Loading...
HomeMy WebLinkAboutBuilding Plans, HC GENERAL NOTES 1. HOLES: Holes are by others unless otherwise indicated. Fields -cut holes thru the units may not cut prestressed strands without prior written approval from Pre -Cast Specialties Inc. Engineering Department. 2. VERTICAL RISERS: The general contractor shall insure that vertical risers, etc., do not interfere with placement of Hollow Core units. 3. HANDLING: Hollow Core units may not be lifted by inserting hooks, bars or other lifting devices into the voids, and may not be inverted. Hallow Core units must be lifted 1'-0" from the end only. 4. DIMENSIONS AND DETAILS: The customer and/or his agent will be responsible for all dimension and details taken from the contract drawings and shown hereon. PCSI will not be responsible for any changes made after approval of these drawings. 5. ROOF UNITS: Slight vertical movement of precast concrete roof units is anticipated but can be reduced by proper insulation. PCSI recommends a physical separation of the plaster at the intersection of non -bearing walls and ceilings. 6. CAMBER: Camber is an inherent condition in all prestressed flexural members and the general contractor shall make allowances for same. If additional thickness of topping is needed for leveling purposes, contact our engineering department for approval. Highest estimated camber at time of erection: __ 7. CONCRETE: Strength of concrete shall be a minimum of 6000 psi at 28 days. Structural topping where specified shall be of 4000 psi 28 day strength concrete, reinforced with 6 x 6 - 10/10 weldeC wire mesh. or fiber reinforced concrete. The thickness of such topping shall be a minimum of 2 inches at the center of the span and may vary due to camber or deflection from the center to the supports as required for a level surface. The topping pour and all materials required same are by others. 8. GROUTING: All joints between slabs shall be fully packed with a pourable grout consisting of 1 part Portland Cement to 3 parts clean sand. The grouted deck shall be allowed to cure before removing any leveling shores, cutting any holes or applying any further construction loads. THE OPERATION OF GROUTING THE HOLLOW CORE SLABS KEYWAYS MUST BE PERFORMED REGARDLESS OF ANY TOPPING BEING APPLIED TO HOLLOW CORE SLABS. 9. PRESTRESSED STRANDS: Strands to be 7 wire, 7/16" dia., tensioned to 21700 lbs. each for 6" planks. (7 wire, 1/2" dia., tensioned to 28900 lbs. for 8" & 10" planks). The number of strands are indicated by the first two digits following the letter HC or US in the designation. 10. TOLERANCES: Width Full Width Units t 1/4" Saw Cut Units t 1/2" Split Units t 1 1/2" 11. DESIGN LOADS: Length t 1" Thickness t 1/4" Deviation From Square t 1" 2nd. FLOOR: 8" U.S. W/65 P.S.F. (L.L.= 4O P.S.F. + D.L.= 25 P.S.F.) & ±2" TOPPING 2nd. FLOOR: 6" U.S. W/100 P.S.F. (L.L.= 80 P.S.F. + D.L.= 20 P.S.F.) & ±2" TOPPING 3rd. FLOOR: 8" U.S. W/65 P.S.F. (L.L.= 40 P.S.F. + D.L.= e5 P.S.F.) & ±2" TOPPING 3rd. FLOOR: 6" U.S. W/100 P.S.F & t TOPPING L.L.= 80 P.S.F. + D.L.= 20 P.S.F.) 12. Minor cracking (hairline and tension) will occur in precast/prestressed concrete created by shrinkage of concrete and temporary loads during production, transportation or erection without being structurally detrimental to the units. These cracks have no structural significance and does not affect durability of these units. Cracking should not be cause for rejection, when properly repaired. 13. FIRE RESISTANCE: All Precast/Prestressed concrete products shown on these shop drawings have a maximum fire resistance of one (1) hour, unless indicated otherwise 14. All Precast/Prestressed concrete products shown on these shop drawing§ are structural quality, any rework/finishing necessary for final architectural appearance is by ®-hers. 15. TIE BEAMS: Tie beams must be true, level and free of knots. If precast perimeter beams or knockout blocks are used, they must be COMPLETELY FILLED. 16. ACCESS: General Contractor agrees to provide and maintain for the duration of precast installation, stabilized access, acceptable to PCSI so trucks and cranes can move under their own power to various points of erection with no overhead obstruction. Customer accepts all liability for deliveries beyond the curb line, including all underground utilities and cost for loss of time. PCSI reserves the right to stop deliveries and/or erection in the event such conditions are not provided. A THIS SYMBOL INDICATES SAWCUT OR SPLIT EDGE OF HOLLOW CORE PLANKS, - WHERE STRUCTURAL TOPPING IS TO BE APPLIED, PLANKS ARE TO BE THOROUGHLY CLEANED AND PREPARED BY G.C. PRIOR TO TOPPING TO INSURE ADEQUATE BOND STRENGTH. - TIE BEAMS MUST BE TRUE, LEVEL AND FREE OF KNOTS. IF PRECAST PERIMETER BEAMS OR KNOCKOUT BLOCKS ARE USED, THEY MUST BE COMPLETELY FILLED. - ALL NON BEARING WALLS SHOULD BE HELD DOWN 1" UNTIL SLABS ARE SET AND GROUTED AND ALL DEAD LOADS ARE APPLIED TO THE SLABS BEFORE DRY PACKING THE GAP BETWEEN THE NON BEARING WALL AND THE SLAB. - Dowels must be placed in the beams in a manner to allow the proper bearing of our product as detailed in our different sections. Non compliance with this item may delay the erection of these product with additional cost to the General Contractor. - SAFETY REQUIREMENTS: ALL SAFETY RAILING AND HOLE PROTECTION VIA SECURED PLYWOOD ARE BY G.C. IMMEDIATELY AFTER PRECAST/ PRESTRESSED MATERIALS ARE INSTALLED. GROUTING WILL NOT TAKE PLACE UNTIL ALL HOLES & RAILING ARE IN PLACE BY G.C. - MINIMUM BEARING: 2" BEARING IS STRUCTURALLY ACCEPTABLE, GENERAL CONTRACTOR MUST ADD 2 #5 REBAR 03'-0" LONG WITH 6" HOOK AT EDGE POUR PER SLAB. BEARING LESS THAN 2" MUST BE APPROVED BY PCSI ENGINEER. - SPLIT SLABS (NARROW DOWN): DUE TO MANUFACTURING & CONSTRUCTION TOLERANCES THERE MAY BE A GAPS BETWEEN SLABS AND OR WALLS. FIELD SPLIT SLABS WILL HAVE A ROUGH EDGE GAP, ALL GAPS SHALL BE FORMED AND POURED BY CONTRACTOR. CUTOUTS/NOTCHOUTS: TOLERANCE GAPS MAY OCCUR AROUND COLUMNS, BEAMS REBAR, PIPES, ETC. THESE GAPS SHALL BE FORMED AND POURED BY CONTRACTOR. N I 1'-11" 6'-3" 0 1'-2" fflw 6'-3" 4'-7y2" 50A 1 '-2" 52A -44„ ALLO DS ALE HOLLOW CORE (US) ; with toppin{ no topping Rev. Mark Unit No. Req. 2nd. FL No. Req. 3rd. Fl. L( inches) ( FEET L 1 total length Wlinc 65 1A 8" US-038 2 0 238 19.83 476 30.! 16 8"US-038 1 0 238 19.83 238 29 1C 8" US-038 1 0 238 19.83 238 48 2A 8" US-038 2 0 54 4.5 0 108 25.5 2B 8" US-038 1 0 54 4.50 54 27.5 2C 8" US-038 1 0 54 4.50 54 32.5 21D 8" US-038 1 0 54 4.50 54 34.5 3A 8" US-038 2 0 124.5 10.38 249 27 4 8" US-038 3 0 181 15.08 543 48 4A 8" US-038 1 0 181 15.08 181 38 5 8" US-068 2 0 368.5 30.71 737 48 5A 8" US-068 1 0 368.5 30.71 368.5 25.5 5B 8" US-068 1 0 368.5 30.71 368.5 32.5 6 8" US-038 5 0 233 19,42 1165 48 6A 8" US-038 1 0 233 19.42 233 22 7A 8" US-038 1 0 95 7.92 95 35.5 8A 8" US-038 1 0 171 14.25 171 34.5 9A 8" US-038 2 0 235 19.58 470 30.5 9B 8" US-038 1 0 235 19.58 235 27 C10 8" US-038+028 TS 1 0 263 21.92 263 48 C10A 8" US-038+028 TS 2 0 263 21.92 526 28 C11 8" US-038+028 TS 1 0 259 21.58 259 48 C11A 8" US-038+028 TS 2 0 259 21.58 518 28 100 30 6" US-037 1 0 198 16.50 198 48 30A 6" US-037 1 0 198 16.50 198 37.5 C31 6" US-037+027 TS 6 0 173.5 14.46 1041 48 C31A 6" US-037+027 TS 1 0 173.5 14.46 173.5 32 32A 6" US-037 2 0 115 9.58 230 36 32B 6" US-037 2 0 115 9.58 230 37 C33 6" US-037+027 TS 8 0 75.5 6.29 604 qg C33A 6" US-037+027 TS 2 0 75.5 6.29 151 30.5 C33B 6" US-037+027 TS 2 0 75.5 6.29 151 36 65 50 8" US-038 0 4 238 19.83 952 48 50A 8" US-038 0 1 238 19.83 238 48 51 8"US-038 0 4 181 15.08 724 48 52A 8" US-038 0 1 '_32.5 19.38 232.5 48 53 8" US 068 0 2 68.5 30.71 737 48 53A 8" US-068 0 1 168.5 30.71 368.5 32.5 53B 8" US-068 1 68.5 30.71 368,5 27 54A 8" US-038 0 1 95 7.92 95 35.5 55A 8" US-038 0 1 171 14.25 171 34.5 56 8" US-038 0 4 235 19.58 940 48 57 8" US-038 0 5 233 19.42 1165 48 57A 8" US-038 0 1 233 19.42 233 22 0 0 100 80 6"US-037 0 1 198 16.50 198 48 80A 6" US-037 0 1 198 16.50 198 37.5 81 6" US-057 0 2 ! 229 19.08 458 48 81A 6" US-057 0 2 229 1 19.08 1 458 1 25.5 81B 6" US-057 0 2 229 19.08 458 36.5 TOTAL 61 34 18575 MISCELLANEOUS MATERIALS SCHEI REV. MK. No. MATERIAL N" Required 2nd. FLOOR N° Required 3rd, FLOOR - M-A 1/811x3"x47" KOROLATH STRIPS 122 68 - M-8 #5x14 CANTILIVER PINS 25 0 ENGR. DATE SEAL \� CHECKED DATE "C J.C. 9/15/17 �`� V I'� DATI DESCRIPTION BY DRAWN DATE REVISIONS J.B. 8/17/17 I ST. LUCIE COL. WB REVIEWED FOR VOINI REVIEWED BY I DATE PLANS ANC PE FfI T OR NO INSPECTION W PROJECT: SIMMERMACHER RESII 7912 S. OCEAN Dr. JENSEN I CONTR.: COASTAL CONSTRUCTION & TEL.: (772)219-2180 SECOND FLOOR FRAMING PLAN SCALE: 1/4'=1'-0' 8" U.S. W/65 P.S.F & f2" TOPPING 6" U.S. W/100 P.S.F. i & t2" TOPPING APPROVED DRAWINGS 9 15 17 IN 0 THIRD FLOOR FRAMING PLAN SCALE: 1/4"=1 C 8" U.S. W/65 P.S.F & t2" TOPPING a C U 6" U.S. W/100 P.S.F. i & ±2$1 TOPPING 50'-6" a Ln APPROVED DRAWINGS 9 15 1 '7 0 SECONDARY POUR (by G.C.) #4 BAR CAST IN TOPPING 4 -0" O.C., AND 3 BAR CONTINUOUS. by G.C.) t2" TOPPIJ (by C. F O O -- 6" U.S. LAP VARIES 8" MASONRY WALL W/REINF. (by G.C.) i � SECTION �3.0) SCALE: 3/4" = 1'-0" VBAR CAST IN BEAM AT 0" O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (BY GC.) t2" TOPPING #4 BAR CONT. (BY G.C.) (BY G.C.) t2" TOPPING (BY G.C.) 6" U.S. O O 3 1 2" t 3 4" BRG. 6" U.S. CAST W/ BEAM W/1 #4 R.A BAR CONT. IN 4" SECTION ° ' • . CONC. BEAM (BY G.C.) W/REINF. (BY G.C.) #5 BAR FROM FILL CELL ON 1 -0' (BY G.C.) s SECTION 3. o SCALE: 3/4" = 1'-0" #5 REBAR W/3" HOOK, DRILL & EPDXY MIN. 6" INTO BEAM ONE PER PLANK (by PCSI ERECTOR) - RAILS (by G.C.) - SEC NDARY POUR gby G.C. 4„ EDGE POUR (BY CANTILEVER G.C.) 4'-6„ 3 BAR CONT. AND 4 BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) W/REINF. (by G.C.) 8" MASONRY WALL #4 BAR CONT. (BY G.C.) TOPPING (BY G.C.) SECONDARY POUR (by G.C.) #4 BAR CAST IN TOPPING 4'-0- O.C., AND 3 BAR CONTINUOUS. by G.C.) GROUTING BUTT (by G.C.) f2 TOPPING (by G.C.) 007 8" U.S. LAP VARIES 8" MASONRY WALL W/REINF. (by G.C.) z SECTION 3• o SCALE: 3/4" 8" U.S. 3"t 1/2" BRG CONT. BEAM by G.C.) ,. r ° as, =3_ G. ; #5BAR FROM FILL CELL DIN (BY G.C.) a CONC. BEAM W/REINF. (BY G.C.) 11 SECTION 3. o SCALE: 3/4" = 1'-0" t2" TOPPING (by G.C.) .a \- 81 U.S. 3 t 1 2 BRG, • #4 HOOKED BAR CAST IN BEAM ® 4'-0" O.0 & AND #4 BAR HORIZONTAL IN CORE, ONE PER PLANK. (by G.C.) rfSECTION 3. SCALE: 3/4" = 1'-0" TOPPING (BY G.C.) \-8" U.S. ,3 1 /2"t 3/4" BRG. CAST W/ BEAM W/1 #4 BAR CONT. IN 4" SECTION (BY G.C.) — #5 BAR CAST IN BEAM AT 4'-0" O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (BY GC.) 1 �l •I T/l ff lllal/� SECONDARY POUR (by G.C.) #4 BAR CAST IN BEAM AT 4'-0" O.C., #3 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) 3 SECTION 3 J0 SCALE: 3/4" SECONDARY POUR (by G.C.) #5 BAR CAST IN BEAM AT 4'-0" O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) SECONDARY POUR (by G.C.) #4 BAR CAST IN BEAM AT 4'-0" O.C., #3 BAR CONT AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) \�8" U.S. 3 1 2"t 3/4" Bf 8" MASONRY WALL W/REINF. (by G.C.) a SECTION 3 0 SCALE: 3/4" t2" TOPPING PAM I "S MERE 6" U.S. a. L 3 }" t J" BRG. #5 REBAR W/3" HOOK, DRILL & EPDXY MIN. 6" INTO BEAM ONE PER PLANK �(by PCSI ERECTOR) 8" MASONRY WALL W/REINF. (by G.C.) t2" TOPPING (BY G.C.) t2" TOPPING i (BY G.C.) O j.4 #5 BAR CAST iN BEAM AT 4'-0" O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (BY GC,) t2" TOPPING (BY G.C.) #4 BAR CONT. (BY G.C.) t2" TOPPING (BY G.C.) 8" U.S. J 6" U.S. 8„ U.S. LAP VARIESBRG. . 3 1 2't 3 4' BRG. CAST W/ BEAM W/1 #4 d BAR CONT. IN 4" SECTION #5 BAR FROM (BY G.C.) FILL CELL ON (BY G.C.) CAST W/ BEAM W/1 #4 R BAR CONT. IN 4" SECTION BAR FROM 8" MASONRY WALL #5 BAR CAST IN BEAM AT W/REINF. (BY G.C.) ( BY G.C.) ° ° FILL FILL CELL DIN (BY G.C.) 4 -0 O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR CONC. BEAM GROUTED IN CORE, ONE W/REINF. (BY G.C.) PER PLANK. (BY GC.) 1,-0„ 4 SECTION 5 SECTION 3. o SCALE: 3/4" = 1'-0" 3 o SCALE: 3/4" = 1'-0" 3 BAR CONT. AND 4 BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) SECONDARY POUR (by G.C.) 4" EDGE POUR (BY G.C.) CANTILEVER LINE INDICATE CB-1 BEYOND BOND BEAM W/REINF. (by G.C.) RAILS - (by G.C.) SECONDARY POUR - by G.C.) 1z SECTION 3. o SCALE: 3/4" = 1'-0" 4" a EDGE POUR CANTILEVER (BY 1'-0" G.C.) 3 BAR CONT, AND 4 BAR GROUTED IN CORE, ONE PER PLANK. (by G.C.) #4 HOOKED BAR CAST IN BEAM ® 4'-0" O.0 & AND #4 BAR HORIZONTAL IN CORE, ONE PER PLANK. (by G.C.) t2" TOPPING (by G.C.) 8" U.S #5 REBAR W/3" HOOK, DRILL & EPDXY MIN. 6" INTO BEAM ONE PER PLANK (by PCSI ERECTOR) 9 SECTION 3 0 SCALE: 3/4" = 1'-0" SECONDARY POUR (by G.C.) #4 BAR CAST IN TOPPING 4 -0" O.C., AND 3 BAR CONTINUOUS. by G.C.) POUR IN PLACE t2" TOPPING (BY G.C.) (BY G.C.) d' a, e B. U.S. #5 BAR CAST IN BEAM AT 3 1 2"t 3/4" BRG. 4'-0" O.C., #4 BAR CONT. AND #4 x 1 -6" LG BAR GROUTED IN CORE, ONE PER PLANK. (BY GC.) 8" MASONRY WALL W/REINF. (G.C.) io SECTION 3. SCALE: 3/4" = 1'-0" f2" TOPPINQ (by G.C. � -OO- �•• a' A. 8" U.S. GAP VARIES 8" MASONRY WALL W/REINF. (by G.C.) 13 SECTION 3, o SCALE: 3/4" = 1'-0" GROUTING BUTT (by G.C.) 6" U.S.-j 3 1 /2" t 3/4" BRG. CONT. BEAM by G.C.) t2" TOPPING (by G.C.) ° 6" U.S. 3 1 /2" t 3/4" BRG. #4 HOOKED BAR CAST IN BEAM ® 4'-0" O.0 & AND #4 BAR HORIZONTAL IN CORE, ONE PER PLANK. (by G.C.) 14 SECTION 3, o SCALE: 3/4" = 1'-0" APPROVED DRAWINGS ENGR. DATE SEAL `� 01 �� PROJECT: SIMMERMACHER RESIDENCE APPROVED DATE 8/28/17 SHEET NO. - 3.0 - WO#: P-17-6323 S P E C FO t TT I Z 8 OPY Pre —Cast Specialties, LLC 1380 N.E. 48th. St. Pompano Beach, FL. 33064 PHONE: 954 781-4040 FAX: 954-781-1194 CHECKED DATE J.C. 9/15/17 7912 S. OCEAN Dr JENSEN BEACH CONTR.: COASTAL CONSTRUCTION & DESIGN TEL.: 772 219-2180 - - _ DATE DESCRIPTION BY DRAWN DATE J.H. 8/17/17 — REVISIONS