ADDITIONAL OR MODIFIED ACCEPTANCE (MODULARS/PANELIZED)
This form is to be used only when the manufacturer is seeking acceptance of an additional model, modified model or model name change which uses a previously accepted
building system.
Current PFS Building System Acceptance #: 1391
Model Name/ No. 6233-MA
Manufacturer's Name: Champion Home Builder's (dba Skyline Homer Ocala FL
Plant(s) at which model will be produced
Check One: ✓ NEW MODEL Revised Model*
TECHNICAL DATA
Floor Plan Showing:
Braced Wall Method or Shearwalls
Building Size (LxW Dimensions)
Room Sizes, Light & Ventilation Schedule
Exit Requirements
Electrical Outlet Spacing & Smoke Detector
Location of Labels & Data Plates
Use Group, Type Const., Total Sq.Ft. Area
Plumbing System Design or Reference No. ( Sheets 7 - 8
Heat Loss Calculations or Reference No. ( 1
HVAC/Furnace Size/Model No. ( Field supplied heat pump
Thermal Performance Calculations or Reference No. ( Sheets 11 A - 11 F
Electrical Load Calculations or Reference No. ( Sheet 4D
Service Size and Location ( 200 Amp / Utility
Applicable Building Codes See Sheet 1
Submit model to the followingstates: Florida
*Description of Modification:
Conforms
Yes
No
N/A
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Requested by: Edward Weber Date:
(designer)
10-10-19
For PFS Use
Staff Plan Reviewer IBC Certification #:
Structural Calculation(s) Reviewed By: P.E. #:
Remarks:
Date:
Date:
.(1) copy sent to IBC within 15 days of approval.
VERBAL APPROVAL GIVEN By Whom: To Whom
MODEL WAS DEVIATED Revision Number:
Date:
THIS FORM SHALL BE FILLED OUT COMPLETELY WITH EACH MODEL ACCEPTANCE OR MODIFICATION PRIOR TO SUBMITTAL TO PFS.
\forms\form-m
Rev 05/13/08 mb
DRAWING INDEX
No.
DESCRIPTION
1
Coversheet
2-2A
Elevations
3
Floorpian
3C
Door& Window Schedule
3C
Fastening Schedule
4
Electrical Plan
4C
Electrical Legend
4D
Electrical Specifications
5
NIA
6
Cross Section
7
Drain Line
8
Water Line
9
N/A
10
HVAC Plan
11
Energy/HVAC Specifications
11A-11F
Energy Compliance Reports
12
Wall Sys. - Framing
12A
Wall Sys. - Ext. Wall Bracing
12B
Wall Sys. - Other Details
13 - 13.1
Roof System
13A
Roof System - End Overhangs
13B
Roof System - Centerbeam
13C
Roof System - Other Details
13D
Roof System - Penetrations
13E
Roof System - Dormers
14
Floor System
15
Fire Separation
16
Product Approval Sheet
App. A
N/A
App. B
Structural Calculations
SITE INSTALLED ITEMS
Note: This list shall not be considered all-
inclusive. All site installed items are subject to
local code review and compliance.
1) Complete foundation support, sill plate
anchorage and tie -down system.
2) Ramps, stairs and general access to the
home.
3) Structural and aesthetic Interconnections
between modules.
4) Exterior siding and roofing at mating line
of modules.
5) Opening (windows, doors, etc.) protection
in windbome debri regions.
6) Building drains, dean -outs and hook-up to
the plumbing system.
7) Potable water service and main shutoff
valve.
8) DWV crossover connections.
9) HVAC equipment and disconnect.
10)HVAC crossover ducts and connections.
I1)Portable fire extinguisher(s).
12)Electrical service hook-up.
13)Electrical crossover connections.
14)Hinged potion of roof.
Skyline Homes
State of Florida
Model
6233-MA
DESIGN BASIS
.%%01 11 111%.,,�
O'9G'�
Roof Snow Load: Floor Live Load:
20 PSF 40 PSF
���FFP �GEivs
�, F •.,
]!V: �j!.
Wind Speed: Floor Dead Load:
No 52231
Vult (3-sec gust) = 160 MPH 10 PSF
a
Vasd (3-sec gust) = 124 MPH
; STATE OF
Roof/Ceiling Dead Load:
O ,
��i�'A4
Exposure Category: 15 PSF
0 R
%
C
�'�sS�ONA� � �`�
Jeffrev T.
DESIGN CRITERIA Legault
a
Codes & Regulations: 2019.10.10
a
2017 Florida Building Code Residential / 14:40:56
2014 National Electrical Code 04'00'
61 G20-3 for Product Approval
Minimum Design Loads for Buildings and Other Structures (ASCE 7-10)
MODEL DESCRIPTIONS
PROJECT LOCATION
Ranch:
27282 Sunset Drive
m
A two module single level home placed on
Punta Gorda, FL 33955
W
rn
a permanent foundation.
o
m
j5
Model No.: Square Footage:
6233-MA 1692 sq. ft.
GENERALNOTES
1) All notes pertaining to 'in field", "on site, or "by builder' shall be the responsibility of the general contractor.
�!
2) These plans must not be scaled for dimensional reference. All dimension lines and notes supercede any
such references.
jam
3) 32' wide models actual floor width is 3W4" max.
r
M
4) State insignia shall be located Inside the electrical panel cover. Data plate and third party labels shall be
th
located under the kitchen sink in an area that is not readily removable. An additional label (for adjoining
ty
module(s)) is to be located in the closet (on its longest wall) of the largest bedroom.
�O
5) Exterior walls, openings & penetrations shall have a fire separation of not less than 3 feet Homes
designed for a site-bullt attached garage shall have the common wall with not less than a 1-hour fire -
resistive rating & common door with not less than a 20-minute fire -resistive rating.
C
6) If home is destined to be placed in a windbome debris region, precut wood structural panels and
-resistant hardware have been supplied for the home owner to install
permanent corrosion attachment
over window and door openings In the event of a wind storm. The home was built with permanently
r
installed anchors for attachment of the panels.
F
7) Structure has been designed for installation on site -built permanent foundation and is not intended to be
installed.
W
moved, once so
8) This home is NOT approved for High Velocity Hurricane Zone.
W1.ry
9) This home will comply with the 2017 Floriday Building Code -Energy Conservation. Ducts shall be pressure
F+H
tested to determine air leakage per section R403.3.3.
10) If home has less than 3 air changes per hour after blower door test, whole house ventilation (per sections
MANUFACTURING DIVISION
ENGINEERING OFFICE
W
?
1230 SW 10th Street
2520 By Road
-Pass
Ocala, FL 34478
(608)723-4171
Elkhart, IN 46514
(574)294-6521
V
CORPORATE OFFICE
3RD PARTY INSPECT. AGENCY
Champion Home Builders, Inc.
PFS Corporation
755 West Big Beaver Road, Suite 1000
1507 Matt Pass
Troy, MI 48084
Cottage Grove, WI 53527
(248) 614-8200
(608) 839-1013
ai
4
SHEATHING, FLASHING,
154 FELT, LAMINAT
FINISH GRADE
r
NOTES
.,,I�f�mu�mmm�lnnnrnn\IL.
I■
Ir Ir .'II
�_—�__—�__—
�nmm......
16W�.1■Ip.l■Ipa■ppl■I\ipl
mni\L.'--------------------------
II�IIIII�IIIII�IIIII�IIIII�111!
fI�I1111�11111�I1111�I111I
�mm�nnnn■�nnnnn�nti�
I■
�i+r"i+
�
"�uIIIIIIIIhtllllllulillllrllllllllallllllllllill
r�lilllllllllllllllllllllllllllllllllllllllllll
III■
�+U�lllill�
—
............11lllllillll
--
'In'u
"
j❑
I
i❑i
❑��i
��mnmm�mnnnnmm���
UP
: ;
FRONT ELEVATION
REAR ELEVATION
1. EXTERIOR LIGHTS MAY BE SHIPPED LOOSE FOR ON -SITE INSTALLATION BY OTHERS TO PRE -WIRED BOXES.
2. SIDING FOR ENDS IS SHIPPED LOOSE FOR ON -SITE INSTALLATION BY OTHERS.
3. HANDRAILS, STOOPS, STAIRS, GUTTERS, DOWNSPOUTS, AND SPLASH BLOCKS ARE FURNISHED AND INSTALLED BY OTHERS IN ACCORDANCE WITH STATE AND LOCAL CODES.
4. ELEVATIONS ARE SHOWN WITH A 3/12 ROOF PITCH.
5. SHUTTERS ARE OPTIONAL ON ALL MODELS.
6. SIDING IS SHOWN AS VINYL LAP. OTHER PROFILES.ARE AVAILABLE. INSTALL SIDING PER MANUFACTURERS INSTRUCTIONS.
7. BOTTOM ROW OF SIDING MAY BE SHIPPED LOOSE FOR FIELD INSTALLATION BY OTHERS.
& SEE FLOOR PLAN &WINDOW SCHEDULE FOR WINDOW SPECS.
9. ATTIC -ROOF VENTILATION SHALL BE 11300 OF ROOF AREA WITH UPPER HALF PROVIDING 40% MIN. (AND NOT MORE THAN 507) OF VENTILATION
,N T. LE
No 52231
9 : ; iz
STATE OF : 4/
41.
A cc �4 a R.I. p .N
•,''SdfONAE�C��.
Jeffrey T.
-12" O.H. Legault
�g�2019.10.10 r
14:40:14
-04'00,
IYL LAP SIDING
SHEATHING, FLASHING,
TE SHINGLES TYP
3
FINISH GRADE
z \
Roof Ventilation Calculation:
Attic Area = 1698.7 sq. ft.
Req'd Ventilation = Attic Area x 1/300 = 5.66 sq. ft = 815 sq. in. total
Ridge vent requires 326 sq. in. min. - 407 sq. in. max.; balance to be located in sidewall soffit.
(Ridge vent net free area =18 sq. in. / ft. Soffit vent net free area = 4.8 sq. in. / ft.) a
Ridge vent to be 19' min. - 22' max. and sidewall soffit to be fully vented.
r<iun i LLLVH IIUIV
SHEATHING, FLASHING,
15Q FELT, LAMINATE SHINGLES TYP.
NOTES: LEFT ELEVATION
1. EXTERIOR LIGHTS MAY BE SHIPPED LOOSE FOR ON -SITE INSTALLATION BY OTHERS TO PRE -WIRED BOXES.
2 SIDING FOR ENDS IS SHIPPED LOOSE FOR ON -SITE INSTALLATION BY OTHERS.
3. HANDRAILS, STOOPS, STAIRS, GUTTERS, DOWNSPOUTS, AND SPLASH BLOCKS ARE FURNISHED AND INSTALLED BY OTHERS IN ACCORDANCE WITH STATE AND LOCAL CODES.
4. ELEVATIONS ARE SHOWN WITH A 3/12 ROOF PITCH.
5. SHUTTERS ARE OPTIONAL ON ALL MODELS.
6. SIDING IS SHOWN AS VINYL LAP. OTHER PROFILES ARE AVAILABLE. INSTALL SIDING PER MANUFACTURERS INSTRUCTIONS.
7. BOTTOM ROW OF SIDING MAY BE SHIPPED LOOSE FOR FIELD INSTALLATION BY OTHERS.
B. SEE FLOOR PLAN & WINDOW SCHEDULE FOR WINDOW SPECS.
9. ATTIC -ROOF VENTILATION SHALL BE 1/300 OF ROOF AREA WITH UPPER HALF PROVIDING 40% MIN. (AND NOT MORE THAN 507) OF VENTILATION
SHEATHING, FLASHING,
15# FELT, LAMINATE SHINGLES TYP.
:• No 52231 ••: *�
�90; STATE OF :4U
1.41
I -I ``�
Jeffrey T.
Legault I
AyF,p A 2019.10.1 e
�J 0
14:39:39
-04'00'
Roof Ventilation Calculation:
Attic Area=1698.7 sq. ft.
Req'd Ventilation = Attic Area x 11300 = 5.66 sq. ft = 815 sq. in. total
Ridge vent requires 326 sq. in. min. - 407 sq. in. max.; balance to be located in sidewall soffit.
(Ridge vent net free area =18 sq. in. / ft. Soffit vent net free area = 4.8 sq. in. /ft.)
Ridge to be 19' 22' soffit to be fully vented.
vent min. - max. and sidewall
N
1.) Required glazing area is 8
capable of producing 6 footcandles of illumination over room area.
2.) Natural light and vent may be shared between adjacent rooms per the following requirements:
- One half the common wall area is open and unobstructed.
- The opening is equal to at least 10
- The opening is equal to at least 25 square feet.
3.) The floor plan may be reversed in either direction, in part or in its entirety.
4.) Attic access is required when attic area has a vertical height of 30 inches or greater.
Attic access opening shall not be less than 22" by 30" and shall be located in a hallway or
bedroom closet. Weather strip and insulate access hatch to match surrounding construction.
5.) Egress windows are required in all bedrooms.
6.) Interior doors to bathrooms or closets to be 28' min. Interior doors to bedrooms, dens,
utility rooms, kitchens, etc. to be 30' min.
7.) Any window within a 24" radius of a door shall be safety glazed.
B.) Any window installed in a tub or shower enclosure shall be safety glazed
(unless the window is 60" or more above the floor of the fixture).
9.) Where space for a clothes dryer is provided, an exhaust duct system.
shall be installed.
® - EXTERIOR WALL BRACING PER SHEET 12A ** _RETURN AIR GRILL
0- = 1190 LB MINIMUM HOLD-DOWN
= 1560 LB MINIMUM HOLD-DOWN ***-29" MIN. CLEAR OPENING
...........
�' No 52231
7-pt
STATE OF
Oct` �4 0 R 1 O P,
i�'�Sis'ON A;
JeffreyT.
g Legault
2019.10,10
14:39:06-04'00 t
56' WINDOWS DESIGNATED
10'�6'-8" 1 19' 1 10' 10'-4" V ARE AT LEAST 5'-0"
ABOVE THE
5'-6' 5-3' © z1'-a' ® 12'-4" TUB / SHOWER FLOOR.
PT
i
F KITCHEN / DINING
— NET AREA=320.73 if, r — — — — -
3 MIN. LIGHT=25.66 if. I �---� I
LN I UTILITY y� BEROOMMIN. VENT=12.83 s.f. NET LT�
10 — MIN. GH10 2 s2649 L O
MIN. VENT=5.06 if.
BATH I
NE AREA=102.87 s.f. I
MIN LIGHT=ART. LIGHT I
N. VENT=FAN I W/�{
0 ACCESS :)ta
I
LN W/H I AIR PT
I HANDLER
OO II II
I L---J
4-2x4
C�
20@
---------,
-------------------
I
MASTER BEDROOM I
I
NET AREA=182,45 s.f.
I I LIVING ROOM
MIN. LIGHT=14,60 if.
I
I I NET AREA=28B.78 &L
I MIN. VENT=7.30 if. I
rt-
I I MIN. LIGHT=23.10 &I I
I I
I I
I I MIN. VENT=11.55 if. I
I I
I I
I I
II
L1
I
I I
I
I
7 \
\
---4-
I
EGRESS
I I 13'-'7 ® - ® 3'-1°
_ "�_ - 13' 4 4' 4" 21'-4"
***
11
0
I' Ifl
IAf t
BEDROOM
NET AREA=110.45 if.
MIN. LIGHT=8.84 if.
MIN. VENT=4.42 if.
4'-7' ' 4'-11'
M
1`
No 52231
. * Z
IF
9. STATE OF' �/Z
%0
c�S�<OR1pF
.,�S1
01oNA1
,�P,,�
e ray .
D A Legault a r
,�9VQ 2019.07.24
��, 444 16:08:32
04'00'
s
R
Single hung windows are Kinro 9750
series. All windows, glass doors and skylights to be labeled as conforming to
ANSUAAMA 101/I.S.2 or TAS 202. All windows and doors shall have a min. Design Pressure (DP) rating of 45. Install per
their manufacturer instructions.
Basements and every sleeping room
shall have at least one operable emergency rescue or exterior door opening of 6.7 sq. ft.
(20" min. width, 24" min. height) and
shall have a sill height of not more than 44" above the floor.
W a
Doors and windows may be moved if egress and light and ventilation requirements are met. Additional doors and windows
may be added to the floorplan, their does that in the
provided area not exceed shown energy calculations.
Where the opening of an operable window
is located more than 72" above the finished grade or surface below, the lowest part
of the dear opening of the window shall be a mnimum of 24" above the finished floor. An acceptable alternate is
W
documentation from the builder indicating that the home will be installed in a manner that assures the window openings are
less than 72" above finished grade or
surface below.
Skylight (# 8 $) sizes vary from 16" x 32" to 24" x 48". Rough opening sizes will vary from 14-1/2' x 30-1/2" to 46-1/2" to 22-
1/2" x 46-112".
U
7�7
Z
W
[�
y o
A
H
12
maz
gym" O
��6
\A
z T
M
W' dow Sch d 1
Code
Width
Height
Rough Opening
Mfgr.
Type
Remarks
14"
40"
14-1/4" x 40-1/4"
Kinro
Vinyl -Sin le Hun
30"
27"
30-1/4• x 27-1/4"
Kinro
Vinyl -Single Hung
30°
40"
30-1/4' x 40.1/4"
Vin -Single Hung
14°
60"
14-1/4" x 60.1/4"
Vinyl -Single Hun
30'
60"
30-1/4° x 60.1/4"
Vinyl - Sin Single Hung
36'
60"
36.1/4' x 60-1/4"
Vin-Single Hung
Eross46-114"
40"
46-1/2° x 40-1/4'
rKn
Vinyl - Single Hun20-1l2"20-1/2'
20�/4° x 20-3/4•
Octagon -Vinyl, Fixed, Acrylic
14"
72"
14-1/4• x 72-1/4"
Vinyl -Fixed30"
36"
30-1/4" x 36-1/4•
Vinyl - Sng. Hun
46"
15"
46-114° x 15-1/4'
Kinro
Vinyl -Fixed
72"
15"
72-114" x 15-1/4°
Kinro
Vinyl -Fixed
24"
27°
24-1l4' x 27-1l4'
Kinro
Vinyl -Single Hung
46-1/4"
36"
46-1/2' x 36-1/4"
Kinro
Vinyl -Single Hung
31.3i4"
7�/4"
3Y x 8"
Kinro
Vinyl -Fixed
30°
12"
30-114• x 12-1/4°
Kinro
Vinyl -Fixed, Acrylic
46-1/4"
60"
46-1/4' x 60.1/4'
Kinro
Vinyl -Single Hung
Egress
36"
12"
36-1/4' x 12-1/4'
Kinro
Vinyl -Fixed
46°
12°
46-1/4' x 12-114"
Kinrit o
Vinyl -Fixed
varies
varies
varies -see below
Wasco
E-class, flat lass
Door Schedule
Code
Width
Height
Mfgr.
Type
Remarks
34'
- 80°
Thermo-Tru
Insulated Core
38°
80°
Thermo-Tru
Insulated
Fire Rated
72"
80°
Kinro
Vin I Insulated Slider
38°
62'
Thertna-Tm
Insulated Core
75°
82•
Thenna-Tru
tri French Doo
Li
ht &Vent Schedule
Code
Single Hun
Windows
Double Hun Windows
Doors
Light ft^2
Vent ft^2
Light ft"2
Vent ft"2
Light ft^2
Vent ft^2
A
2.48
1.30
B
3.90
1.90
-
-
-
-
C
6.28
3.14
-
-
-
-
E
3.92
2.08
-
-
-
-
G
9.95
5.03
-
-
-
-
I
1z.2o
s.1a
J
10.08
4.97
Q
5.55
2.78
T
3.01
1.48
-
-
-
-
U
8.91
4.37
X
15.97
7.98
-
-
-
5
-
-
-
-
31.19
15.65
7
18.0
16
Fastening Schedule
Ceiling/Roof:
/Roof: Building Element Element Fastener Size & e Number ors spacing
Simpson H2.5T Tie 8dx1-1/2" nails 5 per end, every truss
Edge Rail to trusses 16Ga.x7/16"x2-1/2" staples 3 per truss
Underlayment Metal/plastic cap nails 12" o.c. at center /
per Table R905.1.1 6" o.c. at ends
Shingles 12Ga. galy. roofing nails, 3/8" dia. Per manufacturer's Installation
1/2" or 5/8" Ceiling Gypsum Foamseal F2100 or Alphaseal 5200 Continuous along each truss
1!2" or 5/8" Ceiling Gypsum #8x1-1/2" type W or S screws 12" o.c. direct
(optional)
7/16" or 1/2" roof sheathing Sd ring shank nails (0.113" min. 4" o.c. edges / 6" o.c. inter.
shank dia., 2" min. length)
Trusses to wall plate 16d nails or#8x3-1l2" screws 3 (toe-nailed/screwed)
Ridgebeam to wall plate 16d nails or #8x3-1/2" screws 16" o.c. (toe-nailedlscrewed)
Interior or Exterior Walls:
Interior or Exterior Walls:
Building Element
Fastener Size &type
Number or spacing
Sole plate to floor 8
16d nails
10" o.c. (direct @ floor,
top plate to roof
toe -nail @roof)
Sole plate to floor 8 top
3 -16d nails
16" o.c. (direct @floor,
plate to roof, braced walls
toe -nail @roof)
Sole plate or
12d nails or
3 nails per stud or
top plate to studs
15Ga.x7/16"x2-1/2" staples
5 staples per stud
Double top plate and
10d nails Or
2 nails or staples 24" o.c.
double studs
15Ga.x7/16"x2-1/2" staples
Multiple header members
16d nails or
16" o.c, each edge
w/ 1/2" spacers
15Ga.x/16"x2-1/2" staples
Corner studs
1od nails or
15Ga.x7/16"x2-1/2" staples
24" o.c. direct
Stud to header Or Sill
16d nails or
15Ga.x7/16"x2-1/2" staples
4 nails or 5 staples (direct)
(5 nails or 7 staples @sill)
1/2"gypsum wallboard
1-5/8" gypsum nails or
nails 8" o.c.
to framing
1-1/4" long type W drywall screws
1/2" gypsum wallboard to
0.045"x0.030"x1l4"x1-1/4" staples
6" o.c. at edges
framing (optional)
12" intermediate
7/16" plywood panel
t0 framing
gd box (0.113" x 2-1/2") nails
See Sheet 12A
Wall Insulation to framing
19Ga.x1/8"x1/2" staples or adhesive
2 within 6" of top edge
Vinyl siding to sheathing
Per Florida Product Approval report &installation instructions and
manufacturer's installation instructions; whichever is more stringent.
Soffits
Roof truss to endwall plate
16d nails or #8x3-1l2" screws 16" o.c. (toe-nailed/screwed
Floor:
Building Element
Fastener Size $ type
Number or s acing
2x21edger to Center Girder
15Ga.x7l16"x2-1/2" staples &glue
4" o.c.
Band joist to floor joist
8d nails or
15Ga.x7l16"x2-1/2" staples
4 nails (direct or toe -nail)
5 staples (direct)
Multiple joists
Bd nails or
15Ga.x7/16"x2-112" staples
32" o.c. top 8 bottom, staggered. 2
nails at ends 8 splice
19132" floor sheathing
15Ga.x7/16"x1-3/4" staples 8 glue
3" o.c. edges
Notes:
1) Smoke alarms (conforming to UL 217) ceiling mounted and installed on o dedicated unswitched 15—amp circuit and are interconnected.
2) All electrical wiring to be in compliance with the National Electrical Code (Model year per state codes & regulations).
3) Exterior light boxes are wired and light shipped loose for field installation. Exterior lights shall be listed for use in wet locations.
4) Non—metallic sheathed cable shall be secured at intervals not exceeding 4'-6" and within 12' from all cabinets or boxes.
5) Non—metallic sheathed cable passing through framing members within 1-1/4' of the edge of such framing member shall be protected with
1/16" (min.) thick steel bushing. Cables passing through notches are protected with 1/16" (min.) thick steel plates.
6) All factory —installed wiring is to be copper.
7) Electrical service to be grounded in field by others after circuits have been completed according to local authority having jurisdiction.
8) Circuits supplying outlets in all dwelling rooms (except for outdoors, bathrooms, garages and unfinished basements) shall have
Arc —Fault Interrupter (AFCI) protection.
9) See sheet 4C for electrical legend
10) See sheet 4B for typical panel board and electrical load calculation.
11) For units intended for installation of a site built attached garage, install 2 additional boxes on the garage side of the exterior wall.
One box to be serviced by a 15—amp general lighting circuit. The other to be serviced by a 20 amp dedicated circuit. The 20—amp
circuit shall be GFCI protected. The 15—amp circuit is for garage lighting, and the 20—amp circuit is,for garage receptacles.
12) Electrical circuits which crossover unit mating lines must be spliced in a Junction box. All circuits that crossover shall be clearly identified
13) Bath, exterior and kitchen countertop receptacles shall have GFCI protection.
14) Kitchen countertop receptacles shall be supplied by not less then two 20—amp circuits. They shall be located not more than 20" above
the countertop. Island and peninsular receptacles are permitted to be mounted not more than 12" below the countertop and where the
countertop extends not more than 6" beyond its base.
56'
10' SA" 19'-
fl r��i
J • lc o N
© , o
KITCHEN
9e Q ilia U
v>�r`�
Chi \ ®'sA/cM
I
I/
I
ly
I
I
,
I
MASTER
if1 n
BEDROOM
µ I I
\
\
I
I !
F------------------�
I I
I I
I I
I I
I � I
I I
LIVING ROOM
I I
�------------------��\
Ir
15) All electrical equipment and conductors shall be listed or labeled by a notionally recognized testing laboratory and in combination with
listing and labeling shall be suitable for location and use.
16) Boxes used to support ceiling fans shall be listed for such use.
17) Carbon Monoxide Alarms (conforming to UL 2034) are installed on an unswitched 15—amp circuit,
(or be battery operated) and located outside of each separate sleeping area.
18) Hallways of 10 feet or more in length shall have at least one receptacle outlet.
19) Balconies, porches and decks require a receptacle outlet when the area is 20 square feet or greater.
20) A switched receptacle outlet ccnnoot be counted towards the minimum spacing of outlets.
The outlet may be counted if only one outlet of the duplex receptacle is switched.
21) Exterior receptacles must be listed as weather resistant in addition to being listed for wet locations. (Weather resistant includes UV protection.)
22) Listed tamper —resistant receptacles are required for all 120 volt, 15 & 20 amp receptacles in dwelling units.
23) A minimum of one communications outlet shall be installed and cabled to the provider service point.
24) The service disconnecting means shall be installed at a readily accessible location either outside
of the home or inside nearest the point of entrance of the service conductors.
25) A receptacle for a cord —and —plug connected range hood shall be supplied by an individual branch circuit.
—10'
1
1
DINING
II 1
BEDROOM
I
II II I
II
II I
i
i
SAD
FI 3
\
1 \1 \ A®
I, ,
BAITNI
0 i BEDROOM
— — — 3 3 `1 ' '' L WA1ERpR0aF y' &
9 I
' CARBON MONOXIDE DETECTOR REQUIRED ONLY WHEN FUEL -BURNING APPLIANCE IS INSTALLED
I—13'-4" 1 4'-4° 1 21'-4" i 5'-4"---L II'-B"�
* No 52231
STATE OF :4u��
Legault
TIK 2019.10.1
14:38:28
-04'00'
N
�O
N
w
U
0--
DUPLEX RECEPTACLE
0===—
CEILING TRACK LIGHT
Q�,
ELECTRIC RANGE RECEPTACLE
® FLUORESCENT STRIP LIGHT
DRYER RECEPTACLE
Fj - RECESSED CEILING
I-- - - - J FLUORESCENT LIGHT
RECEPTACLE, G.F.I. PROTECTED
►
PHONE JACK
a
1p
WATER PROOF RECEPTACLE
G.F.I. PROTECTED
®
SPEAKER
OF
BELOW FLOOR RECEPTACLE
Y
WALL MOUNTED STRIP LIGHT
C�
SINGLE SWITCH
CEILING MOUNTED JUNCTION BOX
DOUBLE SWITCH
❑
CROSS -OVER JUNCTION BOX
TRIPLE SWITCH
O
WALL JUNCTION BOX
�}
CEILING MOUNTED LIGHT
m
SERVICE ENTRANCE PANEL
PULL CHAIN CEILING LIGHT
b
THERMOSTAT
SWITCHED WALL LIGHT
®FURN FURNACE
+
WALL MOUNTED LIGHT
OSv
WALL MOUNTED VENT FAN
Oy
CEILING VENT FAN
®SA
SMOKE ALARM
CEILING LIGHTED VENT FAN
d
POWER RANGE HOOD
QT
SWITCH/RECEPTACLE COMBO
Q^
3-WAY SWITCH
DIMMER SWITCH
®w/R
WATER HEATER
O"
FURNACE SAFETY SWITCH
❑N
TELEVISION JACK
® CM/SA CARBON MONOXIDE/SMOKE ALARM
RECESSED LIGHT
ORv
WHOLE HOUSE VEN11LA110N
ELECTRICAL LEGEND
CIRC. #
DESCRIPTION
AMPS
WIRE SIZE
1
GENERAL LIGHTING
15
14/2 w/grd *
2
GENERAL LIGHTING
15
14/2 w/grd *
3
GENERAL LIGHTING
15
14/2 w rd *
4
GENERAL LIGHTING
15
14/2 w/grd *
PORTABLE APPLIANCE
20
12/2 w/grd
PORTABLE APPLIANCE
20
12 2 w/grd
PORTABLE APPLIANCE
20
12/2 w/grd
Pa
LAUNDRY
20
12/2 w/grd
GENERAL LIGHTING
15
14/2 w/ rd
ELECTRIC RANGE (SEE NOTE #4)
11
COOK TOP 7 KW MAX.
1 30
1 10 3 w/ rd
12
ELECTRIC OVEN 3.7 KW MAX.
20
12/3 w/grd
13
ELECTRIC W H SEE NOTE 3
14
FURNACE FAN (GAS & OIL)
1 15
1 14/2 w/grd
15
ELECTRIC FURNACE/BASEBOARD HTR (SEE NOTE #4)
16
AIR CONDITIONER (SEE NOTE #4
17
CLOTHES DRYER
30
1013 w/grd
18
DISH WASHER
15
14/2 w/grd
19
HEAT LAMP 1600 WATT MAX.
15
14/2 w/ rd
20
HEAT LAMP 800 WATT MAX.
15
14/2 w/grd
21
EVAPORATIVE COOLER
15
14/2 w/grd
22
EVAPORATIVE COOLER
15
14/2 w rd
23
TRASH COMPACTOR
15
14/2 w/grd
24
MICROWAVE OVEN/GAS/MICROWAVE
15 20
14 12 2 w rd
25
FOOD FREEZER
15
14/2 w/grd
26
RECIRCULATING WATER TUB
20
12/2 w/grd
27
BATH GA RECEIPTS
20
12/2 w rd
28
ELECTRIC FURNACE/AIR HANDLER
60/25
4/10/2 w/grd
29
GENERAL LIGHTING
15
14/2 w/grd
30
GENERAL LIGHTING
15
14/2 w/grd
31
PORTABLE APPLIANCE
20
12/2 w/grd
32
---
I ---
I ---
33
SMOKE/CARBON MONOXIDE ALARM
1 15
1 14/3 w/grd
" - 14/3 w/GRD. @ THREE-WAY SWITCH APPLICATIONS
ELECTRICAL CIRCUITS
Jeffrey T.
q Legault
2C".O.24
16:07:01 -0
FP Gy �i
ENSF•:G��:
.: No 52231
10 cc
9 STATE OF ,4u
NOTES: S�ONAi-Ill
E?+`+
1.) WHERE UG4HTS (OPTIONAL.) ARE INSTALLED IN THE HDME, THE ROOM SNITCH WILL BE CONNECTED
TO THE CEILING LIGHT IN PLACE OF THE RECEPTACLE SEE ELECTRICAL LAYOUT FOR THIS OPTION.
2.) JUNCTION BOX ON EXTERIOR WALL MGUNONG HEIGHT IS Ir. LABEL WIRES TO INCLUDE CIRCUIT NUMBERS
WIRE NUT LOOSE ENDS.
3.) CIRCUIT �3 ELECTRICAL W/H REQUIREMENTS:
20 GALLON 120Y 1920 WATTS MAX 20 AMP 12/2 r/99rd
30/40 GALLON 240V 45DO WATTS MAX 25 AMP 10/2 r/gd.
3D/40/50 GALLON (snje dement) 240V 3500 WATTS MAX 20 AMP 12/2 r/gd.
(SEES SPECS FOR SIZE AND TYPE OF W/H)
4.) OR TO EQUIPMENT INSTALLATION REQUIREMENTS FOR WIRE SONG & AMPERAGE RATINGS.
5.) OUTDOOR RECEPTACLE SHALL BE PROTECTED BY WEATHERPROOF ENCLOSURES AND SHALL BE WTH GFCI PROTECTION.
THIS TYPE OF RECEPTACLE IS SHOWN ON EACH FLOOR PLAN NTH 'WP' SYMBOL RECEPTACLES WITH 'Br SYYBOL ARE
INSTALLED UNDER FLOOR WITH WEATHERPROOF ENCLOSURES.
6.) DEDICATED CIRCUIT NOT PROVIDED FOR WINDOW A/C UNITS.
MAX. NO. COND.=VOL. OF BOX -(NO. OF DEVICES x A) - (BOX CLAMP x A) - BxA - CA
A
CALC TO DETERMINE MAX. NO. OF CONDUCTORS
A=2.0 IF 14ga WIRES A=2.25 IF 12ga WIRES
8=1 FOR ALL GROUND WIRES, C=1 FOR YOKE
w
w
o
w
m
C_�
MAX. # OF COND. IN OR
OUT OF BOX - NOT
INCLUDING GROUND WIRE
14ga 12ga
DESCRIPTION
SIZE
IN3
ROUND
1 3/43 1/2 dia.
11.5
0
1
2
2
SINGLE
1 3 4x2 9/320 1/2
12.0
1
1
2
1
ROUND
2 1/80 1/2 dia.
14.0
0
1
4
3
SINGLE
2 3/42 3/8x3 5/16
16.0
1
0
5
4
DOUBLE 1 dev.
1 3 4x4 1 16x3 1 4
16.0
1
1
4
3
DOUBLE 2 dev.
1 3/44 1/160 1/4
16.0
2
1
3
2
SINGLE
3 5/16x2 3 8x3 5/16
18.0
1
0
6
5
SINGLE
2 11/16x2 1/40 3/4
18.0
1
0
6
5
METAL HB
18.9
0
1
6
5
ROUND
2 7/80 1/2 dia.
20.5
0
1
7
6
METAL HB
24.0
1
1
B
6
DOUBLE
2 1 4x4 1 2x3 5/16
25.0
2
1
7
6
DOUBLE
2 11/16x4x3 1/2
32.0
2
1
11
9
TRIPLE
2 1/2x5 15/160 5/16
37.0
3
1
12
10
METAL JB
4x4x4
60.0
0
1
1 27
23
METAL JB
6x6x6
207.0
0
1
1 100
89
BOX SIZING
U,L. listed distribution
panelboard. Pictoral
only, actual configuration
may vary.
Typical circuit
breakers. See
sheet 4C
disconnect - 150 AMP or 200 AMP
Neutral
bus bar
bus bar
Notes:
1. A metal underground water pipe that Is in direct contact with me earth
for 10 feet or more shall be considered as a grounding electrode. An
electrode encased by at least 2 inches of concrete, looted
horizontally near the bottom or vertically and within a footing that Is In
direct contact with the earth, consisting of at least 20 feet of one or
more electrically conductive mated steel reinforcing bars of not less
Pan 112 inch diameter shall be considered as a grounding electrode.
2. An intersystem bonding termination for connecting intersystem
bonding and grounding conductors required for other systems shall
be provided external to enclosures at the service equipment and at
the disconnecting means for any additional buildings or structures. It
shall be accessible for connection and Inspection and have the
capacity for connection of not less than three Intersystem bonding
conductors.
Feeder noway. Rigid
nonmetallic Conduit
1-1/2' min. at 150 AMP. Field install 4 wire service entrance conductors to distribution paneiboard. Use 75 degree
2' min. at 200 AMP. C rated conductors (type RH, RHH, RHW, w/o covering THIN or XHHW).
At 150 AMP service - 2-110 (AWG), 1-#1 (AWG) w1#6 ground.
To Service 4 At 200 AMP service -2-310(AWG), 1-1/0(AWG) w1#4 ground.
Entrance - Site
Installed. TYPICAL PANELBOARD INSTALLATION
r o «
rvinAol'in'.d• v 7R' hnv rmav 1
DESCRIPTION
LOAD
WATTS
Lighting at 3w/square foot
3 x 2305
6915
Small Appliance
4 x 1500
6000
Laundry Circuit
1 x 1500
1500
Bath & Kitchen Fan - 1.3A+1.9A
3.2 x 120
384
Heat Lamps (800 w each)
2 x 800
1600
Dishwasher - 9A
9 x 120
1080
Disposal - 5A
5 x 120
600
Water Heater
1 x 4500
4500
Clothes Dryer- 24A
24 x 240
5760
Recirculating Tub-12.25A
12.25 x 120
1470
Cooktop
1 x 6700
6700
Wall Oven
1 x 7000
7000
Furnace (Gas or Oil)
12 x 120
1440
Microwave -11A
11 x120
1320
Freezer -12A
12 x 120
1440
Maysabshm. 15.5xwren9a Total Watts: 47709
for Cooktop 8 wefloven. -
K
0
First 10KW at 100%, remainder at 40%: 25083.6 watts
Air conditioning and cooling: 43.75A at 100%: 10500.0 watts
oElectric
Furnace at 65 % x wafts: watts
U
TOTAL WATTS: 35583.6 watts
J
2
TOTAL WATTS 1240V: 148.3 amps
c
150 AMP SERVICE OK.
Minimum Feeder Size: 110 CU at 75 degree C
Maysubs5tafa 15.510wrange Total Watts: 47709
for Cooktop 8 wall oven. -
First 10KW at 100%, remainder at 40%: 25083.6 watts
Air conditioning and cooling: 43.75A at 100%: 10500.0 watts
0
Controls Electric Furnace at 65 % x 25000 watts: 16250.0 watts
U
TOTAL WATTS: 41333.6 watts
o,
TOTAL WATTS / 240V: 172.2 amps
j
200 AMP SERVICE OK.
Minimum Feeder Size: 3/0 CU at 75 degree C
Lighting, small appliance and laundry circuits: 14415 watts
first 3000 at 100%, remainder at 35%: 6995.3 watts
Appliance:
Bath & Kitchen Fans: 384.00 watts
Heat Lamps: 1600.0 watts
Dishwasher. 1080.0 watts
Disposal: 600.00 watts
Clothes Dryer (at 70%): 4032.0 watts
Z
Recirculating Tub: 1470.0 watts
Cooking units at (70%): 9590.0 watts
Furnace (Gas or Oil): 1440.0 watts
ti
Microwave: 1320.0 watts
Freezer. 1440.0 watts
TOTAL WATTS: 29951 .3 watts
TOTAL WATTS / 24OV: 124.8 amps
Minimum Neutral Size: #1 CU at 75 degree C
Notes:
1) Use a minimum 150 AMP panelboard. Use 200 AMP panel with an electric furnace.
2)1.112" min. factory Installed feeder raceway for 150 AMP, 2" for 200 AMP.
ELECTRICAL LOAD CALCULATION
?* : No 52231 # t
O. * it
STATE OFoz
C O R
n Legault
lie Tq ( 2019.07.24 d
/ V 16:06:19 c d
-04'00'
Roof Flashing:
Flashings Shan be Installed at waft and roof intmadcWm, wherever
Hera Is a change in mot slope or direction and around roof openings.
Where flashing is of metal, the metal Shen be corrosion resistant with a
thickness of not less than 0.019 inch (No. 26 galvanized steel).
site instal min � lag agates staggered from aide
ru aide et 24'— (—) and Wth 3 sgaes W ox:
war eadl oNc—.
Rmstruct ladpe Con&f—n ridge beam
\ ad�Ouss Par Sheet l3B.
PE CemGietl Rod Trusses per sheet 13. \ 12 '
2A9-S
1.6(. 2xa)fasde /
Alum. Vented Somt-
AmedmazstandardY /
Tmsa to exkdorwan
fastening per Sheet 13C.
Wag Flashing:
Approved conasion- eslst mi flashing shaft be applied
shingle -fashion in a mannerfo prevent the entry of water
Into the wan cov&y or penetration of water to the building
structural Gaming components. The fiashhg shag eaten
to the surface W the exterior wall finish. Approved
flashings shaft be Installed at the foAving locations:
1. Exterior window and door openlgs.
2. the Intersection oftlmmmeys or other masonry
constmcgon with frame or stucco wars.
3. Under and at the ends of masonry, wood or metal
copings and sins.
4. Continuouslyabove aprojecting wood trim.
5. Where exterior porohes, decks or stairs attach to
a wail or floor assembly ofwood-frame
conWc an.
8. Al wan an groof ulunlersectbns.
7. Al buiRtin dagutters.
Typical WM— \
Typical S. p.
Sheet lZ
Double 42 SPF 2x10
Pedmetericluder
Sheet 14.
Cenng Interior flnbh mateiiai Flat m
& 31ng shown (may
Spray—vapa,b.rrW(vd1 elm be raNalml)
perm (max.)—g).
Typical Header per Sheet 12.
Seappiog per
Sheet 138.
Typical ademar well fre n ng per
Sheet 12.
1913T or SW APA mted (vagemq
approved) T&G iiom aheaNvg par
Short 14.
Streppkg per �J\Typicml maM Supply
She.12. HVAC duct (May
We. be.¢mead.)
519' x 8-1R- anchor boh Prassuro haatetl era
wfd'x3•xlla- (rah.) Plate p.d in
—She'. 4'-0'o.a, minter- 31a'aa'(mid.) lag Scows.
sunk �Oand fmtlng, handatlon 2a48oAg mlm(FIeN lltubled).
2V m (yp.)
Elderfor Finish Material:
Roof-Asphaft shingles complying with ASTM D225 or D3462 and tested and bearing a label 'aindicate compliance with AST- D7158 Class H co D3181 Class F. Shingles installed over a double
layer gf 154 felt per manufacturers specifications.
Wan - Vinyl siding (complying with ASTM D3679) or fiber cement siding (compying with ASTM
C1186. Typo A -Grace II) and installed per manufacturers specifications.
Rdgev.d-9enjamm
Obdy e, - xirdCce Vent X1 a
QI16'APA rated (or egenq t ted)mef
/ h¢aNbg per sheet l3.
Sandie roof
�appliation
Note.:
1) See Skyline Modular Home Installation Manual for typical foundatlbn details & Information.
2) An approved f blockNg)dmfta pping —k (or other approved material) shag be Installed on -site at the floor &
tailing maflng line.
3) Madder Insulation shag be covered with a protective material to prevent damage from sunlight, molshure, landscaping
operations, equipment maintenance, and wind.
slaver oeluwe¢ mor Insulation
perShoes 11A-11E.
Weir—.W. �
Fm
.U.'s 'oo wage �ft4i
h4., 18'ac) hvwlat
mting>
IFS=A
ter per Sheet 14. 2x10 e2 SPF fbor)olab IV o<.
per She. 14.
am fm4ng at drawl spa. fort h.
S�QkEY
No 52231 ,k5
90. STATE OF :�W`
JeffreyT.
g Leg..Jt
2019.07.24 t %
16:05:18 -04'00
1-124-laede and eddrid, Sf Ane.
InsNatbn bellies Nsfaled ldn'.inlein a 1'
mIr. ventilation epem above Insulation
r mat.
sairt, r heStWrIA nit fl
mlhh mammal.
W
W
a
Won emSino Material It Fasleninm
711a'APA r.ed (or agency lasted)
pylvpd shealhlag mrasWtlM per
Sheet l2A.
WabrAdsr tall ShS. irw Fee—
Appwad weather reel,Wd—val
t11A-
keep
flow
Shag be epysd overdroeW.g a
I xterior wage.
-20• mid. (W.)
I11SAIr Finish Material:
Celina -10 or W"gypsum board complying with AMM C36 and insisted per Sheet 3C.
Well -10 gypsum board complying with ASTM C36 and Installed per Sheet 3C.
Flame Spread /Smoke Developed Indexes:
Wag and coging finishes she. have a flame spread Index.1 net greater than 200 and a smoke-
d webped Index of not greater than 450. Flame spread index requirements for finishes shal not
appy m trim; m doors and windows or theta flame.
NOTES:
1.) Drain lines to maintain 1/4' per fool minimum slope.
(1/B' min. slope for 3' piping)
2.) Dram lines ran below floor may be field 'installed.
3.) Any part of the plumbing system installed in the factory
must be inspected, tested and approved at the factory.
4.) A minimum of one main 3' vent shall extend outdoors to the open or.
5.) Drain line prying shall be supported 4'-O' o.c. horizontally,
and at each story vertically.
6.) Dram lines may be stubbed through floor, and remainder field installed by
builder on -site.
7.) Maximum distances from fixture trap to vent is 6' for 1-1/2' line,
5 for 27 line and 12' for 3' line.
8.) Vents through the roof to extend 1 foot above the roof. Every vent extension
through the roof shall be not less than 3 inches in diameter. Any increase in the
size of the vent shall be a mininum of 1 foot below the roof or inside the wall
9.) Maximum distance from waste outlet to trap we'v is 24'.
10.) Cleanouts shall be accessible. Minimum clearance in front of cleonouts shall
be 18' on 3' pipe, and 12' on smaller pipes. Concealed cleanouts shall be
provided with an access
11.) Standpipes shall extend a minimum of 18 inches and a maximum of 42 inches
above the trap wier. Access shall be provided to an standpipe traps and drains.
12.) Slip pints shall be made with an approved elastomeric gasket and shall be
Installed only on the trap outlet, trap inlet and within the trap seal. Fixtures with
concealed slip -pint connections shall be provided with an access panel or utility
space at least 12 inches in its smallest dimension or other approved arrangement
so as to provide access to the slip connections for inspection and repair.
13.) In concealed locations, where piping is installed through holes or notches in
studs, joist, rafters or similar members less than 1-1/2 inches from the nearest
edge of the member, the pipe shall be protected by steel shield plates. Such shield
plates shall have a thickness of not less than 16 Gage and shall cover the area of
the pipe where the member is notched or bored, and shall extend a minimum of 2
inches above the sole plates and below the top plates
T. Le
F(3,q'ii
* : No 52231
0 STATE OF
�%%���
JeffreyT. Legau
2019.10.10
14:37:58-04'00'
TEE
LEGEND:
VTR = VENT TNRU ROOF.
C.O. = CLEANDUT.
SAN TEE = SANITARY TEE.
LTTY = LONG -TURN T-Y OR COMBINATION
WYE w/ 1/8 (45') BEND.
TP = TERMINATION POINT.
AAV = AIR ADMITTANCE VALVE.
SEE MAN. INSTALLATION INSTRUCTIONS.
4
12
r-
NOTES:
1) Shut-off valves required at all fixtures, except tubs or showers.
2) Water lines ran below floor may be field installed.
3) Plastic water line piping shall be supported 3'-O" o.c. horizontally, and at each story vertically.
4) Pax water line piping shall be supported 2'-8" o.c. horizontally, and at each story vertically.
5) One anti -syphon type frost -free hose bibb installed standard per home.
6) Water hammer arrestors shall be installed at washer box, ice maker and
dishwasher connections per the manufacturer's installation instructions.
7) Maximum flow rates for fixtures are as follows:
a) Lavatory or Sink faucet - 2.2 gpm at 60 psi
b) Shower head or hand held shower - 2.5 gpm at 80 psi
c) Water closet (toilet) - 1.6 gallons per flush
B) Water heater shall be equipped with a separate pressure and temperature relief valve or a combination
pressure -/temperature relief valve. Bottom fed tank -type water heaters
shall have have vacuum relief valve installed. WASHER
9) Inlet to be field installed with shut-off valve.
10) Any part of the plumbing system installed in the factory must be
inspected, tested and approved at the factory.
11) Water heaters shall be installed in a galvanized steel pan (having a ^
minimum thickness of 24 Gage), or other pans approved for such use.
The pan shall be not less than 1-1 inches deep and shall be of sufficent
size to recieve all dripping from the water heater. It shall be drained by
on indirect waste pipe (with minimum j inch diameter) per water line TOILET
material specifications. The pan drain shall extend full-size and terminate
over a suitably located waste receptor or shall extend to the exterior of
the home and terminate not less than 6 inches and not more than 24
inches above the ground. —
12) Individual shower and tub/shower combination valves shall be equipped
with control valves of the pressure -balance, thermostatic -mixing (or
combination) valve types to limit water temperature to a maximum
limit of 120 degrees F. The hot water supplied to bath tubs and 1/\\
whirlpool bathtubs shall be equipped with a water -temperature -limiting
device to limit water temperature to a maximim of 120 dgrees F.
13) All hose bibbs shall be protected by vacuum breakers and equipped with
an accessible slop -and -waste -type valve inside the building.
14) Acess shall be provided to circulation pumps in accordance with the
installation instructions. Where these instructions do not specify the
location and minimum size of the access opening, a 12-inch by 12-
inch minimum size opening shall be installed. Where pumps are located
more than 2 feet from the access opening, an 18-inch by 18-inch
minimum size shall be installed. A door or panel shall be permitted to
close the opening. The access opening shall be unobstructed and be of
the size necessary to permit the removal and replacement of the
circulation pump.
15) In concealed locations, where piping is installed through holes or notches
in studs, joist, rafters or similar members less than 1-j inches from the
nearest edge of the member, the pipe shall be protected by steel shield
plates. Such shield plates shall have a thickness of not less than 16
Gage and shall cover the area of the pipe where the member is notched
or bored, and shall extend a minimum of 2 inches above sole plates
and below top plates.
1" INLET
W/ CAP & CHAIN
SHOWER
LAV
LAV
m SHUT-OFF VALVE
T WATER HAMMER ARRESTOR
PIPE
=3/4- PIPE
=1/2I PIPE
KITCHEN
SINK
OPT.
DISHWASHER
n
n
APPROVED
CONNECTION
T/P VALVE
W/OVERFLOW
WATER
HEATER
The following hot water piping shall be insulated to R-3 min.:
1. All 3/4' or larger piping.
LAV
T.
*: No 52231
o' * irZ
=�9 W? STATE OF :
,0
Jeffrey T.
/J/QgyO 2019.1Legault
,A! /7 ^ 9Y 2019.10.10
14:37:30-04'00'
TOILET
TUB
11
WATER UNE MATERIAL SPECIFICATIONS:
Chlorinated polyvinyl chloride (CPVC) plastic pipe - ASTM D-2846, F-441 or F-442
Chlorinated polyvinyl chloride (CPVC) plastic fittings - ASTM F-437, F-43B or F-439
Cross -linked polyethylene (PEX) plastic tubing - ASTM F-877
Cold expansion fittings w/reinforcing rings for PEX tubing - ASTM F-1960
PLUMBING FIXTURE SPECIFICATIONS:
Enameled cast-iron plumbing fixtures - ASME A112.19.1
Hand held showers - ASSE 1014
Shower & tub/shower combination control valves - ASSE 1016 or CSA B125
Non -vitreous ceramic plumbing fixtures - ANSI A112.19.9M
Plastic bathtub units - ANSI Z124.1
Plastic lavatories - ANSI Z124.3
Plastic shower receptors and shower stall - ANSI Z124.2
Plastic sinks - ANSI Z124.6
Porcelain enameled formed steel plumbing fixtures - ASME A112.19AM
Stainless steel plumbing fixtures - ASME A112.19.3M
Vitreous china plumbing fixtures - ASME A112.19.2M
Water closet flush tank ball cocks - ASSE 1002
Whirlpool bathtub appliances - ASME A112.19.7M
Water Hammer Arrestors - ASSE 1010
Water Heater Relief Valves - ANSI 221.22
Water temperature limiting device - ASSE 1070
Water heater pans (listed) - CSA LC3
Vacuum relief valves - ANSI Z21.22
21'-4°
Notes:
1) Heat pump to be provided on -site by others.
,, . ,P pluugpr
%` EY T. LEA�i,��
* No 52231 •:
9 : 2
�'. STATE OF
••°nm
} Legault
gzq�kl 2019.10.10
66 44 14:37:01
-04'00'
MWaSalleBristol
onurnnturrna
Engineered System Using
v �'
Overhead Graduated Flex
m Z
Ducts w/ Ceiling Diffusers
m
for Up -Flow Split A/C
8
O
0
BUILDING THERMAL ENVELOPE
REQUIREMENTS
Building Envelope Item
All joints, seams and penetrations.
Site -built windows, doors and skylights.
Openings between window and door assemblies
and their respective jambs and framing.
Utility penetrations.
Dropped ceilings or chases adjacent to the thermal
envelope.
Knee walls.
Walls and ceilings separating the garage from
conditioned spaces.
Behind tubs and showers on exterior walls.
Common walls between dwelling units.
Attic access openings.
Rim joists junction.
Other sources of infiltration.
Notes.
a) The building thermal envelope shall be durably sealed to
Imit infiltration. The above items shall be caulked, gasketed,
weatherstripped or otherwise sealed with an air bailer
material, suitable film or solid material.
PRESCRIPTIVE COMPONENT EFFICIENCY REQUIREMENTS
Climate
Zone
Fenestration
U-Factor
Skylight
U-Factor
Max. SHGC
Factor
Catlin
R-Value
Ext. Wall
R-Value
Floor
R Value
1
NR
0.75
0.25
30
13
13
2
0.40
0.65
0.25
38
13
13
Notes.
a) Roof/ceiling Insulation is blown cellulose. Install per manufacturer requirements, including density and thickness.
The thickness of the blown Insulation shall be Identified by markers that are labeled In Inches Installed
at least one for every 300 square feet throughout the attic space. The markers shall be affixed to the trusses and
marked with the minimum Installed and settled thickness. The markers shall face the attic access.
b) Wall insulation is fiberglass batts.
c) Additional or higher insulation levels maybe required for specifcfloorplans. Refer to model -specific energy
calculations for required insulation levels.
d)'U'values to be determined in accordance NFRC 100 by an accredited, independent labomtoryand labeled and
certified by the manufacturer.
e) As an altemative to the prescriptive requirements, compliance based on simulated energy performance requires
that a proposed design be shown to have an annual energy cost that is less than or equal to 80 percent of the
annual energy cost of the standard reference design.
0 R-values listed above are minimums and U-factors listed above are maximums.
g) See Sheet 11A-11F for the Performance -Based Compliance Report.
General Requirements:
1) Joints, penetrations and all other such openings in the building envelope that are sources of air leakage must be sealed.
2) Recessed lights must be Type IC rated,
3) Vapor retarder with a maximum permeance rating of 1.0 is required on warm -in -winter side of non -vented framed walls and ceilings.
4) Furnace and water heaters when provided are 3rd party listed and labeled and installed per their manufacturer instructions. Manuals for all installed equipment are provided with home.
5) All duct joints, seams and connections must be securely fastened with welds, gaskets, mastics, mastic -plus -embedded -fabric, or tapes. Duct tape is not permitted. Tapes, if used, shall be a metallic type U.L.
listed 181A for rigid duct systems 181E for flexible duct systems.
6) Air filters are required in the return air system.
7) Each home shall be provided with one thermostat caple of automatically adjusting the space temperature set point of the largest zone.
8) Main HVAC trunk is 314" U.L. Listed fiberglass rigid duct board.
9) Supply ducts located in attics shall be insulated to a minimum of R-8. All other ducts shall be insulated to a minimum of R-6.
10)Waler heaters with vertical risersmust have a heat trap on both the inlet and outlet unless the water heater has an integral trap.
11)Attic access panels in ranch homes shall be weatherstripped and Insulated on the attic side with fiberglass batt insulation with same R-value as rest of attic.
12)Energy Performance Level (EPL) display card shall be completed and certified by the builder.
13)ducl-tightness shall be verified on -site by testing to ASHRAE Standard 162, per Florida Building Code - Energy Conservation 403.2.2.1.
14)Adequate return air shall be provided for fuel-buming forced air furnaces through air -tight ducts. The total return air area shall be in accordance with the furnace manufacturer's instructions. Return air shall not be
taken from a closet, bathroom, toilet room, kitchen or garage. Grilled or lowered openings shall be installed between all habitable rooms and the main return air grille.
15)Air balancing dampers (or other means of supply air adjustments) shall be provided in the branch ducts or at each individual duct register, grille or diffuser.
16)Make-up air requirements for the operation of exhaust fans, kitchen ventilation systems and clothes dryers shall be considered In determining the adequacy of a space to provide combustion air.
17)The air removed by every mechanical exhaust system shall be discharged to the outdoors. Air shall not be exhausted into an attic, soffit, ridge vent or crawl space. Clothes dryer exhaust ducts shall have a
smooth interior finish and shall be constructed of 0.016 inch metal. Kitchen range hood ducts shall discharge to the outdoors through a galvanized steel single -wall duct with a smooth interior finish (which is
air -tight and equipped with a backdraft damper) designed to have a ventilation rate of 100 cfm intermittent or 25 cfm continuous. Bathroom exhaust duct material shall be in compliance with UL 181 and UL 181A
or UL 181 B designed to have a ventilation rate of 50 cfm intermittent or 20 cfm continuous.
161Vent terminals for direct -vent appliances shall be installed in accordance with the manufacturer's instructions. Vent terminals shall not be located less than 3 feet above a forced air Inlet located within 10 feel.
'they shall be located not less than 4 feet below, 4 feet horizontally from, or 1 foot above any door or window and shall be located at least 12 inches above finished ground level.
PEY T.L�c,���i .
.E
No 52231
ji
:t
'P STATE OF 4
•,,SS',ONA%e 1%%�
p Legault
#j '?7 t1 2019.07.24
0" 4 16:02:39
-04'00'
�i
s � �
REScheck Software Version 4.6.5
Lvi
Compliance Certificate
Project 6233-MA
Energy Code:
2017 Florida Building Code, Energy Conservation
Location:
Fort Pierce, Florida
Construction Type:
Single-family
Project Typo:
Now Construction
Orientation:
Unspecified
Conditioned Floor Area: 1,692 11:2
Glazing Area
20%
Climate Zone:
2 (490 XDD)
Permit Date:
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor.
Southwind Trall
Ft. Pierce, FL 34951
Compliance: 10.0%Bcttor7ban Codo • P.M.— UA. 402 YourUA 362 rdatlmum SiMC: 0.25 Your5114C: 0.25
IIDOEESttMtpmvldeanftt,ate�aie�nc'wmwmirelativeWamtu�inu odeeno . on nwa vaaoan wrs.
`Et
I T. LE in, EIVg
*� No 522311
q::
STATE OF
A,:OR1OP ' N=
ss,ONA;
Compliance Statement- The proposed building design described hero is consistent with the building plans, specifications, and other) -
calculations submitted with the permit application. The proposed building has been designed tomcat the 2017 Florida Building Code,
Energy Conservation requirements In REScheck Version 4.6.5 and to cemplywith the mandatory requirements listed in the REScheck
m¢nprtinn M1 klict.
Edward L. Weber, P.E. -.�zlL 1019119 Jeffrey T. Legault
Name - le Signature Date 2019.10.10
14:36:31-04'00'
Project Notes:
32'x56' Ranch / 8'-81 Sidewall / Crawl Space.
Calliba l: Flat Ceiling or Scissor Truss
1,692
19.0 0.0 0.051 86
Wall l: Wood Frame, 36• o.c.
1,520
17.4 0.0 0.063 83
Orientation: Unspedlled
Window 1: Vinyl Frame:Doublo Pane with Low-E
120
0.350 42
SIIGC: 0.25
Orientation: Unspecified
Door 2: Solid
43
0.350 15
Orientation: Unspecified
Door 3: Glass
40
0,350 14
SHGC: 0.25
Orientation: Unspecified
Floor 1: AO -Wood joist/rmss:Over Unconditioned Space
11692
11.0 0.0 0.072 122
Mechanical Equip
n
Alf Source
7.7 HSPF, 13 SEER
u,
m o1pi. z
oML
N y
U°Nr7i
t
Project Title: 6233-MA
Report date: 10/09/19 Project Title: 6233-MA
Report date: 10/09/19
Data filename: MAEnglneeringlPOElModulars\Check\REScheck16233.rck
Page 1 of10 Data filename: M:1EnglneeringlPDE\Modulars\Check\REScheck\6233.rck
Page 2 of10
_
fREScheck Software Version 4.6.5
Inspection Checklist
Energy Code: 2017 Florida Building Code, Energy Conservation
Requirements: 0.0% were addressed dlrectiy In the REScheck software
Text In the 'Comments/Assumptions" column Is provided by the user In the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that Is documented, or that an exception
Is being claimed. Where compliance Is Itemized in a separate table, a reference to that table is provided.
3ectlon
M
Pro-Inspectlon/Plan Review
Plans VodOed
Value
Fla1d=fl d
Velua
Complies? Comments/Assumptions
& R .ID
203.1.
;Construction drawings and
O[omplles
103.2
'documentation demonstrate
ienorgy
ODxs Not +
'
IPRlIt
0
code compliance forthe
building envelope. Thermal
ONot Observable 1
envelope represented on
-
ONot Applicable
l construction documents.
l
103.2.
ICocume t drawings and
OCompllas ;
303.2,
'documentation demonstrato
ati
ODoes Not
403.7,
403.E
ionorgy coda compliance for
ONot Observable
IPR311
1lighting and mochanicol systems.
!Systems serving multiple
I
ONot Applicable I
al
idwelling units must demonstrate
'complianco with the IECC
� [ammcmin] Provisions.
302.2.
Heating and cooling equipment Is
11 Heating:
I Heating:
;OComplies ;
403.7
sired par ACCA Manual 5 based
t BtuJlir_
I Btuihr
'ODoeS Not
iPR21'
ton loads calculated per ACCA
I Manual
; Cooling:
cooling:
1ONot Observable j
J or other methods
approved by the code official.
p tvlhr_
I
! Otufir
loNot Applicable i
i
302.2.
lHeating and cooling equipment Is
1 Heating:
Heating:
IOCornplias
403.7
i shod per ACCA Manual 5 based
Btuihr_
I Stulhr
'ODoes Not i
1PR2)1
ion leads calculated per ACCA
Manual J or other methods
I Cooling:
I
Coolin W.
i
jONot Obsarvablo i
approvad by the coda official,
Btuihr_
Btufir
1
,ONot Applicable
Refor to R403.7.1 forfull details.
I Additional Comments/Assumptions.
1 I High Impact (Tior 1) 12 IMedium Impact friar 2) 13 Low Impoct (Tier 3)
Section .. _ .
0 Foundation Inspection complies? Comments/Assumptions
& R .ID
303.2.1.3 A protecave covering is Installed to IOComplies ;
IF01111 jpmtm exposed cxtodarinsulation '1ODoos Not j
9 '9naddaextends a minimum of 61n. below IONot Observable
1 10N0[Applicab10 !
403.9 15now• and Ice malting system controls:Oeomplies
gI
IF012P iinalled, ioDaes Not
5b IONot Observable
iONoc Appllcoblo
Additional Comments/Assumptionst
Project Title:6233-MA Report data: 10/09/19 ProlectTitle:6233-MA Report date: 20/09/19
Data filename: M:\Englneering\PDE\Modulars\Check\REScheck\6233.rck Page 3 of10 Data filename: M:\Engincering\PDE\Modulors\Chock\REScheck\6233:rck Page of10
T CF9�,��
E
No 52231
= 0' irZ
9O: STATE OF :�4U`�
4.
0NA� L� %%
Legault a
off 2019.10.1
0 14:36:02
-04'00'
T. LF
���•�PEY
.��G E N SF
No 52231 :.
0: :XS
STATE OF :urn
NA- E�%%
Section -
Plans VoFIRod
Field
JeffreyT.
Legault
p.zot9.lo.t
S
014:35:1
04'00'
?�
m
J
W
o
i
u
°g
�+
C4
►zQU
Additional Comments/Assumptions:
NMI
U
W
W
y
U
���
Q
maZ
O
_
w
U N 7
a
1 High Impact (Tier
1) 2 Modlum impact (Tier 2) ,3" Low Impact (Tier 3)
o
F
!�
1 High Impact (TI¢r 1) 2. Medlumimpact (Tier 2) 3; Lev Impact (Tier 3)
Project Title:6233-MA Report date: 10/09/29
Project Title:6233•MA
Report date: 10/09/19
Data filename: M:\Engineer(ng\PDE1Modulars\Chock\REScheck\6233.rck Page 7 of10
Data Rlename: M*.Wngineering\PDE\Modulars\Clteck\REScheck\6233.rck
Page 8 of10
M Insulation Inspection..
-.ID
value
Vonaed
Valud compllosT Comments/Assumptions
ffeR
303:1. 1AII installed Insulation Is labeled
� Complies l
IIN33]° jor the Installed R•values
-❑Does NM j
- _�m0v�d�'
[]Not Observable
^`
❑Not Applkable
303.2 �WaO Insulation is Installed per
OComplics
(INQP lmanufacturor's instructions.
}}❑DcesNa j
'f❑Not Obsorvabla
❑Not Applkable j
303.2, iFloor Insulation lnsWOod per❑Complies
402.2.7 jmanulacturer's lnstmctlons and
]❑Dces Not
(IN211 11n substantial contact with the
'untl¢rside Roar
; ❑Not Observable ;
of the subfbon or
j/rominq cavity Insulation is In
❑Not Applicable
;contact with the top side of
-
jsheothing, or continuous
y
,insulation Is Installation the
• f I
;undersltlo of floor framing and
;
le#ends from the bottom to the
:top of all perimeter floor framing
members.
..l❑Does
402.1:1, jWali Insulation R-value. if this lsaj❑R-Wood
R-_ Complies 'see McOnvelape Assemblies
402.2.5, mass wall with at Ica st Vi of the
jwall
j❑Wootl Not table lorvalues
j
402.2.E Insulation on the wall
I❑ Mass
�❑ Mass � Observable 1
11N31t jc#crier, the exterior Insulation
:requlremone applies (FR30).
j❑ steel
�❑Not
;❑ Stool ❑Not Applicable ;
j
1
402.1.3, Floor insulation R-value.
; R-_
R-_ ❑Complfes. is.. ma Emxiopa Asscmbaas
402.2.E j
t
'❑ Wood
1❑ Wood j❑Ooes Not lwble far values
(IN3t
� ❑ Steel
j ❑ Steal j❑Not Observable I
1
I
;❑Not Applicable j
I
Ap2.2.14 Walls, c¢Ilings orlloors common
!❑Compiles
IIN14Jt' -, to separate conditioned
❑Does Not j
_ tenancies are insulated to >m R-
❑Not Observable
' �31, space permitting. Mass
temman wails arc fOsoixed to
❑Not AppRW¢le ;
!>e R•6.
Section - -
tt - Flnal Inspocdon Provislbns
pions VeNfted
Value
Field VorID¢d
CompliadT Commotits/Assumptldna
.Value
303.1.1.2. ;Ceiling Insulatbn InstaOad par
.. •^. . `, ' •
OComplies ;
1, 303,2 jmanufacturor's lnstmc[lons.
❑Dces Not j
[FI2]t ;Blown Insulation marked very
;
❑Not Observable I
.300 ft'.
'
❑No[ Applicebb j
303 3 - Manufacturer manuals for
.
❑Complies 1
mechankal and water hlvting
❑Does Not {
systems lava been providetl.
'.
❑Not Observable ;
.IAn
,.`❑Nat
Applicable
401.3 en¢r9y poAomwnce Ievol
,
❑Complies. 1
(F1331r j (EPL) display card must be
❑Does Not j
yy completed and certlfletl by the
-
❑Not Observable '
lbullder before (Taal approval of
111lll the building faroeeupancy.
a
k ,{❑Not
Applkable
Fladda law (Section 553.0085,
Statutes) roqulres the EPt
�Flodda
tllsplay cartl to be Included as an
¢Otlendum to each sales contract
for both pmsoltl and nonpmsold
f
resitl¢ndal buildings. A copy of
the EPL card form can ho found
;
Tin Appendlk C of the
� �. � •'
,Energy Conservation°.
402.1.1, ;Ceiling insulation R•value. :
R• ; R•
i❑Complies IseorM Envoropo Asscmali¢s
402.2.1, j j
❑ Wood I ❑ Wood
❑Does Not ,rebto Iarvalues
6 �
Steal Stcol
;❑Not Observable I
r
fU1 2
i❑ f❑
;❑Not AppllWble
i
402.23 (Vented oltics with air permeable
❑Complies
[FI221t Insulation Indudo bafOc adJacent
❑Oces Not
i
Ito sofOt and ¢eve vents [hat
;eMends over lnwlatlon.
•. '❑Not
Observable I
❑Not Applkable j
402.2.4 ,Attk access hatch and door
I R•_ ; R•_ ;❑Complies
Ifl31r Ilnsulation aR-value of the
j ❑Dots Not
jatlJxentassembly.
i ;❑Not ObServobla ,
j
+
❑No[Applkoble j
402.4.1.2 !Blower doortest @ 50 Pa. a=T
j ACW SO =� ACH SO =_
;❑Complies ,
(FI17)1 ;ach.
1
j❑Does Not
j
I❑Not Observabl¢ j
'
!❑Not Applicable j
403.1.1 fEach separoto heating/coogng
❑Complies '
[Fig)rsystem has a thermostat
❑Does Not
❑Not Observably
❑Not Applicable I
403.1.2 Programmable thermostats
❑Campli¢s I
[FI91 {I Installed for control of primary
,❑Dces
Not
fleeting and cooling systems and
Initially sat by manufacturer to
y
❑Not Observable j
code specifications.
'
❑Not Applicable j
403.1.3 Hex pump thermostat Installed
❑Complies
(FIlOP �on heat pumps.❑Does
Not
pNot Observable
1
� '
❑Not Applkable j
4033 :Hoc water hollers supplying heat
❑Compiles I
IF26Pthrough one- or two -pipe heating
_ - -
❑Does Not ;
systems have outdoor setback
❑Not Observable
#- control to Tower boiler water
[empnature based on outdoor
'
❑Not Applicable 1
i temperature.
APPENDIX RD
FORMS
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX" =_
The lower the Energy Performance Index, the more efficient the home.
%%%%% T. Er,, 4I4 0
`O;�.OENSF9G�
*: No 52231 *S
90: STATE1.
NALG�.
rr0nutt►tttw
1. New home or, addition
1. Now
12. Ducts, location & Insulation level
p Legault
2. Single-family or multiple -family
2 Single-family
a) Supply ducts
R=9.0Ffl
2019.10.10
3. No. of units (if multiple -family)
3.1
b) Return ducts
R=
14:34:21
4. Number of bedrooms
4. 3
e) AHU location
-04'00'
S. Is Otis a ivorst case? (yeslno)
5. Yes
13. Cooling system:
Capacity: 3.0 tom
G. Conditioned floor area (sq. ft.)
6. 1692
a) Split system
SEER
7. %Yndow% type and area
b) Single package
SEER
a) U-factor:
7a. 0.36
c) Groundhvater source
COP
b) Solar Ilea( Gain Coefficient (SHGC)
7b.0.25
d) Room unit/PCAC
EER
c) Area
7c. 120 sq, ft
e) Other
8. Skylights
14. 1 Jesting system:
a) U-factor
8a
a) Split system (heat pump
I.ISPF 7.7
a
b) Soler Heat Gain Coefficient (SHGC)
8b.
b) Single package leat pump
HSPF
9. Floor type, insulation level:
c) Electric resistance
COP
w
o
9
a) Slab -on -grade (R-value)
9a.
d) Gas furnace, natural gas
AFUE
b) Wood, raised (R-value)
9b. 11.0
e) Gas furnace, LPG
AFUE
o
o
c) Concrete, raised (R-value)
9c.
f) Other
10. Wall type and insulation:
15. Water heating system
a
A. Exterior.
a) Electric resistance
EI 0.95
I. Wood frame (Insulation R-value)
IOA 1, 19.0
b) Gas fired, natural gas
EF
W
2. Masonry (Insulation R-value)
IOA2.
c) Gas rtrcd,.LPG
EF
B. Adjacent:
d) Solar system with tank
EF
W
U
I. Wood frame (insulation R-value)
IOB1.
c) Dedicated heat pump with lank
EF
2. Masonry (Insulation R-value)
IOB2.
9 Heat recovery unit
HcatRcc%
11. Ceiling type and insulation level
g) Other
A4
a)Under attic
11a.19.0
16. HVACcredits claimed (Performance Method)
■�
b) Single assembly
Ilb.
a)Ceiling fnns
c) knee walls/skylight walls
I I c.
b) Cross ventilation
W
d) Radiant barrier installed
I ld.
c) Whole (rouse fan
Q
d) Multizone cooling credit
w'
e) Mullizone healing credit
W
f) Programmable thermostat
U
'Label required by Section R303.1.3 of the rlorlda Binding Carle, Energy Cotuenailon, if not DEFAULT.
1 certify, dint Obis home has complied with theriorlda Building Cocle, Energy Coruen-ation, through the above energy saving features which
o <
will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL display cant will be completed based on installed
c
a
code compliant features. / / /
m
E
4 Z
m
0�y
Builder Signature:
Data 1018119
e
a
Addross omcw Noma: SouthwinclTrall
City/FLZip: FortPierce, FL 34951
FLORIDA BUILDING CODE -ENERGY CONSERVATION, 6th EDITION (2017)
R-51
Max. Marriage Wall Colum Spans
Column 28' & 32' Wides
Configuration 20 PSF Roof Snow
Load
V
13'-l"
26-3"
16'-0'
Double 2x #3 SPF top plate at exterior sidewalls
/and marrige walls. See notes 2 & 12.
Max Exterior Sidewall Header S ans
28' & 32' Wides wl 7" max. overhang
Header
20 PSF Roof
Configuration
Snow Load
HE
3-2x3s
30.5"
36.5"
®3-2x4s
41"
48"
on edge
®
1-24 laid
19"
24.5"
®
2-2x6s
38"
47"
laid flat
®
3-2x6s
57"
68"
®3-2x6s
59"
72"
on edge
/2x cripples above and below
Window openings 16" o.c. Same
material and size as o-c- studs -
for headers.
Pine 2x sill
1
All Normal studs 16" o.c. max
\
2x6 #3 SPF / Pine for exterior walls.
343 SPF! S. Pine jamb studs at
343 SPF! S. Pine jamb
'
2x4 il3 SPF forrmarriage walls.
window openings. (2 w/ 46.5" max.
opening.) 1 to be a jack stud.
studs between windows.
2 to be jack studs.
Bottom plate to be 2x
any grade.
2x3 #3 SPF for interior non -load bearing walls
TYPICAL WALL FRAMING
Max. Sidewall Opening Sans
28' & 32' Wides w/ 7" max. overhang
Strap from header -to -stud & from stud -to- floor
w/ 9-0.148'xl-1/2' nails per strap
1-Simpson ST22 strap
5'-0"
2-Simpson ST22 straps
1 11'-4"
Typical center beam.
See sheet 13B.
Varies. See Sheet 13B
Marriage wall
Mating Line columns
required at marriage
wall openings. See
table above.
CENTERLINE COLUMNS
Notes:
1) Exterior sidewalls tobel04*highmax. Cathedral exterior endwalls, interior partitions and marriage walls maybe 126'max.
2) Interior non -load bearing panitlons, and exterior endwalls may have a single top plate. Staggerend joints on double top plates 48" min. Fully glue and staple top plates in lapped area.
3) Headers in table are applicable to exterior sidewalls only. Headers to be same as sill for exterior endwalls.
4) Exterior walls to be 2x6 construction. Centedine marriage walls to be 2x4 construction and be on both halves of unit (double wall). Interior partitions to be 2x3 construction (min.).
5) See specifications sheet 3C for fastening schedule.
6) Multiple member laid flat headers shall be glued.
7) All exterior walls are to be sheathed with 7/16" min APA rated (or agency tested) wall plywood sheathing. See sheet 12A for wall bracing requirements.
8) Marriage wail is to be on both halves of units. Columns in the above table, shown on one half must be used In combination with columns on opposite half. Add individual spans together to determine allowable span. Size columns
between adjacent marriage wall openings by adding spans together.
9) Required column configurations are shown on the model specific floorplan.
10) If hole is between 40 % & 60 % of stud depth, then then stud must be doubled and no more than two successive studs are doubled and so bored. Load bearing studs only.
11) Bored holes shall not be located In the same cross section of cut or notch in stud.
12) If the top plate of a sldewall or marriage wall is cut, drilled or notched by more than 50 %of It's width, then install a 16Ga.xl-l/2" min. galy. steel strap to each plate across and to each side of the cut out w/8-10d nails or equivalent.
L Strap must extend 6' past the opening.
,`,,���Yt T. iL
i
* : No 52231 *L
9O: STATE OF
ONAt 1��G`,
2019.07.24
15:58:18 -04'00
Hole max di.. 60%
Hole max. dia. 40% of stud depth.
of stud depth. 2-1/16" far 2x4
2-118'1or2.6 1-1/2'for2x3
1-3/8'for 2x4 3.1.4'for2x6
J
W N
5/8"mIn.
(=
to edge 0
5/8• min.
to edge
Notch net to
Notch not to
exceed 40%of
exceed 25%o} Mutl depth.
stud depth.
tale"for2x4.
7/8'for2x4,
1. for 23
1.a/6'for2x6
i 2.118'for2xe.
Load Bearino Non -load
Studs Bearing Studs
W
(Side & Marriage (Endwags &
Wags) Panitlons)
STUD NOTCHING & DRILLING
y
See notes 10 & 11.
maz
5 n o
0
U N W
JN
Strap double stud to rim joist (at each comer) wl t Fasten ban. plate to floor
2-Seep—ST22 Strap Ties w1 g-0.148-xt-1 W w=x3-10 a-- 6' o.c
naffs ea. end. See note 4.
WALL BRACING REQUIREMENTS AT SIDEWALLS
Unit Centemne
Sid-13
Double stud
each and of t
1Shnpson ST22 Strap Tie w/ e-0.148'x1-12' required at centerline (4
nails ea. end. See note 4. studs total).
WALL BRACING REQUIREMENTS AT ENDWALLS
=asten Wes bottom chord to top
data w#W,3-12' screws 16' o.c.
Toe -screwed)
Well sheathing to be 7116' min APA
rated (or agency tested) sheathing.
Fasten to well framing with Bid gal,
box nabs (0.113'x2-12') G o.c. at
Panel edges and 12' mc. at
intermediate members.
Double stud"""
"" at each end
/ of sldewaR
I i _
o r -_ _ - I✓. fault 1 1
I �, I 1433:1FUR height wall seclions must be FUR height wet section required at each
/Wall sheathing to he Ills' min APA ated (or agency tested) sheathing. Fasten to wall framing
with ad gaN. box nags RDA 13'x2-10) 6' o c. at panel edges and 12' o.c. at Intermediate
emhem. AM fa ua, to finer W t R dnuh1n tnn Nat,, w/ 2. of - A• n m.
``��%�PE�Y T......
.�GENgF.(i�•�
No 52231 '.
O: t�
:9 STATE OF .';
Full height wall section required at
each sidewalVendwall comer.
(See Note 4.)
NOTES:
1) This sheet indicates requirements for exterior wall bracing due to the effects of wind.
2) Stagger nails at adjoining panel edges. Nails shall be located 318' min. from panel
edges.
3) See Sheet 12 for framing requirements (studs, jambs, headers, sills & fastening).
4) If a full height well section is not located at a comer, any hill height sheathing
in this area cannot be counted. Also, the opening edge furthest from the
sidewalllendwall comer will be strapped the same as the comer.
5) All vertical aM horizontal joints shall occur over, and be fastened to, studs or
blocJdng.
11 1
Members Omd & stc*d
v/15Gax7%1fi'x2-1/2'
Sttp. r -
B
2-2x6b R SPF
SECTION 'B-B'
B
Plymod 9-1 to be APA rated sh.thi.% PS -I. 5/6'
material to hove 10 / 20 spm mti g. Struct - 1 mderid to
be 5 ply / 5 Iaya rith I/V fam -- Ihidm— Gbe A
stile to truss chords v/16Ga x 7/16' R 1-1/2' st*m 6'
36' mox
Dude 2i6 lanb
ne.
Sn¢e ffi Sa pkte
Fwlen truss to4.�
(omitted vilh car
shcel 1$.
E avtiFied true
7' mn
v/ Oyvood. ihq ..lend
DETAIL 'A'
bu
Recessed sidmsdl "
W-al Framhig for Opmngs
SECTION 'A -A'
n Rtxesed Entry
Poster vdls tog&er •/IDd
nozs or 18-J 1/z' Sam 1Y
ae. (may toe -.I/— B'
o c)
A4—]
E
65�o�t�cg, I
A
r
f
04 max.
1
D.We plsts al Umslllen
TOP VEW
N—Sl IV a.c. jdsls,
O-0' M.
E
Double rim PISU
12
FLOOR FRAMING
RECESSED ENTRY
4��QEO E N F�9G� •'�
.No 52231 *%
y9�; STATE OF :�24`
JeffreyT.
g Legault
' 2019.10.10
14:32:40-04'00' p
Job
Truss
Truss Typo
Oly
Ply
21 6 FL
91095
M818805
MONO TRUSS
1
1
IRM"6"'
Div- 635
Rc/ 020023'
universal Forest Products ink., Grand Repels, MI 49525. Weston Gorey B.130 a Dot 122017 MITek lnduslrlos,lno. Wed Fab 2807:57:532010 Paget oft
Copyrlght02018 Univorsal Forest Products, Inc. All Rights Reserved
4-5-12 T 3-9-2 ' 3-10.0 r 368 '
-1m n
ere >
7A7 12 b
Or-110{i �
F°i1°R{ n
to u
i s
I =•
•r
e.e a a e a
1,311 1e1II ati= 6N=
`1.7-4, 3•f0$ 3-0-2 3.10-0 3-0-8
r
16.7$ i
Plato Olkok 2:0�•R 0.1-0 4:1),1$0.1-0 5:0.1.120.1.12 0 -0 B:0.7.00.1.0
LOADING (psQ
SPACING- 2.0-0.
CSI.
DEFL In (10c) Won Ud
PLATES GRIP
TCLL 20.0
Plato Grp DOL 1.25
TC 0.76
VCd(LL) 0.39 10 >460 240
MT20 1071144
TCDL 5.0
Lumber OOL 1.25
BC 0.67
Vert(CT) 0.W 10 >400 180
BCLL 0.0
Rap Stresslner YES
WE 0.97
P4rz(CT) •0.05 7 r9a Ala
BCDL 6.0
Code FBC2017frP12014
Matdx-R
Weight 43Its FT-O%
LUMBER. DRACING-
TOPCHORD 2x4 SPFNo.2 TOPCHORD StrudutalwoodSheathing diroctlyoppliodorb-2.5o0
BOT CHORD 2x4 SPF No.2 purflm. except end verticals.
WEBS 2x2 SPF Stud 'Except' BOTCHORD Rigid ceiling directly applied or 3-0.7 cc bracing.
W3: 2x2 SPF Not
REACTIONS. (Mize) 2=48310-3$ (min.0-1-8), 7r=443fMechard"I
Max Hors, 2.391(LC 7)
Mnx Upi112=-Bg9(LC 5), 7=-e02(LC 7)
FORCES. Ob) - Moxlmum CSmprosslorVMaximum Tension
TOP CHORD 1-2-". 2.3=-11212114, 3.4=108V2171, 4-5=-5141998, "- 441f0, 0.7=-731204
BOT CHORD 2-10-241511055, 9.10=-241511055, 8.9=•241611055, 7-8=-1094/481
WEBS 3.10--40224,49•-1841168,5$a•500W5, 4.8••63011462,6.7a-59311349
NOTES.
1) This truss has been chocked for uniform roof Ova load only, except as noted. '
2) Wind: ASCE 7.10; WE- 180mph (3saoond gusQ Vasdal39mph; TCOL-3.0pst; DCDL-3.0psh, h-30n; Cat. 11; F-V E•dgned by Kovk Freemen
D; End., OCpl=0.18; MWFRS(envelope) gable end zone and QC Exteder(2) zone; canllever left exposed;C-C t�tttliir/
for
members
neWghttnsrapchrd uns
e doashroJ Ices n�htaiuoaorddeiaGi(psioo aoqu3) tk FR es�7i�i
o pss oala fora
of oikshinglo %0
�Cr �io
roof. Architect to verify adequacy o/ top lard dead load. ��� C E N' ee; 9
4) Thle (ruse has been declined for 10.0 five food loads. �,� • V� 8-S '•,y ��
a psfbollorn chord nonooneurrent with onyolherfive, Q
5) • ••;
This truss has been designed for a Ova load of 20.Opsf on the bottom chord In a8 areas where a reclanglo 3-0-0 ��� N o 56254
tag by 2-0-0 wide will fit between the bottom chord and any other mombero. * ;•
6) Provide mechanical connedlon (by others) of truss to bearing plate capable o(wilhstandi ng 899 fb upfdt at Joint 2
and 8821b upin atlolnI7.
7) Fhdly of mambers 6-6, 7 - 6 have been changed. '
a) Basco an: FAB ISS03
����
9) RovEton: Updated Code
p p •`����
,iI,,S�ONA� �C, ,,,
ilv/Mezdnal MdrwrMace�ledeYe7r+gxllrenmtpdOssidoal natrv/m•mv:e deacn wqa aw eU*derdl refcrmoodrt7Jn 0t7 dxotrdu
ralrons:mty Nouaer4 wwbaldnp ta6a.Icon=Bluer]0 eon Kneen Opfmrelaufelnespad(puoa.7ro arelaa4rnrns7mmrW9aHr 2rta2018
a W,s dedQ„la dcerLYJetni>r lh low)rodryMdbinlrvd coda rent W h au wna, ddsuaso�orweaoppser:,.
A, WARNING - Verify design parameters and READ NOTES urcverulPaoelPtoduax,lwo =1CAST UELIUNEwx,Ne
tNs+,hdlrolhe eaatmoedeeWdw Rrw.ldnewueeuanagrcer, PHONE (a18)3a4.a1a1 FAX (e101-M&O 10 M=RAP114,1449525
TIO, GbrO.=dm hesmYaO.adx'predbae WeerxxedMP.h be„i,} CaY15MK9"n eNOey In[ee M1aerMbeer,wMfseM1 The N,ed,thre+Pxtsae
IxtNpulbdr end eystw'mOeldn nde.rrmermwrm dodCrod uNallll.iMe dcxlglb5awd cNY Wea9etanixra strewn, eMhLY
anb,avMLlwnmOcm¢cmm�aoeYrrclledmabadeAadeuly./ypl=etyondnyn pr.-aumreempardtowpormnamrywnlhrosrn,mnyawkn7
arulN+•teen hfdN+MetlxMaY,3KOuNwb,ew+htaemy.Ad,irmY WrprwyNlupghWe wbLbdu4'OtM>tKWn
bPO ova
ron�ayaencti<lxA4dlarNC��xNNetrq aanwdrlaWct.e[sWnpweWd�epOlrgdnf}�d.Fd� 191daderepafd,q
alrxaaoaPn,lyee,rvcl Yraep';delr«� e,eN:eorl0trdip,ar+xaP.C3114p6em IMNNodTrvtltdusadNbcha et0irvee liYnlroemraee,.e.rom,wox,Be
e.,.wnra,uooerwyru. un.u=d.dsv4Osn ta,4,2deu�.Plvwr�w+xy,rPa
J W
y °a
i
' Noted:
' 1) Truss spacing Is 24" o.c. max. y v
i2) Trusses to be P.E. certified. y �'
3) Roof sheathing requirements:
-Approved Agency tested sheathing (plywood or OSB), 4'x8' sheets installed with long dimensions pependicular to trusses. a w
- 7/16" thick minimum with 24/16 span rating. m a z
- Roof sheating butt ends to have 1/2" minimum bearing on trusses. Gap butt joints over trusses 1/16" minimum -1/4" max
-Stagger courses 16" min. Minimum course width is 15-718". Sheathing panels to be continuous Over 2 or more bays. N
4) Finish the roof system by applying undedayment and shingles. Install undedayment and shingles and c:x N M
construct valley per ARMA (Asphalt
I Roofing Manufacturer's Association) guidelines or manufacturer's Instructions. Ice barrier protection Is required.
Ice barrier shall be two layers of undedayment cemented together or a self -adhering polymer modified bitumen
sheet and shall extend from eave's edge to a point at least 24' Inside the exterior wall line of the building. ` • I
1 5) For truss end overhang construction, see Sheet 13A.
6) For framing at roof penetrations, see Sheet 13D.
doD
Truss TruasType
my Py
Skyyline 216 FL
91095
M879802 MONO TRUSS
1 1
F-536-E Div. #535
Re/ b2002331 '
Unfvoraol ForoalProdudalrw,GwMRapida, M14052b, 1•vnnlon Gorky f1.f30oDoo 1220f7hUTaklnduclfbs, Inc. Wod Feb 280&.022020fe Pogol of
Copyrl9ht02016 Universal Forest Products, Inc. All Rights Reserved
7-0 aaz 8•0•0 (
��.,r�-•'ter'" ,�wa n
=.4s(ii
l�oo.0
oµ
• • TI ` •�
+a f vu
1
� e
os
�I. "e In u
z.sas n Y r.a n za,a n zwa u
e.a e
3.7.0 55.2 2_6•14 3-52
�F I
1b•a2
Plain orraats B. t-e aoa 7:a-f-� o-o-1
:0•2.5 a-4-i :td o o• .4 g•a1.12 o•o-e
LOADING (pgQ
SPACING- 2.0•o
C91.
DEPL M Qoe) VdoO L!d
PLATES GRIP
TCIJ- 20.0
PWlo Grip DOL 128
TC 0.90
Vod(LL) 0.58 3.0 >303 24o
MT20 1971144
TCDL 10.0
Wmhw DOL 126
BC 0.91
V9d(CT) 0.50 3.8 >354 180
BCLL 0.0 •
Rep Stress Iner YES
WB 0.01
Hoa(Cl") -0.13 7 Na Na
BCOL 8.0
Cade FBC2017lOa12014
Aletrix•R
Wo1ghL 051b FT>0$
LUMBER- BRACING -
TOP CIIORD 2x0 SP No.t TOP CHORD Structural wool alloaU1610 dU0d1yapD0ed, exceptend
BOTCFIORD 2.0 SPF Na2•Excopl• vaAcals,
02: 2x8 SP No.2 BOTCHORD Rigid wlllq 9iredly9pplled or taD-o as bracing.
1116IIS 2x4 SPF Stud •Except• Except
WI: 21CJ SPF Slud, V172: 2x4 SP No.t 240
a
m
J
W N
r a �
F
{S•I
y °a
m
N
maz
Emw
o N
N 7l
Z
-This buss has as noted.
0
NOTES.
1) Ahaehed 8.0-0 yeah Ito 4, front face(s) 2a0 SP No.t with 2 row(s) of 10d (0.y01'%3')
%\\1\11711111F7F�,/
%
NO HINGE AT BREAK
Em TRIG TOP CMOim -
HOTO® I-1/2' FOR MlLW.
= * : No 52231 :. * t
IN FLY RAFTER. II 2' MLF.
II-��III
FLY RAPIER
= *'
a, 2�
ISf OTTEDOR TWI55
i�
NaT�
I� Zx4 OR
CEWrEIW� RerwomcaIENY w
LOCATION
10O......
D DETAIL'A• IS INTENDED TO BE USED WHEN NA'GEO PORTION OF AM ATTACHED TO NOTCHED TRUSS TOP DETAIL 'A' - AFTII111111\1
KNNGPDST NN3FE✓ES WITH REMARED PIlRL[M LOCATION OR WT$/ ovM To BE SAID: GRAOI. SPECIE Alm
SEE TABLE HINGED TOP CHORD IS SANE SIZE OR LARGER THAN FLY RAFTER OI BITE AS TO' O D. ELLE AND FASI@N SEE NGTE I Jeffrey T.
zx4 PLTaIN 5PF ON TOP O Om w/BD NAas 6• o.a Legault §
SEE TABLE TMLAID FLAT 2019.07.24
C
16' 11AK. TOP oNam 15:57.24-04'00'
SEE I-I/2'KCHDROHDTa
DETAIL 'B' I6• MAIL HINGE CL �-155 GA. A 7/FASTEN x 2 I/2' 2X6 FLY BAFNFA FASTEN TOP LIIOfm TO Bm OF IN TOP OIOFm 2JW PL.PAIN
SEE
STAPLES PlRBIN W/2-BD NASS.� FLY RAFTER
DETALL SFY T S-I2D NABS• OR 3-ISGA. x
TYPICAL RDGE DEAN A B C TM• XL VY STAPLES TFRD
2K6, F3 SPF FLY RAFTER 2X6 INTO PLDERN, RIDGERAL
SEE TABLE OR EDGE AIL I6• M wI FO cEmw BLOM ANY GRADE SPF/IET}FR BLOCK 2
CENTERED AT PIRLIN LOCATION IS REG'0. FASTEN EACH BLOCK TG Kxm
RIDGE NWRFRDAPS
sane S As IF. GRADE •D. BLOM TO BE SSIZE, AND TOP CIM W/2-15 GA. K 7116• K 2
a SPECIE As Tor CHORD. 112• STAPLES (4 STAPLOC LES EA. BK)
�7Lmrm TGLLE BNAK TO TOP
HINGED TRUSS END OVERHANG DETAIL i
NABS OR ISGA. K 2 Ve
AsraPLs 6• o.c. NAx.AK.
MAXIMUM PURLIN SPACING y,- MpK, Ir m' 2G• nAIL
FAN G LLoom DETAIL 'S'MAX49 d
20 P.S.F. -7-77777F7-7 1A o z
F2 SPF/SP 2X6 411, 7
2K6 PLT3D8 F2 6PF/SP LAM FLAT. IV
2 TABLE
NmE: IA6 FASCA 3
.SRIQ:
BOAR) WITH I>4x14-Vr
D
ONG. Gl1Ll®Nm STAnID Al
LTo
O
I OF
2K6 ♦3 BPF FLY RAFTEi
Ic•1
Ix6 FASCIA
TABLE
WK•
E'I
2
S 3
= COOFD F 12D N its on
NAGS di
V]
W
•
ISGA. x m x
x 2 UY'
• 3 STTAAftS4..
a
2-120 NAILS al b155A. 11 z
2 of STAPLES 12. nAx. SEE TABLE
z4• nIN.
FIXED TRUSS END OVERHANG d
P.E. Certified roof Ridge beam at manige wall
trusses 16" or 24" o.c.
F— A
a JX—V
�A
Variesw/floor plan. 24'max. See
Table 1 for beam size per span.
Columns per model specific
floor plan and sheet 12.
Ranch Center Beam Application.
ridge beam per Table 2
Table
1 - Maximum Rid a
Beam Clear Spans
Beam
Height
28742' w)des
20 PSF Roof Snow Load
32' wides
20 PSF Roof Snow Load
(inches)
15.875
—
—
17.875
—
—
19.875
20'-5"
21.875
23.875
h
T.
i
E N
* : No 52231
= 0: :Ir
� P% STATE OF :�W
2x4 marriage wall studs Notes:
�i'ON AI`110'
16" o.c. max. 1) Ridge beam is fabricated from 5/8" or 19/32" plywood. 2 web layers and 1 flange layer.
2) Plywood material:
Le dU�t a
g
5/8" or 19132", 5 ply/5 layer APA rated or TECO TESTED sheathing, 40/20 span rating,
PS-1-95, exp.1, Struct-1.??
2019.10.1
3) Full glue coverage between all layers.
0 14:32:1 m
4) The plywood ridge beam to run full length of unit.
5) Beam may be three full layers instead of having flanges. Fastening for 3rd web layer same as
-04'00'
other web layers.
2"- 2-1/2°\l,
Table 2 - Ridge Beam Strapping Spans
f Typical hinged Strap from stud -to -ridge beam & from stud -to -floor
Ridge Beam -fasten to/ truss w/ 9-0.148"xl-1/2" nails per strap
kingpost w/7-12d nails. 1-Simpson ST22 strap 1'-11"
2-Simpson ST22 straps 5'-3"
3-Simpson ST22 straps 8'-6'
4-Simpson ST22 straps 11'-10"
Ridge beam bears o� 6-Simpson ST22 straps 18'-5"
marriage wall May use Marriage wall
1
W
solid lumber shim width Notes:
of beam at cathedral 1) Standard strapping (no spans) shall consist of 1-Simpson ST22 Strap Tie w/ g-o.148"xt-1/2"
applications. Section'A•A' nails per end of each strap from stud -to -ridge beam and stud -to -floor @ 16" o.c.
c
u
h
2) All marriage wall straps are required on 1-half of home. Strap spacing may be doubled when
,
straps are Installed on both halves.
0
1" (typ-)
\ 2'-0' (typ.) min.
. between splice Flange splices may occur at same section.
Flange
Web
Flange 16Ga.x7/16" crown x 1"leg staples Plywood Spacing
(crown parallel to face grain).
- Itoz1" (typ.)o.c. (typ•) I 1(typ )/�
WEB (Fleldt (') Is--- 12,.( \ WEB (loint)
Ridge Beam Fabrication
FLANGE
5-1/2' top
& bottom
flanges
1 I
`,ttttltT Lt-,/I
T. CFGq/,.
SIMPSON H2.5T TIE w/5-81)X7-1/2" NAILS AT �'k No. 52231
EACH END. 24" O.C. MAX. (EVERY TRUSS). — ,t
TOE -SCREW TRUSS BOTTOM CHORD TO TOP
TYPICAL TRUSS PLATE w/3-#8X3-1/2" SCREWS. .. STATE OF : 4il►
10
CEILING BOARD — NI-1 "'-i\ \X \ _,2-3/4`XIl2° WOOD SHIM
0
DOUBLE 2X6 Ti I _WALL STUD
PLATE
SIDEWALL UPLIFT CONNECTION DETAIL
TRUSS BOTTOM CHORD 3/4" ALPHASEAL FOAMBEAD EACH SIDE OF
I" FOAMSEAL TRUSS AT GYPSUM SEAMS,
CEILING GYPSUM 1/2" MIN.
ALPHASEAL 5200 OR GYPSUM SEAM
FOAMSEAL F2100 FOAM BEAD.
TYPICAL FOAM BEAD GYPSUM SEAM APPLICATION
CEILING GYPSUM BOARD TO TRUSS ATTACHMENT
NOTES:
1.) APPLY FOAM PER MANUFACTURER INSTRUCTIONS.
2.) FOAM BEAD TO RUN ENTIRE LENGTH OF BOTTOM CHORD.
Jeffrey T.
g Legault
/ I17 ' 2019.07.24
15:56:24 -0
1/8" MIN. CONTACT
3/8" MAX. GAP H W/TRUSS CHORD.
GAP DETAIL
1=1a,1
See Detall'A'
Is up to
truss doubled
Fasten 2x4 blocks to truss
chords w/3-l5Ga.x7/16'x2-12'
Truss top charA R7 SPF 2x4 block Fasten truss stapk.. 2A #3 SPF black. One required
\\lr chords to block w(b each sloe of each wl truss.
15Ge.x7/16'x2-12' staples.
Truss top chord
2.4 headermembers.
Truss baao chord f Tmas bottom Mond
Festan header members to 2.4 blacks
Fasten block or two chard to header member w/4.16d w/3-15Gax7/16'x2-12'staples.
nails or 3-Nx3' spews on headers up to 30.5%
DETAIL'A'
NOTES:
1) If no trusses are cut, futon headers & blocks per Delail'A' & ignore Detail'B'.
DETAIL'S'
T. L,,:r .
No 52231 '.
STATE OF
O R 1 O
,a�?O
Je19.07.415!5t
2019.0724155558
3-1/4' min.
1.3/4' min. flanga Mange
1.31V min. flange
TYPICAL ROOF FLASHING DETAIL FURNACE ROOF JACK WEDGE
For DW V system or Roof Vent
Ceiling Fan Vents
Gas Water Heater Vent
APPLICATION NOTES:
1) Apply shingles up to protrusion.
2) Cut a hole in a shingle to fit tight around base of protrusion and embed it in asphalt cement.
3) Install flashing around/over protrusion. Butyl caulk or sealant tape will be applied to perimeter ofall flashing or a
coating of asphalt cement applied to roof underlayment before stapling to roof.
4) Attach flashing 4" o.c. with 16Ga.x7/16"xl" galvanized staples (all staples: I6Ga.xl "xl" staple may be used) or 314" long
(min.) roofing nails along edges to be overlaid with shingles. The exposed edge of the flashing should not be fastened;
however, if it is, the fastener and penetration must be covered (100%) with an asphalt roof scaler. Altemately, cover
exposed fasteners with a weather resistant caulking material that is compatible with the flashing material.
5) After flashing is in place, resume shingle application. Cut shingles in successive courses to fit mound the protrusion
and embed them in asphalt cement where they overlap the flashing.
6) Flashing to be 24 Ga. aluminum (min.).
�de�i
a �p
Mi
m C
81RM2
TABLE 1
Max, span w/ dormer
rafters 16" o.c.
Dormer
Raker
#2 S. Pine
1-2x6
137"
2-2x6
172"
2x6 dormer rafter, installed over main unit
A /sheathing, dims. upon roof trusses. (See
Figures
j1 & 2 for alternate.)
16" o.c.
Dormer sheathing. I
Extedor LIA
wan line PLAN VIEW
I B
i
rc
-�B 1--►C Sidewall eave
Dormer and panel
1x6 domlerfascia. Fasten to each dormer C.L. dormer
rafter w/3-15Ga.x7/16•x2-1/2" staples.
Dormer and panel
2x6 or 2x8 roof edge rail (any grade)
maybe ripped to size. Standard sidewall 1x6 main
construction unit fascia
SIDE VIEW
2x6 c
(see
NOTES:
1) When dormer rafters do not line up with main unit trusses, add a 2x8
#2 SPF/ S. Pine dormer rail as shown In Figures 1 & 2. Install
additional roof trusses. One truss must be installed at dormer
centedine (peak). The other two additional trusses shall be Installed
at increment from dormer centedine (16' o.c.) or double each
standard truss located each side of the dormer centedine.
,,111111111/1/j�/
T. LFU'y,o
ENS�.
••
Fasten dormer rafter to roof truss w/2-#8x3-1/2" screws Q 16" o.c.
1x6 Fascia, an grade
•`�'�
�•' No 52231 •:
trusses.
+ * : * '�
y I� See table for max. spans.
TT
Fasten rafter to dormer panel chord
'9? 'STATE OF : Q/
0 • �/
••.'c4
wl standard truss to sidewall
fastening Sheet 12.
i,F O
per
Main
unit sheathing
�ON A�
Jeffrey T.
Standard P.E. certfl.d of Dormer and panel. 2.3 chords w/ 618"
#Sx3-1/2"
Q Legault
trusses. 24• o.c. max. plywood glued & stapled to chords
screws 8" o.C.
[' 2019.07.24
w/l5Gax71l6'x1.1t4' staples 6' o.c.
155538 -04'00
(may be spliced at 2x3 blocks)
Sheathing to be continuous to
SECTION 'A -A' dormer panel top
chord.
2x6 dormer rafter 1x6 dormer
fascia
SECTION 'B-B' Main unit fascia
A&I-4 roof m,ccne roan nntn 21
TOP VIEW FIGURE #1
2x6 dormer o
rafter tx6 dormer
fascia \
SECTION 'C-C' Main unit fascia
W
Attach 2x6 rail to main unit roof trusses
w/same number and type of fasteners as
dormer rafter connection.
r 172" max.
Fasten dormer rafter to 2x6 rail
per standard dormer fastening
2x6 dormer rail
(see note 1)
SIDE VIEW FIGURE #2
Dormer bearing
brace location
(standard)
r
Stagger butt end
decking courses
16' min. decking
Canter Gnder. h h.I S. Pine or
SPF2x12seachhalf. (Mayne
an 28' W firam.s.) Stn application
on 26'wibetw between
aggerder
ta
24' min. between all girder
members including jolne on
opposite hag. (See note 4 for
alternate appticatioa.) Floor blocking.
Sea note 3.
Centergirderand,m . Sae
detaL (Not required with hame-
on construction.
Unit Centerline!
Center Gkder
�2x2 any grade SPF ledger.
! Glue & fasten per schedule.
2x2 LEDGER DETAIL
floor decking. Decking to be rated 20oao. or sspent rated e 1) See. sheet 13 for fastening schedule. �N T Q�'���j
4020. Installed with strength direction acrossjoists. Bug 2) Main I -beams for frame on construction shall be M10x8 or M12xl0.8 ��`Q�P•�G E N S 9G ii
edges to fag over a OoorjoisL minimum and be A36 steel minimum. : '�rj� ' V F '.•
3) Full -depth floor blocking @ 24" o.c. in the first twojoist spaces at each •`�•
end is required No 52231
Normal floor joists to be #2 SPF or S. Pine 2x10s, 161 4) Center girder may be 243 SPF 2x10 ea. half when home will have
o.c. mex. Joists may be #3 SPF 2x10s for 28' wide.. continuous support al the marriage line when installed on -site.
Joists may be 93 SPFwith frameon censtmction. pp g - -G - 2 Q
/ 5) End & bandjoists may be triple members whrn required far certain STATE O F + 9 :• 4Lj
foundation applications. i O_•• ; •!(�.
Double #3 SPF ed joist &
band joisL Same.1. as
anal joists.
3/W4.lag screw each outrigger to 600rlokt
Place in any pre- punched hole
ettre 1: d4!
�]g 2
15:55:16-04'00'
3r8'x3' lag screw w/4Ga. Steel
pressure dip - every otherjoist
(32' o.c..a ). Joists located
floor joist over outriggers need not be
clipped. `
/ /I� / / 10'or 12'Sleel l-Beam _I
158" max for 28' ,ides. 14Ga. Min. steel Z-sedlon 41.25" max. - 32' wides • 99.5" C.C.
182" max (w 32',ides. outriggers. 4 min. par side 2g 25' max - 26 wide. 13Ga. min. 3'x1.12'steel C- p
162' max for 42',ides. ndudirg o 8rear cross 31.25'max-42'vAdes channel 6'-0'o.c. mu. Rear
rnB1" ssmember to be placed at
STEEL SUPPORT FRAME -ON top flange of l-beams. W
#3 SPF IeO joist, secure to
header joist w/4-8d nab or 5-
15Ga.x7N6W-12' staples.
(direct).
Unit Centerline
-1. Center
Girder
2x10 Tmnsvers Simpson LU28 hanger (or equivalent)
Joist w/ 8-10d nab Into center girder & 6•
10d nails into joist
JOIST HANGER CONNECTION
AT CENTER GIRDER
Center Girder :��:� �� Double end jolat
2' w12x10s or 1 Zs -�
- �9 °+or- 10
CENTERLINE GRIDER NOTCH DETAIL
Ntrimmerjoists w/4-8d nails
III ors-15Ga.x7/16'x2-1/2'
40 max. staples. (Maytoe-natl).
Double #3 SPF Joist length / 3 (max.)
ldmmerloists 3' max. di.. hote for -to
3°max for 2x10s.
0
FLOOR OPENING 2' min edge distance
1-12' for 2x10 Notch may be at top or tmm top 8 bottom.
bottom of told
NORMAL FLOOR JOIST DRILLING & NOTCHING DETAIL
3/8" mir
wall bog
outside
Truss
Ceiling penetration for fireplace
chimney, furnace or water roof jacks,
round metal duct connectors, etc.
Too of opening is closed off by
ig gypsum. See detail for
atratlons.
10 min. gypsum board colter. Two
Ceiling penetration for fireplace pleces tight fitted around penetration
chimney, fumace or water roof lacks, (no gap.). If gap is present, treat per
round metal duct connectors, etc. ` - detail above.
ALT. CEILING PENETRATION
Inside walls of compartment are
covered with 3/8" min. gypsum
wall board.
Tight fitting hole (+ 12' diameter
max) with fiberglass insulation
tat door or passage packed Into void or sealed with a Stud
rr with inside covered fre resistant foam or caulk.
1318• min, gypsum//
Pipe
,��pVEY T. LF��,��+
��4 ��G.ENSF•;G�
Tight fitting hole (+ 1/2' No 52231 *�
diameter max.) with
fiberglass insulation
packed into void or sealed
with a fire resistant foam or 9 STATE OF W
caulk. �i O •' �!/;
Firestop DWV B water line
penetrations through the floor. a
Tight filing hole (+ 12" diameter max.) U Jeffre T.
with fiberglass Insulation packed into void y
or sealed with a fire resistant foam or Legault
caulk. Blocking each side of floor 2019.07.24
cutout Size blocking to Waterlines 15:54:50-04'00'
CEILING PENETRATION match joists.
PLUMBING FIRE STOP
12' min. ceiling gypsum.
Truss bottom chord /
1 Fasten gyp. collar to 3/8" min.
plywood or OSB backer w/4-
#Bxt-12' screws (each piece).
12" min. ceiling Tub shown for typical
/gypsum. firestopping detail.
/ Apply 2x lumber backer to _
r( perimeter of cutout area and
fasten 12' min. gypsum
board (or fiberglass
insulation) to it Seal any
gap or void with fire resistant
foam or caulk.
Fl—joist
FURNACE OR WATER HEATER COMPARTMENT
Appliance installed on main level
NaN�es
1) Exterior walls, openings and penetrations shall have a fire separation of not less than 5 feet.
' - Top or bottom plate
CONCEALED WALL SPACE
518" type X Gypsum Installed
on garage side of the exterior
wall and ceiling.
.y Garage Area
The gypsum board installed on
the garage side may be
overlaid on 318" OSB or
plywood sheathing.
Doors installed between living
area and garage shall be have a
20 minute rating.
Dormer edge rail at , end
truss bottom chord att end
endawall
W
2x6 exterior framed wall w/R-
19 fiberglass insulation.
Living Area ------ ►
SITE BUILT GARAGE FIRE SEPARATION
J
a t �
PRODUCT APPROVAL, SPECIFICATION SIIFET
Mmunracturer: Skyline Hmues, Ocala, Florida Plan N 6233 MA
As required by Florida Statue 553.842 and Florida Administrative Code 61 G20-3.006, please provide the information
and the product approval number(s) on the building components listed below if tilcy are to be utilized on the
manufactured building for which you tee applying for a PFS certification. We recommendyou contact your product
supplier should you not know the product approval number for any of the applicable listed products. More information
about statewide product approval cam be obtained at tww Arvidalmilding.ivn
Cate ory
Manufacturer
Product Description
Approval #. s)
EXTERIOR DOORN
Swinging
Swinging
TrinityGlass International
Thelma Tm Corporation
Fiberglass InfOut Swing
Double Fiberglass 1/0 Swing
Fiber ass idOut Swing
FLI5255.9/FL15129.1
FLI5129.8
FLI5225.5
Sliding
Khoo
Vinyl 1600 Series
F12865.2
Atrium
'nierma Tru Corporation
Fiber ass In/Out Swing
FL15225.5
Outer
NA
wiminws
Sin Ic Hunct
Kimo
Vinyl 9750 Series Sit
FL993.1
Hodzontnl Slider
More
Vinyl 9750 Series IIS
FL993.2
Casement
NA
DoubleHung
NA
Fixed
Kinro
Vinyl 9700 Series PW
FL995.2 / FL995.3 / 171,995.4 /
FL995.5 / 171,995.6 / FL995.7
Auning
NA
Projected
NA
Mullion
NA
Other
NA
1 rncl %. all
Siding
Nicldba USA, Inc.
Ply Gem Siding Group
Fiber Cement Panel Siding
Vinyl -Georgia Pacific
Parksido
FL12098.1
FL17758.1
Soffits
Ply Gcm Siding Group
Alum. Vardform/Dumbuilt D6
FL17673.1
Wall Louver
NA
Glass Block
NA
Membrane
NA
Ogler
NA
ROOFING
PRODucrs
Asphalt Shingles
Owcre-Corning
Supreme AR
FL10674.1
Underlavmcnls
Mid-Statcs As mlt
MSA ASTM D 226 159 Felt
FLI5067.1
Roofing Fasteners
NA
Non -Structural Metal
NA
* : No 5223.1
Q: STATE OF :�41J
OR
T 1 2019.10.1'00'
9auib�Fss,ONA�E E`` o' 4 14:31:57
Category
Manufacturer
Product Description
Approval # (s)
Roofin Awcssorics
Ucniamin Obdykc Inc.
Xtmctor Xl8 Ride Vent
FL7751.3
ModiOed Bitumen
NA
Roofin Tiles
NA
Roolintinsulation
NA
Waterproofing
NA
Cements -Adhesives-
Coatings
TAMKO Building Products
Tam -Pro Wei or Dry
FL1960
Roof Tile Adhesive
NA
Olhcrs
NA
SIII7rTRR.S
Others
NA
SKVLIGIITS
Skylight
Solatube International
10"114"/21"domes
FL11480/FLI 1561
Others
NA
SPRUCTURAI.
COMPONENTS
Wood
Connector/Anchor
Simpson Strong -Toe
Simpson Strong -Tic
Simpson Strong -Tic
thvricaneTie
Joistilanger
Straight Suop
F1.10456
FL10655
FL10852/FL13872
Truss Plates
Mitck
Connector Diates
FL2197
Engineered Lumber
NA
_
Railing -Porch
NA
Deck &Roof
NA
Walls
NA
Owners
NA
The products listed below did not demonstrate product approval at plan review. 1 understand that at the time of
inspection of these products, the following information must be available to the Inspector at the manufacturing plan: 1)
Copyof the product approval for the Local or Slide Building Commission, or supply all of the information fisted on
Fori No.61020-3.006. (2) Copy of One applicable manufacturers' installation requirements.
I understand these products may have to be removed if approval carrot be demonstrated during the inspection.
Edward L Weber. P.E. 111'_e^_- 1018119
Manufacturers' Authorized Agent Signature Printed Name Bate
3
w
TABLE OF CONTENTS
(Structural Calculations)
Pacte No. / No. of Sheets
Calculation Description
App. B: 0 - B: 0.1 / 2 shts.
Design Wind Pressures
App, B: 0.2 / 1 sht.
Design Wind Pressure Table
App. B: 1 - B: 1.1 / 2 shts.
Floor Joist
App, B: 1.2 - B: 1.4 / 3 shts.
Floor Girder
App. B: 2 - B: 2.2 / 4 shts.
Exterior Studs
App. B: 2.3 / 1 sht.
Sills
App. B: 2.4 / 1 sht.
Sill & Plate Fastening
App. B: 2.5 - B: 2.6 / 4 shts.
Headers
App. B: 2.7 / 1 sht.
Header Fastening
App. B: 2.8 / 2 shts.
uplift Fastening
App. B: 3 - B: 3.1 / 2 shts.
Wall Bracing
App. B: 4 - B: 4.2 13 shts.
Endwall Hood
App. B: 5 / 1 sht.
Roof Diaphragm
App, B: 6 / 1 sht.
Ridge Beam
App. B: 7, - B: 7.2 13 shts.
Centerline Columns
App. B: 8 - B: 8.1 / 2 shts.
Dormer Rafters
App. B: 9 / 1 sht.
Truss Cantilever
���uurrrr��
�,,��•�. GEN0.0
sF:�G��
No. 52231
STATE OF00.
0rN
Jeffrey T.
g Legault
2019.10.10
14:31:38-04'00'
' BY: ELW
Design Wind Pressures (Comp. & Clad.) PAGE: App. B; 0
DATE: 31612018
for
Vult. =160
mph - Exp. C REF: Caics.
Design References -ASCE 7 -10 (Method 1)
• See Figure 30.5-1 for loading descriptions per ASCE 7 -10..
Component and Cladding Variables:
Height, h = 15.0 ft
Importance
Factor, I = 1.0
r End Zone, a = 4.0 ft
Adjustment Factor, F = 1.21
Min. Roof Pitch = 14.0 degrees (3 in 12)
Topographic Factor, Kzt = 1.0
Max. Roof Pitch = 26.6 degrees (6 in 12)
-
Conversion to Allowable Stress Design
Pnet30 @ 1 - interior zone of roof =
-42.1
psf x 0.6 =
-25.3
psf
Pnet30 @ 2 - end zone of roof =
-73.4
psf x 0.6 =
-44.0
psf
Pnet30 @ 3 - comer zone of roof =
-108.5
psf x 0.6 =
-65.1
psf
Pnet30 @ 4 - interior zone of wall =
-50.0
psf x 0.6 =
-30.0
psf
46.1
psf x 0.6 =
27.7
psf
Pnet30 @ 5 - end zone of wall =
-61.7
psf x 0.6 =
-37.0
psf
46.1
psf x 0.6 =
27.7
psf
-57.2
psf x 0.6 =
-34.3
psf @ 21.6 sq. ft. Swinging Doo
43.9
psf x 0.6 =
26.3
psf @ 21.6 sq. ft. Swinging Doo
-53.8
psf x 0.6 =
-32.3
psf @ 40.0 sq. ft. Sliding Door
42.1
psf x 0.6 =
25.3
psf @ 40.0 sq. ft. Sliding Door
Pnet30 @ 2 - end zone of roof overhang * =
-85.9
psf x 0.6 =
-51.5
psf
Pnet30 @ 3 - corner zone of roof overhang * =
-144.4
psf x 0.6 =
-86.6
psf
Design Wind Pressures:
Design Wind Pressure, Pnet = F x Kzt x I x Pnet30
Pnet @ 1 - interior zone of roof =
-50.9
psf x 0.6 =
-30.6
psf
Pnet @ 2 - end zone of roof =
-88.8
psf x 0.6 =
-53.3
psf
Pnet @ 3 - comer zone of roof =
-131.3
psf x 0.6 =
-78.8
psf
Pnet @ 4 - interior zone of wall =
-60.5
psf x 0.6 =
-36.3
psf
55.8
psf x 0.6 =
33.5
psf
Pnet @ 5 - end zone of wall =
74.7
psf x 0.6 =
-44.8
psf
55.8
psf x 0.6 =
33.5
psf
-69.2
psf x 0.6 =
-41.5
psf @ 21.6 sq. ft. Swinging Doo
53.1
psf x 0.6 =
31.9
psf @ 21.6 sq. ft. Swinging Doo
-65.1
psf x 0.6 =
-39.1
psf @ 40.0 sq. ft. Sliding Door
50.9
psf x 0.6 =
30.6
psf @ 40.0 sq. ft. Sliding Door
Pnet30 @ 2 - end zone of roof overhang * =
-103.9
psf x 0.6 =
-62.4
psf
Pnet30 @ 3 - corner zone of roof overhang * =
-174.7
psf x 0.6 =
-104.8
psf
* - Not applicable to roof coverings, per R301.2.1 Florida
Building Code - Residential.
BY: ELW
Design Wind Pressures (MWFRS)
PAGE: App. B: 0.1
DATE: 10/19/2016MEN�
for Vult. =160 mph - Exp. C
REF: Calcs.
Design References - ASCE 7 -10 (Method 2)
•
t
See Figure 28.6-1 for loading descriptions.
f
' Main Wind Force Resisting System Variables:
Height, h = 15.0 ft
Importance Factor, I =
1.0
End Zone, 2a = 8.0 ft
Adjustment Factor, F =
1.21
Roof Pitch = 11.6 degrees (2.46 in 12)
Topographic Factor, Kzt =
1.0
`
Conversion to Allowable Stress Design
Ps30 @ A - end zone of wall =
47.5
psf x 0.6 = 28.5 psf
Ps30 @ B - end zone of roof =
-18.3
psf x 0.6 = -11.0 psf (use 0.0)
•
i
Ps30 @ C - interior zone of wall =
31.6
psf x 0.6 = 19.0 psf
'
Ps30 @ D - interior zone of roof =
-10.6
psf x 0.6 = -6.4 psf (use 0.0)
i
Ps30 @ E - end zone of windward roof =
-48.8
psf x 0.6 = -29.3 psf
Ps30 @ F - end zone of leeward roof =
-30.5
psf x 0.6 = -18.3 psf
Ps30 @ G - interior zone of windward roof =
-34.0
psf x 0.6 = -20.4 psf
Ps30 @ H - interior zone of leeward roof =
-23.3
psf x 0.6 = -14.0 psf
Ps30 @ EOH - end zone of roof overhang =
-68.3
psf x 0.6 = -41.0 psf
i
Ps30 @ GOH - interior zone of roof overhang =
-53.5
psf x 0.6 = -32.1 psf
Design Wind Pressures:
Design Wind Pressure, Ps = F x Kzt x I x Ps30
Ps @ A - end zone of wall =
57.5
psf x 0.6 =
34.5
psf
Ps @ B - end zone of roof =
0.0
psf x 0.6 =
0.0
psf
Ps @ C - interior zone of wall =
38.2
psf x 0.6 =
22.9
psf
Ps @ D - interior zone of roof =
0.0
psf x 0.6 =
0.0
psf
Ps @ E - end zone of windward roof =
-59.0
psf x 0.6 =
-35.4
psf
Ps @ F - end zone of leeward roof =
-36.9
psf x 0.6 =
-22.1
psf
Ps @ G - interior zone of windward roof =
-41.1
psf x 0.6 =
-24.7
psf
Ps @ H - interior zone of leeward roof =
-28.2
psf x 0.6 =
-16.9
psf
Ps @ EOH - end zone of roof overhang =
-62.6
psf x 0.6 =
-49.6
psf
Ps @ GOH - interior zone of roof overhang =
-64.7
psf x 0.6 =
-38.8
psf
By: Ed Weber Design Wind Pressures per 2010 Page: App. B: 0.2
Date: 316/18 ONE per ASCE 7 -10 & 2017 Florida Ref: Calcs,
Building Code - Residential
TABLE OF DESIGN WIND PRESSURES (ail values are PSF) - h =15 ft- I=1.0 - Roof Pitch = 2.46/12
Element:
Vult. WIND SPEED
(MPH - 3 SECOND GUST)
180 MPH, EXPOSURE C
ANCHORAGE FOR LATERAL AND
VERTICAL STABILITY
Net horizontal drag (in all areas
except the following):
22.9
Within 8 ft. of sidewall/endwall comer.
34.5
Net horizontal drag on roof projection
(in all areas except the following):
0.0
Within 8 ft. of sidewall/endwall comer.
0.0
Uplift (in all areas except the following):
-24.7
Within 8 ft. of endwalls:
-35.4
Overhangs:
-38.8
Overhangs (within V of comer):
-49.6
MAIN WIND FORCE RESISTING SYSTEM
Shearwalls, diaphragms & anchorage systems
(in all areas except the following):
22.9
Within 8 ft. of sidewall/endwall comer.
34.5
Ridge beams and other roof supporting beams
(in all areas except the following):
-24.7
Within 8 ft. of endwalls:
-35.4
Overhangs:
-38.8
Overhangs (within 8' of come!):
-49.6
COMPONENTS AND CLADDING
Roof framing, sheathing & fastening
(in all areas except the following):
-30.6
Within 4 ft. of endwalls, sidawalls & ridge:
-53.3
Within 4 ft. of corners & endwall ridge:
-78.8
Overhangs:
-62.4
Overhangs (within N of comer):
-104.8
Exterior roof coverings
(in all areas except the following):
-30.6
Within 4 ft. of endwalls, sidawalls & ridge:
-53.3.
Within 4 ft. of comers & endwall ridge:
-63.3
Wall studs In sidawalls & endwalls, exterior
glazing, exterior coverings & fastenings:
+33.5 / -36.3
Within 4 ft. of sidewall/endwall corner
+33.5 / -44.8
Swinging Door within 4 ft, of comer:
+31.9 / -41.5
Sliding Door within 4 ft. of comer.
+30.6 / -39.1
'By: ELW ■
Date: 4/27/2012
W
Page: App. B: 1
FLOOR JOIST CALC. Ref: Sheet 14
L
JOIST: 143 SPF Zx10 DURATION FACTOR (Cdr):
1
DECKING:
19/32" or 5/8" PLYWOOD
Fb: 500 PSI SIZE FACTOR (Cq:
1.1
N. 1.655 IN^2/FT
Fv: 135 PSI REP. USE FACTOR (Cr):
1.15
A: 1.728 IN"2
E: 1200000 PSI FLOOR LIVE LOAD (LL):
40
PSF
B': 16 IN
B: 1.5 IN FLOOR DEAD LOAD (DL):
10
PSF
D': 0.625 IN
D: 9.25 IN JOIST SPACING (JS):
16
IN
E': 1000000 PSI
** Calculate Section Properties **
AREA Y N
AxN^2
Ix
Ix+(AxN^2)
SECTION (IN"2) (IN) AREAxY (IN)
(IN^4)
(IN A4)
(IN A4)
JOIST 13.875 4.625 64.172 0.5468
4.148
98.932 •
103.079 '
DECKING 1.728 9.6625 16.522 4.3907
33.309
0.271
33.580
TOTALS 15.603 80.694
Ixx =
136.660
i
IN^4
Be=B'*(E'/E)= 13.333
IN
;
N.A. = TOTAL AREW / TOTAL AREA-- 5.172
IN
Q=Bx(N.A.)x[(N.A.)/2]= 20.060
IN113
Sxb = Ixx / N.A. = 26.424
IN^3
<--. CONTROLS
Sxt = ixx / (D+D'-N.A.) = 29:057
IN^3
*** MAX. SPAN BASED ON ROOF LOAD ***
** Calc. Distributed Loading **
** Calc. Max. Span Based on Shear"
(DL+LL)*(JS)
Fv'' = Fv *
Cdr =
135.0 PSI
W = = 5.56 PLI
144
2*Fv*B*I
L max2 =
+ (2 * (D+D')) 516.4 IN
(LL)*(JS)
Q * W
W1 - -- - - 4.44 PLI
144 **Caic. Max. Span Based on Deflection**
384*E*I
*''Caic. Max. Span Based on Bending** L max3 = (------) A (1/3) 211.4
5*240*W
Fb' = Fb * Cdr * Cf * Cr = 632.5 PSI
384*E*l
Lmaxl=(FV*S*8/W)A(1/2) 155.1 Lmax4=(----)A(1/3) _
__-___ <--con ro s 5*360*W1
• • By: ELW
Date: 6/6/2014
4
JOIST: 142 SPF / S. Pine 2xl0
Fb:
800
PSI
Fv:
135
PSI
E:
1200000
PSI
B:
1.5
IN
D:
9.25
IN
Page: App. B: 1.1
N_ FLOOR JOIST CALC. Ref: Sheet 14
DUR. FACTOR (Cdr):
1
SIZE FACTOR (Cf):
1
REP. USE FACTOR (Cr):
1.15
FLOOR LIVE LOAD (LL):
40 PSF
FLOOR DEAD LOAD (DL):
10 PSF
JOIST SPACING (JS):
16 IN
DECKING: 19/32" or 5/8" PLYWOOD
A:
1.555 I N^2/FT
A:
1.728 IN^2
B':
16 IN
D':
0.625 IN
E':
1000000 PSI
** Calculate Section Properties **
AREA Y N AxN^2 Ix Ix+(AxNA2)
SECTION (IN^2) (IN) AREAxY (IN) (IN^4) (IN^4) (IN^4)
JOIST 13.875 4.625 64.172 0.5468 4.148 98.932 103.079
DECKING 1.728 9.5625 16.522 4.3907 33.309 0.271 33,580
TOTALS 15.603 80.694 Ixx = 136.660 INA4
Be = B' * (E'/ E) = 13.333 IN
N.A. = TOTAL AREAxY I TOTAL AR EA-- 5.172 IN
Q=Bx(N.A.)x[(N.A.)/2]= 20.060 IN^3
Sxb = Ixx / N.A. = 26.424 IN^3 <--- CONTROLS
Sxt = Ixx / (D+D'-N.A.) = 29.057 IN^3
*** MAX. SPAN BASED ON ROOF LOAD ***
** Cale. Distributed Loading **
(DL+LL)*(JS)
W = —r ----- = 6.56 PLI
144
**Cale. Max. Span Based on Bending**
Fb' = Fb * Cdr * Cf * Cr = 920.0 PSI
L maxl = (Fb'* S * 8 1 W) A (1/2) _
** Cale. Max. Span Based on Shear **
Fv' = Fv * Cdr = 135.0 PSI
2*Fv*B*I
L max2 = -- + (2 * (D+D'))
Q*W
**Cale. Max. Span Based on Deflection**
384*E*1
Lmax3=( )A(1/3) _
5*360*W ====== <—con ro s
Uy. L.L.VV v��� r�.. �. vv.•. ... .. .. .�...
Date: 4/10/2014 SECTION MODULUS CALCULATION
• -V-. ..rr• -' --
Ref: Sheet 14
. JOIST: 442 SYP or SPF 2xl2s
Decking: 19/32" PLYWOOD
B: 4.5 IN (only 3 effective)
B':
16 IN
• D: 11.25 IN
D':
0.196 IN
E: 1400000 PSI
E':
1000000 PSI I
AREA Y N
AxN"2
Ix Ix+(AxN"2)
SECTION (IN"2) (IN) AREAxY (IN)
(IN-4)
(IN"4) (IN^4)
JOIST 50.625 5.625 284.766 0.242
2.977
533.936 536.913
DECKING 2.24 11.348 25.420 5.481
67.280
0.007 67.288 f
TOTALS 52.865 310.185
Ixx = 604,200
- Be = B' * (E'/ E) = 11.429
IN
N.A. = TOTAL AREAxY / TOTAL AREA = 5.867
IN
`
Q = B x N.A. x (N.A./2) = 77.462
IN"3
Sxb = Ixx / N.A. = 102.974
IN^3
<----- CONTROLS
Sxt = Ixx J (D+D'-N.A.) = 108.309
IN^3
2.354/12 = 0.196"
r
See plywood design spec.
JOIST: 442 SYP or SPF 2x10s
Decking: 19/32" PLYWOOD
B: 4.5 IN (only 3 effective)
B':
16 IN
D: 9.25 IN
D':
0.196 IN
E: 1400000 PSI
E':
1000000 PSI
AREA Y N
AxN^2
c
Ix Ix+(AxNA2)
SECTION
(IN "2) (IN) AREAxY (IN)
(IN-4)
(IN-4) (IN^4) E
F
JOIST
41.625 4.625 192.516 b.241
2.421
296.795 299.216
DECKING
2.24 9.348 20.940 4.482
44.994
0.007 45.001
`s
TOTALS
43.865 213.455
Ixx = 344.218
Be = B' * (E'/ E) = 11.429
IN
N.A. = TOTAL AREAxY / TOTAL AREA = 4.866
IN
Q = B x N.A. x (N.A./2) = 53.279
IN"3
Sxb = Ixx / N.A. = 70.737
IN"3
<----- CONTROLS
Sxt = Ixx / (D+D'-N.A.) = 75.160
IN^3
2.354/12 = 0.196"
See plywood design spec.
BY: ELW ■ Center Beam calculation PAGE: App. B:1.3
DATE: 6/6/2014 ORNIUME (32' Wide) REF: Sheet 14
(Floor Load Only)
WL
f
LTA
' I '
AL AL
L L L L
Roof Duration factor, Cd =
1.00
Floor Dead Load, FDL =
10.00
PSF
Repetitive factor, Cr =
1.15
Floor Live Load, FLL =
40.00
PSF
Shear Stress factor, Ch =
1.00
Roof Dead Load, RDL =
0.00
PSF
Beam Dead Load, BDL =
17.50 PLF
Roof Live Load, RLL =
0.00
PSF
W = [(((RLL + RDL + FLL + FDL) x (182-5.5/12)) + BDL) / 12] = 62.74 PLI
Center Beam is: 442 SPF / S. Pine 2x12s
Fb = 750.00 PSI B = 4.50 IN MOE = 1400000, PSI
Fv = 135.00 PSI D = 11.25 IN
Sx = B x D^2 / 6 = 102.974 IN13 Ix = B x DA3 / 12 = 604.200 IN^4
Q = 77.462 IN^3
DETERMINE MAXIMUM SPAN (pq2-309 AISC 9th ED.)
SHEAR:
V = 0.600 x W x (L-2D) Fv x Cr = VQ/IB => V = FvCrBI/Q
=> L=(FvxCdxChxBxl/(Qx0.600xW))+20= 148.37 IN.
BENDING:
M=0.1 xWxL^2 FbxCr=M/Sx=>M=FbxCrxSx
=> L = ((Fb x Cd x Cr x Sx) / (0.100 x UV))^1 /2 = 118.98 IN. Controls
DEFLECTION:
Allowable deflection = U360
DEF = (0.013021 x W x LA4) / (MOE x 1) = U360
=> L = ((MOE x Ix) / (360 x 0.013021 x W))^1/3 = 142.21 IN.
J
-----------------------
BY: ELW ■ Center Beam calculation PAGE: App. B: 1.4
DATE: 6/6/2014 �6,E (32' Wide) REF: Sheet 14
WL
WL
L L L
Roof Duration factor, Cd =
1.15
Repetitive factor, Cr =
1.15
Shear Stress factor, Ch =
1.00
Beam Dead Load, BDL =
17.50 PLF
Floor Dead Load, FDL =
10.00
PSF
Floor Live Load, FLL =
40.00
PSF
Roof Dead Load, RDL =
15.00
PSF
Roof Live Load, RLL =
20.00
PSF
W = [(((RLL + RDL + FLL + FDL) x (182-5.5/12)) + BDL)112] = 10544 PLI
Center Beam is: 442 SPF / S. Pine 2x12s
Fb = 750.00 PSI B = 4.50 IN MOE = 1400000 PSI
Fv = 135.00 PSI D = 11.25 1N
Sx = B x D^2 / 6 = 102.974 IN^3 Ix = B x D^3 / 12 = 604.200 IN^4
Q = 77.462 IN^3
DETERMINE MAXIMUM SPAN (pa 2-309 AISC 9th ED.)
SHEAR:
V = 0.600 x W x (L-21)) Fv x Cr = VQ/IB => V = FvCrBI1Q
=> L=(FvxCdxChxBxl/(Qx0.600xW))+2D= 108A7 IN.
BENDING:
M=0.lxWxL^2 FbxCr=M/Sx=>M=FbxCrxSx
=> L = ((Fb x Cd x Cr x Sx)1(0.100 x W))^112 = 98.33 IN. Controls
DEFLECTION:
Allowable deflection = U360
DEF = (0.013021 x W x L^4) / (MOE x 1) = U360
=> L = ((MOE x Ix) / (360 x 0.013021 x W))^1/3 = 119.54 IN.
--,-.-..,,-----•---„--..,,,�-.r.�-.-.w-:_,-..._,.
. r- -- --------
- Y_,.\,.
- r. .. -c- .----- -- --•- - _-..-._,.....-- :°:1..
BY: ELW
DATE: 10/20/15
N
�
SIDEWALL STUD CALC. PAGE: App. B: 2
Ranch (2.46/12) REF: Sheet 12
160 mph - Exp. C
` Lumber: 142 SPF or S. Pine 2x6
Size Factor, Cf:
1.3
Roof Dead Load, DL: 15 psf
Fb (SPF): 875
psi
Wind Duration Factor; Cd:
1.6
Wind Horiz. Drag, WD: 44.8 psf
Fb (SP): 1000
psi
Repetitive Use Factor, Cr:
1.15
Stud Spacing, SS: 16 in
FV: 135
psi
Unit Width, UW:
182
in
MOE: 1400000
psi
Sidewail Overhang, SO:
7
in
Ft: 450
psi
Stud Height, SH:
101
in
B: 1.5
in
D: 5.5
in
** Section Properties ** ** Check Stud Fastening **
Sx = B * D^2 / 6 = 7.5625 inA3
Ix = B * D^3 /12 = 20.80 in^4 15Ga.x7/16"x2-1/2" staple capacity:
64 x 0.82 x1.6 x 0.67 = 56.26 Ibs
** Calculate Distributed Loading ** No. staples req'd = V / staple capacity= 4.47
W = WD* SS * 1/144 = 4.98 pli Therefore use 5-staples at each end of studs.
12d nail capacity:
** Check Bending Stress **
79 x1.6 x 0.67 = -84.69 Ibs
Mmax = (W * SH^2) / 8 =
6347
in-Ibs
No. staples req'd = V / staple capacity = 2.97
Fb' (SPF) = Fb*Cf Cd*Cr =
2093
psi
Therefore use 3-nails at each end of studs.
Fb' (SP) = Fb*Cd*Cr =
1840
psi
fb req'd = Mmax /Sx =
839
psi < fb therefore OK.
** Check Shear Stress **
Vmax = (W * SH) / 2 = 251 Ibs
Fv' = Fv * Cd = 216 psi
fv req'd=(3*Vmax)/(2*B*D)= 45.7 psi < fv therefore OK.
** Check Deflection "*
DEF =(5 * W * SH^4) / (384*MOE*lx) = 0.232 in
DEF allow. = SH / 240 = 0.421 in > DEF, therefore OK.
•BY: ELW
JAMB STUD CALL. PAGE: App. B: 2.1 I
DATE: 10/20/2015
Wn. ism
Ranch (2,46/12) REF: Sheet 12
160 mph - Exp. C
• Lumber. 242 SPF or S. Pine 2x6
Size Factor, Cf
1.3
Roof Dead Load, DL: 15 psf
Fb (SPF): 875
psi
Wind Duration Factor, Cd:
1.6
Wind Uplift Load, WU: 78.8 psf
Fb (SP): 1000
psi
Repetitive Use Factor, Cr.
1.1.5
Uplift Load @ Eave, WE: 104.8 psf
Fr. 135
psi
Unit Width, UW:
182
in Wind Horiz. Drag, WD: 44.8 psf i
MOE: 14000b0 'psi
Sidewall Overhang, SO:
7
in Header Length, HL: 46.5 in 1
Ft: 450
psi
Stud Height, SH:
101
in I
w
B: 3 ,
in
;
!
D: 5.5
in
** Section Properties **
Sx = B * D^2 / 6 = 15.125 inA3
Ix = B * D A 3 /12 = 41.59 in^4
**Calculate Distributed Loading,**
W = WD* ((HL+14.5)/2+1.5) * 1/144 = 9.96 pli
*" Check Bending Stress **
Mmax = (W * SH^2) / 8 = 12695 in-Ibs
Fb' (SPF) = Fb*Cf Cd*Cr = 2093 psi
Fb' (SP) = Fb*Cd*Cr = 1840 psi
fb req'd = Mmax /Sx = 839 psi < fb therefore OK
** Check Shear Stress **
Vmax = (W * SH)12 = 503 Ibs
Fv' = Fv * Cd = 216 psi
fv req'd=(3*Vrmax)/(2*B*D)= 45.7 psi <fvtherefore OK,
** Check Stud Fastening **
15Ga.x7116"x2-1/2" staple capacity:
64 x 0.82 x1.6 x 0:67 = 56.26 Ibs
No. staples req'd = V / staple capacity / No. of studs = 4.47
Therefore use 5-staples at each end of studs.
12d nail capacity:
79 xl .6-x 0.67 = 84.69 Ibs
No. staples req'd = V / staple capacity / No. of studs = 2.97
Therefore use 3-nails at each end of studs.
** Check Deflection **
DEF =(5 * W * SH^4) / (384*MOE*Ix) = 0.232 in
DEF allow. = SH / 240 = 0.421 in > DEF, therefore OK
** Check Tension **
((W U-D L)*(UW)^2/2)+((W E-DL)*SO*(UW+SO/2))
Wu = — . - 44.77 pii
UW*144
T = Wu * ((HL+14.5)/2+1.5) = 1433 Ibs
Ft = Ft * Cf * Cd = 936 psi
ft req'd = T / (B*D) = 86.8 psi < ft, therefore OK
** Check Combined Bending & Tension **
(ft req'd/Ft) + (fb req'd/Fb') < or = 1.0
(ft req'd/Ff) + (fb req'd/Fb') = 0.49
and
(fb req'd - ft req'd) / Fb' < or = 1.0
(fb req'd - ft req'd) / Fb' = 0.36
Both less than or equal to 1, therefore OK
BY: ELW
c DATE: 10/20/2015 .
� '��
JAMB STUD CALL. PAGE:
Ranch (2.46/12) REF:
App, B: 2.1 a
Sheet 12
160 mph - Exp. C
Lumber: 342 SPF or S. Pine 2x6
Size Factor, Cf.
1.3
Roof Dead Load, DL:
15
psf
Fb (SPF): 875 psi
Wind Duration Factor, Cd:
1.6
Wind Uplift Load, WU:
. 78.8
psf
Fb (SP): 1000 psi
Repetitive Use Factor, Cr:
1.15
Uplift Load @ Eave, WE:
104.8
psf
Fv: 135 psi
Unit Width, UW:
182
in Wind Horiz. Drag, WD:
44.8
psf
MOE: 1400000 psi
Sidewall Overhang, SO:
7
in Header Length, HL:
72
in
Ft: 450 psi
Stud Height, SH:
101
in
B: 4.5 in
D: 5.5 in
** Section Properties **
** Check Stud Fastening **
Sx = B ` D112 16 = 22.688
in"3
Ix = B * D A 3 /12 = 62.39
in^4
15Ga.x7/16'W-1 /2" staple capacity:
+
64 x 0.82 x1.6 x 0.67 = 56.26
Ibs
** Calculate Distributed Loading **
W = WD* ((HL+14.5)/2+1.5) * 1/144 = 13.92 pli
** Check Bending Stress **
Mmax = (W * SH^2) / 8 = 17753 in-lbs
Fb' (SPF) = Fb*Cf Cd*Cr = 2093 psi
Fb' (SP) = Fb*Cd*Cr = 1840 psi
fb req'd = Mmax /Sx = 782 psi < fb therefore OK.
** Check Shear Stress **
Vmax = (W * SH) / 2 = 703 Ibs
FV = Fv * Cd = 216 psi
fv req'd=(3*Vmax)/(2*B*D)= 42:6 psi < fv therefore OK.
No. staples req'd = VI staple capacity / No. of studs = 4.17
Therefore use 5-staples at each end of studs.
12d nail capacity:
79 x1.6 x 0.67 = 84.69 Ibs
No. staples req'd = V / staple capacity / No. of studs = 2.77
Therefore use 3-nails at each end of studs,
** Check Deflection **
DEF =(5 * W * SHA4) / (384*MOE*Ix) = 0.216 in
DEF allow: = SH 1240 = 0.421 in > DEF, therefore OK.
** Check Tension **
Wu=
((W U-DL)*(UW)^2/2)+((WE-D L)*SO*(UW+SO/2))
- = 44.77 pli
UW*144
T = Wu * ((HL+14.5)/2+1.5) = 2003 Ibs•
Ft' = Ft * Cf * Cd = 936 psi
ft req'd = T /(B*D) = 80.9 psi < ft, therefore OK.
** Check Combined Bending & Tension **
(ft req'd/Ft) + (fb req'd/Fb') < or = 1.0
(ft req'd/Ff) + (fb req'd/Fb') = 0.46
and
(fb req'd - ft req'd) / Fb' < or = 1.0
(fb req'd - ft req'd)•I Fb' = 0.34
Both less than or equal to 1, therefore OK.
•BY: ELW
JAMB STUD BETWEEN WINDOWS PAGE: App. B:
2.2
• DATE: 10/20/2015
Ranch (2.46/12) REF:
Sheet 12
160 mph - Exp. C
Lumber. 342 SPF or S. Pine 2x6
Size Factor, Cf.
1.3
Roof Dead Load, DL:
15
psf
Fb (SPF): 875
psi
Wind Duration'Factor, Cd:
1.6
Wind Uplift Load, WU:
78.8
psf i
Fb (SP): 1000
psi
Repetitive Use Factor, Cr.
1.15
Uplift Load @ Eave, WE:
104.8
psf I
Fv: 135
psi
Unit Width, UW:
182
in Wind Horiz. Drag, WD:
44.B
psf
i
MOE: 1400000
psi
Sidewall Overhang, SO:
7
in Header Length, HL:
46.5
in
Ft: 450
psi
Stud Height, SH:
101
in
B: 4.5
in
D: 5.5
in
** Section Properties **
Sx = B * D A 2 / 6 = 22.688 in^3
Ix = B * D A 3 /12 = 62.39 inA4
** Calculate Distributed Loading **
W = WD* (HL+B) * 1/144 = 15.87 pli
** Check Bending Stress ** -
Mmax = (W * SH^2) / 8 = 20232 in-Ibs
Fb' (SPF) = Fb*Cf Cd*Cr = 2093 psi
Fb' (SP) = Fb*Cd*Cr = 1840 psi
fb req'd = Mmax /Sx = 892 psi < fb therefore OK.
** Check Shear Stress **
Vmax = (W * SH) / 2 = 801 Ibs
Fv' = Fv * Cd = 216 psi
fv req'd=(3*Vmax)/(2*B*D)= 48.6 psi < fv therefore OK
** Check Stud Fastening **
15Ga.x7/16'V--1/2" staple capacity:
64 x 0.82 x1.6 x 0.67 = 56.26 Ibs
No. staples req'd = V / staple capacity / No. fo studs = 4.7
Therefore use 5-staples at each end of studs.
12d nail capacity:
79 x1.6 x 0.67 = 84.69 Ibs
No. staples req'd = V / staple capacity / No. of studs = 3.15
Therefore use 3-nails at each end of studs.
(Within 5%, OK)
** Check Deflection **
DEF =(5 * W * SH^4) / (384*MOE*Ix) = 0.246 in
DEF allow. = SH / 240 = 0.421 in > DEF, therefore OK.
** Check Tension **
Wu=
((WU-DL)*(UW)*(UW/2)+((WE-DL)*SO*(UW+SO/2)
= 44.77 pli
UW*144
T = Wu * (HL+B) = 2283 Ibs
Ft' = Ft * Cf * Cd = 936 psi
ft req'd = T / (B*D) = 92.2 psi < ft, therefore OK.
** Check Combined Bending & Tension **
(ft req'd/Ft') + (fb req'd/Fb') < or = 1.0
(ft req'd/Ft') + (fb req'd/Fb') = 0.52
and
(fb req'd - ft req'd) / Fb' < or = 1.0
(fb req'd - ft req'd) / Fb' = 0.38
Both less than or equal to 1, therefore OK
• - 7
DATE: 10/20/2015 W SILL CALC. - Ranch (2.46/12) PAGE: App. B:2.3
BY: ELW ,160 mph - Exp. C REF: Sheet 12
• Cf = Size Factor
— Calculate Sect. Properties —
— Check Deflection —
Cd = Duration Factor
Sx = (B * D^2) / 6
DEF = (5*W*SL"4) / (384*MOE*Ix)
• SL = Sill Length
Ix = (B * D113) / 12
DEF allow. = SL / 240
SH = Max Stud Height
WL = Wind Load
— Check Bending Stress —
— Check Shear Stress —
Mmax. _ (W * SL^2) / 8
Vmax. _ (W * SL) / 2
— Calculate Dist. Loading —
fb req'd = Mmax / Sx
fv req'd = (3 * V) / (2 * B * D)
W = (SH/2) WZ * (1/144)
Fb' allow. = Fb * Cf * Cd * Cr
Fv' allow. = Fv * Cd
-
142 SPF
142 S. Pine
Lumber
2x6
2x6
B (in)
1.5
1.5
D (in)
5.5
5.5
Fb (psi)
875
1000
Fv (psi)
135
175
MOE (psi)
1400000
1400000
Sx (in"3)
7.5625
7.5625
Ix (in^4)
20.7969
20.7969
Cf
1.3
1
Cd
1.6
1.6
Cr
1
1
SL (in)
46.5
46.5
SH (in)
101
101
WL (PSF)
44.8
44.8
W (pli)
15.71
15.71
Mmax (in-Ibs)
4246
4246
Fb' allow,. (psi)
2093
1840
fb req'd (psi)
561.51
561.51
Vmax (Ibs)
365.28
365.28
FV allow. (psi)
216
280
fv req'd (psi)
66.42
66.42
DEF (in)
. 0.033
0.033
DEF allow (in)
0.258
0.258
_
I
i
By: Ed Weber
■
Exterior Wall
Page: App. B: 2.4
Check SIII Fastening:
Vmax. = 365.28 lbs.
12d nail capacity = 79 x 1.6 x 0.67. = 84.69
lbs.
. Number of nails = Vmax. / Nail capacity =
4.31'
Use 5 min.
- 15Ga. staple capacity = 64 x 0.82 x 1.6 x 0.67 =
56.26
lbs.
Number of staples = Vmax. / staple capacity =
6.49
Use 7 min..
Check Bottom Plate Fastening:
W = 44.8 Ibs/ft^2 x (126"12) x ft^2/144 in"2 =
19.60
pli
#8x3-1/2" screw capacity = 78 x 1.6 =
124.80
lbs.
Screw Spacing = screw capacity / W =
6.37
inches max.
Check Top Plate Fastenina:
P = W x 24" = 470.4 lbs.
Simpson H2.5T Tie Capacity (Lateal) = 135 lbs.
Pact. = P - 135 lbs = 335.40 lbs.
Fasten Ea. Truss w/ 3-#8x3-1/2" Screws = 3 x 78lbs x 1.6 x (1.525"/1.624") = 351.58 lbs.
351.58 lbs. > 335.40 lbs.; therefore OK
,.... ..... ... y:..�J. : � - i.. .. .... .'I , ..a�. .. i 'i-: :-. tit..--:�,�-r„•, y,
r BY: ELW
DATE: 10/20/2015
.
INS
HEADER CALCULATION PAGE: App. B: 2.5
Ranch (2.46/12) REF: Sheet 12
160 mph - Exp. C sheet 1 of 2
Unit Width (UW):
182 in
Roof Duration Factor (Cdr):
1.15
#2 SPF / S. Pine
Sidewall Overhang (SO):
7 in
Wind Duration Factor (Cdw):
1.6
_
Fb (SPF): 875 psi
Sidewall Height (SH):
99.5 in
2x3 Size factor (Cf :
1.5
Fb (SP): 1000 psi
Roof Live Load (LL):
20 psf
2x4 Size factor (Cf):
1.5 I
Fv: 135 psi
Roof Dead Load (DL):
15 psf
2x6 Size factor (Cf):
1.3
E: 1400000 psi
Wind Uplift Load (WU):
78.8 psf
2x8 Size factor (CO:
1.2
Wind Uplift Load @ Eave (WE):
104.8 psf
2x10 Size factor (CO:
1.1
Wind Horizontal Load (WH):
44.8 psf
2x4 flat use factor (Cfu):
1.1
2x6&8 flat use factor (Cfu):
1.15
2xl0 flat use factor (Cfu):
1.2
** DISTRIBUTED LOADING **
W1 (horiz.) _ (WH*SH) / (2*144) =
15.48 pli
W2 (roof)=(DL+LL)*((UW+SO)^2) / 2*UW*144 = 23.85 pli
((W U-DL)*(UW)*(UW/2)+((WE-DL)*SO*(UW+SO/2)
W3 (uplift) = — = 44.77 pli
UW * 144
** SECTION PROPERTIES **
—Vertical Loads—
Sx1 = b*(d^2)/6
Ix1 = b*(dA3)/12
** DESIGN CRITERIA **
—Shear—
Vmax = W * (L-20) / 2
fv = 3*V / 2*b*d
F'v=Fv*Cd*Ch>fv
—Deflection—
Def. = 5*W*(L"4) / 384*E*Ix
Def. allow. = L/240 > Def.
—Horizontal Loads—
Sx2 = d*(bA2)/6
Ix2 = d*(bA3)/12
—Bending—
Mmax = W * (LA2) /8
fb = Mmax / Sx
Fb = Fb*Cf" Cd (*1.15 if 3 members),(* Cfu if applicable) > fb
—Combined Loading--
lu = Ud if lu < 7, then le = 2.06*16
Kbe = 0.438 if lu > 7, then le = 1.63*lu + 3*d
CL = [(fbl / F'bl) + [fb2 / (F'b2*(1-(fbl/Fbe)^2))] < or = 1
fb1 = bending stress in uplift
F'b1 = Allowable bending stress in uplift
fb2 = bending stress in'horizontal
F'b2 = Allowable bending stress in horizontal
Rb = ((le*d) / (bA2))^0.5
Fbe = Kbe*E / Rb^2
BY: ELW
DATE: 10/20/2015
HEADER CALCULATION
Ranch (2.46/12)
160 mph - Exp. C
*Section Properties & Dimensions*
orientation
edge
edge
flat,
flat
flat
edge
lumber
3-2x3
3-2x4
1-2x6
2-2x6
3-2x6
3-2x6
L (in)
36.5
48
24.5
47
68
72
b (in)
4.5
4.5
5.5
5.5
5.5
4.5
d (in)
2.5
3.5
1.5
3
4.5
5.5
Sx1 (in A3)
4.688
9.188
2.063
8.250
18,563
22.688
Ix1 (in^4)
5.859
16.078
1.547
12.375
41.77
62.391
" Sx2 (in A3)
8.438
11.81.3
7.563
15.125
22.688
18.563
b(2 (in A4)
18.984
26.578
20.797
41.594
62.391
41.766
` *ROOF LOAD*
Mmax (in-Ibs)
3972.1
6869.4
1789.7
6586.2
13786.6
15456.2
fb (psi)
847.4
747.7
867.7
798.3
742.7
681.3
F'b (psi)
1322.5
1.322.5
1322.5
1322.5
1322.5
1322.5
Vmax (Ibs)
375.7
489.0
256.4
489.0
703.6
727.5
fv (psi)
50.09
46.569
46,620
44.452
42.645
44.090
F'.v (psi)
155.250
155.250
155.250
155.250
155.250
155.250
Def (in)
0.067
0.013
0.052
0.087
•0.114
0.096
allow Def (in)
0.152
0.200
0.102
0.196
0.283
0.300
*UPLIFT LOAD*
Mmax (in-Ibs)
7455
12893
3359
12361
25875
, 29009
fbl (psi)
1590.4
1403.3
1628.6
1498.3
1394.0
1278.6
F'bl (psi)
1840.0
1840.0
1840.0
1840.0
1840.0
1840.0
Vmax (Ibs)
705.1
917.7
481.2
917.7
1320.6
1365.4
fv (psi)
94.01
87.403
87.500
83.430
80.038
82.752
F'v (psi)
216.0
216.0
216.0
216.0
216.0
216.0
Def (in)
0.126
0.137
0.097
0.164
0.213
0.179
allow Def (in)
0.152
0.200
0.102
0.196
0.263
0.300
*HORIZONTAL WIND LOAD*
Mmax (in-Ibs)
fb2 (psi)
F'b2 (psi)
Vmax (Ibs)
fv (psi)
F'v (psi)
Def (in)
allow Def (in)
*COMBINED LOADING*
lu (in)
le (in)
Rb
Fbe (psi)
CL
2577.5
4458
1161.3
4273.8
8946
10030
305.5
377.4
153.6
282.6
394.3
540.3
1840.0
1840.0
1840.0
1840.0
1840.0
1840.0
243.8
317.3
166.4
317.3
456.6
472.1
32.503
30.219
30.252
28.845
27.672
28.610
216.0
216.0
216.0
216.0
216.0
216.0
0.013
0.029
0.002
0.017
0.049
0.093
0.152
0.200
0.102
0.196
0.283
0.300
14.60
13.71
16.33
15.67
15.11
13.09
31.30
32.85
31.12
34.54
38.13
37.84
1.97
2.38
1.24
1.85
2.38
3.21
158598
107986
397329
179030
108102
59667
1.0
0.97
0.97
0.97
0.97
0.99
PAGE: App. B: 2.5
REF: Sheet 12
BY: ELW HEADER CALCULATION PAGE: App. B: 2.6
' DATE: 10/20/2015 Ranch (2.46/12) REF: Sheet 12
#3 SPF
Fb: 500 psi
Fv: 135 psi
E: 1.200000 psi
Unit Width (UW):
Sidewall Overhang (SO):
Sidewall Height (SH):
Roof Live Load (LL):
Roof Dead Load (DL):
Wind -Uplift Load (WU):
Wind Uplift Load @ Eave (WE):
Wind Horizontal Load (WH):
** DISTRIBUTED LOADING **
160 mph - Exp. C Sheet l of 2
182
in
Roof Duration Factor (Cdr):
1.15
10
in
Wind Duration Factor (Cdw):
1.6
103.5
in
2x3 Size factor (Cf):
1.5
20
psf
2x4 Size factor (CO:
1.5
15
psf
2x6 Size factor (Cf):
1.3
78.8
psf
2x8 Size factor (CO:
1.2
104.8
psf
2xl 0 Size factor (Cf):
1.1
44.8
psf
2x4 flat use factor (Cfu):
1.1
2x6&8 flat use factor (Cfu):
1.15
2xl 0 flat use factor (Cfu):
1.2
W1 (horiz.) = (WH*SH) / (2*144) = 16.10 pli
W2 (roof)=(DL+LL)*((UW+SO)^2) / 2*UW*144 = 24.62 pli
W3 (uplift) =
((W U-DL)*(UW)*(UW/2)+((WE-DL)*SO*(UW+SO/2)
46.73 pli
UW*144
** SECTION PROPERTIES **
—Vertical Loads —
SA = b*(d^2)/6
Ix1 = b*(d^3)/12
** DESIGN CRITERIA **
—Shear—
Vmax = W * (L-2D) / 2
fv = 3*V / 2*b*d
F'v=Fv*Cd*Ch>fv
—Deflection—
Def. = 5*W*(L^4) / 384*E*Ix
Def. allow. = U240 > Def.
—Horizontal Loads—
Sx2 = d*(b^2)/6
Ix2 = d*(b^3)/12
--Bending—
Mmax = W * (L^2) /8
fb = Mmax / Sx
F'b = Fb*Cf Cd (*1.15 if 3 members),(* Cfu if applicable) > fb
—Combined Loading—
lu = Ud if lu < 7, then le = 2.06*lu
Kbe = 0.438 if lu > 7, then le = 1.63*lu + 3*d
CL = [(fbl / F'bl) + [fb2 / (F'b2*(1-(fbl/Fbe)^2))] < or = 1
fb1 = bending stress in uplift
F'b1 = Allowable bending stress in uplift
fb2 = bending stress in horizontal
F'b2 = Allowable bending stress in horizontal
Rb = ((le*d) / (b^2))^0.5
Fbe = Kbe*E / Rb^2
BY: ELW
HEADER
CALCULATION PAGE: App. B: 2.6
DATE: 10/20/2015
Ranch
(2.46/12) REF: Sheet 12
160
mph - Exp. C FSF,7et 2 �,f 2
*Section Properties & Dimensions*
orientation
edge
edge
flat
flat
flat
edge
lumber
3-2x3
3-2x4
1-24
2-2x6
3-2x6
L (in)
30.5
41
19
38
.3-2x6
57
59
b (in),
4.5
4.5
5.5
5.5
5.5
4.5
d (in)
2.5
3,6
1.5
3.
4.5
.5.5
Sx1 (in A 3)
4.688
9.188
2.063
8.250
18.563
22.688
Ix1 (inA 4)
5.859
16.078
1.547
12.375
41.77
62.391
Sx2 (in A 3)
8.438
11.813
7.563
15.125
22.688
19.563
Ix2 (in A 4)
18.984
26.578
20.797
41.594
62.391
41.766
*ROOF LOAD*
Mmax (in-Ibs)
2862'3
5172.3
1110.8
4443.1
9996.9
10710.8
fb (psi)
610.6
563.0
638.6
538.6
538.6
472.1
F'b (ps)
991.9
991.9
859.6
859.6
988.6
859.6
Vmax (Ibs)
313.8
418.5 -
196.9
393.8
590.8
596.8
fv (psi)
41.85
39.853
.35.804
35.804
35.804
35.804'
F'v (psi)
155.250
155.250'.
165.250
155.250
155.250
155.250
Def (in)
0.039
0.047
0.023
0.045
0.068
0.052
allow Def (in)
0.127
0.171
0.079
0.158
0.238
0.246
*UPLIFT LOAD*
Mmax (in-Ibs)
5433
9818
2108
8434
18976
20331
fb1 (psi)
11159.1
1068.6
1022.3
1022.3
1022.3
896.2
F'b 1 (psi)
1380.0
1380.0
1196.0
1196.0
1375.4
1196.0
Vmax (Ibs)
595.7
794.3
373.8
747.6
1121.4
1121.4
fv (psi)
79.43
76.651
67.964
67.964
67.964
67.964
F'v (psi)
216.0
216.0
216.0',
216.0
216.0
216.0
Def (in)
0.075
0.089
0.043
0.085
0.128
.0.098
allow Def (in)
0.127
0.171
0.079
0.158
0.238
0.246
*HORIZONTAL WIND LOAD*
Mmax (in-Ibs)
1872.1
3383
725.5
2906.1
6539
7006
fb2 (psi)
221.9
286.4
96.1
192.1
288.2
377.4
F'b2 (psi)
138.0.0
1518.0
1040.0
1040.0
1196.0
1375.4
Vmax (Ibs)
205.3
273.7
128.8
257.6
386.4
386.4
fv (psi)
27.370
26.067
23.418
23.418
23.418
23.418
F'v (psi)
216.0
216.0
216.0
216.0
216.0
216.0
Def (in)
0.008
0.019
0.001
0.009
0.030
0.051
allow Def (in)
0.127
0.171
0.079
0.158
0.238
0.246
*COMBINED LOADING'
lu (in)
12.20
11.71
12.67
12.67
12.67
10.73
le (in)
27.39
29.59
25.15
29.65
34.15
33.99
Rb
1.84
2.26
1.12
1.71
2.25
3.04
Fbe (psi)
155458
102755
421511
178765
103471
56941
CIL
1.00
0.96
0.95
1.0
0.98
1.0
By: MGN � �� Header Fastening Page: App. B: 2.7 i
Date: 10/13/2015 Ranch (2.46/12) Ref: Sheet 5
160 mph - Exp. C
Header Max span for single member, SM: 24.5 in. Wind Load, WL: 44.8 PSF
Header Max span for double member, DM: 47 in. Unit Width, UW: 182 in.
Header Max. span for triple member, TM: 72 in. Sidewall Eave, SE: 7 in.
Sidewall Stud Height, SH: 103.5 in.
' * FASTENER CAPACITIES **
15Ga.x7/16"x2-1/2" staples = 64 x 0.82 x 1.6 x 0.67 = 56.259 lbs. kind Load
12d nails = 79 x 1.6 x 0.67 = 84.688 lbs. ��L
** CHECK HORIZONTAL WIND **
Single member:
W = (SH/2 x WL x l/144) =
16.100 pli
P=WxSM/2=
197.23 lbs.
Double member:
W = (SH/2 x WL x l/144) =
16.100 pli
P=WxDM/2/2=
189.18 lbs.
Triple member:
W = (SH/2 x WL x l/144) =
16.100 pli.
P=WxTM/2/3=
193.20 lbs.
P / Staple capacity = 3.5 staples
P/ nail capacity = 2.3 nails
P / Staple capacity = 3.4 staples
P/ nail capacity = 2.2 nails
P / Staple capacity ,= 3A staples
P/ nail capacity = 2.3 nails
K
• By: Et_W Uplift - Ranch (2.46/12) Page: App. B: 2.8
Date: 3/6/2018 '�E 160 mph - Exp. C Ref: Sheet 12
��.. Sheet 1 of 2
Sidewall Uplift Loads:
P sidewall - 24"o.c. = 899 lbs (per truss design drawing)
W sidewall = 899 lbs / 24" = 37.46 pli
P sidewall-16"o.c. = W x 16" = 599 Ibs
Check Sidewall Uplift:
Roof to sidewall connection:
Trusses 24" o.c., P = 781 lbs, use Simpson H2.5T Tie (capacity = 545 lbs) wl 5-8dxl-112" nails.
Remainder of load to be carried by 2484-1/2" toe -screw connection = 781 lbs - 545 lbs = 354 lbs
Toe -Screw Connection Capacity = 3 x 82 lbs x 1.6 x 1.57&' x (1.576"M.64") Toe -screw penetration:
= 695.4 lbs > 236 lbs, therefore OK. x = (1.167" + 0.5")1 COS 30 =1.925"
Pene. = 3.5" -1.925 = 1.575"
1.575" > 1.640", take reduction.
Check Wall Sheathina:
7116" APA rated sheating (plywood or OSB) with 24/16 span rating - See APA tech. Note N376B
FtA = 2600 pif Ft = Ws x 12" = 449.50 pif, < FtA, OK.
Check fastenincl:
8d nail capacity = 46 x 1.6 = 73.6 lbs
Check spacing:
Use 2 rows of fasteners @ top & bottom.
Spacing = nail capacity / Ft x 2 x 12"/ft= 3.9 in. Use 4" o.c. max. (within 3%)
Fasten sheathing (w/ 2 rows of 8d nails) to double top plate & perimeter floor Joist
Check strapping at sidewall openings:
Use Simpson ST22 Strap Tie - Capacity = 1420 lbs.
Fasten w/ 0.1.48"xl-1/2" nails - capacity = 100 x 1.6 = 160 lbs. / nail (16 Ga. Steel)
Strap capacity w/ 9 nails = 9 x nail capacity = 1440 lbs. Use 9 nails at each end of strap (strap controls)
Max, opening w/ 1-strap & 9 nails = ((Strap Cap. I Ws)-(16"/2)) x 2 = 59.8 in.
Max. opening w/ 2-straps & 9 nails = ((Strap Cap.x2 / Ws)-(16"/2)) x 2 = 135.6 in.
By: ELW 0 Uplift - Ranch (2.46/12) Page: App. B: 2.8
Date: 3/6/2018 =NEI 160 mph - Exp. C Ref: Sheet 13B
.�.�� Sheet 2 of 2
Ridge Beam (Mating Line) Uplift Loads:
P mating line - 24"o.c. = 862 lbs (per truss design drawing)
W mating line = 862 lbs / 24" = 35.92 pit (ea. half? ,
P mating line-16"o.c. = 575 lbs
Check matinq Line:
Use Simpson ST22 Strap Tie - Capacity = 1420 lbs.
Fasten w/ 0.148"xl-1/2" nails - capacity =100 x 1.6 = 160 lbs, / nail (16 Ga. Steel)
Strap capacity w/ 9 nails = 9 x nail capacity = 1440 Use 9 nails at each end of strap (strap controls)
Strap spacing = Strap capacity / (Wml x 2) = 19.77 in., use straps 16" o.c. max, on one half
Check matinq line straps at openings:
Use Simpson ST22 Strap Ties (see above for capacity).
Max. Opening w/ 1 strap: 23 in. 1.92 ft.
P = j((Wml x 2) x (MO/2 + 16"/2))] = 1400.8 lbs. < Strap capacity, therefore OK.
Max. Opening w/ 2 straps: 63
in.
5.25 ft.
P = [((Wml x 2) x (MO/2 + 16"/2))] / 2 =
1418.7
lbs. < Strap capacity, therefore OK.
Max. Opening w/ 3 straps: 102
in.
8.50 ft.
P = [((Wml x 2) x (MO/2 + 16"/2))] / 3 =
1412.7
lbs. < Strap capacity, therefore OK.
Max. Opening w/ 4 straps: 142
in.
11.83 ft.
P = j((Wml x 2) x (MO/2 + 16"12))] / 4 =
1418.7
lbs. < Strap capacity, therefore OK.
Max. Opening w/ 6 straps: 221
In.
18.42 ft.
P = [((Wml x 2) x (MO/2 + 16"/2))] / 6 =
1418.7
lbs. < Strap capacity, therefore OK.
Check truss kingpost to ridge beam uplift connection:
12d nail capacity = 79 x 1.6 = 126.4 lbs
.No. of 12d nails = P / 126.4 = 6.82 (Use 7-12d nails at ea. ridge beam to truss connection)
Also check truss kingpost to ridge beam gravity connection:
P mating line - 24"o.c. = 443 lbs (per truss design drawing)
12d nail capacity = 79 x 1.15 = 90.85 lbs
No. of 12d nails = P / 90.85 = 4.88 (Use 5-12d nails at ea. ridge beam to truss connection)
BY: ELW Endwall (Shearwalls) PAGE: App. B: 3
DATE: 10/8/19 s INN Ranch REF: Sheet 12A
7/16" sheathing w/ 6'712" 8d nail spacing (Shear capcity per AWC SDPWC Table A.4.3.A)
104" Sidewall - 32' Wide - 2.46/12 Roof - Ranch -160 mph - Exp. C.
Wind Load (WZ): 22.9 psf Wall Sheathing (PP1): 365.0 plf
Wind Load at Roof Projection (WR): 0.0 psf Endwall Unit Width (UW): 182.0"
Wind Load at Corner (WZ1): 34.5 psf Sidewall Height (H): 104.0"
nd Load at Roof Projection at Corner (WR1): 0 psf Kingpost Height (K): 43.0"
Max. Box Length (BL): , 56' Framing Specific Gravity (SG): 0.42
Calculate Shear Loads:
W = ((H/2 x WZ) + (K x WR)) x l/144 = 8.269 pli, = 99.23 pif
W1 = ((H/2 x WZ1) + (K x WR1)) x l/144 = 12.458 pli, = 149.6 pif
Vmax. = [(W1 x 16) + (W x (BL-16))] x l/2 = 3181 lbs.
Check Shearwall Sheathing:
Specific gravity adjustment factor (SGAF) = 1 - (0.5 - SG) = 0.92
Max. opening height = 82 in. = 6.83 ft.
Percent full height wall segments, FH% = 90.1 %
Shear Capacity adjustment factor (SCAF) = 0.882
(See AWC SDPWC Table 4.3.3.4 - Value is interpolated)
Shear capacity req'd = Vmax. / (UW x FH% x 2 / 12) = 116.38 plf
Effective Shear Capacity = PP1 x SGAF x SCAF = 296.1 plf, > Req'd capacity, therefore OK.
Max. Endwall Opening = (100%-FH%) x UW x 2 = 36.04 in. (for both halves)
Check end Tiedowns for Overturning:
T = (Vmax. x H) / (SCAF x (364" -12") x FH%) = 1183 lbs.
Use Simpson 1-ST22 Strap Tie - Capacity = 1420 lbs., > T, therefore Ok.
Fasten w/ 0.148"x1-1/2" nails, capacity = 100 x 1.6 = 160 lbs. / nail (16 Ga. Steel)
Number of nails req'd = T / nail capacity = 7.4 nails
Check Top & bottom plate fastening:
Use #8x3-1/2" screws - Top plate is toe -screwed Toe -screw penetration:
Screw capacity = 78 lbs x 1.6 x 1.675"/1.64" = 119.9 lbs. / screw x = 1.167" + 0.5"/ COS 30 = 1.925"
Pene. = 3.51' -1.925" =1.575
Number required = Vmax. / (screw capacity x 2) = 13.3 screws 1.575" > 1.640", NO - take reduction
Spacing = UW / number of screws = 13.72 in. o.c.
_Check end Tiedowns for Overturning (at foundation):
T = 1183 lbs.
Use 1-Simpson ST2122 Strap Tie w/ 816d common nails - Capacity = 1505 lbs.. > T, therefore Ok.
BY: ELW IME Sidewall (Shearwalls) PAGE: App. B: 3.1
DATE: 10/8/19SWRRanch REF: Sheet 12A
s 7116" sheathing w/ 6"112" 8d nail spacing (Shear capcity per AWC SDPWC Table A.4.3.A)
104" Sidewall - 32' Wide - 2.46/12 Roof - Ranch -160 mph - Exp. C.
Wall Sheathing (PP1): 365.00 plf
Wind Load (WZ): 22.90 psf Unit Width (UW): 182.0"
Wind Load at Comer (WZ1): '34.50 psf Sidewall Height (H): 104.0"
Min. Box Length (BL): 56' Roof Projection (K): 43.0"
Framing Specific Gravity (SG): 0.42
Calculate Zone Areas:
K1 = (2.46 x 106") / 12 = 21.73 in
t K2 = (2.46 x (UW-96" )) / 12 = 17.63 in
8' Corner Zone:
Area A = (H12 x W') =
4992
in^2
= 34.67
ft"2
Area B = (6" x 106) =
636
in^2
= 4.42
ft"2
Area C = (K1 x 1061 / 2 =
1152
in^2
= 8.00
ft^2
Total Area =
6780
inA2
= 47.08
ft^2
Middle Zone:
Area D = (H/2+6") x (UW-96") =
4988
in^2
= 34.64
ft^2
Area E T K1 x (UW-96") =
1869
in"2
=- 12.98
ft"2
Area F = K2 x (UW-96") / 2 =
758.1
in^2
= 5.26
ft"2
.Total Area =
7615
MA2
= 52.88
ft"2
Calculate Shear Loads:
Vmax. = (Corner Zone Area x WZ1) + (Middle Zone Area x WZ) = 2835 lbs.
Check Shearwall Sheathing
Specific gravity adjustment factor (SGAF) =1 - (0.5 - SG) = 0.92
Max. opening height = 104 in. = 8.67 ft.
Percent full height wall segments, FH%a = 54 %
Shear Capacity adjustment factor (SCAF) = 0.524
(See AWC SDPWC Table 4.3.3.4 - Value is interpolated)
Shear capacity req'd = Vmax. / (BL x FH%) = 93.8 pif
Effective Shear Capacity = PP1 x SGAF x SCAF = 175.9 pif, > Req'd capacity, therefore OK.
Max. Sidewall Openings=(100%-FH%) x SL = 26.76 ft. = 309.1 in.
Check end Tiedowns for Overturning:
T = (Vmax. x H) / (SCAF x BL x FH%) = 1552 lbs.
Use 2 -Simpson 1-ST22 Strap Ties - Capacity = 2840 lbs., > T, therefore Ok.
Fasten w/ 0.148"x1-1/2" nails, capacity =100 x 1.6 = 160 lbs. / nail (16 Ga. Steel)
Number of nails req'd = T / nail capacity = 9.7 nails
Check Top plate fastening_
;ck #Sx3-1 /2" screws, capacity = 78 lbs x 1.6 x 1.57671.64" = 119.85 lbs. / screw
Number required = Vmax. / screw capacity = 23.7 screws
Spacing = (BL x 12") / number of screws = 17.50 in. o.c.
Check end Tiedowns for Overtumina fat foundation):.
T = 1552 lbs.
Use 2-Simpson ST2122 Strap Ties - Capacity = 3010 lbs., > T, therefore Ok.
0
t
t
it
j
By: ELW ■ Hood Page: App. B: 4
Date: 10/20/2015 Mini
Calculation Ref: Sheet 13A
LUMBER: #2 SPF or S. Pine 2x5 (laid flat)
Fb (SPF):
875
PSI
ROOF LIVE LOAD (LL):
Fb (SP):
1000
PSI
ROOF DEAD LOAD (DL):
Fv:
135
PSI
WIND UPLIFT (WU):
E:
1400000
PSI
PURLIN SPACING (PS):
B:
5.5
IN
HOOD DEPTH (HD):
D:
1.5
IN
MAX TRUSS SPACING (TS1):
DURATION FACTOR - Wind (Cd):
1.6
MIN TRUSS SPACING (TS2):
DURATION FACTOR - Roof (Cd):
1.15
SIZE FACTOR (Cf):
1.3
FLAT USE FACTOR (Cfu):
1.15
** Section Properties **
Sx = (B * D^2)/6 = 2.0525 IN^3
Ix = (B * D^3)/12= 1.5469 IN-4
Proof = (DL+LL)*(PS)*(HD/2) / 144 = 47.8 LBS
P wind = (WU-DL)*(PS)*(HD/2) 1144 = 165.4 LBS <— CONTROLS
** Check Bending **
M max = Pw * HD = 1984.4 IN-LBS
Fb' (SPF) = Fb * Cd * Cf * Cfu = 2093.00 PSI
Fb' (SP) = Fb * Cd * Cfu = 1840.00 PSI
fb = M max / Sx = 962.13 PSI, < FU therefore OK.
** Check Shear **
V max = Pw = 165.367 LBS
Fv' = Fv * Cd = 215 PSI
fv = (3 * V max) / (2 * b * d)= 30.1 PSI, < Fv', therefore OK.
Check Deflection **
Def. Max. = (Pw*(HD^2))/(3*E*Ix) * (TS1+HD) = 0.132 IN
Def. Allowable = 2*HD / 180 = 0.133 IN, > Def, therefore OK.
** Calculate truss reactions **
Ra = Reaction at end truss Rb = Reaction at first inside truss
Ra = (Pw/TS2) * (TS2+HD) = 289.4 LBS
Rb = (Pw*HD) / TS2 = 124.0 LBS
** Calculate Purlin Fastening to Truss **
Capacity of 15Ga.x 7/16" x 2-1/2" staples:
64 * Cd * 0.82= 83.97 lbs.
Number of staples req'd:
20 PSF
8 PSF
104.8 PSF
41 IN
12 IN
24 IN
16 IN
@Ra = Ra/59.62 = 3.45 Therefore, use 4-15Ga. x 7/16" x 2-1 /2" staples
@Rb = Rb/59.62 = 1.48 Therefore, use 2-156a. x 7/16" x 2-1 /2" staples
-.- - -IT T
By: ELW . Hood Page: App. B: 4.1
Date: 10/20/2015 ' Calculation Ref: Sheet 13A
(Fly Rafter)
• ** Section Properties **
LUMBER: #3 SPF 2x6
Fb:
500
PSI
• Fv:
135
PSI
E:
1200000
PSI
B:
1.5
IN
- D:
5.5
IN
DURATION FACTOR - Wind (Cd):
1.6
DURATION FACTOR - Roof (Cd):
1.15
** Section Properties **
Sx = (B * D"2)/6 = 7.5625 INA3
Ix = (B * D"3)/12= 20.7969 IN^4
W wind = (WU-DL)*(HD/2) / 144 = 4.03 PSI
W roof = (LL+DL)*(HD/2) / 144 = 1.17 PSI
SIZE FACTOR (CO:
1.3
FLAT USE FACTOR (Cfu):
1
. WIND UPLIFT (WU):
104.8
PSF
ROOF LIVE LOAD (LL):
20
PSF
ROOF DEAD LOAD (DL):
8
PSF
PURLIN SPACING (PS):
41
IN
HOOD DEPTH (HD):
12
IN
<--- CONTROLS
** Check Bending **
M max = Ww * PS^218 = 847.5 IN-LBS
Fb' = Fb * Cd * Cf * Cfu = 1040.00 PSI
fb = M max / Sx = 112.07 PSI, < Fb' therefore OK.
** Check Shear **
V max = Ww * PS / 2 = 82.683 LBS
Fv' = Fv * Cd = 216 PSI
fv = (3 * V max) / (2 * b * d)= 15.0 PSI, < Fv', therefore OK.
** Check Deflection **
Def. = (5 * Ww * (PS"4)) / (384 * E * Ix) = 0.006 IN
Def. Aliowable = PS / 240 = 0.171 IN, > Def, therefore OK.
** Check Fastening **
P max = Ww * PS = 165.4 LBS
Capacity of 15Ga.x 7/16" x 2-1/2" staples:
64 * Cd * 0.82 * 0.67 = 56.26 lbs.
No. of Staples = P / staple capacity = 2.9 , use 3 staples.
...r ,..�,.,::•�,�:..:> ,... ... ins.:;:- :.. ;�....�, ,..>.�:..: i 7„�.-a,�.-....... ........ 9 ....
• By: ELW . Hood Page: App. B: 4.2
Date: 10/20/2015 $mini
Calculation Ref: Sheet 13A
(Sidewall Fascia)
• ** Section Properties **
LUMBER: Utility Gr. SPF 1A
WIND UPLIFT (WU):
104.8
PSF
Fb: 275
PSI
ROOF LIVE LOAD (LL):
20
PSF
` Fv: 135
PSI
ROOF DEAD LOAD (DL):
8
PSF
E: 1100000
PSI
PURLIN SPACING (PS):
41
IN
B: 0.75
IN
HOOD DEPTH (HD):
12
IN
D: 5.5
IN
MAX TRUSS SPACING (TS1):
24
IN
DURATION FACTOR - Wind (Cd): 1.6
MIN TRUSS SPACING (TS2):
16
IN
DURATION FACTOR - Roof (Cd): 1.15
` SIZE FACTOR (Cq: 1
FLAT USE FACTOR (Cfu): 1
** Section Properties **
Sx = (B * DA2)/6 = 3.78125
INA3
Ix = (B * DA3)/12= 10.3984
IN"4
W wind = (WU-LL)*(PS/2) / 144 =
13.8
LBS <--CONTROLS
W roof = (LL+DL)*(PS/2) / 144 =
4.0
LBS
** Check Bending **
M max = Ww * HDA2 / 2 = 992.2 IN-LBS
Fb' = Fb * Cd * Cf * Cfu = 440.00 PSI
fb = M max / Sx = 262.40 PSI, < Fb' therefore OK.
** Check Shear **
V max = Ww * HD = 165.367 LBS
Fv' = Fv * Cd = 216 PSI
fv. . = (3 * V max) / (2 * b * d)= 60.1 PSI, < Fv', therefore OK.
** Check Deflection **
Def. Max. = (Ww*(HD"3))/(24*E*Ix) * (4*TS1 + 3*HD) = 0.011 IN
Def. Allowable = 2*HD / 180 = 0.133 IN, > Def, therefore OK.
By: Ed Weber Roof Diaphragm Calc. Page: App. B: 5
Date: 10/8/2019 � Ranch at 160-C Ref: Sheet 13
- 104" Sidewall - 7116" APA rated sheathing roof decking - 28' Wide - 2.46/12 Roof
Wind Load (WZ): 22.90 psf
Wind Load at Roof Projection (WR): 0 psf
Wind Load at Corner (WZ1): 34.50 psf
Wind Load at Roof Projection at Corner (WR1): 0.00 psf
Sidewall Height (H): 104.00"
Kingpost Height (K): 43.00"
Max. Box Length (BL): 56'
Caic. Max. Diaphragm Shear:
W = ((H/2 x WZ) + (K x WR)) x l/144 = 8.269 pli, = 99.23333 plf
W1 = ((H/2 x WZ1) + (K x WR1)) x l/144 = 12.458 pii, = 149.6 plf
Vmax. _ [(W1 x 16) + (W x (13L-16))) x 112 = 3180.667 lbs.
Caic. Max. Shear on Roof Sheathing:
i
Specific gravity adjustment factor SGAF = 1 - (0.5 - SG) = 0.92
V1 = PP1 x SGAF x l/12 x UW x 2 = 8999.9 lbs.
Caic. Diaphragm Chord Tensions:
Wroof = (Vmax x 2) / BL =
113.6
pif
M1 = Wroof x BL^2 / 8 =
44529
ft.-lbs.
Ti (roof) = M1 / (UW/12 x 2) =
1468
lbs.
Top Plate: 243 SPF
2x6
Top plate depth (D):
3.00"
Top plate width (B):
5.50"
Ft:
250
psi
Duration Factor (Cd):
1.6
Size Factor (CO:
1.3
Check Roof Diaphragm Chord:
ft=T1/(BxD)= 89.0 psi
Roof Sheathing (PP1): 322.50
Unit Width (UW): 182.00"
Framing Specific gravity (SG): 0.42
F't = Ft x Cd x Cf = 520 psi > ft, therefore OK.
Check Top Plate Connectors:
Mitek M20-2x4 plates (2 plates top & bottom)
Plate Capacity = 1126p1i x (4" - 318") / 2 x 2 = 4081.8 lbs.
Lateral Capacity = 197psi x 2" x ((4 - 3/8")12) x 2 x 2 x 1.33 = 3799.1 lbs.
T roof 12 = 734 lbs. < of plate capacity, therefore OK.
* - As an alternative, top plate splice may also be fully glued & stapled.
plf
By: ELW • SKYLINE CORPORATION Page: App. B: 6
Date 10/08/19 '�� OPEN SPAN RIDGE BEAM ANALYSIS Ref. Sht. 13B
•Per APA Plywood.Design Specification - Supplement 5, Design and Fabrication of All -Plywood Beams (Page 1 of 1)
LOADING CONDITIONS: ROOF LIVE LOAD: - 20 " PSF UNIT WIDTH: 32' WIDE: 182 IN
ROOF DEAD LOAD: 15 PSF
TOTAL LOAD, TL: 35 PSF
(1). UNIFORM LOAD ON BEAM: W = TL * (WIDTH/2) * (1/144)
W (32' WIDE) = 22.118 PLI
(2). MATERIAL SPECIFICATIONS: 19132In. APA RATED SHEATHING
40120 SPAN RATING, 1/8" MINIMUM VENEER THICKNESS
5 LAYER, 5 PLY, MARKED PS-1 and STRUCr-1
1 FLANGE LAYER, 2 WEB LAYERS, SINGLE SPAN CONDITION
Tb = 0.347 IN Fb = 3300 PSI x 1.15 = 3795 PSI
Ts = 0.707 IN Fv = 225 PSI x 1.15 = 258.75 PSI
BEAM HEIGHT, Hw = 19.875 IN Fs:; 75, PSI x .5 x1.1 43.125 PSI
WEB HEIGHT, Hs = 19,875 IN E = 1800 KSI x 1.10 = 1980 KSI
FLANGE HGT., Hf = 5.5 IN (SHEAR DEFLECTION CONSIDERED SEPARATELY)
K = 1.367 G = 90 KSI (MAX. DEF. BASED ON U180)
Fc = 1540 PSI x 1.15 = 1771 PSI
(3), NET MOMENT OF INERTIA (In):
(a). Iws (WEB SPLICE PLATE) = (Tb*HsA3) / 12 = 227.023 INA4
(b). If (FLANGE) = Tb*[HwA3-(Hw-(2*Hf)A3)]/12 = 206.809 INA4
(c). In (NET) = Iws + If = 433.832 INA4
(4). DETERMINE MAX. SPAN BASED ON ALLOWABLE WEB -FLANGE BENDING STRESS:
L (MAX) = [(8*Fb*In)/(1N*C)]A.5
SPANS (MAX):
32' Wide = 244.793 IN Gbntrols
(5). TOTAL MOMENT OF INERTIA (It):
(a). Iw (WEB) = 2*Tb*HwA3 / 12 = 454.046 INA4
(6). STATICAL MOMENT OF AREA OF PARALLEL PLIES (Q):
(a). Qw (WEB) = 2*Tb*HwA2 / 8 = 34.2676 INA3
(C). TOTAL Q = Qw + Qf = 47.985 INA3
(7). MAX. SPAN BASED ON WEB SHEAR STRESS:
L (MAX) = (2*Fv*It*Ts)/(W*Q) + 2*Hw
32' Wide = 267,666 IN
(b). It (TOTAL) = Iw + If = 660.855 INA4
(b). Of (FLANGES) = Tb*(HW-Hf)*Hf / 13.717 INA3
(8). DETERMINE MAX. SPAN BASED ON ALLOWABLE WEB -FLANGE SHEAR STRESS:
L (MAX) = (2*FelrHf)/(Qf*W) + 2*Hf
32' Wide = 1044.263 IN
(9). DETERMINE MAX. ALLOWABLE SPAN BASED ON TOTAL OF BENDING AND SHEAR DEFLECTIONS:
(a). SHEAR DEFLECTION (K):
r = Ts/b = 0.666667
(Hw - 2*Hf) / Hw = 0.446541 ---> K = 1.367 (FROM APA SUPPLEMENT 5)
(b). EFFECTIVE SHEAR AREA:
As = Asw + Asf = Ts*HW + 'Ts*Hf = 35.880 INA2
(a). TOTAL SPAN = ALLOWABLE SPAN OF:((5*W*LA4)/(384*E*It))+((W*WLA2)/(8-As*G))<L/180
32' WIDE ====> '0.9395 IN < L1240 = 1.0200 IN OX
MAX. BEAM SPAN (SUMMARY):
32' Wide = 244.793 IN = 20' - 5"
(10). BEARING LENGTH REQUIRED (BEAM ONLY):
P = V = W*L/2 P (ALLOW.) = Fc*A = Fc*BI.1.78125 It BI = (W*Lu(2-WIDTH*Fc)
I
32' Wide = 0.987 IN
BY: ELW SKYLINE CORPORATION PAGE: App. B: 7
DATE: 11/12/12 CENTERLINE COLUMN CALCULATION REF: Sht. 12
Lumber: 243 SPF 2x4s
Roof Live Load, LL:
20 psf
Fc parallel: 625 psi
Roof Dead Load, DL:
15 psf
Fc perpendicular: 405 psi
Unit Width UW:
182 in
` MOE: 1200000 psi
Column Height CH:
126 in
B: 1.5 in
Comp Size Factor Cfc:
1.15
D: 7 in
Duration Factor Cd:
1.15
-
Ke:
1
Bearing Area Factor Cb:
1
** COLUMN PROPERTIES **
' Le / D = (CH/D) * Ke = 18.00
--less than 50 therefore, OK.
Fe = Fc parallel * Cd * Cfc = 827
psi
FcE = (0.3 * MOE) / (Le /D)^2 = 1111.1
psi
Cp=((1+(FcE/Fc*))/(2*0.8))-(((1+(FcE/Fc*))/(2*0.8))"2-((FcE/Fc*)/0.8)}^0.5=
0.782
** CHECK COMPRESSION **
Fc' = Fc parallel * Cd * Cfc * Cp = 646.57 psi
P allowable = Fc'* B * D = 6789 lbs.
Allowable Span = P*144 / (DL+LL)*UW = 153.47 in.
** CHECK BEARING ON COLUMN **
Ridge Beam Bearing on Column
Bearing Area (BA) = 1.875" * B * 2 = 5.625 in"2
P allowable = BA * Fc* * 0.75 = 3487.06 Ibs
Allowable Span = P*144 / (DL+LL)*UW = 78.83 in. <----- CONTROLS
** CHECK BEARING ON FLOOR **
Column Bearing on Perimeter Joist & block.
Bearing Area = 3" * B * 2 = 9 in^2
Fc' = Fc perpendicular * Cb = 405 psi
P allowable = Bearing Area * Fc' = 3645 Ibs.
Allowable Span = P*144 / (DL+LL)*UW = 82.40 in.
** ALLOWABLE SPANS **
Compression =
153.47 in
Bearing on Column =
78.83 in
Bearing on Floor =
82.40 in
Therefore, Max Span for Column = Allowable Span * 2 = 157.66 in
13.14 ft,
s
f
BY: ELW SKYLINE CORPORATION PAGE: App. B: 7.1
DATE: 11/12/12 CENTERLINE COLUMN CALCULATION REF: Sht. 12
Lumber: 44F3 5Pr ZX4S Koor Live Loaa, LL:
Fc parallel: 625 psi Roof Dead Load, DL:
Fc perpendicular. 405 psi Unit Width UW:
` MOE: 1200000 psi Column Height CH:
B: 3 in Comp Size Factor Cfc:
D: 7 in Duration Factor Cd:
Ke:
Bearing Area Factor Cb:
** COLUMN PROPERTIES **
Le / D = (CHID) * Ke = 18.00 -- less than 50 therefore, OK.
Fc* = Fc parallel *Cd *Cfc = 827 psi
FcE = (0.3 * MOE) / (Le /D)^2 = 1111.1 psi
Cp=((1+(FcE/Fc*))/(2*0.8))-(((1+(FcE/Fc*))/(2*0.8))"2-((FcE/Fc*)/0.8))"0.5= 0.782
** CHECK COMPRESSION **
Fc' = Fc parallel * Cd * Cfc * Cp = 646.47 psi
P allowable = Fc' * B * D = 13578 lbs.
Allowable Span = P*144 / (DL+LL)*UW = 306.94 in.
** CHECK BEARING ON COLUMN "*
Ridge Beam Bearing on Column
Bearing Area (BA) = 1.875" * B * 2 = 11.25 in"2
P allowable = BA * Fc* * 0.75 = 6974.12 Ibs
Allowable Span = P*144 / (DL+LL)*UW = 157.66 in. <---- CONTROLS
** CHECK BEARING ON FLOOR **
Column Bearing on Perimeter Joist & block.
Bearing Area = 3" * B * 2 = 18 in"2
Fc' = Fc perpendicular * Cb = 405 psi
P allowable = Bearing Area * Fc' = 7290 Ibs.
Allowable Span = P*144 / (DL+LL)*UW = 164.80 in.
** ALLOWABLE SPANS **
Compression =
306.94 in
Bearing on Column =
157.66 in
Bearing on Floor =
164.80 in
Therefore, Max Span for Column = Allowable Span * 2 = 315.31 in
26.28 ft.
20 psf
15 psf
182 in
126 in
1.15
1.15
1
1
IJ
BY: ELW SKYLINE CORPORATION
DATE:-11/12/12 CENTERLINE COLUMN CALCULATION
Lumber: 143 SPF 2x6 Roof Live Load, LL:
Fc parallel: 625 psi Roof Dead Load, DL:
Fc perpendicular: 405 psi Unit Width UW:
MOE: 1200000 psi Column Height CH:
B: 1.5 in Comp Size Factor Cfc:
D: 5.5 in Duration Factor Cd:
• Ke:
Bearing Area Factor Cb:
** COLUMN PROPERTIES **
Le / D = (CHID) * Ke = 22.91 -- less than 50 therefore, OK.
Fc* = Fc parallel * Cd * Cfc = 827 psi
FcE _ (0.3 * MOE) / (Le /D)^2 = 685.9 psi
Cp=((1+(FcE/Fc*))/(2*0.8))-(((1+(FCE/Fc*))/(2*0.8))"2-((FCE/Fc*)/0.8)}"0.5= 0.623
** CHECK COMPRESSION **
Fc' = Fc parallel * Cd * Cfc * Cp = 515.31 psi
P allowable = Fd * B * D = 4251 lbs.
Allowable Span = P*144 / (DL+LL)*UW = 96.11 in. <----- CONTROLS
** CHECK BEARING ON COLUMN **
Ridge Beam Bearing on Column
Bearing Area (BA) = 1.875" * D = 10.3125 in"2
P allowable = BA * Fc* * 0.75 = 6392.94 lbs
Allowable Span = P*144 / (DL+LL)*UW = 144.52 in.
** CHECK BEARING ON FLOOR **
Column Bearing on Perimeter Joist & block.
Bearing Area = 3" * D = 16.5 in"2
Fc' = Fc perpendicular * Cb = 405 psi
P allowable = Bearing Area * Fc' = 6682.5 lbs.
Allowable Span = P*144 / (DL+LL)*UW = 151.06 in.
** ALLOWABLE SPANS **
Compression =
96.11 in
Bearing on Column =
144.52 In
Bearing on Floor =
151.06 in
Therefore, Max Span for Column = Allowable Span * 2 = 192.21 in
16.02 ft.
r
PAGE: App. B: 7.2
REF: Sht. 12 c
f
20 psf
15 psf ,
182 in
126 in
1.15
1.15
1
r
..n...�:..,.-:..-T,-=.cam...,--.,_.�.:e:- _.,,___ •.::.:r____-'___� ..... ..__ .i... �s...... ..:....=r -�.._._.,'..a ... _.. AZ
C ` i
s ,
By: Ed Weber BMW Dormer Page: App. B: 8 I
Date: 10/20/2015 N&MIME Rafter Calc. Ref: Sheet 13E
' Rafter Span, RS:
137
in
Rafter Cantilever, RC:
7
in
. Roof live load, (LL):
20
psf
Roof dead load, (DL):
10
psf
Wind Uplift, WU:
53.3
psf
Wind Uplift @ Eave, WUe:
62,4
psf
SECTION PROPERTIES:
Sx = BxDA2 / 6 =
7.5625
in^3
Ix = BxD^3 / 12
20.79688
inA4
142 S. Pine 2x6
Rafter. 142 S. Pine 2x6
Fb:
1,000
psi
Fv:
135
psi
MOE
1400000
psi
B:
1.5
in
D:
5.5
in
Wind Duration Factor, Cw:
1.60
Roof Duration Factor, Cr.
1.15
Size Factor, Cf:
1
Repetitive Use Factor, Cr.
1.15.
Rb 137 max. Ra 7 max.
CHECK CANTILEVER:
Wind: Roof:
W1 = (WUe-DL) x 16"x 1/144 = 5.82 pli Wr= (LL+DL) x 16"x 1/144 = 3.33 pli
Mmax = W x RC^2 / 2 = 142.64 in. lbs. Mmax = W x RC^2 / 2 = 81.67 in. lbs.
V max. = W x RC = 40.76 lbs. V max. = W x RC = 23.33 'Ibs.
fb = Mmax. / Sx = 18.86 psi
F'b = Fb x Cw x Cf = 1600 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 7.41 psi
F'v = Fv x Cw = 216 psi, > fv, OK.
Def. = (WxRC^3) / (24xMOExlx) x (4RS + 3RC) =
Def. = 0.002 in.
Def. Allow. = 2xRc / 180 = 0.078 in., > Def., OK.
CHECK MAIN SPAN:
Wind:
W2 = (WU-DL) x 16"x 1/144 = 4.81 pli
Mmax = W x RS^2 / 8 = 11287.47 in. lbs.
V max. = W x RS / 2 = 329.56 lbs.
fb = Mmax. / Sx = 1492.56 psi
F'b = Fb x Cw x Cf = 1600 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 59.92 psi
F'v = Fv x Cw = 216 psi, > fv, OK.
Def. = (5xWxRS^4) / (384xMOExlx) =
Def. = 0.758 in.
Ref. Allow. = RS / 180 = 0.761 in., > Def., OK.
fb = Mmax. / Sx = 10.80 psi
F'b = Fb x Cw x Cf x Cr = 1322.50 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 4.24 psi
F'v = Fv x Cw = 155.25 psi, > fv, OK.
Def. = (WxRC^3) / (24xMOExlx) x (4RS + 3RC) _
Def. = 0.001 in.
Def. Allow. = 2xRc / 180 = 0.078 in., > Def., OK.
Roof:
Wr = (LL+DL) x 16"x 1/144 = 3.33 pli
Mmax = W x RS^2 / 8 = 7820.42 in. lbs.
V max. = W x RS / 2 = 228.33 lbs.
fb = Mmax. / Sx = 1034.10 psi
F'b = Fb x Cw x Cf x Cr = 1322.50 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 41.52 psi
F'v = Fv x Cw = 155.25 psi, > fv, OK.
Def. = (5xWxRS^4) / (384xMOExlx) =
Def. = 0.525 in.
Def. Allow. = RS 1180 = 0.761 in., > Def., OK.
CHECK RAFTER TO DORMER WALL CONNECTION:
W' = (WU-DL)xRS42/2 + (WUe-DL)xRCx(RS+(RC/2)) / (RSx144) 23.21 pli
Ra = W' x 16" = 371.36 lbs.
Capacity of Simpson H2.5T Tie w/ 5-8dxl-1/2" nails plus 2-48x3-1/2" screws = 941.9 lbs., therefore OK.
CHECK RAFTER TO TRUSS CONNECTION:
Rb = (W1xRC)+(W2xRS) - Ra = 328.52 lbs.
Capacity of#8x3-1/2" screw (toe -screwed) = 821b/in x 1.6 x 1.575" = 206.6 lbs.
Rb / screw capacity = 1.6 screws, therefore 2-#8x3-1/2" screws (toe -screwed) OK.
c
By: Ed Weber ,
Date:10/20/2015
Dormer -
Rafter Calc.
Page: App. B: 8.
Ref: Sheet 13E
• Rafter Span, RS:
Rafter Cantilever, RC:
Roof live load, (LL):
Roof dead load, (DL):
Wind Uplift, WU:
Wind Uplift @ Eave, WUe:
172 in
7 in
20 psf
10 psf
53.3 psf
62.4 psf
SECTION PROPERTIES:
Sx = BxD^2 / 6 = 15.125 inA3
Ix = BxD^3 / 12 41.59375 inA4
242 S. Pine 2x6
Rb 1 172 max.
CHECK CANTILEVER:
Wind:
WI = (WUe-DL) x 16"x 11144 = 5.82 pli
Mmax = W x RCA / 2 = 142.64 in. lbs.
V max. = W x RC = 40.76 lbs.
fb = Mmax. / Sx = 9.43 psi
F'b = Fb x Cw x Cf = 1600 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 3.71 psi
F'v = Fv x Cw = 216 psi, > fv, OK.
Def. = (WxRC^3) / (24xMOExlx) x (4RS + 3RC) =
Def. = 0.001 in.
Def. Allow. = 2xRc / 180 = 0.078 in., > Def., OK.
CHECK MAIN SPAN:
Wind:
W2 = (WU-DL) x 16"x 1/144 = 4.81 pli
Mmax = W x RS^2 / 8 = 17791.49 in. lbs.
V max. = W x RS / 2 = 413.76 lbs.
fb = Mmax. / Sx = 1176.30 psi
F'b = Fb x Cw x Cf = 1600 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 37.61 psi
F'v = Fv x Cw = 216 psi, > fv, OK.
Def. = (5xWxRS^4) / (384xMOExlx) =
Def. = 0.942 in.
Def. Allow. = RS / 180 = 0.956 in., > Def., OK.
Rafter: 242 S. Pine 2x6
Fb:
1,000
psi
Fv:
135
psi
MOE
1400000
psi
B:
3
in
D:
5.5
in
Wind Duration Factor, Cw:
1.60
Roof Duration Factor, Cr:
1.15
Size Factor, Cf:
1
Repetitive Use Factor, Cr:
1.15
Ra
7 max.
Roof:
Wr= (LL+DL) x 16"x 1/144 = 3.33 pli
Mmax = W x RC^2 / 2 = 81.67 in. lbs.
V max. = W x RC = 23.33 lbs.
fb = Mmax. / Sx = 5.40 psi
F'b = Fb x Cw x Cf x Cr = 1322.50 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 2.12 psi
F'v = Fv x Cw = 155.25 psi, > fv, OK.
Def. = (WxRC^3) / (24xMOExlx) x (4RS + 3RC) _
Def. = 0.001 in.
Def. Allow. = 2xRc / 180 = 0.078 in., > Def., OK.
Roof:
Wr= (LL+DL) x 16"x 1/144 = 3.33 pli
Mmax = W x RS^2 / 8 = 12326.67 in. lbs.
V max. = W x RS / 2 = 286.67 lbs.
fb = Mmax. / Sx = 814.99 psi
F'b = Fb x Cw x Cf x Cr = 1322.50 psi, > fb, OK.
fv = 3xVmax / 2xBxD = 26.06 psi
F'v = Fv x Cw = 155.25 psi, > fv, OK.
1
Def. = (5xWxRS^4) / (384xMOExlx) _
Def. = 0.652 in.
Def. Allow. = RS / 180 = 0.956 in., > Def., OK.
CHECK RAFTER TO DORMER WALL CONNECTION:
W' = (W U-DL)xRS^2/2 + (WUe-DL)xRCx(RS+(RC/2)) / (RSx144) = 28.46 pli
Ra = W' x 16" = 455.34 lbs.
Capacity of Simpson H2.5T Tie w/ 5-8dx1-1/2" nails plus 2-#8x3-1/2" screws = 941.9 lbs., therefore OK.
CHECK RAFTER TO TRUSS CONNECTION:
Rb = (W 1 xRC)+(W2xRS) - Ra = 412.93 lbs.
Capacity of #8x3-1/2" screw (toe -screwed) = 82lb/in x 1.6 x 1.575" = 206.6 lbs.
Rb / screw capacity = 2.0 screws, therefore 2-#8x3-1/2" screws (toe -screwed) OK.
a
By: Ed Weber ■EN Truss reinforcement Page: App. B:9
Date: 11/20/2015 $nil for Cantilever Ref: Sheet 12B
Plate Truss with APA rated plywoodto increase allowable cantilever.
Plywood Specifications: See APA Supplement 5, Design and Fabrication of all Plywood Beams.
Plywood: 5/8" APA rated 40/20 span - Struct-1
_ Height (H) = 6 in MOE = 1800000 psi
tb = 0.347 in Fb = - 2800 psi
is = 0.707 in Fv = 190 psi
Roof Duration Factor, Cdr = 1.15
Wind Duration Factor, Cdw = 1.6
Sx = tb x H12 / 6 = 2.0820 in^3
Ix = tb x (H13) /12 = 6.2460 in44
Roof Loadina:
20 psf Roof Load w/24" o.c. trusses
W = (20+15) x 24" x 1/144 =
5.833
pli
a = 7" truss overhang + 16" wall recess =
23
in
L = unit width - 16" recess = 182 - 16 =
166
in
M = W x aA2 / 2 =
1542.9
in.-lbs.
V=Wxa=
134.2
lbs.
fb = M/Sx =
741.1
psi
F'b' = Fb x Cdr =
3220
psi, > fb, therefore OK.
fv=(3xV)/(2xisxH)=
47.4
psi
F'v = Fv x Cdr =
218.5
psi, > fv, therefore OK.
Def. = (Wxa^3) x (4L + 3a) / (24 x
MOE x Ix) =- 0.193 in
Def. allowable = 2 x a / 180 = 0.256 in
62.4 psf Wind Uplift Load w/24" o.c. trusses
W = (62.4) x 24" x 1/144 =
10.400
pli
a = 7" truss overhang + 16" wall recess =
23
in
L = unit width - 16' recess = 182 - 16 =
166
in
M = W x aA2 / 2 =
2750.8
in.-lbs.
V =Wxa =
239.2
lbs.
fb = M/Sx =
1321.2
psi
F'b = Fb x Cdw =
4480
osi. > fb. therefore OK.
fv=(3xV)/(2xisxH)= 84.6 psi
F'v = Fv x Cdw = 304 psi, > fv, therefore OK.
Def. = (W x a"3) x (41- + 3a) / (24 x MOE x Ix) 0.344 in
Def. allowable = 2 x a / 180 = 0.256 in