Loading...
HomeMy WebLinkAboutProject Informationt Manual S Compliance Report Job: Lot 18 Block 1 Waterston... wrightsoft® Date: Entire House By: SIR DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project [nformation For: ADAMS HOMES 5380 Lugo Street, Fort Pierce, FL 34951 Cooling Equipment Design Conditions design DB: 90.4OF Sensible gain: 22025 Btuh Entering coil DB: 76.5OF Outdoor design WB: 77.4OF Latent gain: 4014 Btuh Entering coil WB: 63.3OF Indoor design DB: 75.0 OF Total gain: 26040 Btuh Indoor FIR 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment. type: SplitASHP Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfmSensible LRECEIVEDManufacturer: �Latent capacity: 22678 Btuh 103% of load capacity: 4723 Btuh 118%of loadTotal capacity: 27400 Btuh 105%of load SHR: 83% ty, Permitting Heating Equipment Design Conditions Outdoor design DB: 41.0 OF Heat loss: 24348 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SplitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Output capacity: 26646 Btuh 109% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 6.3 kW 88% of load Temp. rise: 21 IF Meets all requirements ofACCA Manual S. Entering coil DB: 69.5OF Capacity balance: 37 OF Economic balance: -99 OF .` �' - wrightsoft' 2021-Jan-2614:3233 ^'� aM:*o.•��,nw .��mwM Right-Sute®Uriversal202121.0.02RSU23828 Page ��...aterstone1720AGR�Lot18BIkiWaterstone1720AGR.nQ Calc=MJB Housefaces: N Component Constructions Job: Lot 18 Block 1 Waterston... -- wrightsoft0 Date: Entire House By: SIR DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Enialect Intormation For: ADAMS HOMES 5380 Lugo Street, Fort Pierce, FL 34951 Design Conditions Location: St Lucie Co Intl, FL, US Indoor: Indoor temperature (T) Heating 70 Cooling 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (grAb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - Wet bulb (T) - 15 (L 77 ) Method Simplified Wind speed (mph) 15.0 7.5 Construction quality Fireplaces Average 0 Construction descriptions or Area U-value Insul R Htg H711A Loss Clg H711A Gain ft� Btu"*F ftz°F/Btuh BtuMP Btuh BtutVft� Btuh Walls Blk wall, stucco ext, r-4.1 ext bd ins, 8" thk, 1/2" gypsum board int fnsh 1613-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Partitions 12C-Osw. Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'S44' wood frm, 16" o.c. stud Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 1.33 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.17 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2X2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.33 ft overhang (5.3 ft Window ht, 3.58 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, dr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.31); 11.83 ft overhang (1 ft window ht, 0.67 ft sep.); 6.67 ft head ht 213-2fv: 2 glazing, clr low-e outr, air gas, vnl fan mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 11.83 ft overhang (6.7 ft window ht, 2.75 ft sep.); 6.67 ft head ht n 377 0.201 4.1 5.83 2196 4.06 1530 e 85 0.201 4.1 5.83 493 4.06 343 s 483 0.201 4.1 5.83 2816 4.06 1961 w 224 0.201 4.1 5.83 1308 4.06 911 all 1169 0.201 4.1 5.83 6812 4.06 4745 e 5 0.049 19.0 1.42 7 2.59 13 s 15 0.049 19.0 1.42 21 2.59 39 all 20 0.049 19.0 1.42 28 2.59 52 276 0.091 13.0 2.64 729 1.31 362 n 16 0.330 0 9.57 156 9.90 162 w 49 0.330 0 9.57 469 26.3 1289 all 65 0.330 0 9.57 626 22.2 1451 n 7 0.330 0 9.57 66 8.52 58 s 7 0.330 0 9.57 66 8.52 58 all 14 0.330 0 9.57 131 8.52 117 e 33 0.330 0 9.57 313 21.6 707 e 4 0.330 0 9.57 38 11.6 46 e 7 0.330 0 9.57 64 9.72 65 .� -r�F wrightsc ft- 2021-Jarr2614:3213 ACCP. Right-Sute®Uriversal2021 21.0.02 RSU23828 Page 1 aterstonel720AGRtLotl8BlklWaterstorel720AGR.np Calc=MJB Housefaces: N ' 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 10 0.330 0 9.57 93 9.90 97 thk; NFRC rated (SHGC=0.23); 1.33 ft overhang (3.17 ft window ht, 0.83 ft sep.); 6.67 ft head ht A 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 16 0.330 0 9.57 156 8.52 139 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 10C-m: 2 glazing, clr low-e outr, air gas, mtl no brk frm mat, clr innr, 1/4" w 18 0.550 0 16.0 285 12.6 226 gap, 1/8" thk; NFRC rated (SHGC=0.70); 50%drapes, medium; 11.67 ft overhang (6.7 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 17 0.330 0 9.57 161 9.90 166 thk; NFRC rated (SHGC=0.23); 11.67 ft overhang (5.3 ft window ht, 0.83 ft sep); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type a 20 0.600 6.3 17.4 350 17.6 353 11 DO: Door, wd sc type n 18 0.390 0 11.3 201 11.4 203 Ceilings 1613-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1/2" 1899 0.032 30.0 0.93 1763 1.69 3209 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 206 0.989 0 28.7 5908 0 0 c wrright soft® 2021-Jarr2614:3233 ,4cc% RigM-Srite@Uriversal 2021 21.0.02 RSU23828 Page 2 aterstone1720AGR\Lot18BIk1Waterstor)e1720AGR.np Calc=MJ8 Horsefaces: N - - wrightsofte Project Summary Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project Information For: ADAMS HOMES 5380 Lugo Street, Fort Pierce, FL 34951 Notes: L. S. 1-26-21 VWK Desim. Information Weather: Winter Design Conditions Outside db 41 OF Inside db 70 OF Design TD 29 OF Heating Summary Structure 20857 Btuh Ducts 3491 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 24348 Btuh Infiltration Method Construction quality Fireplaces St Lucie Co Inti, FL, US Simplified Average 0 Heatingg Cooling Area (ft2) 1720 1720 Volume (ft3) 15844 15844 AirchangesJhour 0.38 0.20 Equiv. AVF (cfm) 100 53 Heating Equipment Summary Make Carrier Trade Model 25HBC530AP03 AHRI ref 204840289 Efficiency 8.5 HSPF Heating Input Heating output 28200 Btuh @ 47°F Temperature rise 27 OF Actual air flow 947 cfm Airflowfactor 0.039 cfm/Btuh Static pressure 0.40 in H2O Space thermostat Capacity balance point = 37 OF Backup: Input = 6 kW, Output = 21472 Btuh,100 AFUE Job: Lot 18 Block 1 Waterston... Date: By: SIR Summer Design Conditions Outside db 90 OF Inside db 75 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr4b Sensible Cooling Equipment Load Sizing Structure 17182 Btuh Ducts 4843 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swin multiplier 1.00 EquipmN sensible load 22025 Btuh Latent Cooling Equipment Load Sizing Structure 2841 Btuh Ducts 1173 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4014 Btuh Equipment Total Load (Sen+Lat) 26040 Btuh Req. total capacity at 0.75 SHR 2.4 ton Cooling Equipment Summary Make Carrier Trade Cond 25HBC530AP03 Coil FX4DNF031L00 AHRI ref 204840289 Efficiency 12.5 EER,15 SEER Sensible cooling 21300 Btuh Latentcooling 7100 Btuh Total cooling 28400 Btuh Actual airflow 947 cfm Airflowfactor 0.043 cfm/Btuh Static pressure 0.40 in H2O Load sensible heat ratio 0.85 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .� � wrightSoft® 2021-Jarr2614.32:33 .� RigH-Sute®Uriversal 2021 21.0.02 RSU23828 page 1 'CC-P`...aterslone1720AGR\Lotl8BlkiWaterstone1720AGR.nQ Calc=W8 Hoisefaces: N `- - wriyntsofts Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 18 Block 1 Waterston 17... Date: By: SIR 1 Room name Entire House Laud 2 6posed wall 206.0 ft 9.0 ft 3 Room height 9.0 It 10.0 it heat/cool 4 Room dimensions 9.0 x 6.5 it 5 Room area 1769.3 ft2 58.5 ft2 Ty Construclion U-value Or HTNI Area (ft2) Load Area (ft2) Load number (Btuh/ft2-F) (Btuh/ft2) or perimeter (ft) (Btuh), or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 -C 2A 2 �I e 0 330 n 5 83 9.67 4 Q6 990 400 16 377 �r 0 2196 156 1530 162 0 0 �3 30 �r0_ 0 0 0 0 G 2A 2ov w _ 0 330 9.57 8 52 b7,xnx 0 ..- �_ 66 M.. w 0 w +0. ? 0Q W 1613119ad 0.049 e 1.42 2.59 5 5 7 13 0 ... 0 0 0 11 �Ikwallstu000ext 2A2ov Q201 0330 a r e , 583 + 957,2162 f f 148 33 t , 00A 4we 26 2fv Q 330 r e i� 9 57 11 58 4 , 4 38 46 2B 2fv A 330 e ` S 9 57 9.72 r 7 ' 7 s 64 65 0 0 r. 0 0 " 0 0 0: allJ0 u_ .. w0.600 e_ 17.40. _ 1Z5$ a 20_ ".> .,.20 LL350L.a 353 s'0 W 16B-19ad 0.049 s 1.42 2.59 15 15 21 39 0 .0,-u 0 0 0 Blkwall stu000ezt ss 2A 2ov 0201 0 Wo s { 583 957 406 516 10 and 483 s2816 1961 0 0 0 � 0 s 9 9Q " : °� 10 93 97 0 0 0 0 2A 2ov 0.336 s a 957 852 7 1' 7 66 58 0 0 0 0 _ :2A2ove` 0330 s 957 852 2_. Blk wall, stucco e)d _ 0.201 w 5.83 , 4.06 308 224 1308 911 0 0 0 0 10C-m 0.550 w 15.95 12.64 18 18 285 226 0 0 0 0 2A-2ov 0.330 w 9.57 2629 49 3 469 1289 0 0 0 0 2A-2ov 0.330 w 9.57 9.90 17 17 161 166 0 0 0 0 12COsw 0091 264 137 294 27690'- z 729 362 90 4 n 238 118` a1D0 43 1.8 , A f8 ,s €20.1 �203.,, 0 0 0: C 166 30ad 0.032 0.93 1.69 1899 18- 1763 3209 59 w 59 54 99 F 22A tpl 0989 2& 68' era 0:00 1769 206 _ 08 ., 59 �� 9258, s 0 ,r..u. s....,...,v., .,.x. «. ,,, x.. a...........' .i k...................i,,; .,�.e...._.n� * _'�*. �.u< ....e.-._.�2.w»... ..3 a .wy w*...... +.k3z. .di .u�.uu:du.. +�..auf«..w<.Wi' .-w'n�+i..,.+iw.._✓1 »,.a..,:..� _ +. G...Y..,.._. i.5w .aw. _ ....... .:.. ✓... .F....w,_e...........»..�_.w.w.w'n'4e ..+a..u.+.._ .«....._ ._.i:itd. xniw.w +s.mt.,,: �� �.�u.. _=..u.'LY'..M.«.�$..s. .,r.,v°ii,',u. _.,...,..,._ s Y� ..•.v `' " w -F::.t.g.."v1 _l ,�.� .:.. �.�.._...< � � � ,.=n,-.z .r... tea... � n.,.e.ev._ ..,. _ ...-.._...., r✓.w. _...". ,-k, ..«.«rm, u.3.��. Ja+t �....�....w .,,�.v+r:u. i.Gy.:L3,,.... x,.ir,...»s.� ...,� ,<,wtio-�5.. .w�RFn.:..di::.�. , ., - _ ' _ lz;;,_ Z2= ml= M=° � w 6 c) AED excursion 1030 -35 Envelope loss/gain 17659 12968 550 182 12 a) Infiltration 3198 894 0 0 b) Room ventilation 0 01 0 0 13 Internal gains: Occupants pa 230 4 920 0 0 Applianceslother 2400 600 Subtotal (lines 6 to 13) 20857 17182 550 782 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 20857 17182 550 782 15 Duct loads 17 % 28% 3491 4843 17% 28 % 92 220 Total room load 24348 22025 642 1003 Air required (cf n) 947 947 25 43 Calculations approved bvACCAto meet all reaulrements of Manual J 8th Ed. .�-*- =I i!R sott 2021-Jarf2614:3223 fi RighFSute®Universal 202121.0.02 RSU23828 Page 1 aterstone1720AGR\Lot18BIk1Waterstone1720AGR.nns p Calc=MJ8 Hoefaces: N `-r - wrightsofr Right-M Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM Job: Lot 18 Block 1 Waterston 17... Date: By. SIR 1 Room name ktsir Bth kktrwic 2 Exposed wall 26.0 it 0 it 3 Room height 8.5 it heaV000l 9.0 it heattcool 4 Room dimensions 1.0 x 141A it 1.0 x 61.9 it 5 Room area 141.4 ftz 61.9 ftz Ty Construction U-value Or HTM Area (it) Load Area (ftz) Load number (Btuh/ftz-fl (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 '$Ik wall stucco ext 2A 0201 n r 5 83; 4 06 120 i13 659 459 0 0 . 0 � 0„ 2ov 0330 n - 951' 990 0 ; 0 0 0 0 0 , 0 0' 2A 2ou _ Q330 !l ..� 957 852 , . ,'7 .� 0 . � _ 66 : 0 x .,0, Z W 161319ad 0.049 e 1.42 259 0 0 0 . 0 0 _ 0 0 x. 0 116lkwall stu000ext 2A 2ov 0201 0.330 e�; 583' 406 0 0' 0 0 0 0` 0' 0 0 0 ? 0 0 0' 2B 2N 0 330 e 9 5T 11 58 0 0 0 0 0 0 0 0 26 2fv r 0.330 a 9.5T 9:72 , E rf,A r0 0 0 0 0 " W 166-19ad .0.600 0.049 s 1.42 2.59 0~ 0 0 0 0 0 0 0 Blkwall stu000ext 2A2ov 0201 0;330 `ems , s 5a 957, 4.06 9.90 ; 0 ° 0 0 { * k 0 z 0 0� 0 �0 0 0 0 = �0 - 0 0 0` 0 y 2A2ov 0330 s` 967 8.52 000' 2A2ov($30 �_s 957: w. 0 K w0 �0 Blk wall, stucco e)d 0201 w 5.83 4.06 0 0 0 �� `0 . - 0 0 0 0 10C-m 0.550 w 15.95 12.64 0 0 0 0 0 0 0 0 2A-2ov 0,330 w 9.57 2629 0 0 0 0 0 0 0 0 2A-2ov 0,330 w 9.57 '9.90 0 0 0 0 0 0 0 0 R 12C Osw Q;091 2 64,' 13 L 88 t 88 232 115 0 0 0 0' L.—p. 1:1DO K Q;390 __n.w .m 1131. .. Jt 43 H.0 .ram0 r 0 Y . r 0 0 C 1613-30ad 0.032 0.93 1 69 148 148 138 250 69 69 64 116 _w - , ifM ._ _ _ ._ ,H. n, �r.. -u .'m ,' _..-... _..a�...v...�..-_...�....�aa.-..x u......,�� _ „m..a..M 4 Ys 7 .....-..., .K'....v..vyiw4.u..-....w..v. .,..r�.s,_.w......--•A _.sra2.�: _ h.,..vm ...✓... � ...e.+o- <.d`z w...'w �,. o.� � .v..C.�.sm._v1 �"....a ..w... .®..P .:.....r.d+�. _...tom "' +u.a...�. .ir:�, +:.,,.�w� ,..,--.,3i x >.w��-..vvw.,,�.._w..a...,.. .....,tr..,...-,,�.n_� ��.��5 �m' w:..L kw,.,.vawE ....`....,..,..✓..... „�, S.«.,.,,. "� - �,.k ��"�.z s....w,r ...z u..c .... C. `.c.-a, _.,.... * t ..? =.Lz.........W.,.........t.�+..,_' ...�. _ ., ..... �...-.n.z.ak,. r....-� .L....* .,.... .,...`.k wcm.,eT9v..= ...,....... 1w ..x..x. r _2 .....¢...�.....'GR :.... -....- .vA.....am._ -.w.a= ...w ..etMEM 5..0 r. cr ' .. .; .y..'.. `�.y'..' '9 1"F�.v:..,.:.}. �Y'^"....: �.w>..«w...:;: uw.0 v..4.n "k' »w.cwT 1G✓� ..�u.....-... v'5"u^ i.�».v.. ,.=...r a,v,. -.d.� � �Y w, � t�i YF,; .La��qq w"�. .�„ .v.... E........ .....,.....».,.20',..xa s. t;.._az...., .�..3 rcravx. ..w. k la.. ....:v ..,,.3-.. mow.,,..«. u„-... tn... ..,.. ....rv.. ..w.._'.." .,,�...s.,x,i 6 c) AED exalrsion -41 -5 Envelope loss/gain 1841 . 843 64 111 12 a) Infiltration 276 77 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Applianceslother 0 0 Subtotal (lines 6 to 13) 2116 920 64 111 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2116 920 64 111 15 Duct loads 17% 28%, 354 259 17 % 28 % 11 31 Total room load 2471 1179 74 142 Air required (cfm) 96 51 3 6 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rk- wrGgr+tsoTt• 2021-JarF2614:3233 A& a Right-Sute®Universal 2021 21.0.02 RSU23828 Page 2 aterstore1720AGR\Lot18BIk1Waterstore1720AGR.np Calc=MJ8 Hoisefaces: N wrightsofta Right-M Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 18 Block 1 Waterston 17... Date: By: SIR 1 Room name Wr Bdrm Livrm 2 Exposed `mall 34.5 ft 78.5 ft 3 Room height 9.1 ft heaV000l 9.0 ft heaVcool 4 Room dimensions 15.5 x 15.0 ft 1.0 x 841.8 ft 5 Room area 294.5 ftz 841.8 ftz Ty Or HTM Area (ftz) Load Area (ft2) Load number�on BU�aue ( `) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ��l Blk wall stumo eM $0 201 `0330 n ` 5 n 5.83 957 ,4.06 9.90 ' s 152 s �i6 .136 0 791 156 551 40 ;, + x 40 233162 �-(' 2A 162 r 0 0 0 ;d0 2ov • 0330 ,.a!? w. 957 __ 85? _.' �„ 4 ti_ >, W 166 19ad 0.049 a 1.42 2.59 0 0 0 0 5 5 _, 7 13 11 a'?Blkwall stuaoext �2A2ou "� 0201 9330 a a 5.83 406 �1.6� ' 0 0 0 ' 0 0 �0 0 0 52 0 21' �� � 0 124 e0 -86 26 2(v 0330 e - w9.57 9.57 11 58 0 0 0 p 4 ;=,Oi 262N 0330 e,' 9.57 972 , 0 0 " 0 0 4 1 7:' 7 38 46 p600 a 17.40 _�17.58 � ''0 , r > 0 a� 0 Ww.O »20 ° 20. 56 ,_ '353, W 1613-19ad 0.049 s 1 A2 2.59 0 0 0 0 15 15 w_. 21 _ 39 Blk wall stucco ext 2A 2ov 0201 0330 s s'• 5.83 9.57 406 990 0 0 ` 0 0 0 0 0� 0 236 10 - 226 10 1319 ' 93 919 97! PA f957„ .57 2A2ov_n�_, 8.52 Blk wall, stucco ext 10C-m 0.201 0550 w - w 5.83 15.95 4.06 12.64 124 0 91 0 532 0 371 0 184 18 133 18 775 285 540 226 2A-2ov 0.330 w 9.57 2629 33 2 313 859 16 1 156 430 2A-2ov 0.330 w 9.57 9.90 0 0 0 0 .17 17 161 166 0091 264 1.3 0 0 0 0 716 ' 98 r259 129; ,]. 11.43 , o , a v .x0 . 5. 01 �L,.. Q ,� 18 'LL. 78 .� ],...;..201 C 16B-30ad 0.032 0.93 1.69 329 329 306 556 906 , 906 841 _..., ,203 1530 ¢=...295 1w.-u35 L 98.9, D, 842.>a� 2251 7 0; > a 79._ r ew ---.•--c ter; r-*'�, EL x Z._a= > Z_'3Z ,, x- a_ _ a. f= M= = ...tea..,., w _ �,... .,.,... .... � ,.2>. �...b>..w, ....>v...�,..,3:i- ,.....�,w..,... - - �«,.w .,._. ....,...s..us.-.«a...�l.,...m...= ,.s, xa..,.,.....:4....i .vF_o,,..3 .,.->1�......, -� .n .._...emu• r .. ,.z, R� 2 _ a m ....,.._ s_....r�..,.+,�"W,.....,.. _s �A..,....- A.s,.,w�.. ,.._..v,.,,.e: Tl ..a ,._......�. ._..,w.>s,.. w >,,.2.r.a..� 'i+a.,...,..:..-.>+�.-.._.«.w.,'_'...... .ws».....k.........-.... ....,...:dl _mw..e....w.�:.w .ay..v.....�.,�.: «. .�xi...w,.=:A,...> .... -.... ,.,.i...:...,.....�_ ..._w..>..._.....,L, .�->,..-r..r...w .« >::,. .,..aa= :2.,. ..>r... .s- 7.. k-,.... w.a,..-,�,�..'�"'..,.. ,.., .�..._ ..�.�,.......�_.-.._�:s�., .>....-..._. ...-_ .�..,...x.:.. �.,._.a_s. .,,.,.,..G...c^.`n->..1,.....ih.. .,w. u�t..s„ v_,.:,,.-.,� _.,....._...._..�_ .-....«.-.... uZ, �.,..,s..,... ......e. � .w...aay..o-�.v�.. .. _.-..L_ r..,.....`« Y ., F ,t•; jR `4 v*d ..:...«....... excursion .-irI'J''P .u4..«v". 231 6 c) AED 796 Envelope loss/gain 3087 2730 7179 5800 12 a) Infiltration 634 177 1222 342 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 3 690 Appliances/other 600 1200 Subtotal (lines 6 to 13) 3721 3738 8401 W32 Lessexlemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3721 3738 8401 8032 15 Dud loads 17 % 28% 623 1054 17 % 28 % 1406 2264 Total room load 4344 4791 9807 10296 Air required (cfm) 169 206 381 443 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A%-rk- wrigtitsoTC ° 2021-Jan-26143233 K Right-Sute®Unversal 2021 21.0.02 RSU23828 Page 3 aterstone1720AGR1Lot18Blk1Waterstone1720AGR.rup Caic=MJ8 House faces: N -- wrightsoft Right-JO Worksheet Entire House DEL -AIR HEATING &AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM Job: Lot 18 Block 1 Waterston 17... Date: By: SIR 1 Room name Bdrm 3 Bth 2 2 Exposed wall 36.5 It 8.0 ft 3 Room height 8.0 It heaVcool 8.8 ft heattcool 4 Room dimensions 1.0 x 152.0 it 8.0 x 8.0 It 5 Room area 152.0 112 64.0 112 Ty Construction U-value Or HTM Area (ftz) Load Area (It) Load number (Btuh/ft2-'F) (Btuh/ft2) or perimeter ft () (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 $Ik wall stucco ext 2A 2ov 0201 0330 n ` n 5 83 * 957 4 06 9.9b 88 ¢ 0 88 513 * 357 0 ` t "" 0 $p -'d 2A 2ov } :, ._ k 0330 ti P _ 957 852 . vQi0 0 0 . f .a �0w0 0 3 r 0 W 166 19ad 0.049 e 1.42 2.59 0 0 0 0 0 0 0 0 11 �Blk wall'slucoo ext 2A 2ov 2B 2N71 a 0.201 0 330 0330 a r` ' e s 5 83 '9.57 `'4 06 r 21 62 33 63 % 0 369 313 257 707 0 x0 Q = 0 0p. 0 0 a .1158 2B 2N 0 330 a ,, 9.57 972 0 m^ 0 ✓ 0 0' 31J0_w 0600 , =e� _ i7AU 1 758 W 168-19ad 0049 s 142 2.59 0 0 0 0 0 0 0 0 $Ikwallstucooext 2A 2ov Q201' 0336 s` s 583 9.57 406108108 9.90 0 0 630 0 439 0 64 0 57, 0 p 333 6, 232' 0 2A2ov 0330 s 957 852 0 0�0 0 7 7 ti6 58 .2A 2oY 1 __ Q 330 s 9.57 8`.52 _. 0 « . >w.;_ 9 x' Blk vVall, stucco ext 0.201 w 5.83 4.06 0 0 0 0 0 0 0 0 10C-m 0.550 w 15.95 12.64 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 9.57 2629 0 0 0 0 0 0 0 0 2A 2ov 0 330 w 9.57 9.90 0 0 0 0 0 0 0 0 72COsw'a 0091 �7. ;- 264 131� , 0 s00� �� 0 00; 0 r �'0� a _11D0 cy C 16B 30ad0 032 0.93 1.69 152 152 141 257 68 .a�0 68 63 114 f-u Br "t �'x` ��{ � t 6 @' t 6 P^"` Y � � w. _r x._''' ✓"""Yt ,.sw..r.✓ .,... �.. _...v.,.a.„�,._s vn.......c�... �i...._x.s.i us.�.«d...� - .-�..a.mbd ....xw u_.-.ec ._....,.,., �.vsi w...b.:.i «a.l.. o.=. ... uL2 712 ...... = Z2= .so..._ ..�...._..._...w,..�..�.'*'a _ ,........ ........s .E....s.,. v ...... 'c....ww11= av,s.3 u.w+... " .».+.w�..sti.a.._..._+�..+,.s.:. _................. .x.&..,._ _.3..�x,c __....»._.w- ..r.d _ _....�...,.. kr 1 nw ..,.z ..,� w_.a...s......,..t..w �..v... t.uE ..�............"..i.�.m .r w.. _.�.....: t 1s3...,.�`. ...rw.X✓,:7..�t 'Ls{ w �� .....¢,.,.��r..__._. _ .....c.2x.c.. �fl,.#,�. .m........ ...�... „s ✓. -w ^Y#u r'X� ...«.�2m�.....+. _... _ � ,i_�vu,. .. ,. ..._.-_v,d,..._..x...._..,.v - w...uws,c»�. a.. ..._.......-b:. .,._.,...v .».w.+-.,:... a.+.wsn$ e -e 6 c) AED excursion 139 -19 Envelope loss/gain 3012 2155 691 386 12 a) Infiltration 671 187 147 41 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 3683 2343 838 427 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3683 2343 838 427 15 Ductloads 179/6 28%1 616 660 179/6 28%1 140 120 Total room load 4300 3003 978 547 Air required (cfm) 167 129 38 24 Calculations approved byACCAto meet all requirements of Manual J 8th Ed A&-*- wrigF�tsoR^ 2021-Jan-2614:3233 K Rigid-Sdte®Uriversal 2021 21.0.02 RSU23828 Page 4 aterstone1720AGR\Lot18BlklWaterstone1720AGR.np Calc=MJ8 Hoisefaws: N - - wrightsoft, Right-M Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 18 Block 1 Waterston 17... Date: By: SIR 1 Room name. Bdrm 2 2 Exposed wall 13.5 ft 3 Room height 9.3 ft heaVcool 4 Room dimensions 11.5 x 13.5 ft 5 Room area 1552 ftz Ty Construction U-value Or HTM Area (ftz) Load Area Load number (BtuWF) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk wall stucco ext 2A 2ov `, D 201 0.330 n n ': 5 83 9 57 # 406 990 " 0 0 07.00 0 W 16B 19ad 0049 a 142 259 0 0 0 0 11 ;BM%dl stuaooext 2A 2ov 0201 0.330 e'-- a 583 957 7406' 162 i ; 0 0 ` 0 0 0 f 0 ' s 26 2fv =,0.330 :`e ' 0957 11.56 R` t 0 0 ' 2B2fv 0330 , 972 0 0 0 �0 0 0 b' w W 1613•19ad 0.049 s 1.42 2.59 -D 0 0 0 0 131k,wall stii000 ext 2A 2ov 0 201 0330 s s 5 83 957 4 05 + 990 108 O —i92 F 0 " , 0 " 372 0 � '"' 2A2ov 0.330 s' 9 b7 8 52 r 0 0 2A20V 0330 3 s. 957.__ 8.52;�.�....;-;�,,:16 Blk wall, stuao ext 0.201 w 5.83 4.06 0 0 0 0 1007m 0.550 w 15.95 12.64 0 0 0 0 2A-2ov 0.330 w 9.57 2629 0 0 0 0 2A-2ov 0.330 w 9.57 9.90 0 0 0 0 12C Osw 5 ,'0 091 2 64 1.31 M6 .;.11DO...�.�.�...u..�.k�..A � u• C 166-30ad 0.032 0.93 1.69 170 170 157 287 F 22A1p1 ;"9989 28.68 =Da � -'. 1_4 mum �s 0 _ _.a , � a.0A0 y az R., e.+s�_....._....u...�....b.....,.. dui'^., u z! M..m...n. >h...d... ,e�.sa. �..::G.a s..,',... .'..�..�...,.,....; ..............s s.a.-.....»...;.`;_ ..--P-k.'F::..,ru` +` „ ,.. v.xG..,_...«...,✓..him. ....ua...... {.z'.. ....... ,�....dG:,_... a....,+«.n..� v....v.�ii::,....�. :r ..-.w.. .......>,:.i .n. ,...v,s.».. e .u...�i...,, ....�....-j :+U.....t�...n..,. �''.._.a...0 .:,.St-� _...-.:l.,t .h-a .... >., _ .S. «..�,.,d ..< C...a.; �✓.w � �,e.w'�• .....y...,...« =w,._.w>.E.F' .-....e...4..W",.:.2 2..=«.o...s.�e. .s..,.»,ti...a _ "'....'� � "'". � '.�'.; .?'�44 �e �-ts wee `3" 5 : -+ � w =N'"'"� �,3 �^ •r` . �� w._ .,_„v.,........ ......,a.�-x. w. _ .».,5.ew.,..:. .�..,.-.»._.,„ ,..w.i.r.„.;�'�.�.,.m a�--:::�.xi�.x '' a3.u� �.......,... "a��..,.�� ,.... .; ..�a�........-.____.- ...,��.,..... ...._...,.-.a:�. w.�.....i.�� .-,_._»... .N_. .emu ..� ..t.,_ _7. M7,_717CE 1— :- -, -37 6 c) AED excursion Envelope loss/gain 1235 761 12 a) Infiltration 248 89 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Applianceslother p Subtotal (lines 6 to 13) 1483 831 Less external load 0 0 Lesstransfer 0 0 Redistribution 0 0 14 Subtotal 1483 831. 15 Ductloads 17% 28%1 248 234 Total room load 1732 1065 Air required (cfm) 67 48 Calculations approved byACCAto meet all requirements of Manual J 8th Ed wrigF�tsotFt .�CGA Rigl�-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Jan-2614:3203 Page 5 aterstone1720AGR\Lot18BIk1Waterstone1720AGR.rLp Calc=MJ8 Hoisefaces: N y nstem wrightsoft® Duct S Summary Job: Lot 18 Block 1 Watersto... Date: Entire House By: SIR DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM Froject intormation, For: ADAMS HOMES 5380 Lugo Street, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply/return available pressure Lowest fri cti on rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.284 in/100ft 947 cfm 120 SupplyBranch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170/0.170 in H2O 0.284 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bdrm2 h 1732 67 46 0.329 6.0 Ox0 VIFx 18.4 85.0 sti Bdrm3 h 4300 167 129 0.284 7.0 Ox0 VIFx 34.6 85.0 st1 Bth 2 h 978 38 24 0.309 4.0 Ox 0 VI Fx 25.0 85.0 st1 Laud c 1003 25 43 0.462 4.0 Ox 0 VI Fx 3.5 70.0 Livrm c 2574 95 111 0.422 6.0 Ox 0 VIFx 10.6 70.0 Livrm-A c 2574 95 111 0.400 6.0 Ox 0 VI Fx 15.0 70.0 Livrm-B c 2574 95 111 0.374 6.0 Ox 0 VI Fx 21.0 70.0 Livrm-C c 2574 95 111 0.352 6.0 Ox 0 VI Fx 26.6 70.0 Mstr Bdrm c 4791 169 206 0.371 8.0 Ox 0 VIFx 21.7 70.0 Mstr Bth h 2471 96 51 0.411 6.0 Ox 0 VI Fx 12.7 70.0 Mstr ""c c 142 3 6 0.435 4.0 Ox 0 VI Fx 8.2 70.0 Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 PeakAVF 273 198 0.284 500 10.0 0 x 0 VinlFlx ,` * wrightsoft, 1- .-,Ber1 1.1-xo,fomp Rigfd-SuteOUriversal202121.0.02RSU23828 ICCK aterstone1720AGRtLotl8BIklWaterstore1720AGR.rLp CaIc=MJ8 Hoisefaces: N 2021-Jarr2614:3213 Page 1 Return Branch Detail Table Name Grille Size (in) Htg (Cfm) Clg (cfm) TEL (ft) Design FIR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rbi Ox 0 947 947 0 0 0 0 Ox 0 VIFx - wrightsoft- ���M,,.t•,�..�h..bw...,�m„., Right-Srite@Uriversal2021 21.0.02 RSU23828 aterstone1720AGR\Lot18BIk1Waterstone1720AGR.rr{r Calc=MJ8 Horse faces: N 2021-Jarf2614:3233 Page 2 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 18 Block 1 Waterstone 1720 AGR Builder Name: ADAMS HOMES Street: 5380 Lugo Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL v COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in an dropped soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind pophria and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings. a. In addition, inspection or log walls shall be in accordance with the provisions of ICC-400. 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 1/26/2021 2:38:38 PM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Duct Leakage Test Report Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job.lnformation Builder: ADAMS HOMES Community: Lot: 18 Address: 5380 Lugo Street City: Fort Pierce State: FL Zip: 34951 Duct. Leakage Test Results. - System 1 cfm25 System 2 cfm25 System 3 cfm25 Sum of others cfm25 Total of all cfm25 — 1720 = Qn Total of all Total Conditioned systems Square Footage PASS [:]FAI L Q Prescriptive Method;, cfm25 (Total) To.qualify'as'substartbally,Eleak free""Qn.,Total must"be"'less than or'G equal to 0.04 if air handler. unit isF nstailed If air handlbr unit is •not. _ Installed"'On• Total "must be less" .ti amor equal•to `0a03: This testing' me'thod:,meets-'the requirementsin accordance with Section R403 33: 1s the air handler unrf instaged during testing? DrYES (5'0)' NO�`(S;o Q Pe�rformanee/ERI Method- cfm25 (Out or'Total) To qualify using this method, Qri must not be,greater•tfan the . prop"osed duct;leakage"Qn specified on Form R405-2020 or',R406-2020 Leakage Type;selected o`n".Form Qn.specifiec on Form R405 2020. R405-2020 (En ergyCalc), or R406.2020 (EnergyGa/c) or A406:2020t . Proposed Qn 0.06 Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes. Testing Company, Company Name: Phone: I hereby verify that the above duct leakage testing results are in accordance with the Florida Building Code requirements with the selected compliance path as stated above, either the Prescriptive Method or Performance Method. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/26/2021 2:39:48 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information. s Builder: ADAMS HOMES Community: Lot: 18 Address: 5380 Lugo Street City: Fort Pierce State: FL Zip: 34951 Air Leakage Test.;ResultS `Passing"results•must meet erther'`the Performance; Prescnptive; or.ER!•`IVlethoci ., h.. PRESCRIPTIVE METHOD=The building,or dwelling unit shall be=tested and verified as having an air.leakage rate•'of not exceeding"7 air " changes per hour at,a pressure of 0.2'inch w:g '(50 Pascals) in Climate Zones 1 and,2. Q PERFORMANCE `or ERI METHOD=The'building or dwelling unif shall be'tesled an, verified as, having an air Ie_akage rate of ndt�exceedin' the selected ACH(50);value, as shown on form R405-2020 -.(Performance) or R406-2020 (ERI), section labeled as infiltration, sub -section ACH50. ACH(50) specified omForm R405-2020-EnergyGatc (Performance) or, R406>2020 (ERI): 7.000 x 60 _ 15480 = Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans 1-1 PASS • Code software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/26/2021 2:39:35 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5380 Lugo Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. R403.3.2 Sealing (Mandatory) All ducts, 'air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - F]aRes202O FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. ❑ R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. ❑ R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. ❑ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. ❑ R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. ❑ R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. ❑ R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. �. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 1/26/2021 2:39 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5