HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 19 Block 5 Waterston... -- wrightsoft! Date: Ent/re House By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project For: ADAMS HOMES 5373 San Benedetto Place, Fort Pierce, FL 34951 Cooling Equipment Design Conditions design DB: 90.4 OF Sensible gain: 20509 Btuh Outdoor design WB: 77.4 OF Latent gain: 3648 Btuh Indoor design DB: 75.0 OF Total gain: 24157 Btuh Indoor RH: 50% Estimated airflow: 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Sensible capacity: 21358 Btuh 104% of load Latent capacity: 5637 Btuh 155% of load Total capacity: 26995 Btuh 112%of load SHR: 79% Heating Equipment Design Conditions design DB: 41.0 OF Heat loss: 22776 Btuh Indoor design DB: 70.0 OF Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Output capacity: 26672 Btuh 117% of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 5.9 kW 89%ofload Temp. rise: 19 OF Meets all requirements ofACCA Manual S. Entering coil DB: 76.4°F Entering coil W B: 63.2 cF Entering coil DB: 69.5°F Capacity balance: 36 OF Economic balance: -99 OF At. * wrightsoft- 2021-Jarr1412:18:16 ...... — Right-Sprite®Uruversal202121.0.02RSU23828 Pagel aterstone1512AGL\LotlgBlk5Waterstonel512AGL.rp Calc=MJ8 Hoisefaces:S Component Constructions Job: Lot 19 Block 5 Waterston... wrightsoft® Date: Entire House By: FLETCH DEL -AIR .HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax: 407-333-3853 Web: W W W.DEL-AIR.COM • • • For: ADAMS HOMES 5373 San Benedetto Place, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF) 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (OF) - 15 (L ) Method Simplified Wet bulb (OF) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft� Btuh/ftz F ftz`F/Btuh BtuhW Btuh Bluh/ft� Btuh Walls Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1/2" gypsum board int fnsh Partitions 12C-Osw. Frm wall, 1/2" gyp.bd ext, r-13 cav ins, 1/2" gypsum board int fnsh, 2'SK4" wood frm, 16" o.c. stud n 267 0.201 4.1 5.83 1555 4.06 1083 e 434 0.201 4.1 5.83 2529 4.06 1762 se 8 0.201 4.1 5.83 46 4.06 32 s 112 0.201 4.1 5.83 650 4.06 453 sw 8 0.201 4.1 5.83 46 4.06 32 w 323 0.201 4.1 5.83 1884 4.06 1313 all 1151 0.201 4.1 5.83 6711 4.06 4675 278 0.091 13.0 2.64 734 1.31 364 Windows 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n 30 thk; NFRC rated'(SHGC=0.23); 50% drapes, medium; 8.33 ft overhang (5 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n 23 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.25 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n 33 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 0.83 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang " (3.17 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (5.3 ft window ht, 1 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1.3 ft overhang (5 ft window ht, 1 ft sep.); 6.67 ft head ht e 10 0.330 0 0.330 0 0.330 0 0.330 0 9.57 287 8.52 9.57 222 8.52 9.57 313 8.52 9.57 93 22.8 256 198 279 223 e 16 0.330 0 9.57 156 23.0 376 se 10 0.330 0 9.57 96 15.0 150 s 15 0.330 0 9.57 144 8.22 123 sw 10 0.330 0 9.57 96 15.0 150 all 35 0.330 0 9.57 335 12.1 423 Wrightsci t- 2021-Jarr1412:18:16 ate* �• �. •�• -.,� •m Right-Slrite® Uriversal 2021 21.0.02 RSU23828 Page 1 aterstone1512AGL1Lot19BIk5Waterstore1512AGL.rLp Calc=MJ8 Hosefaoes: S 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1 /8" s 3 0.330 0 9.57 29 9.72 29 thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 7.33 ft overhang (1 ft window ht, 0.75 ft sep.); 6.67 ft head ht 10C-v: 2 glazing, clr low a outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" w 18 0.550 0 16.0 285 16.2 289 thk; NFRC rated (SHGC=0.70); 13 ft overhang (6.7 ft window ht, 1.3 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr outr, air gas, vnl frm mat, clr low a innr, 1/4" gap, 1 /8" w 7 0.330 0 9.57 66 22.1 151 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.3 ft overhang (3.17 ft window ht, 0.83 ft sep.); 6.67 ft head ht F Doors 11JO: Door, mtl fbrgl type s 20 0.600 6.3 17.4 350 17.6 353 11 DO: Door, wrl sc type n 18 0.390 0 11.3 202 11.4 204 Ceilings 166-30ad: Attic ceiling, asphalt shingles roof mat, r-30 cell ins, 1 /2" 1580 0.032 30.0 0.93 1467 1.69 2670 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 192 0.989 0 28.7 5519 0 0 ti � Wrightsoft- 2021-Jan-1412:18:16 JCCA •�" • •N• Right-SUte®Uriversal202121.0.02RSU23828 Paget aterstone1512AGL\Lot19Blk5Waterstone1512AGL.np Calc=MJ8 Hosefaces: S Project Summary Job: Lot 19 Block 5 Waterston... wrightsoft® o Entire House Date: By: FLETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIRCOM Project • • For: ADAMS HOMES 5373 San Benedetto Place, Fort Pierce, FL 34951 Notes: RVSD 8-17-15 JA L. S. 1-14-21 VWK Design Information Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 °F Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19507 Btuh Structure 15972 Btuh Ducts 3269 Btuh Ducts 4537 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh none (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 22776 Btuh Use manufacturer's data y Rate/swing multiplier Equipment 1.00 Infiltration sensible load 20509 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2548 Btuh Ducts 1100 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolin Area (none) (ft2) 1512 1515 Equipment latent load 3648 Btuh Volume (ft3) 13571 13571 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 24157 Btuh Equiv. AVF (cfm) 86 45 Req. total capacity at 0.75 SHR 2.3 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC530AP03 Cond 25HBC530AP03 AHRI ref 204840289 Coil FX4DNF031 L00 AHRI ref 204840289 Efficiency 8.5 HSPF Efficiency 12.5 EER,15 SEER Heating Input Sensible cooling 21300 Btuh Heating output 28200 Btuh C) 47°F Latent cooling 7100 Btuh Temperature rise 27 OF Total cooling 28400 Btuh Actual airflow 947 cfm Actual airflow 947 cfm Air flow factor 0.042 cfm/Btuh Air flow factor 0:046 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.85 Capacity balance point = 36 OF Backup: Input = 6 kW, Output = 20230 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr1ghtso1Ft- 2021-Jan-14 12:18:16 ICE ^M °° ° - Right-Srrite®Uriversal202121.0.02 RSU23828 Page 1 aterstone1512AGL1Lot18BMWaterstore1512AGL.nQ Calc=MJB House faces: S -140- wrightsoft, Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM Job: Lot 19 Block 5 Waterston 15... Date: By: FLETCH 1 Room name Entire House WIC 2 Exposed wall 192.4 It 8.0 ft 3 Room height 9.0 ft 8.3 ft heaV000l 4 5 Room dimensions Room area 1516.0 ft2 1.0 x 41.8 ft 41.8 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area 02) Load number (Btuh/ft2-fl (Btuhfit2) or perimeter (ft) (13 h) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 �VLBlk 131kwall oext stucc 2A-26v 2A-2ov wall, stucoo ext 0.201 0,330 0.330 _0.330 0.201 n n n n_ a 583 9.57 9 57. _9 57 5.83 406 8.52 8 52 ._-. 8 52 4.06 353 30 23 . 33 460 267 0 0 - _ __. 0 434 1555 287 222 _e 313 2529 1083 256 198 _: _ .----279 1762 - 0 ` 0 0 0 0 0 0 0 0 '0 0 0; 0 2A-2ov 0.330 a 9.57 22.83 10 0 93 223 0 0 0 0 4_ Vil 2A-2ovT� Blkwall, sluoco ext- 0330 0201 e se' : - 957, 5 83 22_98 4.06 16 0 156 46 376 32 0 -- 0 0 0 0 0 _ 0 0 18 ' 8 2A-2ov.___., ___.- Blk wall, sluoco ext _______0.330 0.201 -se- s ____9.57" 5.83 _­_14.96 4.06 _-.._..'_10 150 _.._ .`- 2 �_.___96 .._150 453 ___,._.__-0 3 _ .- 0 3 __'_-0. 17 12 112 650 -- VIJ qR C F_ 2A-2ov 213-2tv 11,Jo Blk wall stucbo ext Blk wall, stu000 ext 10C-v 2A-2ov 12C Osw w 16B-30ad _ 0.330 0.330 0.600 0201 0.201 0.550 0.330 0.091 0.032 s s s snr suY_ w w w 9.57 9.57 17.40 5 83' .. 9 57: 5.83 15.95 9.57 2 64'296 _.�. 1131, 0.93 8.22 9.72 17.58 4.06, 14 96 4.06 16.20 22.06 _ 11.43 1.69 15 3 20 18 _. �,'10 348 18 7 _ 18 1580 15 3 20 W 8 .> _ ....._2 323 18 1 1278 . r 18 1580 144 29 350 46 1884 285 66 m734 _ 1, 202 1467 5519 _s:;v_x7-7 123 29 353 1313 289 151 ` : 364 2670 0 0 0 0 0 0 64 43 0 0 0 0 0 0 64 43 0 0 0 0 0 0 4_ 169 _ _ _ 40 0 0 0 0 0 0 84: 73 7r­ 61 c) AED excursion 196 -8 Envelope loss/gain 16768 10686 455 160 12 a) Infiltration 2739 766 6 2 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 4 920 0 0 Appliances/other 3600 0 Subtotal (lines 6 to 13) 19507 15972 461 162 Less external load 0 0 0 0 14 Less transfer Redistribution Subtotal 0 0 19507 0 0 15972 0 0 461 0 0 162 15 Duct loads 17% 28 % 3269 4537 17°/ 28%1 77 46 Total room load Air required (dm) 22776 9471 20509 947 538 22 208 10 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. C -�- wrigt�tsoft- 2021-Jarr1412:18:16 �"�A 5 Right-Sute®Uruversal 2021 21.0.02 RSU23828 Page 1 aterstone1512AGL1Lot19Blk5Waterstone1512AGL.nQ Calc=W8 Housefaces: S -- wrightsoft9 Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM' Job: Lot 19 Block 5 Waterston 15... Date: By: FLETCH 1 Room name MBATH WC 2 Exposed wall 17.5 It 4.0 It 3 Room height 8.7 ft heaV000l 9.0 It heaV000l 4 Room dimensions 1.0 x 136.0 ft 1.0 x 20.3 It 5 Room area 136.0 ft2 20.3 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh4t2) (Btuh4t2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 __ Blk wall stucco ext 2A-2ov 0 201 0336 n n 5 83' 957. 4 06 852 0 0 0 0 0 0 0 0 -- 0 0 0 0 a 0 0' ffi° 2A-2ov 0 330 n 9.5 8 52 0 0 0 0 0, 0 0 a 0 $,4-2ov.�� w' 0330,r1 11 wall, stucco ext 0.201 a 5.83 4.06 0 0 0 0 0 0 0 0 VLBlk 2A-2ov 0.330 a 9.57 22.83 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 9.57 22.98 0 0 0 0 0 0 0 0 V)! _81k wall stuaq ext 0:201 se .. 5�83 4 06 0 0 F U U Q r.0 V 0 Q. L -G 2A-2ov. _, _0.330 se.. .9.57a �14.96 a 0 u . �6 L' c . 0 M a _0 0: Blk wall, stucco ext 0.201 s 5.83 4.06 6 6 32 22 0 0 0 0 2A-2ov 0.330 s 9.57 8.22 0 0 0 0 0 0 0 0 213-2tv 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11J0 0.600 s 17.40 17.58 0 0 0 0 0. 0 0 0 _ Blk wall stucco exi 0201 sw 5 83 4 06A 0 0 017 70 0 .Ua " a32 Blk wall, stucco ext� 0.201 w 5.83 4.06 96 89 520 362 32 187 130 10C-v 0.550 w 15.95 16.20 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 9.57 22.06 7 1 66 151 0 0 0 0 RR 12C Osw i 0 091 2 64131 44 , + 44 116 58 0 0 < C 166-30ad 0.032 0.93 1.69 147 n 147 136 248 .: 22 22 21 38 28:68 O;QQ. ti1-8 20 4 116 :O; __ _ n .:136 _ s502 __ _ .0 a x5.....a...�......................�i, , ¢ x .„4 M S,r...etL,f...i%L'r,e ........ },:-'� .a..: z....-..,.a.. 3.h.s,..u.a 7 ._._..-,�..z._.w..._..,....�......,....xs,t ��.___, _ ........,..... .��,_, ..F...,...._,.c.tik.. .�a.. �,-.,.�... SMx =,« .�...�.:.�.. s....�.»-, .,� .me....,..µ ,..d .,r.,....� "- _>..-.:..as.- .n.,�.s....r.......r:-�.�.._.._ s>.,^«ev........, _,a ......,..z_ �.....,.... .....w,s.�.. a „a.nw...E ,...,,,.... y .w .a: ., ...,.,.....ry ,-..�E:..ja,....£� srt`�i,.�....c.v _.............» ...,-,z,_ ,w..a,�.,a_....�..,.>_..a-„_ ,_........;.�.kz_� .. ....v_.....a. .,max. .....-.L... u,.,,�.a:. ..v,..�„d.=.x.,r.. x....., .,.��c,..._...,� s. n`wia._.._..,.....�,.�,._.,..-k..'y.�.,.��...a.. `�iz..........,.�:.� ,..,.�.,...a.,.,.,.. ...,_.,..-{.,.'e..w....w._-.w.,..+.,...z. .,..._�...,.«. ,.. ...,c„.. .....�....�-a........... .... _._.... w., A+.m,.,FF _ 6 c) AED excursion 53 -8 Envelope loss(gain 1372 894 322 159 12 a) Infiltration 207 58 65 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1578 952 387 178 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1578 952 387 178 15 Dud loads 171/6 28% 264 270 17% 28%1 65 50 Total room load 1843 1223 452 228 Air required (cfm) 77 56 191 11 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - c -*- wrightsoft- 2021-Jarr1412:18:16 Right-Sdte®Udversal 2021 21.0.02 RSU23828 Page 2 aterstore1512AGL\Lot19BIk5Waterstore1512AGL.r p Calc=MJ8 House faces: S Job: Lot 19 Block 5 Waterston 15... Date: 1- wrightsoft' Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM By: FLETCH 1 Room name MBR LAU Exposed 35.5 ft 6.0 ft 3 height 8 6 ft heaYbool 8.0 It heaV000l 4 Room dimensions 13.5 x 16.5 ft 1.0 x 56.0 It 5 Room area 222.8 ftz 56.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz-fl (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk:wall sh�000a#� 2A-2ov 0201 0 330 n n ' 583; 9 57, t 406 8 52 ii6 0} 84 0 488 0 340 0 0 0 0 0 a, 0 0 1 0 0' 2A-2ov 0 330 n 9 57 8 52 P 0 0 g 0 0 0 0 0 0 8 52 0..w313 ,r 279 0 11 Blk wall, stucco ext _. 0.201 a 5.83 4.06 ,e_..-33_. 44 44 256 .� 179 L*w ,_F 0 0 0 0 �G 2A-2ov 0.330 a 9.57 22.83 0 0 0 0 0 0 0 0 L -C 2A-2ov 0.330 e 9.57 22.98 0 0 0 0 0 0 0 0 Vf/ Blk wall shi000 e# 0201 se'' 5 83; 4.06 0 "0 = °"0 0 0 0 p 0 0.330 se 14.9fi "0 _ 0 _ 0 ,_ 0 -0 0: Blk wall, stucco e# 0.201 s 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 8.22 0 0 0 0 0 0 0 0 213-21v 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11 JO 0.600 s 17.40 17.58 0 0 0 0 0 0 0 0 Blk wall stucpo e# O'201 sw 5 83 4 06 0 6 0 xrr7 tl 4 0 ^ � 0 0 w~ F0 N� 0, ^ µ y/ Blk vdi, stucco e# 0201 w 5.83, 4.06 132 132 769 536 0 0 0 10C-v 0.550 w 15.95 16.20 0 0 0 0 0 0 0 0 2A-2ov 0.330 w 9.57 22.06 0 0 0 0 0 0 0 0 Fq� 12C Osw a 0.091� 264' 131, `��_���;''48 127 63 �D JJ;DO 0:390�143. U 0 ' 0, C 1613-30ad 0.032 0.93 1.69 238 238 2-21 402 56 56 52 95 . x ._.+-«..�.......e....�..,.�a.�.....x,.. «..,.«..,.....,». m...i..v.. .,wvw_, ... A.,..�... -.r...a.......,.:..4 .,..} .. ....� as_.... .e._.c +...a.. .._«:... w�..--•-....,..... ..n...v..F.h.'_«. ,i...w-.„..c. .w...-..da.. 2:.:.......� �».. v..�f � � �`, ry�i _...... ..,. x.,.._e.........er...ra 9. =...r L.. .... �A.�....... .YLM..c..w ,..._..vd.z,a23..., ✓nT .., .+. w_.a. ua.1 sa.. a'� .u.�...a..,..w..._.,.,.sL.,..f,..�u....'.: , ...._.e............ :t Y^TM" .m...,...�,... �^..'..�i _ ..xu�. ..»....<..�.J..e u...,.wP..ww.�.- .#".�«...�a->.....0 ..wS.:^»w .a,. �. Q.s..n.,..._..t...�... ..-.-u .wu.......-w..ws, ....._..,..._ �swr - _ z »-... 'w...v...=.......... r+..._.i,..mum.. ,,.,..»v.. .�..... 'i.....x.......-.e .....r�.a .,r..&+�M..n.Y_ w. r..�z....s. ,h k�.rd...sS..�. n� E...e x v.... �<Via. m.=..1.a=,.:..._..vu, � �,..A.a�s� _»..,,._.. _ ....,.. ....�.-.s_........v...._%-- _..:..»..,.....,.z ,. y... _ _> _.�..wh..�...s_... ...ay. w.._. .»_-.,_+�x.,.....t....a..i_ ............. ..ss nw �,._...r. ... ,,..�.:�d......:.°=,_ 't' ter... m....na, .�.., ...i.._.._._«-.-......�. .�.Y.-+ ...u,.+_ W.=v. aa.aa1......, uu+,,..d+... «...u...„....... x .�.......s ..-.v.n,.a_.v,,�,.�« a.e»....,.,..,.4,.u...,.....:..-,.'......-,... .-.... -.,...,...-..wk,-....L+_.. ..-...>..,.. a,..,..,..r- ...-..a..L . .e'e,.... h,. .,.fe.�......,kv,«. MI. ..z....X...i .. , .....,.,..ate.. ..�abK.s:..:.s...... -isa,..,., 5..... SU= =...,a....�..sc,:'Ri ..aF .....,....� _.,.......,..i .gym....._...._. _ a.-.,..,, _ may.._,.,,. s.-a.. aas. .,..,....,. ,..„........�. .. ..M.,,.w. ,...,ab...... ..ti .�...,.2A.e.....'<,.,. ._ dw�>L.. .�... ... e.w...<..£a, ,.Ywv.X .2,Y.....,. ..-e� ;,....-.a 6 c) AED excursion -124 -34 Envelope losstgain 3065 1611 351 123 12 a) Infiltration 595 166 0 0 b) Room ventilation 0. 0 0 0 13 Internal gains: Occupants@ 230 1 230 0 0 Appliances/other 600 600 Subtotal (lines 6 to 13) 3660 2607 351 723 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3660 2607 351 723 15 Dualoads 17% 28% 613 741 17% 28% 59 205 Total room load 4273 3348 409 929 Air required (dm) 178 155 17 43 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -rFF =1gfttso14t_ 2021-Jan 1412:18:16 Right-Sdte®Uruversal 2021 21.0.02 RSU23828 Page 3 ...aterstone1512AGLLot1981k5Waterstone1512AGL.nQ Calc=W8 House faces: S Job: Lot 19 Block 5 Waterston 15... Date: - +- wrightsoft9 Right-M Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM By: FLETCH 1 Room name BR3 BATH2 2 Exposed wall 31.9 ft 6.0 ft 3 Room height 8.0 8 heaUmol 8.9 ft heaUmol 4 5 Room dimensions Room area 1.0 x 162.0 It 162.0 ft2 9.5 x 6.0 ft 57.0 112 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ftzg (Btuh/12) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blkwal1 stucco ext 2A2ov 2A-2ov 0. 201 0330 0 330 n n n 5 83 957 9 57 4 06 852 8 52 " 0 O 0 0 s 0 0 0 0 0 0 0 0 U 0 0 0 0 0 0 0 0 0` 0 A: 11 n it Blk wall, stucco ext n. .._,_033Q 0.201 _n_ a .� 9 57. 5.83 _ 8.52 4.06 . _ _ _0 108 , s.. _ 20 108 .. _ ._ Q 630 ._._ '_0 439 48 48 280 0 195 YVu t-C 2A-2ov 2A-2ov_ Blkwall,stu000ext �_ 2A:2ov. Blk wall, stu000 ext 0.330 0.330 -0201 _-0.330 0.201 a a se .._se_ s 9.57 9.57 5:83' ..-.-.957 5.83 22.83 22.98 4:06 _14.96 4.06 0 0 0 0 0 0 0 0 _ 32 _.-160 215 0 0 p __ _0 8 0 0 . --' .- _.A 8 0 0 0 0 _ _,_.._O. 34 18 _ 10 68 8 - 53 46 309 ._.,._,__20 49 1�/ V�-�--(GG' R G 2A-2ov 28-21v 11 JO Blk wall stucco ext 2A,2oy . _ Blk wall, stu000 ext- 10C-v 2A-2ov 12C Osw .ry 16B-30ad 0.330 0.330 0.600 � 0201 _ 0,330 _ 0.201 0.550 0.330 0 091 ...__,00,0 0.032 s s s sw _. sw;" w w w 9.57 9.57 17.40 -` 5 83 ,._ _ 9 57 5.83 15.95 ry m 9.57 2 64 0.93 8.22 9.72 17.58 4 06 _. 14 96 4.06 16.20 22.06 i 31. 1.69 15 0 0 18 _...1.0 44 0 0 0 _ 162 15 0 0 8 ,>, __M._2 44 0 0 � 0 _ 162 32 144 0 0 46 . ., 96 256 0 0 0 . 150 915 ' 123 0 0 32 s ,_ ,.1,50 179 0 0 _ 0 274 0 0 0 µ 0 . _ .5 0 0 0 r ._3 0 62 0 0 0 _ _ �, 0 0 0 0 0 _: 0 62 0 0 0 u_..... ._, U. 0 0 0 0 ..: _--.0- 58 0 0 0 m .., Q. 0 0 0 ' .r.0 _•_ 0 105 T.. a mi, 7 7, _ . _.._. .__ .._..,_.,._..,....._...=,...s..,..._...., ......,- _......... ...:5.,i.'_.' ._..,._,. _.. .»s_F.E_s..x .�»�...e . ,4,.5'>s.s_ ......r..<. a_..-,_..... ,.__.,.... 6 c) AED excursion -92 -17 Envelope losssIgain 2688 1500 558 317 12 a) Infiltration 520 145 115 32 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Applianoesrother 300 0 Subtotal (lines 6 to 13) 3208 1946 673 349 Less external load 0 0 0 0 14 Lesstransfer Redistribution Subtotal 0 0 3208 0 0 1946 0 0 673 0 0 349 15 Ductloads 17% 280/6 538 553 170% 28%1 113 99 Total room load Air required (cm) 3746 156 2499 115 786 33 449 21 Calculations approved bvACCAto meet all reauirements of Manual J 8th Ed. -ri &- 2021 -Jan-1 4 12:18:16 Right-SuteOUniversal 202121.0.02RSU23828 Page ACCK aterstone1512AGLtLotl9Blk5Waterstonel512AGL.nQ Calc=MJ8 Housefaces: S Job: Lot 19 Block 5 Waterston 15... Date: -- wrightsofV Right-JO Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DEL-AIR.COM By: FLETCH 1 Room name BR2 Krr 2 Exposed wall 11.0 ft 10.0 ft 3 Room height 8.6 ft heaticool 8.7 ft heaV000l 4 Room dimensions 14.0 x 11.0 ft 1.0 x 120.8 ft 5 Room area 154.0 ft2 120.8 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (BtuhHt2-T) (13tuhHt2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 w n Blk wall stucco ext 2A2ou 0 201 0330 n n 5 83 957:. 4 06 852 D _0� s 0 0� ' 0 ` 0 0 0 0 0. 0 0 0 2A-2ov 0330 n 957 852 0' 0- 57 2, 8 J9 d 0 _ _ A 0 „ 0 .0 " 0 0' 11 Blk wall, stucco ext 0:201 a 5.83 4.06 88 72 418 291 80 70 4o9 285 2A-2ov 0.330 a 9.57 22.83 0 0 0 0 10 0 93 223 2A-2ov 0.330 a 9.57 22.98 16 0 156 376 0 0 0 0 BII<;wall stucco ext 020i se 5 83;Y 4 06 x ^A 0 0 07 77,+ 0, 0 0 �: 4 2A 2ov A.386 _se 9.5Z --, 14.96 0 � .0 �0 0 a e 0 _ a 0 .. �0 _ w ' °0. Blk wall, stucco ext 0.201 s 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 8.22 0 0 0 0 0 0 0 0 2B-2fv 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11.J0 0.600 s 17.40 17.58 0 0 0 0 0 0 0 0 Blkwall sWocoext 0201 sw 583 406 0 0 0 0 4 0 0 0 N 0 oVtJ Blk wall, stucco ext 0.201 w 5.63 4.06 0 0 0 0 0 0 0 0 10C-v 0.550 w 15.95 16.20 0 0 0 0 0 0 0 0 2A=2ov 0.330 w 9.57 22.06 0 0 0 0 0 0 0 0 R 12G Osw "� 00917 264, 77X31_ 6 :77M 0 M_Q 1160 e _ 0.390 , '. 9 " AO e L.. y 0 ~ �., U w n0 ».e C 168-30ad 0.032 0.93 1.69 164 164 152 _,"� 277 130 . 130 _ . 121 219 x ,� r t .._.� _.......__.,-..�...�....�.. :,... m ....,,_�....., w. . Y.r._... _.e... -- -....,.ti,.,.e. k'..t....,...�...�x.s,.,.>..> ,...,,_,-e ...,,... -...�, .... ..,,._n«z .,-........-.+.6:.. ... a._ _ n...95< ,... �.R,....�' .w:`.E=.o 112_.... a.». ........,._.,_......... .....a...,__.,..,..... ...c-......w....., .., .a..,.«s. u,.�.,_ m..>.�sM.t`.�;.rw -�,...-.- :i�z.,m»... ...� wts.,.x�„w`",. �k.,.-.,<.....� .,. _»_w ., s. ..._.rw.a .,:-..,U�-..._,�.._. .... ' -„...�..,..a�.w:.,.. ,:.. ..__......�...5« ,_..?.3.. ....... ........aw ",. ,n,..,.,.,;zu:,,. sx. �.�s�•s,m..,.. �,. t a a.,.a..T �.a...&...._. �...rs.....,.«.....,..a:t ..=..'a ,... «_,:v,..�Ma.-..,..._�..,. H.,.s. - ..,,....,,.,,s.., ,._ .aa.,ma.»,. _..s,,_. ... <.<, -.., a,.�o..._ ...8,...�. «..i..._.._ x.�.�c.. ._,.......,__.:%: ...•s._,k_x ..�.,.,....c_.. � _.izr,. awe...:x � a e�_ .�..........�....��_e...o.._......-A.w.. _..�.�,_ _.E_ .. .�s..,.a ,....�.....� ..._.,....as'.:..�. � �..U.� __.az:.�.v..�..,a. _<�.....,�,. .�...�.w a,., ._.x.w.� � ..�......,�.d .,_....._ .�'�.�: j1,7 v..�....-_. .......�a.,.2..�s..w�.Y.n.v....._t ..�.r..n ....._„ X:. ri= ....n. o-, > Z_v.s- s_x = ..-.,Y•`.1.-.....:� ._i...,e »a'SJ .. w......C.'=;. .............. ...:.,......,..+iw"w _......a,....-.v., a...w..._ «s.L.. u.,.._ v.w...ln "::. e. �u o..a r..n e.........,. ....-�.a„uf. u.. ....T... M.ZEm.:::1:1 -.L.w. ,..tu .x..,,,.a+.w.�...w....,r..... .........e.. .- -mr.Y ., v..,a. .,...v .r m w�...-.�e'�.. a�._�arvA a rso-R.3 .. w.un....wa.....a• _._._.._.w- s ..v....rw.«. .-�,s?�,.s:..d..._.. T a,:.'v..,,.-.. = ...,.d,.>... ..w-..� m..�a.,.a&.s..;.P r.n ..,..h �...,�i a..,.. �:.0 ._.. uu. .,....i..,..,.....a;.t. 6 c) AED excursion 60 -24 Envelope losstgain 1042 1003 910 704 12 a) Infiltration 179 50 163 46 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 0 0 0 0 Appliances/other 300 1200 Subtotal (lines 6 to 13) 1221 1354 1073 1949 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1221 1354 1073 1949 15 Ductloads 179/. 28% 205 384 17% 28%1 180 554 Total room load 1425 1738 1253 2503 Air required (cfm) 59 80 52 116 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -4- wrightsoft- 2021-Jarr1412:18:16 Right-Suite®Universal 2021 21.0.02 RSU23828 Page 5 aterstone1512AGLLot19Blk5Waterstore1512AGL.rLp Calc=MJ8 Housefaces: S wrightsoft° Right-M Worksheet Entire House DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone; 407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Job: Lot 19 Block 5 Waterston 15... Date: By. FLETCH 1 Room name DIN GRT/FOY/HALLS 2 Exposed wall 28.0 It 34.5 It 3 Room height 8.8 ft heatbool 10.0 It heaV000l 4 Room dimensions 1.0 x 119.0 ft 1.0 x 426.5 It 5 Room area 119.0 ft2 426.5 ft2 Ty Construction U-value Or HTM Area (1112) Load Area (ft2) Load number (Btuh/ft2-`-) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blf< wall slu000 ext 2A 2ov 0201 0:330 n n "5 83 9 57• 4 06 8 52 96 0 ; 73 f 0 426 X 0 , ` 297 0 140110 30 0 641 287 447 256 2A 2ov 0330 n 957 85.2 23 0 222 198 933Q'.,n �_9.57- �,M8.5� �...,,.0.,.�..->.'0_....-: �.O Q��a.�_0 1 1 Blk wall, stucco ext 2A-2ov 0.201 0.330 a e 5.83 9.57 4.06 22.83 92 0 92 0 536 0 374 0 0 0 0 0 0 0 0 0 2A-2ov 0.330 e 9.57 22.98 0 0 0 0 0 0 0 0 1Q/ Blk wall, stu000 ext 0201 se 5 83 4 U6 ' 0 0 0 0 0 0 0 U _ 242ov _ _ 0.330 a9.57 , _ 14.960 0 XF Blk wall, stucco ext 2A-2ov 0.201 0.330 s s 5.83 9.57 4.06 8.22 o 0 0 0 0 0 0 0 65 0 42 0 244 0 170 0 2B-2fv 0.330 s 9.57 9.72 0 0 0 0 3 3 29 29 11JO 0600 s 1740 1758 0 0 0 0 20 20 350 353 lr?! Blk wall stu000 exf � 0201 sw - 5 83 4-06 0 0 0 r 0 r 6 0 0. 2A=2ov 95TL4:96 .v 300 M Blk wall, stucco ext 1OC-v 0.201 0.550 w w 5.83 15.95 4.06 16.20 44 18 26 18 152 285 106 289 0 0 0 0 0 0 0 0 ���-------(GG' 2A-2ov 0.330 w 9.57 22.06 0 0 0 0 0 0 0 0 R 12, Osw 0.091 264 0 w 0 0 s 0 " 14Q i22 160' 0390 . n 20.4, C . 166-30ad .--. .,..,. ....4 0.032 5 .y - .W.., 0.93 1.69 129 129 120 219 427 427 396 721 22A WI U,989 28;68 .,.. Z_. 42713.$5 z ' mW0 z = _z _u.._ --" ;w...r ' ,+..,.. ........._...�...�....a....,._.: rw...a A.a.,,., -,,... r,_..~ ...._.a....�_... ,�.._s... .,.a ,_.., ..�..,_.s,� ....d.a�.. w.r�-.....,.,.... .-. d,..._ ._.�,.....s..M_ ..,..__.d:�., ..,.....-.�:nm. a x ,w....wK �.m.ww..<...,.w....e.a.0 ,......sue ...... ...... ..-,....-,=. ..Av._.,a_, ......,$_._.., _w.=.,...ss n.wa.....x.>.. .......»S�i.F-,....,. a,..��.,.,., ....«.= � .. t,...,._.n. xz, a........, ...°S .A..>....~.r. ."re_..�._,+.a._...-.tM� ,.P....a?..n cr.,.....,s-«..,., i}..s»M.,...s .d'..'.. ..a...Y...., ,....w,.eL.Nr.u. 'u 550 -159 6 c) AED excursion Envelope loWgain 2545 2033 3461 2180 12 a) Infiltration 473 132 417 117 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 2 460 Appliancesiother 0 600 Subtotal (lines 6 to 13) 3018 2395 3878 3357 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 3018 2395 3878 3357 15 Duct loads 17% 289/. 506 680 17% 28% 650 954 Total room load 3524 3075 4528 4311 Air required (dm) 147 142 188 199 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. - I&K Right-Stite®Universal 2021 21.0.02 RSU23828 2021-Jarr141 Page 6 aterstonel512AGL\L.otl9Blk5Waterstonel512AGL.rLp Calc=MJ8 Housefaces: S g wlrightsoft® Duct System Summary Job: Lot 19 Block 5 Waterston... Date: • Entire House By. RETCH DEL -AIR HEATING & AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DEL-AIR.COM Project Information For: ADAMS HOMES 5373 San Benedetto Place, Fort Pierce, FL 34951 External static pressure Pressurelosses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.1.70 / 0.170 in H2O 0.359 in/100ft 947 cfm 95 ft Supply Branch Detail Table Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.359 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH2 h 786 33 21 0.379 4.0 Ox 0 VIFx 19.7 70.0 BR2 c 1738 59 80 0.408 6.0 Ox 0 VIFx 13.3 70.0 BR3 h 3746 156 115 0.359 7.0 Ox0 VIFx 24.7 70.0 DIN h 3524 147 142 0.370 7.0 Ox 0 VI Fx 22.0 70.0 GRT/FOYHALLS c 4311 188 199 0.458 8.0 Ox 0 VIFx 4.3 70.0 KIT c 2503 52 116 0.406 6.0 Ox 0 VIFx 13.7 70.0 LAU c 929 17 43 0.456 4.0 Ox 0 VI Fx 4.6 70.0 MBATH h 1843 77 56 0.430 6.0 Ox 0 VI Fx 9.0 70.0 MBR h 4273 178 155 0.411 8.0 Ox 0 VIFx 12.8 70.0 we h 452 19 11 0.417 4.0 Ox 0 VI Fx 11.5 70.0 WIC h 538 22 10 0.453 4.0 Ox0 VIFx 5.0 70.0 Return Branch Detail Table Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb2 Ox 0 947 947 0 0 0 0 Ox 0 VIFx ,ti ft * wrightso® ��ek!lB.r6hufaMxa,cnarymry Right-Sute@Urlversa1202121.0.02RSU23828 aterstone1512AGL1Lot19BIk5Waterstone1512AGL.nQ Calc=MJ8 Hoisefaces: S 2021 -Jan-1 4 12:18:17 Page 1 2020 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA 1 TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 19 Block 5 Waterstone 1512 AGL Builder Name: ADAMS HOMES Street: 5373 San Benedetto Place Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: • 661000 w Design Location: FL, ST_LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind l2apong and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceffilongs, a. i l auuniun, mspeauon of log waus snau be in accordance with the provisions of ICC-400. 1/14/2021 12:35 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default leakage" then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 1/14/2021 12:34:13 PM EnergyGaugeg USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information. Builder: ADAMS HOMES Community: Lot: NA Address: 5373 San Benedetto Place City: Fort Pierce State: FL Zip: 34951 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, orER1Method O PRESCRIO-tiVE-METHOD-The building or dwelling unit shall be tested and verified as'having an air leakage rate of,not exceeding air, 'a changes perhour atpressure,of 0.2 inch -# g (50;P-ascals) in. Climate Zones, 1.,an6l;2; 0 PERFORMANCE or ERI METHOD -The buildin' or 'dwelling unit shall be tested and verified as having an atr=leakage rate of,not exceeding the selected ACH(50) value, as shown on.Form R405-2020;(Performance) or R40, 2020�(ERI),:section'labeled'as.infiltration,�sub-section ACH50. ACH(50) specified on Form R405-2020-Energy Calc (Performance) or R4062020 (ERI): 7.000 x 60 : 13608 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans F-1 PASS Code 0 software calculated When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company, Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/14/2021 12:35:08 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5373 San Benedetto Place Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. , V/ SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory)The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. . R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 Us/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 1/14/2021 12:34 PM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. ❑ R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. R403.1 Controls. SECTION R403 SYSTEMS ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. ❑ R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned Floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) or below 55°F (13°C) shall be insulated to a minimum of R-3. ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall ❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1/14/2021 12:34 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) ❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'Y2 inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy. When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 1/14/2021 12:34 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ElR403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 1/14/2021 12:34 PM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 ❑ R403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. ❑ R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. ❑ R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 1/14/2021 12:34 PM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5