HomeMy WebLinkAboutProject Information I �Summary Job: -�- w,�-ightsoft° Project Date: Jul 27,2017 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS AOL.COM _-Proiect Information For. BOLLER RESIDENCE, PARADISE HOMES YUCCA DRIVE, FORT PIERCE, FL Notes: Desi• n Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 °F Outside db 90 °F Inside db 70 °F Inside db 75 °F Design TD 28 of Design TD 15 °F Daily range M Relative humidity 50 % Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 26769 Btuh Structure 18614 Btuh Ducts 5825 Btuh Ducts 8336 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 32594 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 25603 Btuh Method Simplified Latent Cooling Equipment Load Sizing' Construction quality Average Fireplaces 0 Structure 3939 Btuh Ducts 2237 Btuh Heating Cool ingg Central vent(0 cfm) 0 Btuh Area(ft') 1885 1885 Equipment latent load 6176 Btuh Volume(ft') 21104 21104 Air changes/hour 0.38 0.20 Equipment total load 31779 Btuh Equiv.AVF (cfm) 134 70 Req. total capacity at 0.70 SHR 3.0 ton Heating Equipment Summary Cooling Equipment Summary Make Make Carrier Trade Trade CARRIER AIR CONDITIONING Model Cond CA16NW0360000A AHRI ref Coil FX4DNF037L AHRI ref 7693195 Efficiency 100 EFF Efficiency 13.5 EER, 16 SEER Heating input 9.3 kW Sensible cooling 24780 Btuh Heating output 31618 Btuh Latent cooling 10620 Btuh Temperature rise 24 °F Total cooling 35400 Btuh Actual air flow 1180 cfm Actual air flow 1180 cfm Air flow factor 0.036 cfm/Btuh Air flow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2& Space thermostat Load sensible heat ratio 0.81 File Copy 1. Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -�- wrightsoftm 2017-Jul-27 12:16:30 'Right-Suite®Universal 2017 17.0.08 RSU08101 Pagel �'p` E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S -A1-wrightsoft Right-J®Worksheet Job: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name Entire House MASTER SUITE 2 Exposed wall 192.3 ft 51.2 ft 3 Room height 11.2 ft 9.4 ft heat/cool 4 Room dimensions 1.0 x 322.0 ft 5 Room area 1885.0 ft2 322.0 ft2 Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft?°F) (Btu 2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool + 6 13A4ocs 0.143 ri 4.00 2.19 638 405 1622 867 141 111 444 243 2 glazing,cir low-e 0.650 n 18.20 14.99 9 0 164 135 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 60 0 1092 899 30 0 546 450 2 glazing,clr low-e 0.650 n 18.20 14.99 64 0 1165 959 . 0 0 0 0 11 W 13A-4ocs 0.143 _ne 4.00 219 40 40 160 87 40 40 160 _ 87 yJ 13A-4ocs 0.143 a 4.00 Z19 347 269 1076 588 122 74 297 162 LI-�G 2 glazing,cir low-e 0.650 a 18.20 32.42 30 4 546 973 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.93 48 4 874 1581 48 2 874 1581 y/ 13A-4ocs 0.143 s 4.00 2.19 430 316 1264 691 0 0 0 0 IFL-�Gp 2 glazing,clr low-e 0.650 s 18.20 14.99 6 12 109 90 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 60 120 1092 899 0 0 0 0 11GO 0.540 s 15.12 14.31 48 48 726 687 0 0 0 0 13A-4ocs 0.143 w 4.00 219 633 573 2296 1255 179 159 635 347 2 glazing,clr low-e 0.650 w 18.20 30.39 4 1 73 122 0 0 0 0. 2 glazing,cir low-e 0.650 w 18.20 30.39 6 2 109 182 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 3242 20 3 364 648 20 1 364 648 2 glazing,cir low-e 0.650 w 18.20 32.42 30 4 546 973 0 0 0 0 13A-4ocs 0.143 nw 4.00 219 59 49 198 108 0 0 0 0 2 glazinq,clr low-e 0.650 nw 18.20 26.88 10 0 182 269 0 0 0 0 C 16A-30md 0.032 0.90. 2.24 1885 1885 1689 4222 322 322 _289 721 F 22A-tph 1.358 38.02 0.00 1885 192 7310 0 322 51 1946 0 i i 6 c)AED excursion 0 -86 Envelope loss/gain 22656 16254 5554 4153 12 a) Infiltration 4113 1160 968 273 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1200 0 Subtotal(lines 6 to 13) 26769 18614 6522 4426 Less extemal load 0 0 0 0 Less transfer 1 0 0 0 0 Redistribution 0 0 9 23 14 Subtotal 26769 18614 6531 4449 15 Duct loads 22% 45% 5825 8336 22% 45% 1421 1992 Total room load 32594 26950 7952 6442 Air required(cfm) 1180 11801 1288 282 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. � A wright9oft" 2017-Jul-27 1 Right-Suite®Universal 2017 17.0.08 RSU08101 Pagel E:1Documnets\Wrightsoft HVACIBOLLER RESIDENCE.rup Cale=MJ8 Front Door faces: S -t1-wrightsoft' Right-J®Worksheet Job: Entire House Date: Jul 27,2017 By: • QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772.466-6799 Fax:772-466-6796 Email:QUICKCALCS AOL.COM 1 Room name M WIC M W IC 2 2 Exposed wall 7.0 ft 0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 8.0 x 7.0 ft 3.0 x 7.0 ft 5 Room area 56.0 ft' 21.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft2 7) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 2 glazi g, 0.650 n 4.20 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 W 13A-4ocs 0.143 ne_ 4.00 2.19 0 0 0 0 0 0 0 0 1 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 11----GG 2 glazing,cir low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 ti 2 glazing,clr low-e 0.650 a 18.20 3293 0 0 0 0 0 0 0 0 13Aaocs 0. s 4. .19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650650 s 18.2020 144.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 1100 0.540 s 15.12 14.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 66 66 263 144 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 3242 0 0 0 0 0 0 0 0 2 glazing,.clr low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 2 glazinq,cir low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 56 56 50 125 21 21 19 47 F 22A-tph 1.358 38.02 0.00 56 7 266 0 21 0 0 0 i l 6 c)AED excursion -6 -1 Envelope loss/gain 580 264 19 46 12 a) infiltration 132 37 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 712 301 19 46 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 -19 -46 14 Subtotal 712 301 0 0 1151 Duct loads 122% 45% 155 135 22% 45% 0 0 Total room load 867 436 0 0 Air required(cfm) 1 31 19 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .4CCP.� wrightsoft- Right-Suite®Universal 2017 17.0.08 RSU08101 2017-Jul-27 1:11630 E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S 9e -�-wrightsoft• Right-J®Worksheet Job: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name M TOILET MASTER BATH 2 Exposed wall 3.0 ft 7.0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 8.0 x 3.0 ft 1.0 x 126.0 ft 5 Room area 24.0 ft2 126.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft'°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool . 6 V)! 13A4ocs 6.143 n 4.00 2.19 0 0 0 0 0 0 0 0 L��-(GG 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clrlow-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2glazing,cir low-e0.650 h 18.20- 14.99 0 0 0 0 0 0 0 0 11 W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0 0 0 0 0 V�1 13A-4ocs 0.143 e 4.00 2.19 0 0 0 0 0 0 0 0 �G 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 I--( 2 glazing,cir low-e 0.650 a 18.20 3293 0 0 0 0 0 0 0 0 V 2 glazing, 0.650 s 4.20 4.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 11GO 0.540 s 15.12 14.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 28 24 97 53 66 60 239 131 2 glazing,clr low-e 0.650 w 18.20 30.39 4 1 73 122 0 0 0 0 2 glazing,clrlow-e 0.650 w 18.20 30.39 0 0 0 0 6 1 109 182 2 glazing,cir low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 V)/ 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 I--G 2 glazinq,cir low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 .- 0.9.0, 2.24 24 24 22 54 126 126 113 282 F 22A-tph 1.358 - 38.02 0.00 24 3 114 0 126 7 266 0 i 6 c)AED excursion 60 85 Envelope loss/gain 305 288 728 680 12 a) Infiltration 57 16 132 37 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 362 304 860 717 Less external load 0 0 0 0 Less transfer , 0 0 0 0 Redistribution j 0 0 3 7 14 Subtotal 362 304 863 724 1151 Duct loads 122% 45% 79 136 22% 45% 188 324 Total room load 441 440 1050 1049 Air required(cfm) 16 19 38 46 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. WrightsOft- Ri ht-Suite®Universal 2017 17.0.08 RSU08101 2017-Jul-27 12:16:30 ACCA 9 Page 3 E:1Documnets\Wrightsoft HVACIBOLLER RESIDENCE.rup Calc=MJS Front Door faces: S -�-wrightsoft° Right-JO Worksheet Job: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name BEDROOM 2 CLST 2 2 Exposed wall 28.0 ft 5.0 ft 3 Room height 9.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 1.0 x 195.5 ft 1.0 x 16.0 ft 5 Room area 195.5 ft' 16.0 ft' Ty Construction U-value Or HTM Area (ft') Load Area (ft') Load number (Btuh/ft'°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) • Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 '[-�G 13A-4ocs 0.143 n 4.00 1219 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing;clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing:clrlow-e 0.650 n 18.20:. 14.99 0 0 0 0 0 -- 0 ... 0 0 11 W 13A-4ocs _ 0.143 ne 4.00 219 0 0 0 0 0 0 0 0 13A-4ocs 0.143 e 4.00 219 0 . 0 0 0 28 28 113 62 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20. 32.93 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 150 120 482 263 19 19 75 41 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 30 30 546 450 0 0 0 0 1100 0.540 s 15.12 14.31 0 0 0 0 0 0 0 0 13A flocs 0.143 w 4.00 219 113 98 392 214 0 0 0 0 2glazing,clrlow-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2glazing,clrlow-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clrlow-e 0.650 w 18.20 32.42 0 0 0 0 0 0 . 0 0 2-glazing,clrlow-e 0.650 w 18.20 32.42 15 1 273 486 0 0 0 0 V)/ 13A-4ocs 0.143 nw 4.00 2-19 0 0 0 0 0 0 0 0 __0 2 glazinq,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 196 196 175 438 _ 16 16 14 36 F 22A-tph 1.358 38.02 0.00 196 28 1665 0 16 5 190 0 I - I I 6 c)AED excursion 118 -3 Envelope loss/gain 2933 1969 393 136 12 a) Infiltration 529 149 94 27 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 3461 2118 487 162 Less extemal load 0 0 0 0 Less transfer 0 0 0 1 0 Redistribution 302 101 -487 -162 14 Subtotal T 3764 2219 0 0 1151 Duct loads 22% 45% 819 994 22% 45% 01 0 Total room load 4583 3213 0 0 Air required(cfm) 166 141 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ACCA Wrigtft9oit` 2017-Jul-27 1 Right-Suite®Universal 2017 17.0.08 RSU08101 Page ae 4 E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S 9 i ' I AL rF wrightsoft Right-J®Worksheet Date: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@J\OL.COM 1 Room name FOYER CLST 3 2 Exposed wall 8.0 ft 5.0 ft 3 Room height 11.4 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 8.0 x 6.0 ft 1.0 x 16.0 ft 5 Room area 48.0 ft2 16.0 ft2 Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/ft?'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0. 0 n 4. 4.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.65650 n 18.220 0 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 6 0 0 0 0 0 0 0 11 W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0 0 0 0 0 13A-4ocs 0.143 e 4.00 219 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 T� 2 glazing,clr low-e 0.650 a 18.20 32.93 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 91 37 149 81 19 19 75 41 2 glazing,clr low-e 0.650 s 18.20 14.99 6 6 109 90 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 11GO 0.540 s 15.12 14.31 48 48 726 687 0 0 0 0 13A-4ocs 0.143 w 4.00 219 0 0 0 0 28 28 113 62 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 V)/ 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 -G 2 glazinq,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 - 0.90 2.24 48 48 43 108 16 16 14 36 F 22A-tph 1.358 38.02 0.00 48 8 304 0 16 5 190 0 i i 6 c)AED excursion -19 -3 Envelope loss/gain 1331 946 393 136 12 a) Infiltration 183 52 94 27 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal(lines 6 to 13) 1514 998 487 162 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 369 123 -487 -162 14 Subtotal 1884 1121 0 0 15 Duct loads 22% 45% 410 502 22% 45% 0 0 Total room load 2293 1623 0 0 Air required(cfm) 83 71 1 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. AC CA WrigF7t8o4ta 2017-Jul-27 1 Right-Suite@ Universal 2017 17.0.08 RSU08101 Page 5 E:\Documnets\WrightsoftHVAC\BOLLERRESIDENCE.rup Calc=MJ8 Front Door faces: S -�-wrightsoft Right-J®Worksheet Job: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS AOL.COM 1 Room name BEDROOM 3 GREAT ROOM 2 Exposed wall 22.0 ft 9.9 ft 3 Room height 9.4 It heat/cool 14.0 ft heat/cool 4 Room dimensions 1.0 x 195.5 ft 1.0 x 348.5 ft 5 Room area 195.5 ft2 348.5 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft?°F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 V+l 13A-4ocs 0.143 n 4.00 2.10 0 0 0 0 140 76 304 166 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clrlow-e 0.650 n 18.20 14.99 0 0 0 0 64 0 .1165 959 11 W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0 0 0 0 0 V+J 13A-4ocs 0.143 e 4.00 219 56 41 166 91 0 0 0 - 0 ECG 2 glazing,clr low-e 0.650 a 18.20 32.42 15 1 273 486 0 0 0 0 2 glazing,clr low-e 0.650 a 18.20 32.93 0 0 0 0 0 0 0 0 13A-4ocs 0.143 s 4.00 2.19 150 120 482 263 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 s 18.20 14.99 30 30 546 450 0 0 0 0 11GO 0.540 s. 15.12 14.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 219 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 3242 0 0 0 0 0 0 - 0 0 2 glazing,clr low-e 0.650 w. 18.20 32.42 0 .0 0 0 0 0 0 0 W 13A-4ocs 0.143 nw 4.00 2.19 0 0 0 0 0 0 0 0 T-G 2 glazinq,clr low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 196 196 175 438 349 349 312 781 F 22A-tph 1.358 38.02 0.00 196 22 837 0 349 10 377 0 i • i I 6 c)AED excursion -35 -38 Envelope loss/gain 2479 1693 2158 1868 12 a) Infiltration 415 117 281 79 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 10 Subtotal(lines 6 to 13) 2894 1810 2440 1948 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 302 101 7 16 14 Subtotal 3196 1911 2446 1964 15 Duct loads 1 122% 45% 696 856 22% 45% 532 879 Total room load 3892 2766 2979 2843 Air required(cfm) 141 121 108 124 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrightsoft' 2017-Jul-27 12:16:30 .4CCP. Right-Suite®Universal 2017 17.0.08 RSU08101 Page 6 E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S I I -i r wrightsoft Right-l® Worksheet Date: Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax:772-466-6796 Email:QUICKCALCS@\OL.COM 1 Room name HALL BATH KITCHEN 2 Exposed wall O ft O ft 3 Room height 9.4 ft heat/cool 14.0 ft heat/cool 4 Room dimensions 13.0 x 6.0 ft 13.0 x 14.0 ft 5 Room area 78.0 ft' 182.0.ftz Ty Construction U-value Or HTM Area (ft') Load Area (ft2) Load number (Btuh/ft'°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A-4ocs 0.143 n 4.00 2.19 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 W 13A-4ocs 0.143 ne 4.00 219 0 0 0 0 0 0 0 0 V(J 13A-4ocs 0.143 e 4.00 219 0 0 0 0 0 0 0 0 t�---GG 2 glazing,clr low-e 0.650 a 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 a 18.2.0 3293 0 0 0 0 0 0 0 0 V�! 13A-4ocs 0. s 4. .19 0 0 0 0 0 0 0 0 !L�-0CG 2 glazing,clr low-e 0.650650 s 18.2020 144.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 11G0 0.540 s 15.12 14.31 0 0 0 0 0 0 0 0 13AAocs 0.143 w 4.00 219 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr'low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.42 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20. 32.42 0 0 0 0 0 0 0 0 W 13A-4ocs 0.143 nw 4.00 219 0 0 0 0 0 0 0 0 t---G 2 giazinq,cir low-e 0.650 nw 18.20 26.88 0 0 0 0 0 0 0 0 C 16A-30md 0.032 0.90 2.24 _ .. 78 78 70 175 182 182 163 408 F 22A-tph 1.358 38.02 0.00 78 0 0 0 182 0 0 0 6 c)AED excursion -3 -31 Envelope loss/gain 70 171 163 377 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 1200 Subtotal(lines 6 to 13) 70 171 163 1577 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 70 171 163 1577 15 Duct loads 22% 45% 15 77 22% 45% 35 706 Total room load T 185 248 F199 2283 Air required(cfm) 3 11 7 100 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. . F.-Fk wrigF7tSOft" Right-Suite®Universal 2017 17.0.08 RSU08101 2017-Jul-27 12P.1age0 E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S 9 - 1-wrightsoW Right-J®Worksheet Job: • Entire House Date: Jul 27,2017 By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM 1 Room name DINING LAUNDRY 2 Exposed wall 38.2 ft 8.0 ft 3 Room height .14.0 ft heat/cool 9.4 ft heat/cool 4 Room dimensions 1.0 x 184.5 ft 8.0 x 9.0 ft 5 Room area 184.5 ftz 72.0 ft2 Ty Construction U-value Or HTM Area (f?) Load Area (ft-) Load number (Btuhfft'°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Vh13A-4ocs 0.143 n 4.00 2.19 182 152 609 333 75 66 265 145 2 glazing,clr low-e 0.650 n 18.20 14.99 0 0 0 0 9 0 164 135 2 glazing,clr low-e 0.650 n .18.20. 14.99 30 0 546 450 0 0 0 0 2 glazing,cir low-e 0.650 n 18.20 14.99 0 0 0 0 0 0 0 0 11 W 13A-4ocs 0.143 ne 4.00 2.19 0 0 0 0 0 0 0 0 VIJ 13A-4ocs 0.143 e 4.00 219 140 125 501 273 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.42 15 1 273 486 0 0 0 0 2 glazing,cir low-e 0.650 a 18.20 32.93 0 0 0 0 0 0 0 0 13A-4ocs 0. s 4. 2.19 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650650 s 18.2020 14.99 0 0 0 0 0 0 0 0 2 glazing,cir low-e 0.650 s 18.20 14.99 0 0 0 0 0 0 0 0 11G0 0.540 s 15.12 _ 14.31 0 0 0 0 0 0 0 0 13A-4ocs 0.143 w 4.00 2.19 154 139 557 304 0 0 0 0 2 glazing,cir low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 30.39 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 3242 0 0 0 0 0 0 0 0 2 glazing,clr low-e 0.650 w 18.20 32.42 15 1 273 486 0 0 0 0 V�/ 13A-4ocs 0.143 nw 4.00 2.19 59 49 198 108 0 0 0 0 O 2 glazinq,cir low-e 0.650 nw 18.20 26.88 10 0 182 269 0 0 0 0 C 16A-30md 0.032 0.90 ... 2.24 185 185 -165 413 72 72 _65 161 F 22A-tph 1.358 38.02 0.00 185 38 1451 0 72 8 304 0 I 6 c)AED excursion -27 79 Envelope loss/gain 4754 3096 798 432 12 a) Infiltration 1076 303 151 43 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 10 Appliances/other 0 0 Subtotal(lines 6 to 13) 5830 3399 949 474 Less external load i 0 0 0 0 Less transfer 0 0 0 1 0 Redistribution 0 0 0 0 14 Subtotal 5830 3399 949 474 15 Duct loads 22% 45% 1269 1522 22% 45% 206 212 Total room load 7098 4921 1155 687 Air required(cfm) 257 215 42 30 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. ACA WrigFltSOft` 2017-Jul-27 1 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 8 E:\Documnets\Wrightsoft HVAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S Ductstem Summary Job: -�- ws'ightsoft System � Date: Jul 27,2017 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE,FORT PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM i Project Information' For: BOLLER RESIDENCE, PARADISE HOMES YUCCA DRIVE, FORT PIERCE, FL Heating Cooling External static pressure. 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply/return available pressure 0.500/0.500 in H2O 0.500/0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 1180 cfm 1180 cfm Total effective length(TEL) 197 ft SupplyDetail Table I I Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv Name (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk' BEDROOM 2 h 4583 166 141 1.000 7.0 Ox0 VIFx 58.1 135.0 st3 BEDROOM 3 h 3892 141 121 1.000 7.0 Ox 0 VIFx 29.7 115.0 st1 DINING h 3549 128 108 1.000 7.0 Ox0 VIFx 15.1 115.0 st2 DINING-A h 3549 128 108 1.000 7.0 Ox0 VIFx 19.9 115.0 st2 FOYER h 2293 83 71 1.000 6.0 Ox0 VIFx 43.5 115.0 st1 GREAT ROOM C 2843 108 124 1.000 7.0 Ox 0 VIFx 62.4 135.0 st3 HALL BATH c 248 3 11 1.000 4.0 Ox 0 VIFx 27.0 115.0 st1 KITCHEN C 2283 7 100 1.000 7.0 Ox 0 VIFx 31.5 115.0 st1 LAUNDRY h 1155 42 30 1.000 5.0 Ox0 VIFx 11.3 115.0 st2 M TOILET C 440 16 19 1.000 4.0 Ox 0 VIFx 62.5 135.0 st3 M WIC h 867 31 19 1.000 4.0 Ox0 VIFx 49.6 135.0 St4 MASTER BATH C 1049 38 46 1.000 5.0 Ox 0 VIFx 58.9 135.0 st3 MASTER SUITE h 3976 144 141 1.000 8.0 Ox 0 VIFx 55.4 135.0 st4 MASTER SUITE-A h 3976 144 141 1.000 8.0 Ox 0 VIFx 47.7 135.0 st4 I Supply TrunkDetailTable Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (Cfm) (cfm) FR (fpm) (in) (in) Material Trunk st4 Peak AVF 319 301 1.000 723 9.0 0 x 0 VinlFlx st2 st3 Peak AVF 328 330 1.000 501 11.0 0 x 0 VinlFlx st1 st1 Peak AVF 562 633 1.000 592 14.0 0 x 0 VinlFlx st2 Peak AVF 618 547 1.000 787 12.0 0 x 0 VinlFlx C wri htsoft' 2017-Jul-2712:16:31 9 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 1 EADocumnetslwrightsoft WACIBOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S i TableReturn Branch Detail Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size(in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk rb1 Ox 0 1180 1180 0 0 0 0 Ox 0 VIFx I i I I j �I i i C wri htsoft' 2017-Jul-2712:16:31 ^� 9 Right-Suite®Universal 2017 17.0.08 RSU08101 Page 2 '� E:\Documnets\Wrightsoft WAC\BOLLER RESIDENCE.rup Calc=MJ8 Front Door faces: S