HomeMy WebLinkAboutEvaluation Report Intertek ' I . REPORT NUMBER: 1 0 071 7048CO(a-003 ORIGINAL ISSUE DATE: May 1,2012 REVISION DATE:May 24, 2012 j EVALUATION CENTER INTERTEK TESTING SERVICES NA LTD. 15W BRIGANTINE DRIVE COQUITLAM, SC V3K 7C1 W RENDERED TO JAMES HARDIE BUILDING PRODUCTS, INC. 10901 ELM AVENUE FONTANA, CA 92337 ,t�t�rruri�f,��` . PRODUCT EVALUATED:-HardiePlank®and HardieShingieO�0f risPW EVALUATION PROPERTY:Transverse Load Testing LLI ; Report of HardiePiankg and HardleShingM tested In accordarree'�• - . FI. ASTM E330-02(2010), Standard Test Wthod for Structural PerformallV%fdi�FSSl Exterior Windows, Doors,Skylights and Curtain Walls by UnHorm Staiic16,,,,,j,r'iri l Pressure Difference I . This report is for the exc►usive use of lntertek's Client and is provided pursuant to the agreement between Intertek and its 0.6ent, latertek's responsibility and liability are limited to the terms and conditions of the agreement Intertek assumes no liability to a!ty Party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use ar¢ivy report. 0niy the Client is authormed to copy or distt^rbute this report and then only in its entirety,Any use of the Wertek name cr one of its marks for the safe or advertisement of the tested material, product or service most first be approved in writing by ! intertek. The observations and rest results In this report are relevant only to the sample tested. This repo e!f d ps ."oramply that the material, product.or service is or has ever been under an�lntertek certification program. "fire lop Janes Hardie Building Products,Inc. NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED A. DRAWINGS "Submitted under NOA #13-0311.07" 1. Drawing No.PNL,PLK&SOFF,titled"HardiePanel,CemPanel, Prevail Panel; HardiePlank, CemPlank Prevail Lap Siding;HardieSoffit, CemSoffit Panel; Installation Details Wood/Metal Stud Construction",sheets 1 through 12 of 12,dated 04/24/2013,prepared by the manufacturer, signed and sealed by Ronald I. Ogawa, P.E. B. TESTS "Submitted under NOA #13-0311.07" 1. Test reports on 1)Uniform Static Air Pressure Test,Loading per FBC TAS 202-94 2)Cyclic Wind Pressure Loading per FBC,TAS 203-94 along with marked-up drawings and installation diagram of HardiePlank,HardieSoffit and HardiePanel,.prepared by Intertek Testing Services NA LTD,Test Report No. 100733361COQ-004,dated 08/24/2012,with revision I dated 04M/2013, signed and sealed by Rick Curkeet,P.E. "Subtttilled ruder NOA #02-0729.02" Laboratory Report Test Date Signature 2. ATI-16423-1 PA 202&203 03/18/96 A.N. Reeves P.E. 3. ATI 16423-2 PA 202 &203 03/18/96 A.N. Reeves P.E. 4. ATI 16423-3 PA 202&203 03/18/96 A.N.Reeves P.E. C. CALCULATIONS 1. None. D. QUALITY ASSURANCE 1. Miami-Dade Department of Regulatory and Economic Resources(RER) h E. MATERIAL CERTIFICATIONS 1. None. F. STATEMENTS 1. Statement letter of code conformance to the 5t'edition(2014)FBC issued by Ronald I. Ogawa&Associates,Inc.,dated 1012612014,signed and sealed by Ronald I. Ogawa,P.E. o)�1S Carlos M. Utrcra,P.E. Product Control Eaaiuiner NOA No.15-0122.04 Expiration Date:May 1,2017 Approval Date:April 9,2015 L++'-1 South GENERAL FASTENING REQUIREMENTS • Consult applicable code compliance report for correct fasteners type and Fasteners must be corrosion resistant,galvanized,or stainless steel. placement to achieve specified design wind loads. Bectro-galvanized are acceptable but may exhibit premature corrosion. • NOTE:Published wind loads may not be applicable to all areas where The manufacturer recommends the use of quality,hot-dipped galvanized Local Building Codes have specific jurisdiction.Consult the manufacturer's nails.The manufacturer is not responsible for the corrosion resistance of Technical Services if you are unsure of applicable compliance documentation.. fasteners.Stainless.steel fasteners are recommended when installing • Drive fasteners perpendicular to siding and framing. Cemboar&products rear the ocean,large bodies of water,or in • Fastener heads should fit snug against siding(no air space).(fig.A) very humid climates. • Do not over-drive nail heads or drive nails at an angle. • If nail is countersunk,caulk nail hole and add a nail.(fig.B) PNEUMATIC FASTENING • Forwood framing,underdriven nails should be hit flush to the plank with a Cemboard products can be hand nailed or fastened with a pneumatic hammer(For steel framing,remove and replace nail). tool.Pneumatic fastening is highly recommended. Set air pressure so ' Do not use aluminum fasteners,staples,or clipped head nails. that the fastener is driven snug with the surface of the siding.A flush Snug Flush mount attachment on the pneumatic tool is recommended. This will Countersunk, help control the depth the nail is driven.If setting the nail depth proves Caulk& difficult,choose a setting that under drives the nail. (Drive under driven ZI add nail nails snug with a smooth faced hammer-Does not apply for installation do not under So POE to steel framing). Figure Figure B drive nails CAULKING PAINTING For best results use an Elastomeric Joint Sealant DO NOT use stain on Cemboard products. complying with ASTM C920 Grade NS,Class 25 or Cemboard products must be painted within 180 higher or a Latex Joint Sealant complying with ASTM days for primed product and 90 days for unprimed. C834.Caulking/Sealant must be applied in accordance 100%acrylic topcoats are recommended. with the caulkinglsealant manufacturer's written Do not paint when wet.For application rates refer to instructions orASTM C1193. paint manufacturers specifications. Bade-rolling is recommended if the siding is sprayed. FACTORY BUILT COLOR TECHNOLOGY CAULKING,TOUCH-UP& LAMINATE • Touch up nicks,scrapes and nail heads using the Factory Built Color technology touch-up applicator.Touch-up paint should be used sparingly. If large areas require touch-up,replace the damaged area with new CemplanV lap siding with Factory Built Color technology. • Laminate sheet must be removed immediately after installation of each course. • Terminate non-factory cut edges into trim where possible,and caulk Color matched caulks are available from your Factory Built Color product dealer. • Treat all other non-factory cut edges using the Factory Built Color technology edge coaters,available from your Factory Built Color product dealer. PAINTING CEMBOARDe SIDING AND TRIM PRODUCTS WITH FACTORY BUILT COLOR TECHNOLOGY When repainting Factory Built Color products,the manufacturer recommends the following regarding surface preparation and topcoat application: • Ensure the surface is dean,dry,and free of any dust,dirt,or mildew • Repriming is normally not necessary • 100%acrylic topcoats are recommended • DO NOT use stain or oil/alkyd base paints on Cemboard products • Apply finish coat in accordance with paint manufacturers written instructions regarding coverage,application methods,and application temperature COVERAGE CHART/ESTIMATING GUIDE Number of 12'planks,does not include waste COVERAGEAREA CEMPLANK'LAP SIDING WIDTH LESS OPENINGS SQ 519 6114 71/4 712 8 8114 91,14 912 12 j1 so=too s%ft) (exposure) 4 5 6 61A 6 314 7 8 8114 10 314 1 25 20 17 16 15 14 13 13 9 2 50 40 33 32 30 29 25 25 19 3 75 60 50 48 44 43 38 38 28 4 100 80 67 64 59 57 50 50 37 5 125 100 83 80 74 71 63 63 47 6 150 120 100 96 89 86 75 75 56 7 175 140 117 112 104 100 88 88 65 8 200 160 133 128 119 114 100 100 74 9 225 180 150 144 133 129 113 113 84 10 250 200 167 160 148 143 125 125 93 11 275 220 183 176 163 157 138 138 102 12 300 240 200 192 178 171 150 150 112 13 325 260 217 208 193 186 163 163 121 14 350 280 233 224 207 200 175 175 130 15 375 300 250 240 222 214 188 18B 140 16 400 320 267 256 237 229 200 200 149 17 425 340 283 272 252 243 213 213 158 18 450 360 300 288 257 257 225 225. 167 19 475 380 317 304 281 271 238 238 177 20 500 400 333 320 296 286 250 250 186 This coverage chart is meant as a guide.Actual usage is subject to variables such as building design.The manufacturer does not assume responsibility for over or under ordering of product. RECOGNITION: In accordance with ICGES Legacy Report NER-405,Cemplanle lap siding is recognized as a suitable alternate tothatspedked irr the BOCA National Building Code11999,the 1997 Standard Building Cade,the 1997 Uniform Building Code,the 1998Internatarel OneandTwo-Famuy Dwelrmg Code,the 20031rtemational Budding Code,and the 2003International Residential Code for One-and No- Family Dwellings.Cemplanke lap siding is also recognized for application in the fe0owir g:City of Los Angeles Research Report No.24ti6'L State of Florida listing F AM.Dade County,Florida HOA No.02.0729.02. U.S.Dept of HUD Materials Release 1263c.Texas Department of Insurance Product Evaluation EC-23.City of Newyork MEA223-93-M,and California DSA PA-019.These documents should aso be consulted for additional information ooncerr&,g the suitability of the product for specific applications CEN10802-P3.r4 9108 i Florida Product Approval Cemplank° Lap Siding • For use inside HVHZ: o Cemplank Lap Siding fastener types, fastening schedule, and installation shall be in accordance with the Miami-Dade County Florida NOA 15- 0122.04. Consult the Cemplank product installation instructions on the follow pages for all other installation requirements. • For use outside of HVHZ, o Cemplank Lap Siding fastener types, fastening schedule, and installation shall be in accordance with Engineering Evaluation Reports RIO-2553-15 or RIO-2557-15. Consult the Cemplank product installation instructions on the follow pages for all other installation requirements. I I Cemplanictth Lap Siding ii INSTALLATION REQUIREMENTS-PRIMED AND FACTORY BUILT COLOR TREATED PRODUCTS EFFECTIVE AUGUST 2010 CEDAR - BEADED CEDAR • BEADED SMOOTH IMPORTANT FAILURE TO INSTALLAND FINISH THIS PRODUCT IN ACCORDANCE WITH APPLICABLE BUILDING CODES AND THE MANUFACTURER'S WRITTEN APPLICATION INSTRUCTIONS MAY LEAD TO PERSONAL INJURY,AFFECT SYSTEM PERFORMANCE,VIOLATE LOCAL BUILDING CODES,AND VOID THE PRODUCT ONLY WARRANTY. STORAGE&HANDLING: Q CUTTING INSTRUCTIONS Store flat and keep dry and covered prior to installation. ouTDoolts INDOORS 1.Position autGrgstation so that wind will blow dust away from user 1.Cut only usngscore and snap,orsh ears(manual,electric orpneunatic). Installing siding wet or saturated and others'n wnddng area 2.Position cutting Baron in well-ventilated area may result in shrinkage at butt 2 Use one of thefollowixJ methods: joints.Car lanky on e a Best i.score and snap 1 Carry g • u.Shears(mannual,elecbicorpnematic) -NEVER use a power saw Moors Protect edges and comers from b.Better. i.Dust reducing circular saw eOpped with a -NEVER me a circular saw blade that does not ca rry the Hardieblade saw blade trademaik breakage.The manufacturer is not Hardiedadeaa saw blada and HEPAracwmext�tion NEVER dry sw'eep—Use wet suppression orHEPAVaam m u Good: L Dust reducing circular saw with a Hardeblaie saw blade responsible for damage caused by (only use for low to moderate cutting) improper =. :. Important Nob.Formaromun protection owest o respirable dust producfi�),the Manutacbuer recommends ahvaysusingBest'aevelcutSngmetladswherefeaside. storage and !`: a r_r%� N{OSHapprmred respirators can be used in co lundion with above cutting practices to further reduce dust exposures.Additional e handling of the 9 xpo xpasue information is availa6le at www.cemboardsdng.comtotwo oudeterminethemostappropriatecufingmettadforyourjobregtmerrents.IfcmcemstillextslsabouteApmumlevelscryou product. do notcemply with the above practices,you should always consult aquatified industrial hygianist or oomRct the Manufacturer for further informatiom �.D7E31C: GENERAL REQUIREMENTS: •CemplaW tap siding can be installed over brad wood or steel studs spaced a maximum of 24"o.c.or directly to minimum 7/16"thick OSB sheathing'.Irregularities in framing and sheathing can mirror through the finished application. •Cemplanka lap siding can also be installed over foam insulation/sheathing up to 1"thick.When using foam insulation/sheathing,avoid over-driving nails (fasteners),which can result in dimpling of the siding due to the compressible nature of the foam insulation/sheathing.Extra caution is necessary if power-driven nails(fasteners)are used for attaching siding over foam insulation/sheathing. •A water-resistive barrier is required in accordance with local building code requirements. The water-resistive barrier must be appropriately installed with penetration and junction flashing in accordance with local building code requirements.The manufacturer will assume no responsibility for water infiltration. • Install Cemboar&products with a minimum 6"clearance to the finished grade on the exterior of the building or in accordance with local building codes if greater than 6"is required(fig.3). •Maintain a 1"-2"clearance between Cemboard products and roofs,decks,paths, steps and driveways(figs.4,5&6). Figure 1 Double Wall Single Wall • Maintain a 1/4"clearance between Cemboard products and horizontal flashing(fig.7). Construction construction • Ensure glitters have end caps.Maintain a minimum 1"gap between end caps and siding water-resistive barrier 24 o e max. let-in bracing &trim(fig.8). plywood or •Install kickout flashing at roof-wall junctions(fig.9). thing •Adjacent finished grade must slope away from the building in accordance with local building codes-typically a minimum of 6"in the first 10'. i{� •Do not install Cemboard products,such that the may remain in contact with P Y Y standing water. •CemplanV lap siding must be installed on vertical wall applications only. i • DO NOT use stain on Cemboard products. INSTALLATION: `1 101MTREATMENi' (Required for Factory Built Color Finish,Recommended for Primed product) \ { k E I f f l It is not recommended to use caulk at field buttjomts. Figure 2 water-resswe stud 9 barrier „k op joint flashing, ) "from r °~ edge ` I ;! / water-resistive —plankge! o \\ t i barrier install planks in W, moderate-contad �•�f V \ i E fastener Install a 1 114"starter strip t ensure a consistent plank ang[a Install factory finished edges together at butt joints. lea a appropriate gap between planks and trim,then caulk"' 'If only nailed to sheathing,plank can be a maximum 9-1/4"wide and must be face nailed at 17 o.c.with 0.09" shank x 0.221'HD x 1.5"long corrosion resistant nails. "As required by local building code "'Apply caulk in accordance with caulk manufacturers written application Instructions. WARNING:AVOID BREATHING SILICA DUST Cemboard*products contain respirable crystalline silica,which is known to the State of California to cause cancer and is considered by IARC and NIOSH to be a cause of cancer from some occupational sources.Breathing excessive amounts of respirable silica dust can also cause a disabling and potentially fatal lung disease caged silicosis,and has been linked wifi other diseases.Same studies suggest smoking may increase these risks. During installation or handling:(1)work in outloorareaswnth ample ventiletihxh:(2)use fibercement shears for cutting or,where not feasible,use a Hardhebtade"-'saw blade and dust-reducing circular saw attached to a HEPA vacuum;(3)warn others in fie immediate area(4)wear a property-fitted,NIOSH-approved dust mask or respirator(e.g.N-95)in accordance wiln applicable government regulations and manufactiuerinsbudions to further lima respirable silica exposures During dean-up,use HEPA heahans or wet cleanup methods-never drysweep.For further information,refer to our installation instnidons and Material Safety Data Sheet available at www.cembDardskfmg.com or by calling"77-236 7526. FAILURE TO ADHERE TO OUR WARNINGS,htSDS. AND INSTALLATION INSTRUCTIONS MAY LEAD TO SERIOUS PERSONAL INJURY OR DEATH. s CEM0802-P1/4 910E South CLEARANCES Install siding and trim products in Maintain a 1"-2" Maintain a 1"-2"clearance At the juncture of the roof and vertical compliance with local building code clearance between between Cemboard products surfaces,flashing and counterflashing requirements for clearance between the Cemboar&products and and decking material. shall be installed per the roofing bottom edge of the siding and the paths,steps and Figs 5 manufacturer's instructions. adjacent 6nished,grade. Figure 3 driveways. Provide a 1"-2"clearance between the stud water roofing and the bottom edge of the water-resistive � Figure 4 siding resistive banter g I siding and trim. barrier Figure 6 concrete j i deck material —�— t'1•-2" foundation joist ' n is � � rig Cemplankg ledger lap siding flastfing -- Figure r) KICKOUT FLASHING Maintain a 114°clearance Maintain a minimum 1°gap sl�ne:nog X� Because of the volume of water that can pour between the bottom of between gutter end caps and sekiiihaug ,; down a sloped roof,one of the most critical ""are flashing details occurs where a roof intersects Cemboard products siding&trim. 9 and horizontal flashing. e�1 a sidewall. The roof must be flashed with Do not caulk gap. Figure a step flashing. Where the roof terminates, It install a kickout to deflect water away from `sv y 1Fashap- Figure 7 y. @fie the siding. siding . It is best to install a self-adhering membrane oo not 114•gap on the wall before the subfascia and trim Caulk 1 sidm9 - boards are nailed in place,and then come back to install the kickout. Figure 9,Kickout Flashing; To prevent water from dumping behind the siding a and the end of the roof intersection,install a"kickout of sufficient length and gutter and end cap angle to direct the water running down the roof away from the-siding. FASTENER REQUIREMENTS** Blind Nailing is the preferred method of installation for all Face Nailing should only be used where required for high wind areas and must notbe Cemplank®lap siding products used in conjunction with Blind Nailing BLIND NAILING FACE NAILING Nails-Wood Framing Nails-Wood Framing • Siding nail(0.09"shank x 0.221"HD x 2"long) • 6d A113"shank x 0.267"HD x 2"long) • 11ga.roofing nail(0.121"shank x 0.371"HD x 125"long) • Siding nail(0.09°shank x 0.221°HD x 2°long) Screws-Steel Framing Screws-Steel Framing • Ribbed Wafer-head or equivalent(No.8 x 1 1/4°long • Ribbed Bugle-head or equivalent(No.8-18 x 1-5/8"long x x 0.375"HD)Screws must penetrate 3 threads into metal framing. 0.323"HD)Screws must penetrate 3 threads into metal framing. Nails-Steel Framing Nails-Steel Framing ° ET&F Panelfaste nails or equivalent • ET&F pin or equivalent(0.10"shank x 0.25"HD x 1-1/2"long) (0.10"shank x 0.313"HD x 1-112"long) Nails must penetrate minimum 114"into metal framing. Nails must penetrate minimum 1/4"into metal framing. OSB minimum 7/16" OSB minimum 7116" • Siding nail(0.09"shankx'0.221°HD x 1-112"long)* • 11ga.roofing nail(0.121"shank x 0.371"HD x 1.75"long) 24" •Ribbed Wafer-head or equivalent(No.8 x 1518"long x 0.375"HD). stud t4_ O.C.max. ,. 24" Figure 10 Figure 11 � f1 c _ stud _^ 1 1/4"min. O.C.max. a _,,y p overla water resistive :r Minimum overlap barrier c for Both Face `�- and Blind Nailing blind nail yr ij' Ii (ir7 1l nor. c min.1 1/4" I ! i �< face nail overlap : I l 1 r "I I Its -., -+' water-resrstie%- water-resistive i r barrier 1 114"min. r' barrier — overlap Laminate sheet to be removed immediately after installation of each course for Factory Built Color products. t The illustration(figure 9)and associated text was reprinted with permission of THE JOURNAL OF LIGHT CONSTRUCTION.For subscription information, visit www.jloonline.com. When face nailing to OSB,planks must be no greater than 9114"wide and fasteners must be 12'o.c.or less. Also see General Fastening Requirements. CEM0802-P214 9108