _...._. ...--- 13A flocs 2 glazing, cir low-e 291azirxf.cirbw-e 13A-4ocs 2 glazing Ir bw-e . __. 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing clr low-e__ _ 13A-4ocs 2 alazirKL_ I low_e- - 13A-4ocs 2 glazing, clr low-e 2 glazing clr low a .. .._ 13A-4ocs 2 glazing cir low-e _._. 13A-40cs 2 lazi clr low-e 9 n9. glazir@ clrlow-e 2glazirxl clr low-e-_._,0.650 13A-4ocs 2.glazing clrIT -e� 22A-tp1--- - -- -.__ _ _.____ 0.143 0.650 ---U:650 0.143 --, ----0.650 0.143 0.650 0.650 0.650 _-._....0.650 0.143 - ____-0.650 0.143 0.650 ._.._0.650 0.143 0.650 0.143 0.650 0.650 0.143 _- 0.650 ------ 0.989 ..__- n n - - ne - ne a a a a - e . se _se s s __s_ sw ._sw- w w w w . nw nw - - ,_ _-t_ 4.00 18.20 18.20 4.00 �1820 4.00 18.20 18.20 18.20 _-18.2Q 4.00 _ _ 18.20 4.00 18.20 -_-_.18.20 4.00 7820, 4.00 18.20 18.20 - 18.20, 4.00 ,_1820 --27.69 -.-,--.m_- 2.55 11.27 11._27' 2.55 _. 18,63 2:55 25.40 23.12 23.12 ---_23.12 2.55 .__._15,04 2.55 11.27 _ 11..27 2.55 __ 17.50 2.55 23.12 23.12 -_-23.12 2.65 18_63 , -----_ 505 8 - - 32 39 - -- __-6 292 6 20 20 _. -. ._41 39 .--.-- - - 8 520 40 __... . - 24 100 _-- -- 47 493 10 50 _48 44 10 .-._2263 - -2263 0 0 0 0 -- 0 0 , 0 0 ------ 0 620 182 -- ---- _0. 0 -- ---- 0 ,. 261 0 0 .. _ . _874 135 - _.- 182 - _--:-219 - - - 946 0 0 0 0 0 0 0 0 .. _ - ----0 0 394 113 _ 0 0 0 166 0 0 _ .__ .1110 86 186 -- 5.67 - 0 ---- 465 0 - 8- 34 - - _..-_0 205 0 6, 6 . _.-_9 34 , ----- -6 456 80 ._... _. 48 53 - -- 18 385 6 0 '_ __-- .--0 34 - 0 _ _..2263;__..__2027 .-- -211 48B3 146 -_-582 135 ------105 ' . 820 109 364 364 .._,_ --743 135 ----- 105 1824 728 _.. __--V7 214 _ .._ 849 1543 174 910 -,_ ---874 135 182 -5831 -- 1184 90 - _361 86 ___ _ 107 521 152 462 462 _ ---- 943 86 1160 451 _.....__271. 136 __._. 817 981 222 1156 ---_-__ 1110 86 186 -- - 31 0 . 0 0 - _ 0 '- --- 0 0 0 0 -__ _ .___ 0 0 165 10 _._.._.._. _0 0 ,- 0 113 0 0 _ _48 44 10 _ _ -246 - - 245 ;,31 .0 0 ^ - F 0 0 �- --0 0 0 '0 _..._ _._- 0'- 0 .-..._. _ NJ _-I----_-__ V}1 155 10 ___... _-_0._ 0 0 V1! - 65 0 0 ..� _ _ _0 34 0 - _245 -- -34 V1J _�-( F - . - 0,00 _. _-.-5249 - ----0 6 o) AED excursion 203 320 Envelope loss/gain 21198 16568 3543 3021 12 a) Wittration b) Room ventilation 10 3616 969 0 10 628 168 0 13 internal gains: Occupants @ 230 Appliances/other 2 460 4800 2 460 0 Subtotal Qines 6 to 13) 24814 22796 4170 3649 14 19 Less external load Less transfer Redistribution Subtotal Duct loads 26% 181/6 0 0 0 24814 6351 0 0 0 22796 4103 2696 189% 0 0 0 4170 1067 0 0 0 3649 657 Total room load Air required (ofm) 31165 1197 26900 1197 5238 199 4305 190 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft" RightSuite® Universal 2017 17.0.08 RSU08101 2018-Aug-23 12::222:56 SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E Page 1 - wrightsoft® Right-J® Worksheet Entire House QUICK CALCS, INC. Job: Date: AUG 23, 2018 By: ,3,17 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS(RAOLCOM 1 -2 3 4 5 Room name Exposed wall Room height Room dimensions Room area wIC 7.0 it 9.3 ft heat/cool 9.0 x 7.0 ft 63.0 ft2 MASTER BATH 28.4 ft 9.3 ft heat/cool 1.0 x 187.0 it 187.0 ftz Ty • Construction number U-velue (Btuh/ft-F) Or HTM (Btuhlft2) Area Qtz) or perimeter (R) Load (Btuh) Area Qtz) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross NIP/S Heat Cool 6 11 + 13A flocs 2 glazing, clr low-e 2 glazing clr bw•e. 13A-4ocs 2 glazing, clr 2 glazing. cirbw-e 2 glazing, clr low-e 2 glazing, clr low-e .. 13A-4acs 2 giazinq clr bw-e-_ 13A-40cs 2 glazing, clr low-e 2-glazing clr' - e- - 13AAocs 2plazirxl cir low-e_______-_-_0.650...sw 13AAocs 2 giazin q cir low-e 2 glazing, clr low-e 2glazirX clrbw-e._ 13AAocs 2 glazing cir bw;e 16A0md ._ ._ _ ._ 22A!ol .. - - -- - 0.143 0.650 _ __. 0_650 0.143 0.650 0.650 0.650 0.143 -__0.650 0.143 0.650 - _ -- 050 0.143 0.143 0.650 0.650 . _ _ .0.650 0.143 _-- 0.650 _ ___.0.032�._.__. - -0.989 nY n __ n_- ne a a a se se s s - s - sw w w w _.w_ nw rtHl __._ . 4.00 18.20 -_ 18.20 4.00 18.20 18.20 18.20 4.00 18.20 4.00 16.20 . 18,20_ 4.00 ___1820-_.-17.50_�__. 4.00 18.20 18.20 ---- -18.20 4.00 T 18.20 _ ._. 27,69< 2.55 11.27 _ 11.27 2.55 18-63 25.40 23.12 23.12 2.55 15.04 2.55 11.27 _. _- -- 2.55 2.55 23.12 23.12 --._23.12 2.55 18_63 0.00 0 0 _._ _.. 0 0 - _- 0 0 0 0 0 ._---- 65 0 - - _-0 0 0._-_._,_0--0-------0---____.-0 0 0 0 --0 0 Y 0 -- - - _.., O 0 .. _ _ _ .0 0 -0 0 0 0 _.-__�...__-----0--------0 0 ---__-0 65 0 0 0 0 0 0 ; 0 0 0 �-- 63 --„- _ Y_ o 0 _ _0 0 0 - - _ . 0 0 0 _-•- -- - 0 39 0 0 __ .-34 54 0 0 0 34 __-- -_ 3 92 10 - 0 0 -.-.----0----..---0._ 0 0 0 "-,0,._.__...-_ 0 0 _----187 -- - 28 0 L 0 ._ . .. 135 218 6 364 0 -0-----_..._0 135 . --_ 10,5 370 182 . - - - -0 0 0 0 0 --0 0 0 _168 ----787 0 0 _86 138 0 462 0 86 _ --_86 235 113 _ .. _ 0 0 -------._..0. 0 0 0 _- _ . 0 0 0 --434 -- 0 W _--�-- _-----_2glazing,_cirbw-e__----------0.650--8-----18.20..__23.12..-----,.0_ - b_ k/ C_ F _. 0 0 0 0 0 _ _-_--0 261 0 _ .. _ -. 0 0 -_•--0' 0 0 _..__._ ..0 0 0 ._ __56 --.1.94 0 0 0 0 0 0 74 0 20 0 ---__-_-o---------0----- 39 6 166 0 . - - -.0 0 0 0 0' 0 0 _ - _ 0 ._,._ 146 -- 102 10 -- - -- 0 0 6 0 0 __--------0 0 _TO _.. ___187 . _ _. 187 _ -- _0 6 c)AED emxursion -25 -76 Envelope loss/gain 511 287 2604 1696 12 a) Intiftration b) Room ventilation 116 ' 0 31 0 471 0 126 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal Vines 6 to 13) 627 318 3076 1822 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 260/6 180/0 0 0 0 627 160 0 0 0 318 57 26 0 180/6 0 0 2 3078 788 0 0 6 1828 329 T-Total room load Air required (cfm) 787 30 375 17 -T 3866 147 2157 95 Calculations awroved bvACCA to meet all requirements of Manual J 8th Ed. A 4 wrightsoft- RightSufteO Universal 2017 17.0.08 RSU08101 2018-Aug-23 1 :222 56 ...SAILFISH 2253 MODEL- PACE- CRUCE RAGUSA RES.rup Cab = MJ8 Front Door faces: E Page 2 - wrightsoft° Right-J® WOrksheet Entire House .. QUICK CALCS, INC. 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSQAOLCOM Job: Date: AUG 23, 2018 By: 1 2 3 -4 5 Room name Exposed wall Room height Room dimensions Room area TOILET 6.0 It 9.3 It heat/cool 4.0 x 7.0 ft 28.0 W LINEN 0 It 9.3 It heat/cool 4.0 x &0 ft 12.0 ft2 Ty Construction number tlxelue (Btuhfltz-°F) Or HTM (Btuhht2) Area qtz) or perimeter (ft) Load (l3tuh) Area Qtz) or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool .6 •' 11 - -. 13A flocs-- - -- 2 glazing, cir low-e 2glazing,-9t1W-e 13A-4ocs 2 glazing clr tow-e ______0.650 13A-46cs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e 2 glazirxj-cir low-e__. 13A-4ocs 2Alazlrxl clr law=e-- - 13A-4ocs 2 glazing, dr low-e 2 glazing,_cir bw-0 -- I aA4ocs 2 glazirtq clr low-e_ -- 13A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2.giazing,_dr_bw-e _--. 13A-4ocs 2.glazing cir low-e - 0:143 0.650 ----0-§50 0.143 --.-. n n ne ne a a a a _ _e - se ._Se - S s s_ sw _ sw . w w w .__ -. rnv nw ----- 4.00 18.20 --18.20 4.00 _____18.20 4.00 18.20 18:20 18.20 --_-18.20 4.00 _--_18.20, 4.00 18.20 _ _.18.20 4.00 _ 18.20 4.00 18.20 18.20 _ -_ t8.20 4.00 18.20 2.55 11.21 1L27 2.55 _ 18_63 2.55 25.40 23.12 23.12 .-_-23.12 2.55 -15.04 2.55 11.27 _w 11.27 2.55 17.50 2.55 23.12 . 23.12 23,12 2.55 18.63 19 0 -- 0..----_0-- 0 - 0 37 0 0 0 _- _.9 0 - -- --_0 0 0 __..--- - _0 0 _.0 0- 0 0 _-` - _. _ Q 0 0 19 0 0 ---- _ 0 37 0 0 0 ._._ 0 0 _ __-6 -0 -0 0 _ . -,--,_0 0 0 0 0 -_ . _ 0 0 -- -0 0 0 0 0 .-_. _ 0 0 0 0 : ---._ . 0 0 0 . �..__ 0 0 ..- -0 0 _ - -- .. _ _0 0 0 0 0 _. - ,0 0 -- - U 0 0 - _- --- . 0 0 _. . .. q 0 0 0 - - -- . - . 0 0 0 0 0 0 _ _ ._ ..-_.._ 0 0 0 0 0 - _- -- - - 0 0 ... --0 0 0 --- - 0. 0 0 0 0 ------- - 0 0 0 74 0 0 0 0 149 0 0 0 --__----_0 0 ---- ---0 0 0 _-..._ _._ 0 0 _ ...____ _-0 0 0 0 ._ -__ __0 0 0 ------- 47 0 -0 0 -- 0 95 0 0 0 _ 0 0 -_, 0 0 ._,._-0 0 ---0 0 0 0 0 __. _._. 0 0 - - - 0 0 0 _ _ . _.-. -.0 0- ._ _---.. _0 0 0 0 . --0 0 0 ____---_-- Nl - _�__. 0.143 0.650 0.650 0.650 ------0.650 0.143 ---_0.650 0.1'43 0.650 __ _ 0.650 0.143 ---- 0.850 0.143 0.650 0.650 _--._-_0.650 0.143 0_650 -_--- _ W/ G. ------ lQ/ ----0 0, 0 ___0 0 _-. 0 0 0 0 -__ ..__-0 0 0 --___v_0 0 0 --- -0 0 -_-- _0 0 0 0 _.._-_._-0 0 0 _ W! IL�_cr" -_ _ -- _ _ - 0.90 27.69..-- - _-2.32 -0.00 :_._ __ -28 --28 --_-_. 28 -- 6 _ _. -__25 168 65 _--- .-12 -� 12 - -- - . _ _ _.:12 --_--0 _ .._. -- -ti: - - - - 0 ..._. - ,_28 0 - ---0 _ --- --- ---- --------- - -- ---- ---- - 6 c) AED excursion -17 -2 Envelope loss/gain 415 190 11 26 12 a) Infiltration b) Room ventilation 99 0 27 0 0 0 0 0 13 intemal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal pines 6 to 13) 514 217 11 26 14 1,i Less extemai load Less transfer Redistribution Subtotal Duct loads 261/6 . 18% 0 0 365 879 225 0 0 414 630 113 261/6 18'/6 0 0 -11 0 0 0 0 .26 0 0 Total room load Air required (cf m) 1 142 1103 744 33 j 0 0 0 0 Calculations amroved WACCA to meet all requirements of Manual J 8th Ed. -IJ& wrighttsoft" 2018-Aug-23 12:22:56 Cam. RightSuiteO Universal 2017 17.0.08 RSU08101 Page 3 ...SAILFISH 2253 MODEL- PACE- CRUCE RAGUSA RES.rup Caic = MJ8 Front Door faces: E wrightsott Right-J® Worksheet Entire House .. QUICK CALCS, INC. .317 ST.. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSQAOLCOM Job: Date: AUG 23, 2018 By: 1 2 3 4 5 Room name Exposed wall Room height. Room dimensions Room area FOYER 7.0 ft 10.0 ft heal/cool 7.0 x 6.0 ft 42.0 ftz DINNG ROOM 13.0 ft 10.0 ft heat/cool 1.0 x 140.0 ft 140.0 W ITy Construction number U•velue (Btuhlft2-°F) Or HTM (BtuhAt2) Area 0t=) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool .. 11 0 _ 0 0 0 .. m_0 0 _ _-_..._.• 0 0 b _ : 0 0 p - 360 0 0 S64 0 0 80 0 0 -------- 0 0 0 0 .. .. 0 0 _ 125 360 0 9 0 ._. _. 0 u;224 0 0'. 462 0 9 51 0 0 .._ ....__ 0. 0 0 0 , - .. 0 0 _ 0 ._: 326 -0 '13A4ocs 2 glazing, cir low a Pglazinc� cirbwe __.-.:_..._0650 13A 2 glazing clr bw-e 13A-4oc§ - -_ 2 glazirxj.clrlow-e 2 glazing cir low-e 2 glazing, cir low-e 2.glazing,cir.low--e:_,v 13A-4ocs 2 giazirKL clr buvAe _ 13A-4ocs 2 glazing, clr low a -2 glazing cir bw..e 13A-4ocs 2 glazirq, clr low a -. 12T flocs 2 glazing clr bw e 2 glazing dr low e 2.glazing clrbw a 13A-4ocs 2 glazug, cir low-e _ 16A30md _,,,_-:_�... 22A tW.---- - 0.143 0.650 0.143 0.650 - n n _n ne ne e _ a a a se se S.' s _s- sw sw_ w w w _w ♦ nw nw _ 4.00. 18.20 _., 1820 4.00 18.20 _ _ 4. 18.20 18.20 18.20: ___ .18.20. 4.00 --_ 18,20 4.00 18.20 1820. 4.00 _- 18.20 4 00 18.20 18.20, _. 18.20 4.00 18.20 2.65 11.27 .__. 11.27 2.55 18_63 2.55 25.40 '23.12 23.12 �-_23:12. 2.55 - 15,04 2.55 11.27 . 11.27 2.55 - 17.50 2 55 23.12 2312 _- , 12 2.55 18.63 , -0 : 0 _ 0 . 0 .,70 6 '0 p _._.... _41 0 0 0 10 > _0. 0 - . _0 23 0 .. 0 0 .... _,._:0 0 0 0 0 „ 0 • 0 __._.__-_ 9., 0 0 .. 0.-0 0` . __ _,0 0 0 ill __.- _ - 4�1 -_-_._ . y/ Ccr; 191 L.-G F,.-- - 0.143 0.650 0.650 0.650 _ _.._0650._e>. 0.143 _ 0.650 0 143 0.650 _ .. _ 0650 0.143 --__0.650 0143 0.650 0.650 0.143 _ 0.650 _ - _ 93 109 0 9 7_ 0 0 0 0 0 0 0 0 0 : _ _ 0 0 _ . < 59 152 0 0 _.:: . a 943:_ 0 ; ' , 110 0 `0 20 _..__. 0 0 _ 90 0 ° , ° 0 0 0 0 - 0 0 . _ _ _.3--0 0 0 .0 , 0 0 _._._.- 0 0 0 .__ __._42..____ _. '12 0 0 0 _0 0 0 0 _� _ . _._0 0 0 20 0 0 .._._.._ -_-0 0 0 0 _. _ Q 0 _ - 0 _ T 20 0 0 __- 0 0 0 0 . _.0 0 0 ._ 7;40 _e 13 _--- T9 0 0 0 _ m _.:: 0 0 0 . 42 _ .�_ .7 0.032 - ---0.989 :.._. U.90 - _.27.69. . 2.32, 0.00 .. __ 38_. _�--� __. _.97 __-0,­-,­T.140 _.__...140:_._ ._ _. 6 c) AED excursion 175 31 Envelope loss/gain 1176 1427 1290 1098 12 a) infiltration b) Room ventilation 125 0 33 0 231 0 62 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 100 Subtotal Pines 6 to 13) 1301 1460 1521 1260 14 16 Less external load Less transfer Redistribution Subtotal Duct loads 26% 181/6 0 0 -1301 0 0 0 0 -1460 0 0 261/6 181/0 0 0 438 1959 501 0 0 498 1758 316 1TTotal room load AIr required (cfm) I 0 0 0 0 2461 941 2074 92 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. C wrightsoft" 2018-Aug-2312:22:56 RightSuite® Universal 2017 17.0.08 RSU08101 Page 4 ...SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E - wrightsoft- Right-J® Worksheet Entire House QUICK CALCS, INC. •317 ST.. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCS@AOLCOM Job: Date: AUG 23, 2018 By: 1 2 3 -4 5 Room name Exposed wall Room height Room dimensions Room area WING ROOM 10.0 ft 11.0 ft heat/cool 1.0 x 254.5 11 254.5 ftz KITCHEN 10.0 ft 10.0 ft heal/cool 1.0 x 266.5 ft 266.5 f? Ty ' Construction number U-value (Btuhlft2-°F) Or HTM (BtuhAtz) Area Vtz) or perimeter (ft) Load (Btuh) Area Vt2) or perimeter (ft) Load (131uh) Heat 1 0001 Gross N/P/S Heat Cool Gross N/P/S Heat Cool • 11 I--G 2 glazing, clrlow-e 2 glazing,,_glrlow-e - - 13A-4ocs 2 glazing clr low-e 13A flocs 2 glazing, cir low-e 2 glazing, cirlow-e 2 glazing, cir bw-e glazing _ciCbwce---- 13A-4ocs 2 glazinc clr low-e ___ 13A flocs 2 glazing, cir low-e glazing-cir low-e.. __- 13A-4ocs 2glazirxl,_clrbw-e_--__-._ 13A-4ocs 2 glazing, cir bw-e 2 glazirxg clr low-9 2.glazi-rlg_clr bw-e_ .__ 13A-4ocs 2glazing_clrlow4e - 22A tpl-- - - - -- ,-- 0 0 0 0 0 0 0 0 0 . _._ ___. 0 0 0 0 _ ._._ ,_. _ 9 0 --------0-------0._ 360 0 364 ,_ _...__ _0 0 0 --.. _ 228 -----277 --- 0 0 0 0 0 0 0 0 0 _'__.. _ 0 0 -- -- --0 0 0 0 0 0 0 0 0 .__-- _-_ _ 0 0 0 0 , -. 0 100 ---.4Z 0 0 0 .--_-- 9 0 -0 _ _ 267 .__... 267 --- --- 76. 0 .___.._.. 0'. 0 0 0 0 0 0 --- .._---- _. 0 0 0 .._ _:.....9 53 _ 0 0 0 •- _-. _.. _.0 0 -. 0 _ ._ 267 _ - 10 - - 0 0 _.. _.._ 0 0 0 0 0 0 0 0 0 0 _ _.. 0 214 _._..__849.__ 0 0 0 0 0 0 . _ .. 239 - - 277 --, --- - 0 0 - _. 0 0 0 0 0 0 0 0 0 0 . _ 136 817 0 0 0 . _....•0 0 _0 °_ 618 . _. --. _ ---0. 0.650 •- --- -- 0.650-__n 0.143 0.650 0.143 0.650 0.650 0.650 ----,-0.650 0.143 _-0.650 0.143 0.650 _ _ ._ __0.850 0.143 -0.650_sw 0.143 0.650 0.650 ---------0-..650 0.143 _- --- 0. 0 ,_ 0.032 - -0.989 n ' no ne a a a a e- se _se s s __ s.._ sw w w w -_w_ nw nw _ . - -= 4.00 18.20 . 1820 4.00 18.20 4.00 18.20 18.20 18.20 18.20. 4.00 _�18.20 4.00 18.20 .__ _ 18.20. 4.00 __-18.20s- 4.00 18.20 18.20 __..18.20. 4.00 1820 _.-_ 090. - _27.69 ---2.65 11.27 _-_ 11.27 2.55 18.63 2.55 25.40 23.12 23.12 _ 23.12 2.55 _-- 15,04---_--_-- 2.5b 11.27 ----11..27 2.55 17,50Q 2.55 23.12 23.12 23.12 2.55 _?8_6i _ _ 2,32 .__ 0.00 ----0 ._- 0 0 _. _ 0 0 0 0 0 0 0. _--, _0 0 -- -- 0 0 0 0 0 0 0 0 0 ._ ._.____ 0 0 0 0 _ _ •_ _.._ Q 0 __.---- 90 0 0 _-_ _:._ 0 0 _. 0 . _ _255 ._... --10 -�. ____ ' G __ ..2 I14/ _-__- - 0 0 _ ..._ 0 0 110 0 20 _0 0 0 25.5 - -- 2$' 0 0 _ _, _ - 0 0 .12 229 0 462 ..._-- -__s 0 0.. 590 . 0 _. _..._.: W/ F --- 6 c) AED excursion 0 199 Envelope loss/gain 1229 1282 1579 1770 12 a) Infiltration b) Room ventilation 196 0 52 0 178 0 48 0 13 htemal gains: Occupants @ 230 Apprrances/other 0 0 1600 0 0 0 Subtotal Vines 6 to 13) 1425 2934 1757 1818 14 4 Less exlemal load Less transfer Redistribution Subtotal Ductloads 260/6 180/0 0 0 511 19W 495 0 0 580 3514 633 26/6 18% 1 0 0 23 1779 455 0 0 55 1872 337 Total room load Air required (cfm) 1 1 2431 93 4146 183 1 1 2235 85 2210 97 Calculations awroved bvACCA to meet all reauirements of Manual J 8th Ed. wrightsoft" 2018-Aug-2312:22:56 C�A RightSulteCal Universal 2017 17.0.08 RSU08101 Page 5 ...SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Cab = MJ8 Front Door faces: E - wrightsofr Right-J® Worksheet Job: Entire House Date: AUG 23, 2018 • QUICK CALCS, INC. By: .317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSQAOLCOM 1 2 3 -4 5 Room name Exposed wall Room height Room dimensions Room area PANTRY 0 it 9.3 ft heal/cool 1.0 x 23.0 It 23.0 ft2 HALLWAY 0 It 9.3 It heat/cool 1.0 x 103.0 It 103.0 ft2 STY Construction number Ll-xdue (I31uhilt2-°F) Or HTM (BtuhAt2) Area (ft2) or permeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 06 11 ------- -13A-fl00s --------- -- 2 glazing, cir low 13A-4ocs 2glazing clr low-e__..- 13A-4ocs 2 glazing, cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 2glazing Gr_bw:e.--- 13A-4ocs 2 alazirxl cir bw-e - 13AAocs 2 glazing, cir low-e .2 gtazirg cir bw-e- _. _ 13AAocs 2.glazirKL cirbw=e_.-- 13A-4ocs 2glazing, clrbw-e 2 glazing, clr low-e 13A-400s _2 glazlr%. 16A-30md_ :._.__._ 22A tW-- _ - - - - - 0.143 0.650 0.143 _-- 0.650 0.143 0.650 0.650 0.650 ----0.650 0.143 - -0.650 0.14$ 0.650 _ R 65p 0.143 -- 0.650 0.143 0.650 0.650 0.143 _ __ 0.650 O.OGi2 -- 0.989 0 0 0 0 0 _- - ___-- 0 0 0 0 0' .. 9 0 0 --0 0 , _---- - 0 0 0 D 0 --0 0 - - - 0 .. 0 0 .. _ _ .. 0 0 ... 06. 0 0 0 ,_..-., .._..0 .- ._._. 239 . . - .. 0 --_n n ne _ ne_ a a a a -._e . se se s s _._S _:... sw _sw w----4.00 w w nw . nw. ._. _ -- �400. 18.20 4.00 __--18.20, 4.00 18.20 18.20 18.20. e. - 1820_ 4.00 - 18.20 4.00 18.20 _18.20 4.00 18.20 18.20 18.20 4.00 __ 1820 _:_`0.90 _ 27.69 11.27 2.55 - 18.63 2.55 25.40 23.12 23.12 _^23.12 2.65 .._ 15.04 2.55 11.27 _ ,..11.27-9-, 2.56 17.60.. 2.55 23.12 23.12 2.55 18�63 0 0 0. 0 0 0 0 __0 0 - -----0 0 0 0 0 0 0 0 0 -.__0 ----- ..23 ---2, 0 0 0 0 0 ------- 0 0 0 - 0 0 --- - ,0 0 0 0 0 -,_ .- U 0 - 0 0 0 ---_ _- 0 0 0 0 0 -----0 0 0 0 0 4 -•_--53 0 0 0 _ 0 0 0 0 _ 0 0 --_---0 0 0 0 . 0 0 0 0 0 ... 0 -----=_23 - 0 0 0 0 0 - -- --0 0 ---0 0 0 0 0 0 0 0 0 _-0 ------103 - 103 ___-- 0 0 0 0 - _0 0 -- ---0 0 0 , _-0 0 0 0 0 -0 _ _._----103 - --- 0 - W -�-. - -- -6-- 0 0 -- a -0 0 0 0 0 ___.--- 0 _ '21:..-- - ----0 -- - -0 0, 0 0 0 0 0 0 0 0 0 _ ., --- -92 - - 0 R l}/ ---...----_ �! �--G_ . C - F - --- T .__ 2.32 -- T0.00 ---0 6 c) AED excursion -4 -17 Envelope loss/gain 21 49 92 222 12 a) Wiftration b) Room ventilation 0 0 0 0 0 0 0 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 21 49 92 222 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 26% 18% 0 0 15 36 9 0 0 J86 26% 18% 0 0 -92 0 0 0 0 -222 0 0 Total room load Air required (cfm) 45 2 0 0 0 0 Calculations awroved byACCA to meet all requirements of Manual J 8th Ed. C -rk wrightsaft` 2018-Aug-2312:22:56 Cf� RightSui[e® Universal 2017 17.0.08 RSU08101 Page 6 ...SAILFISH 2253 MODEL- PACE- CRUCE RAGUSA RES.rup Cab = MJ8 Front Door races: E - wrightsoft° Right-J® Worksheet Entire House • QUICK CALCS, INC. .317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSQAOLCOM Job: Date: AUG 23, 2018 By: 1 Room name UTILITY ROOM CLST 2 2 E) posed wall 0 ft 0 It 3 Room height 9.3 It heal/cool 9.3 It heat/cod 4 Room dimensions 10.0 x 8.0 It 3.0 x 8.0 It 5 Room area 80.0 ftz 24.0 1? Construction U-value Or HTM Area (ftz) Load Area (ft2) Load .TY number (Bluh/ftZ°F) (Btuhltt2) or perimeter (ft) (Btuh) or perimeter (ft) (Bluh) Heat Cool Gross N/P/S Heat Cooi Gross N/P/S Heat Cool •6 - - 13A flocs -- -- -- 0.143 --- n --- --- 4.00 --- - 2:55 - - - 0 - 0 - 0 -- - - 0 - -- - 0 --- - 0 - - -- 0 --- 0 E--( 2 glazing, cir low-e 0.650 n 18.20 11.27 0 0 0 0 0 0 0 0 ' 2glazing clrbw-e 0;650 18.20 -0.... 0 0 0.. 0 0 0 _..._. Yt/ 13A-4ocs 0.143 -_0..._ ne _ 4.00 _11.27__. 2.55 . _ ...0 0 -- 0 0 0 - 0 6 0 . _ 0 11 2.glazing, clrbw-e_. ne 18.20 0 0 0.-.._. 0 0 0, 0 -- - - _ . 13A-4ocs ----_0_650 0.143 _ a _ 4.00 _--18.63 2.55 0 - ..__..- _0 0 .- _ 0 _-- 0 0 0 _.- 0 _ 6 2 glazing, cir low-e 0.650 a 18.20 25.40 0 0 0 0 0 0 0 0 2 glazing cir low-e 0.650 a 18.20 23.12 0 0 0 0 0 0 0 0 2 glazing, cir low-e- 0.650 a 18.20 23.12 0 0 0 0 0 0 0 0 _2 glazing-cir low-e-__ . ._.. 0.650 - .e. __. 18.20 _ _23.-12 _ _ ... ._ 0 . . _- _. _ 0 .. _. . 0 -0 -- 0 -- _ _ .-- _ 0. -0 _. 0 _ NI 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 _�.-._ 2 glazina-clr_low-e _.-- -_se-. -___18.20 _---- -__0 ...._-.__0 -- --. 0 __ _ __.._. --0' _ _ - 0 ----------0 - - ...----.0 13A-4ocs _---0.650 0.143 s 4.00 .--15.04 2.55 0 ,_ 0 0 ,---0 0 0 .. 0 0 0 2 glazing, clr low-e 0.650 s 18.20 11.27 0 0 �0 0 0 0 0 0 2 glazing, clr bw-e - _- - - 0.650 s- _- 18..201 -- --- 11.27 -.0 -- U - . - 0 -- - - • 0 -_ - --. 0 -0 - -0 -- - 0 Vp1 13A-4ocs 0.143 sw 4.00 2.55 0 0 0 0 0 0 0 0 2.glazlnp cir low-e- --- _ -.0.650 _.sw - _ _--17.50 ---._ 9 . -. --- - --- - 0 ------0 --- -0 0 __ _0 W/ ._. - - 0.650 w _18.20 4.20 2.12 0 -0 0 -- 0 ---. _ 0 .__._ 0 0 0 IL.C_-rG- 2 glazing, clr low-e 2 glazing, 0.650 w 18.20 23.12 0 0 0 0 0 0 0 0 0 2 glazing clr low-e 0.650 w 18.20 23.12 0 0 0 0 0 0 0 0 2 glazing clr_low-e .- -- _ -0.650 w ---.-18.20 23.12 _ _ _ _. _ 0 0 -. __..--. _-0 _ --- ----0 -- -- -0 ._-- -0 _ _ - ._ 0 _ 0 4N 13A-4ocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 2 giazing cir low-e 0.650 nw 18.20 15= 0 D 0 - =G C_ -- 16A30md... _ 0.032 -_ -- -- _ _ - 0.90 - _- _ 2.32 - -- -0 _.--- 80 ..- _ _-80 - - -0 _- _ - 72 -- - _ --- _1,86 _ -0 _- -24 - -0 .. _ 24 -- - -0 _ - _ 22 - - 56 F- 22A-tPl- - - - --_0.989 -- ---27.69.-- 0.00 - 80 -_0 - --0 - --_0 _.. 24... - 0 - -0 --0 6 c) AED emursion .64 -4 Envelope loss/gain 72 121 22 52 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants 0 230 0 0 0 0 Appliances/other 700 0 Subtotal Qines 6 to 13) 72 821 22 52 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 26 62 -22 .52 14 Subtotal 98 884 0 0 tb Duct loads 26/6 18% 25 159 269/6 185/6 0 0 Total room load 123 1043 0 0 Air required (cf m) 5 46 0 0 Calculations approved WACCA to meet all reauirements of Manual J 8th Ed. wright5oft- 2018-Aug-2312:22:56 RightSuiteO Universal 2017 17.0.08 RSU08101 Page 7 SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Cab = MJ8 Front Door faces: E ---wrightsofr Right-JU WorkSheet Entire House QUICK CALCS, INC. Job: Date: AUG 23, 2018 By: 317 ST.. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724656799 Fax 7724666796 Email: OUICKCALCS(PAOLCOM 1 -2 3 4 5 Room name Exposed wall Room height Room dimensions Room area BEDROOM 2 120 It 9.3 it heat/cool 12-0 x 12-0 it 144.0 ft2 BATH 2 6.0 It 9.3 it heat/cool 1.0 x 82-0 it 82.0 ft2 Ty Construction number Lkelue (Btuh/ItMF) Or HTM (Btuhflt2) Area (ft2) or perimeter (it) Load (Btuh) Area 012) or perimeter (it) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 • _ _- 13A flocs 2 glazing cir low a 2 glazing cir bw-e 13A flocs- 2 glazing, cir low-e_- 13A-0ocs 2 glazing, clr low-e 2 glazl% clr low-e 2 glazing cir low-e 2 glazing drbw-e___ 13A4ocs .24lazinq,_cir low-e _ 13A-4acs 2 glazing, clr low a 13A-4ocs 2.glazinq cir low-e 2 glazing, cir low-e 2 glazing cir low-e ?.glazing pjr low-e _. 13A-4ocs 2glaglnq clr low-e 16A30md.- _ --_.---, 22A tDl_... - - - _,.___.__,. .... 0.143 0.650 0.650 0.143 - 0.650 0.143 0.650 0.650 0.650 0.650_ 0.143 ._---- 0.1650 0.143 o.65o _ ....0.650 0.143 - 0.650 0.143 0.650 0.650 __-_- 0.650 0.143 0.650 --,-__._ 0.032 ---0.989 __ n n n ne -ne a a a a _e_ se se , s s' _._s.„ sw - sw w w w -_ w - nw _._rw ___. --- 4.00 18.20 18.20 4.00 ---18.20 4.00 18.2o 18.20 18.20 ___. 18.20:._ 4.00 18.20 4.00 18.20 -_--18.20 4.00 18.20 ____4.o0 18.20 18.20 _ 18.20, 4.00 1820 f-. 0.90 ---27.69. 2.55 11.27 11:27 2.55 -_ 18.63 2.55 25.40 23.12 23.12 _ 2312 2.55 _. 15,04 2.55 11.27 __-11.27_ 2.55 -17.50 2.55 23.12 23.12 -_-_23.12 2.55 _ _ 18_63 _-__2.32 ---0.00 112 0 16 0 ---- --0 0 0 0 0 __, __ __._0 0 ----- -_0 0 0 _ 0 0 _____0 0 0 0 0 __-----0 144, -___ 144 _, _ . _- 146 0 0 -- -0 0 0 0 0 0 __.._ --o 0. 0 ._._-. ---0 0 t _.- _ 0 0 0 0 ---_ 0 _-...._.73 . 166 •90 __-_ 0 - 0 0. 0 0 0 0 -------_o 6 0 _..... -- _Q 0 -.-- _.- _.0 0. 0 0 _ ------,.-0 : __. 190 - - 0 96 0 0 0 _ 0 0 0 0 0 .--. _0 0 -__- o 0 0 a_0-_.-____0-_._. 0 ___ 0 0 0 0 0 ---__..__-_--0 144 -.__- .._12 383 0 291 0 - -- --0 0 0 0 0 0 _ _-- 0 0 0 0 _ -__ 0 0 0 0 0 -- 0 ___...- _129 --_--_-332 _ _ _._ 243 0 180 0 -- --0 0 0 0 0 0 o .__-._--- 8. 0 0 -- -0 0 0 0 0 0 ._, 9 0 0 ..- ___._ 9 0 ------- D 0 0 __...- ----0 __ ---. -82 - _-- 82 0 0 0 - - .__ 0 0 0 0 0 0 Q 0 0 _______._0 0 0 0 0 0 0 -__-_- 0 _ ._._ . _82 -- 6 W --�_-(-- - ... N/ _---_ .„2glazirxl..cirbwe.__..• �/ -_r--G ig13AAocs tW/ 77 F 0 0 0 0 -�-0 0 0' 0 0 -_--T__0 --.-- _ 334 __-0 6 c) AED excursion -138 -31 Envelope loss/gain 1135 619 577 371 12 a) Infiltration b) Room ventilation 199 0 53 0 99 0 27 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1100 0 Subtotal Qines 6 to 13) 1334 1773 676 398 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 26% 18% 0 0 17 1351 346 0 0 40 1813 326 26% 185/6 0 0 111 787 201 0 0 75 473 85 • Total room load Air required (of m) 1665 65 21 94 94 988 38 558 25 Calculations awroved bvACCA to meet all requirements of Manual J 8th Ed. wrigttatsoR" RightSuite® Universal 2017 17.0.08 RSU08101 2018-Aug-23 1Pa e 8 ...SAILFISH 2253 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E g + wrightsoft Right-J® Worksheet Entire House • QUICK CALCS, INC. .317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: QUICKCALCSQAOLCOM Job: Date: AUG 23, 2018 By: 1 2 3 •4 5 Room name Fed wall Room height Room dimensions Room area CLST 3 20 If 9.3 ft heal/cool 7.0 x 20 ft 14.0 ft2 BEDROOM 3 120 ft 9.3 ft heal/cool 12-0 x 12-0 ft 144.0 ff2 *Ty Construction number U-value (Btuhht--F) Or HTM (Btuhrtfz) Area Qfz) or perimeter (ft) Load (IM Area Qfz) or perimeter (ft) Load (Btuh) Heat I Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool +6 • 11 f-C n n _ n .. ne _ ne_ a a a a se s s sw _sw- w w w - w - nw nw _._ -_.. 4.00 18.20 _._ 18.20 4.00 18.2o, 255 11.27 _ __ 11.27 2.55 18 0 __ ._ _ __ 0 0 0 19 0 ._ . - __ __0 0 0 0 0 0' 0 _..---_o 0 0 0 0 _.Q._-..__.__Q_-.___-._0__. 0 ---__.__T_4 0 0 0 -.-_ _._ . _-Q 0 _- _- 0 _- - - __74 �._ 2 74 0 0 0 0 _ _--_-r 0 0 0 0 _d`__•. 0 0 0 0 0 0 ___..._ 0 0 0 _ _--- .--0 0 - - ----0 __ __ _.. 93 _._ 55 13A flocs 2 glazing, clr low-e 2 glazirxj cir low-e . _ . 13A flocs 2glazing_ cir_bw-e 13A-4ocs 2 glazing cir low-e 2 glazing, cir low-e 2 glazing, cir low-e 2.giazing.-clr-low_e-_._. 13A-4ocs ---, 13A-flocs 2 glazing, cir low e .2glazingcirbw-e_._. 13A-4ocs 2.41azinq cir bw-e- -- 13A-4ocs 2 glazing cir low-e 2 glazing cir low-e 2.glazing,, clrlow-_8 -__ 13A41ocs 2 glazirg, cir bw _e ._.__..- ..N -. 0:143 0.650 , 0.650 0.143 0_650 0.143 0.650 0.650 0.650 _-.___0.650_..e_ 0.143 ------_0.650._se_. 0143 0.650 ______0(R0._s.._-_.18.20 0.143 --.--,0.650 0.143 0.650 0.650 -_ _ _ _0.650 0.143 -._-_ 0.650 _�_0.032 47 0 .--- _ --- . _0 0 0 -_-__----_.. 0 0 0 0 -... __,__._0._..___.._0 0 _. ,0 0 0 0 �_. -_-0 0 0 0 ------_._ --0 0 -- -- 0 _-_J _.- 32 112 0 _ __ __ _16 0 0 0 0 0 0 0 _._-._� 0 6 0 _0..__..__-0.___-.-_._0..._ 0 -a_-_---__0 0, 0 0 _ _--. - -0 0 -- ----0 - - ------144 _-_ 144 9.6 0 - - 0 Y 0- 0 0 0 0 0 ___.____0._-.__ 0 0 0 0 0 _-_-------.0 0 0 0 _. _. -_ ._-0 0 --0 --_..___144 --} 383 0 291 0 _._. - ..-__ 0 0 0 0 -._0 0 _.--....- 0 0 0 0 ---- --- ___0 0 0 0 --- ---. - 0 0 -- - -0 _---_.-129 ---- - 243 0 180 0 -__-,___--- 0 0 0 -.0 .... ------ 0 0 - _...._..._--0. 0 0 .__.._.0 0 _._- _._-___0. 0 0 0 - - - �.-- '0 0 -- - - - 0 _� . Vj/ __�-(a. 1}/ _G..2glazina_cirbwaa t�/ _�. _ _ VN -L-. -G- _C _ _ ...16A-3Omd F._ 4.00 18.20 18.20 18.20 18.20 4.00 __.-18.20..�_15,04 4.00 18.20 4.00 ---.18.20 4.00 18.20 18.20 -- . 18.20 4.00 - .18.20 ~. _ _0.90 __-18.63 2.55 25.40 23.12 23.12 __23.12 2.55 2.55 11.27 _--1127_-.__._-0-___ 2.55 - �7-50 2.55 23.12 23.12 _ 23a2 2.65 18_63 -- ._2.32 ---0.00 -, 0 . 0 6 0 - -0 0 _ _ _ _.._0 0 0 0 -----0 0 0. . 0 _ _ _-_._ �0 0 - - - 0 -_-----_ 14 __--_ 14 ---_0 6 c) AED excursion -6 -131 Envelope loss/gain 142 73 1135 627 12 a) Infiltration b) Room ventilation 33 0 9 0 199 0 53 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 1000 Subtotal Qines 6 to 13) 176 82 1334 1680 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 26% 18% 0 0 -176 0 0 0 0 -82 0 0 26% 18% 0 0 87 1421 364 0 0 61 1741 313 Total room load Air required (cfm) 0 0 0 0 1785 68 2055 91 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -� wrightsofV 2018-Aug-2312:2256 RightSuite® Universal 2017 17.0.08 RSU08101 Page 9 SAILFISH 2253 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E wrightsoft® Right-J® WOrksheet Entire House • QUICK CALCS, INC. . 317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: OUICKCALCS@AOLCOM Job: Date: AUG 23, 2018 By: 1 2 3 •4 5 Room name Exposed wall Room height Room dimensions Room area FAMILY ROOM 44.0 ft 9.3 ft heat/cool 1.0 x 261.5 it 261.5 If NOOK 19.0 it 9.3 ft heal/cool 1.0 x 149.5 ft 149.5 W +Ty Construction number lJ-xalue (Btuhlftz-°F) Or HTM (BtuhRtz) Area pt2) or perimeter (ft) Load (Btuh) Area 0112) or perimeter (ft) Load (Bluh) Heat 0001 Gross N/P/S Heat 0001 Gross N/P/S Heat Cool +6 11 - 13A40cs - 2 glazing, cir low-e 2glazing_4--__,._..0...__ 13A-400s 2 glazing, cir low-e 13A flocs 2 glazing cir low-e 2 glazing cir low-e 2glazing cir•low-e 2glazirxb-clr_bw,e_-._._ 13A-4ocs -2glazinq clr,low-e.---- 13A4ocs 2 glazing cir low•e 2gl-azir@ cir - 13A-4ocs 2.glazirxl clrbw=e -- 13A-4ocs 2 glazing clr low-e 2 glazirxj cir low-e 2 glazing cir low_e-- 13A-4ocs 2 glazirxl - clr low=e -22A4RL_-.-- - - ------------ 0.143 0.650 0.143 0.650 0.143 0.650, 0.650 0.650 ____-.0.650-...e_ 0.143 ----0.650 0.149 0.650 __0A0__s__ 0.143 ------0:650 0.143 0.650 0.650 - -0.650 0.143 0.650 0.032 --- -0.989 - -- 0 ._ - _._...0 0 0 o 0, 0 0 _.;_0,_ 0 ._ __ 0 165 0 .__ 437 0 0 _--_-,_ -- 368 174 182 _.. - _0 0 0 --- --0 0 _ .___-. 0 0 - 0 0 0 0 _.--_-- 0 0 _ _-__ ___ 0 105 0 _.. _.-271 0 .._ _- _0. 234 222 231 -- _ _ - 0 0 0 _ - -- 347 .. _ 0 _n_.. n ne _ne a e a a se _ se_ s s sw _sw_ w w- w -w nw rrvv -_ . 4.00 18.20 4.00 18.20. 4.00 18.20 18.20 18.20 ___1.820..___23.120w._.-_.___..0 4.00 _18.20 4.00 18.20 _,_ 18.20 4.00 18.20 4.00 18.20 18.20 --18.20 4.00 18.20 _ �.0.90 ---27.69..._ --2.65 11.27 2.55 18.63 2.55 25.40 23.12 23.12 2.55 15.04 2.55 11.27 _ 11.270 2.55 _ 17.50 2.55 23.12 23.12 _23.12 2.55 18.63 ._--2.32 0.00 T----149.._.. 0 0 _ 0 0 0 01, 0 0 _,149 0 0 0 0 0 0 0 -.--._-- 0 82 20 __..__.___0- 0 _._-0 138 0 0 - 0 0 0 _. _ _ .262 44 59.6 0 0 0 0 0 0 -..._.____ 0 0 -__--0 330 364 -- __._0 0 - 553 0 364 - --0 0 0 379 0 0.----_._.0 0 0 0 0 0 _____.___0 0 __- 0 209 225 ._._ _-_0_.r_.-__24-_ 0 ------_0 352 0 462 - _.0 0 0 0 0 0 0 0 0 0 _._-0--_ 0 -_- 65 0 0 Q 112 10 10 - -:0 0 0 0 0 _ ._._ 0 0 0 0 0 0 _.__0 0 --_._-A 41 0 - 24_ 0 _0 82 0 0 _0 0 0 N1 ._ W_ 1�/ _--- Vj! 102 20 0 0..__._ VA -�-__ 1Q/ _ 1�J L-C' F_. _. 158 0 20 .. -0 0 0 .. _-_262 _ _. _ 234 1218 _.__ _ _607 -0 ---- ---150 -150-- __-- 150 -- 19 _ ..__ 134 _ 526 6 c) AED excursion -15 9 Envelopeloss/gain 3659 2219 1986 1418 12 a) Infiltration b) Room ventilation 728 0 195 01 314 0 84 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 300 Subtotal Olnes 6 to 13) 4387 2414 2301 1802 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 260/6 180/0 0 0 0 4387 1123 0 0 0 2414 435 28% 18% 0 0 6 2307 590 0 0 15 1816 327 Total room load Air required (of m) 5510 210 2849 126 2897 110 2143 95 Calculations atwroved byACCA to meet all reouirements of Manual J 8th Ed. C -ry wrightsoft" 2018-Aug-2312:22:56 RightSuiteO Universal 2017 17-0.08 RSU08101 Page 10 SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E Duct System Summary Job: -- wrightsoft® Date: AUG 2s, 2018 • Entire House By: QUICK CALCS, INC. • 1317 ST. LUCIE LN., FORT PIERCE, FL 34946 Phone: 7724666799 Fax 7724666796 Email: OUICKCALCS@AOLCOM • For: CRUCE-RAGUSA RESIDENCE, PACE 2000, INC 5509 HICKORY DRIVE, FORT PIERCE, FL Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply / return available pressure 0.500 / 0.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1187 cfm 1187 cfm Total effective length (TEL) 177 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 988 38 25 1.000 5.0 Ox 0 VIFx 23.0 115.0 sti BEDROOM 2 c 2139 65 94 1.000 7.0 Ox 0 VI Fx 17.0 95.0 BEDROOM 3 c 2055 68 91 1.000 7.0 Ox0 VIFx 26.6 115.0 sti DINING ROOM h 2461 94 92 1.000 7.0 '0x0 VIFx 21.4 115.0 st2 FAMILY ROOM h 5510 210 126 1.000 7.0 Ox0 VIFx 35.8 135.0 st3 KITCHEN c 2210 85 97 1.000 7.0 Ox0 VIFx 27.4 115.0 sti LIVING ROOM c 2073 46 91 1.000 7.0 Ox0 VIFx 19.1 115.0 st2 LIVING ROOM -A c 2073 46 91 1.000 7.0 Ox0 VIFx 26.6 115.0 st2 MASTER BATH h 3866 147 95 1.000 7.0 Ox0 VIFx 33.2 135.0 st4 MASTER BEDROOM h 2619 100 95 1.000 7.0 Ox0 VIFx 32.8 135.0 st4 MASTER BEDROOM -A h 2619 100 95 1.000 7.0 Ox0 VIFx 41.5 135.0 st4 NOOK h 2897 110 95 1.000 7.0 Ox 0 VIFx 42.4 135.0 st3 PANTRY c 101 2 4 1.000 4.0 Ox0 VIFx 23.7 115.0 st1 TOILET h 1103 42 33 1.000 5.0 Ox 0 VIFx 20.4 115.0 st2 U11 LITY ROOM c 1043 5 46 1.000 6.0 Ox 0 VIFx 4.1 95.0 WIC h 787 30 17 1.000 4.0 Ox 0 VI Fx 32.8 135.0 st4 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 605 609 1.000 775 12.0 0 x 0 VinIFIX st4 Peak AVF 377 302 1.000 853 9.0 0 x 0 VinIFIX st2 st3 Peak AVF 320 220 1.000 917 8.0 0 x 0 VinlFlx sti st1 Peak AVF 1 513 1 43$ 1 1.000 1 777 1 11.0 1 0 x 0 VinlFlx + wrightsoft® RightSuite® Universal 2017 17.0.08 RSUG8101 ...SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJ8 Front Door faces: E 2018-Aug-23 12:22:58 Page 1 Name Grill Size (in). Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mati Trunk rb1 Ox 0 1187 1187 0 0 0 0 Ox 0 VI Fx wri htsoft° 201&Aug-2312:22:58 ,.._ 9 RightSude® Universal 2017 17.0.08 RSU08101 Page 2 +� ...SAILFISH 2263 MODEL- PACE- CRUCE RAGUSA RES.rup Calc = MJe Front Door faces: E