wrightsoft® Project Summary Date: Oct 12,2017
Entire House By:
QUICK CALCS, INC.
I317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
Promect Information
For: 151 SE BONITA COURT
FT. PIERCE, FL EX0
Notes:
ILE COPY
Design Information
Weather: Fort Pierce, FL, US
Winter Design Conditions Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db 75 OF
Design TD 28 OF Design TD 15 OF
Daily range L
Re ative humidity 50 %
Moisture difference 61 gr/lb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 17989 Btuh Structure 14338 Btuh
Ducts 3993 Btuh Ducts 6283 Btuh
Central vent(21 cfm) 645 Btuh Central vent(21 cfm) 345 Btuh
Outside air Outside air
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 22627 Btuh Use manufacturer's data n
Rate/swing multiplier 0.95
Infiltration Equipment sensible load 19918 Btuh
Method Simplified Latent Cooling Equipment Load Sizing
Construction quality Average
Fireplaces 0 Structure 1678 Btuh
Ducts 1693 Btuh
Central vent (21 cfm) 875 Btuh
HeatiN Coolin Outside air
Area(ft2) 11 1164 Equipment latent load 4246 Btuh
Volume(ft3) 10476 10476
Air changes/hour 0.45 0.23 Equipment total load 24163 Btuh
Equiv.AVF (cfm) 79 40 Req. total capacity at 0.70 SHR 2.4 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Goodman Mfg.
Trade Trade GOODMAN- JANITROL;AMANA DISTI...
Model Cond GSX1 60301�
AHRI ref Coil ASPT30C14A
AHRI ref 5756173
Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER
Heating input 5.1 kW Sensible cooling 19320 Btuh
at He ing output 17448 Btuh Latent cooling 8280 Btuh
rn Te erature rise 50 OF Total cooling 27600 Btuh
Actual air flow 318 cfm Actual air flow 920 cfm
Air flow factor 0.014 cfm/Btuh Air flow factor 0.045 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.83
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2018-Feb-09 10:14:23
wrightSOft' Right-SuiteO Universal 2017 17.0.14 RSU08101 136ge 1
ACG� ...skQuick CaIcs1DocumentsX151 SE BONITA COURT.rup Calc=M.18 Front Door faces: S
Ifs-wrightsoft' RiOW@ Worksheet Job:
Date: Oct 12,2017
Entire House
By:
QUICK CALCS, INC.
�317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@,AOL.COM
I
1 Room name Entire House LAUNDRY
2 Exposed wall 146.0 ft 15.0 ft
3 Room height 9.0 ft d 9.0 ft heat/cool
4 Room dimensions 8.0 x 7.0 ft
5 Room area 1164.0 ftz 56.0 ft'
Ty Construction U-value Or HTM Area (ftj Load Area (W) Load
number (Btuh/ft2°F) (Btuh/ft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool
6 13A4ocs - 0.143 n 4.00 2.55 324 288 1153 733` 72 M 288 983
. 1Acclom __ 1.270 n_ _35.56 34.�77 36 _0__- 1280._ 1252_,- _ 0_ _ -_._0 _ -____ 0- 0
13A4ocs 0.143 a 4.00 2.55 333 293 1173 746 63 63 252 160
1A-c1om 1.270 a 35.56 91.12 4 0 142 364 0 0 0 0
11 1A-c1om 1.270 a 35.56 91.12 12 0 427 1093 0 0 0 0
T_-.-_.. 1A-r1orn -1.270 a 35.56 28.38 24 - 0 _ ,- 853 681-_ 0 0---- 0 0
IN 13A-46cs 0.143 s 4.00 2.55 324 288 - 1153 733 0 0 0 0
LF-�G 1A-c1om 1.270 s 35.56 34:77 24 24 853 835 0 0 0 0
1A-r1om-_---- -_- - 1.270_"s-- --35.56_ .17.30 _.. 12 _ 12 - -_-427 __ _208,,____ 0_ -_ --0 -0 . .-___0
w 13AAocs 0.143 w 4.00 2.55 333 297 1189 756 0 0 0 0
L--G IA-c1om,__ - 1.270 w_ __35.56 _.91.12 .__- -36 0 .-- 1280 32810 _ 0- 0 0- __ 0
1164_.._1597_. - 2994_ _ 56
C_ _ 16B-19ad--_ ---.- - _:_.0.049-.._--_-__1.37-, _.2.57__. 1164- _ _.-._77._. -, _144
F 22A-tpl 0.989 - 27.69 - 0.00 __1164 146 4043 0 56 15 _415 0
-, - - - -
K: `� fit.
�� 1
--
6 c)AED excursion 0 -46
Envelope loss/gain 15572 13676 1033 442
12 a) Infiltration 2418 662 248 68
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 17989 14338 1281 510
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 -1281 -510
14 Subtotal 17989 14338 0 0
151 Duct loads 22% 44% 3993 6283 22%1 449/6 0 0
Total room load 21983 20620 0 0
Air required(cfm) 318 920 1 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
4 wrightsoft® 2018-Feb-09 10:14:23
Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
'�� ...s\Quick Calcs\Documents\151 SE BONITA,COURT.rup Calc=MJ8 Front Door faces: S
• •
-Ff+wrightsoft® Right-M Worksheet Job:
Entire House Date: Oct 12,2017
By:
QUICK CALCS, INC.
1317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BATH 2 LIVING
2 Exposed wail 7.0 ft 30.0 ft
3 Room height 9.0 ft heaticool 9.0 ft heat/cool
4 Room dimensions 8.0 x 7.0 ft 16.0 x 14.0 ft
5 Room area 56.0 ft2 224.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 -W, � 13A-4ocs-- ' 0.143 ,n 4.00 2.55 0 0 0 0 144 120 480 305
!---G_ IA_-:c1om__ -. _ -- 1.270_ n _35.56 34.77 _0. _.- A-- - . 0 24 -. - -- 0-- 853- - 835
13A-4ocs 0.143 a 4.00 2.55 63 59 236 150 0 0 0 0
IA-c1om 1.270 a 35.56 91.12 4 0 142 364 0 0 0 0
11 IA-c1om 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
1A riom 1.270_ e 35.56 _ 2.838 ---0 0 0 _0 0- 0 0 _ _ 0
I 13A-40cs 0.143 s 4.00 2
l;_GC 1A-c1om 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
- 1A-rlom-- - 1.270 s. 35.56 17.30 -0 _0 0. 0 - 0 --- 0_- - -0 -0
w 13AAocs 0.143 w 4.00 2.55 0 0 0 0 126 102 408 260
LG _1A-c1om._ __ _ 1.270 _w 35.56 91.12 - - _._ 0_,_ .0 _ ,., -_.0 _ _ 0 _ 24 _ _ 0 ___ 853 ____ 21.87
0-.'_ '16B-19ad- __ ____ 0.049_ -_ - 1.37 - 2.57 56 56 _ -77_ _ 144 _ 224 224 307 _ 578.
F 22A-tpl,. 0.469 - 27.69 0.00 56 7 _194 0 224 30 831 b
-
i
6 c)AED excursion -16 382
Envelope loss/gain 649 642 3734 4545
12 a) Infiltration 116 32 497 136
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 765 674 4231 4681
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 683 272 598 238
14 Subtotal 1448 946 4829 4919
15 Duct loads 22% 44% 322 415 22% 44% 1072 2155
Total room load 1770 1361 1 1 5900 7074
Air required(cfm) 26 61 85 316
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoftm 2018-Feb-0910:14:23
Right-Suite®Universal 2017 17.0.14 RSU08101'` Page 2
��` ...s\Quick Calcs\Documents\151 SE BONITA COURT.rup Calc=MJ8 Front Door faces: S
�+ wrightsoft° Right-J®Worksheet °b
Enure House Date: Oct 12,2017
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772-466-6799 Fax 772-466-6796 Email:QUICKCALCS@AOL.COM
1 Room name BEDROOM 1 FAMILY
2 Exposed wall 21.0 ft 36.0 ft
3 Room height 9.0 ft heaticool 9.0 ft heat/cool
4 Room dimensions 1.0 x 102.0 ft 1.0 x 371.0 ft
5 Room area 102.0 ftz 371.0 ftz
Ty Construction U-value Or HTM Area (ft� Load Area (ft� Load
number (Btuh/ftz°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 13A-flocs, 0.143 n' �4.00 2.55 99 87 348 221 0 0 0 0
_G. 1A c1om - -- - 1 270__rr_ 35.56 . ._34.77 __. _12__- - 0 - , 427 07 ______0 _.-0 _0 -- - 0.
13A-4ocs 0.143 a 4.00 2.55 90 78 312 199 0 0 0 0
1A-clom 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
11 1A-clom 1.270 a 35.56 91.12 12 0 427 1093 0 0 0 0
_ 1A-r1om_ __ __ 1.270 e_ 35. 28.38 0 _ _ 0 __0 _ 0 0_ 0 0 0
Vd/ 13A-4ocs '0.143 s 4.00 2.55 0 0 0 6 117 105 420 267
It-�G 1A-clom .1.270 s 35.56 34.77 0 0 0 0 12 12 427 417
- -
1A-r1om -- -- _._..1.270 s_-- -_35.56.. ._17.30. _ _ -. Q__. 0-- 0 .__. _0__'_ .. -0 - -_0_-- _. A_.. ._-__'0
wI _ 13A-4ocs 0.143 w 4.00 2.55 0 0 0 0 207 195 781 496
�--G 1A-clom -_ 1.270 w, 35.56 91.12 0 0 0 , 0 12 0 427 1093
_. _
-_. 1.37- _257 - _v 102. - � 102 ':_. -_140--_ _262_ .,_.371 - 371. _ 509
F 22A-tpl __ 0.989 - 27.69 0.00 102 21 582 0 371 _ _ 36 997 _ 0
EL 7
_
-f
-
6 c)AED excursion -188 29
Envelope loss/gain 2236 2005 3561 3257
12 a) Infiltration 348 95 596 163
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 2583 2100 4157 3421
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 3 5 3 5
14 Subtotal 2586 2105 4160 3426
151 Duct loads 22% 44% 574 923 22% 44% 923 1501
Total room load 3161 3028T 5083 4927
Air required(cfm) 46 135 73 220
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
wrightsoft' 2018-Feb-09 10:14:23
Right-Suite®Universal 2017 17.0.14 RSU08101 Page 3
'' �` ...s\Quick Calcs\Documents\151 SE BONITA COURT.rup Calc=MJ8 Front Door faces: S
-f wrightsoft9 Right-J®Worksheet J Daatt
Entire House e: Oct 12,2017
By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT,PIERCE,FL 34946 Phone:772466-6799 Fax:772-466-6796 Email:QUICKCALCS@,AOL.COM
1 Room name BATH BEDROOM 4
2 Exposed wall 1.0 ft 13.0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 1.0 x 47.0 ft 13.0 x 13.0 ft
5 Room area 47.0 ft' 169.0 W
Ty Construction U-value Or HTM Area (W) Load Area (ft2) Load
number (Btuh/ft?°F) (Btuhlft� or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 V 13A-4ocs b.143 n. 4.00 2.55 9 9 36 23 0 0 0 0
_ _ 1A�1om- -_ ---1.270 n 35.56 34.77 __- __ 0_ _ 0 -0 0 ._ 0 _. _ 0 _.. -0_0 0
13A110cs 0.143 a 4.00 2.55 0 0 0 0 0 0 0 0
1A-clom 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
11 1A-clom 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
..lA-rlom--- - 1.270 e_ -_35.56.. 28.38 -0 - 0 -0 - 0- 0 0 0. .. 0
13A-0ocs 0.143 s 4.00 2.55 0 0 0 0 117 105 426 267
1A-c1om 1.270 s 35.56 34.77 0 0 0 0 12 12 427 417
_._ IA-rlom-. ._ . -- . 1.270 . s 35.56 17.30 0 0. _ __ 0_ ------0_ ._ _ 0- --__._0 0. .. -0
13A-4ocs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
1A-clom_,_,-,• 1.270 w 35.56 91.12 _ -„ 0 . 0 _ 0 0 0 0 0 0
C 16B-19adt.__ ;_ 0.049 -_ 1.37 2.57 47 _ . 47. __64. _ 121 169 _169 232 435
F 22A-tpl__ 0.989 - 27.69 0.00- 47 1 28 0 169 13 360 0
6 c)AED excursion -12 1
Envelope loss/gain 128 132 1439 ills
12 a) Infiltration 17 5 215 59
b) Room ventilation 0 0 0 0
13 Internal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 145 136 1654 1177
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 6 11 0 0
14 Subtotal 151 147 1654 1177
15 Duct loads 22% 44% 34 64 22% 44% 367 516
Total room load 184 211 T2022 1693
Air required(cfm) 3 9 29 76
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
. wwrightsoft- 2018-Feb-0910:14:23
Right-Suite®Universal 2017 17.0.14 RSU08101 Page 4
'�C` ...s\Quick Calcs\Documents\l51 SE BONITA COURT.rup Calc=MJ8 Front Door faces: S
'-�-wrightsoftm Right-JO Worksheet Job:
Entire House Date: Oct 12,2017
By:
QUICK CALCS, INC.
i
1317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax:772466-6796 Email:QUICKCALCS@40L.COM
1 Room name BEDROOM 2 A/C
2 Exposed wall 23.0 ft 0 ft
3 Room height 9.0 ft heat/cool 9.0 ft heat/cool
4 Room dimensions 10.0 x 13.0 ft 3.0 x 3.0 ft
5 Room area 130.0 ft2 9.0 ft2
Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load
number (Btuh/ft2-'F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool
6 13A flocs -0.143 n - '4_60 2.55 6 0 0 _ 6 b b o 6
_ - 1A-c1om__ _ _-1.270 _n 35.56 34.77 -----0 0. _ 0___ __0.___ -_0 - 0 0 0
13A-4ocs 0.143 a 4.00 2.55 117 93 372 237 0 0 0 0
IA-c1om 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
11 IA-c1om 1.270 a 35.56 91.12 0 0 0 0 0 0 0 0
1A-r1om_ -- ---- 1.270 e 35.56 _ 28.38 ._._ 24 0 - _____853 _-- 681 _ ___ _0_ _- 0 _ 0. _-.. - 0
3 4.00 2.55 90 73 312 999 0 6 0 0
1A-clom 1.270 s 35.56 34.77 0 0 0 0 0 0 0 0
���. 13A-flocs 0.14 _ s
1A-rl om---._- . _ 1.270 _s. 35.56_- 17.30 _12 12 427 _ 208 0 - 0 0 -
w 13A-4ocs 0.143 w 4.00 2.55 0 0 0 0 0 0 0 0
1A-c1om---- ---. 1.270 w 35.56 91.12 0 0 0 - - -0 -- - 0 - 0 0 0
0.049 = __1;37 2.57 -_ _-130 - _.._130 178 __ 334 -_ _ 9-__ 9 - 12 23
F 22A-tpl 0.989 - 27.69 0.00 130 23 637 0 9 0 0 ___0
6 c)AED excursion -145 -2
i Envelope loss/gain 2780 1513 12 21
12 a) Infiltration 381 104 0 0
b) Room ventilation 0 0 0 0
13 Intemal gains: Occupants @ 230 0 0 0 0
Appliances/other 0 0
Subtotal(lines 6 to 13) 3161 1618 12 21
Less external load 0 0 0 0
Less transfer 0 0 0 0
Redistribution 0 0 -12 -21
14 Subtotal 3161 1618 0 0
15 Duct loads 22% 44% 702 709 22% 44% 0 0
Total room load 3863 2326 0 0
Air required(cfm) 56 104 0 0
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
-Fk wrightsoft- 2018-Feb-0910:14:23
Right-Suite®Universal 2017 17.0.14 RSU08101 Page 5
�� ...s\Quick Calcs\Documents\151 SE BONITA COURT.rup Calc=MJ8 Front Door faces: S
w
Duct System S Job:
+�+ wrightsoft® emumma Date: Oct 12,2017
Entire House By:
QUICK CALCS, INC.
317 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax 772-466 6796 Email:QUICKCALCS@AOL.COM
I
Project • •
For: 151 SE BONITA COURT
FT. PIERCE, FL
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0.50 in H2O 0.50 in H2O
Supply/return available pressure 0.250/0.250 in H2O 0.250/0.250 in H2O
Lowest friction rate 0.377 in/100ft 0.377 in/100ft
Actual air flow 318 cfm 920 cfm
Total effective length (TEL) 133 ft
Supply Branch - Table
I
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (cfm) (cfm) FR (in) (in) Mat[ Ln (ft) Ln (ft) Trunk
BATH 2 c 1361 26 61 0.382 4.0 Ox 0 VIFx 16.0 115.0 st1
BATH-A c 211 3 9 0.504 4.0 Ox 0 VIFx 4.1 95.0
BEDROOM 1 c 3028 46 135 0.490 6.0 Ox0 VIFx 7.1 95.0
BEDROOM 2 c 2326 56 104 0.480 6.0 Ox0 VIFx 9.2 95.0
BEDROOM 4 c 1693 29 76 0.493 6.0 Ox0 VIFx 6.4 95.0
FAMILY-A c 4927 73 220 0.453 7.0 Ox0 VIFx 15.3 95.0
LIVING-A c 7074 85 316 0.377 8.0 Ox 0 VIFx 17.7 115.0 st1
Supply Trunk - Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk
st1 Peak AVF 111 376 0.377 852 9.0 0 x 0 VinlFlx
Return Branch Detail i
Table
I
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk
rb3 Ox 0 28 70 0 0 0 0 Ox 0 VIFx
rb2 Ox0 159 535 0 0 0 0 Ox 0 VIFx
rb5 Ox0 56 104 0 0 0 0 Ox 0 VIFx
rb4 I Ox0 1 75 211 0 1 0 0 0 Ox 0 1 VIFx
ra . �f
wri htsoft® Lj 201[-Feb-o9 10:14:23
9 Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
ACCA ...s\Quick Calcs0ocuments\151 SE BONITA COURT.rup Calc=MJ8 Front Door faces: S
t v.
wrightca~f Component Constructions Date: Oct 12,2017
Entire House By:
QUICK CALCS, INC.
017 ST.LUCIE LN.,FT.PIERCE,FL 34946 Phone:772466-6799 Fax:772466-6796 Email:QUICKCALCS@AOL.COM
I
Project • •
For: 151 SE BONITA COURT
FT. PIERCE, FL
Design Conditions
Location: Indoor: Heating Cooling
Fort Pierce, FL, US Indoor temperature(°F) 70 75
Elevation: 25 ft Design TD (°F) 28 15
Latitude: 27°N Relative humidity(%) 30 50
Outdoor: Heating Cooling Moisture difference (gr/lb) 1.1 61.5
Dry bulb(°F) 42 90 Infiltration:
Dailyrange(°F) - 15 ( L ) Method Simplified
Wet bulb( F) - 78 Construction quality Average
Wind speed (mph) 15.0 7.5 Fireplaces 0
Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain
ft' Btuh/f'-°F f°-°F/Bluh Btuh/R' Btuh BMW Btuh
Walls
1 3A-flocs:Blk wall,stucco ext,r-4 ext bd ins,8"thk, 1/2"gypsum n 288 0.143 4.0 4.00 1153 2.55 733
board int fnsh a 293 0.143 4.0 4.00 1173 2.55 746
s 288 0.143 4.0 4.00 1153 2.55 733
w 297 0.143 4.0 4.00 1189 2.55 756
all 1166 0.143 4.0 4.00 4669 2.55 2968
Partitions
(none)
Windows
1A-c1om:1 glazing,clr glz,mtl no brk firm mat,1/8"thk;2 ft overhang(4 n 36 1.270 0 35.6 1280 34.8 1252
ft window ht,7 ft sep.);6.67 ft head ht a 12 1.270 0 35.6 427 91.1 1093
S 24 1.270 0 35.6 853 34.8 835
w 36 1.270 0 35.6 1280 91.1 3280
all 108 1.270 0 35.6 3840 59.8 6460
A-clom:1 glazing,clr glz,mtl no brk frm mat,1/8"thk;2 ft overhang(2 e 4 1.270 0 35.6 142 91.1 364
it window ht,7 ft sep.);6.67 ft head ht
1A-r1om:1 glazing,reflective(1/4"only)glz,mtl no brk firm mat,1/4" a 24 1.270 0 35.6 853 28.4 681
trk,low rflct pert;100%drapes,tight white/refl;100%outdoor insect
screen;2 ft overhang(4 ft window ht,7 ft sep.);6.67 ft head ht s 12 1.270 0 35.6 427 17.3 208
all 36 1.270 0 35.6 1280 24.7 889
Doors
(I one)
Ceilings
1I6B-19ad:Attic ceiling,asphalt shingles roof mat,r-19 ceil ins,1/2" 1164 0.049 19.0 1.37 1597 2.57 2994
gypsum board int fnsh
It,loors
22A-tpl:Bg floor,light dry soil,on grade depth 146 0.989 0 27.7 4043 0 0
20 7 Oct-27 09:11:17
igtfa Right-Suite®Universal 2017 17.0.14 RSU08101 Page 1
0% ...s\Quick Calcs\Documents\151 SE BONITA COURT.rup Calc=MJB Front Door faces: S
Planning B Development Services REVIEW COMMENTS
Building i£Code Regulation Division
2300 Virginia Avenue
Fort Pierce,FL. 34982
Phone:(772)462-2172 Fax:(772)462-6443
Page 1
PROPERTY INFORMATION
Address: 151 Se Bonita Ct Owner(s):
Aline Odwazna/William Odwazna
City/State/Zip: Port St Lucie, FI 34983
i
Parcel#: 3419-540-0285-000/5 Jurisdiction: SAINT LUCIE COUNTY
Zoning:
RS-4 Lot#: 18 Block: 51
APPLICATION INFORMATION
PI rmit Number: 1710-0006 Stories: Automatic Sprinkler System? No
PI rmit Type: MECHANICAL/HVAC RESID-FIRST TIME INSTALLATION
"CONTRACTOR INFORMATION
Contractor Name: Nathaniel Mejia Fax Number:
BIusiness Name: Mejia A/C And Heating Llc
Business Addr: 2344 Sw Savona Blvd lVV/ Email: Mejiasabana@Gmail.Com
City/State/Zip: Port St Lucie, FI 34953 ,� I
� I
REVIEWS AND COMMENTS
1
Review Type Status Reviewed By Date Started Date Completed Date Released
FRONT COUNTER REVIEW COMPLETE Lashahna Ingram 10/2/2017 10/2/2017 10/2/2017
Comment:
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 10/11/2017
Comment: SUBMIT AN ELECTRICAL PERMIT FOR THE WIRING CONNECTIONS TO THE NEW MECHANICAL SYSTEM W/
10/11/2017 PANEL BREAKDOWN'NEEDS ELECTRICAL CONTRACTOR TO APPLY FOR PERMIT'SUBMIT WIRING
SCHEMATICS IN DUPLICATE
10/11/2017 Comment: SUBMIT DUPLICATE MANUAL J CALCULATIONS W/ALL EQUIPMENT SPECIFICATIONS'SEE FBCR M 1401.3
10/11/2017 Comment: SUBMIT DUPLICATE MANUAL D DUCT SIZING CALCULATIONS W/CFM CALC[ROOM X ROOM]'FBCR M
1601.1
Comment: SUBMIT DUPLICATE,SCALED FLOOR PLANS FOR THE DWELLING[SEE FBC 107.2.1 ] 'SHOW ALL DUCT
I 10/11/2017 SIZES,DROP LOCATIONS,ROOM REGISTER SIZING,ALL BALANCED RETURN AIR SIZING CALCULATIONS,
EQUIPMENT LOCATIONS,METHOD OF TIE DOWN FOR THE MECHANICAL COMPRESSOR MEETING THE 160
M.P.H.WIND SPEED,
10/11/2017 Comment: SUBMIT DUPLICATE ENERGY CALCULATIONS[WHICHEVER COMPLIES]W/ORIGINAL SIGNATURES BY
THE PREPARER AND THE CONTRACTOR W/EPL CARDS'SEE
Comment:
PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE SUBMITTED
DOCUMENTS.ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS
PLEASE NOTE:(1)ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE,(2)ALL CHANGES WILL BE REQUIRED TO BE CLOUDED
10/11/2017 ON THE PLANS AND(3)THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS,A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE ANY COMMENT NOT ADDRESED MAY BE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION#13-196
COMMENTS SENT
I
, i
I
, I .
Planning&DevelopmentServices REVIEW COMMENTS
Building&Code Regulation Division
2300 Virginia Avenue.
Fort Pierce,FL, M82
Phone:(772)462-2172 Fax:(772)462-6443
Page 2
10/11/2017 Comment: COMMENTS E-MAILED AS OF THIS DATE
i
i
I
I
, I
I
r • •
Joe Cicio
From: Joe Cicio
Sent: Wednesday, October 11, 2017 3:12 PM
To: 'mejiaquisqueya@yahoo.com'
Cc: Joe Cicio
Subject: Review Comments for Permit Number 1710-0006
Attachments: Repo rt_FL_Review_Comments_Noncompliantjrf.pdf
.Dear St Lucie County Permit Applicant,
Thank you for choosing to do business and invest in St. Lucie County. St Lucie County is committed in
.assisting you to navigate the building review process. Please know that county staff is committed to customer service
and part of that service is providing assistance and guidance with our processes. Please do not hesitate to contact us
further to discuss your building project as needed.
Please see the attached plan review comments which have been generated for your permit.As soon as
we receive the modified plans and any additional required documentation back from the Design Professional,
Contractor, Fire Department or Owner we will forward the documents to permitting for issuance.
Thank You
Joseph M. Giciv
Plans Examiner II
Standai d Building Inspector
Building Plans Examiner
One and Two FarnVyDwellingInspector
One and Two Family Plans Examin er
St Lucie County Planning and Development Services
772-�62-1553
i
Please Note:Florida has very broad public records laws.Most written communications to or from County officials regarding County business are public records
available to the public and media upon request.It is the policy of St.Lucie County that all County records shall be open for personal inspection,examination and i
o copying.Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication.If you received this email in error,
please notify the sender by reply e-mail and delete all materials from all computers.
1
lot
ifs da
�.
Pkrtittng&oevetopmerdSarvices S b/n REVIEW COMME TS
Building n;
fJ .2300 Vitgtnla Avenue
=Fort Pierce,Ft..9QJ82
Phone,(772j462-29T2 Faz:(772)4G2=6d4� Page•1
PROPERTY INFORMATION
Address: 151 Se Bonita Ct Owner(s):
Aline Odwazna/William Odwazna
City/State I Zip: `' Port St Lucie, FI 34983
Parcel#: 3419-540-0285-000/5 Jurisdiction: SAINT LUCIE COUNTY
Zoning:
RS-4 Lot#: 18 Block: 51
APPLICATION INFORMATION
Permit Number: 1710-0006 Stories: Automatic Sprinkler System? No
Permit Type: MECHANICAL/HVAC RESID-FIRST TIME INSTALLATION
CONTRACTOR INFORMATION
Contractor Name: Nathaniel Mejia Fax Number:
Business Name: Mejia A/C And Heating Llc
Email: Mejiasabana@Gmail.Com
Business Addr: �zdd s,�,Savona_Slvd _
City I State I Zip:
REVIEWS AND
Review Tvoe � Reviewed By Date Started Date Completed Date Released
FRONT COUNTER I ^/v� Lashahna Ingram 10/2/2017 1012/2017 10/212017
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 10/11/2017
Comment: SUBMIT AN ELECTRICAL PERMIT FOR THE WIRING CONNECTIONS TO THE NEW MECHANICAL SYSTEM W/
10/11/2017 PANEL BREAKDOWN*NEEDS ELECTRICAL CONTRACTOR TO APPLY FOR PERMIT*SUBMIT WIRING
SCHEMATICS IN DUPLICATE
10/11/2017 Comment: SUBMIT DUPLICATE MANUAL J CALCULATIONS W/ALL EQUIPMENT SPECIFICATIONS*SEE FBCR M 1401.3
10/1'1/2017 Comment: SUBMIT DUPLICATE MANUAL D DUCT.SIZING CALCULATIONS W/CFM CALC[ROOM X ROOM j*FBCR M
1601.1
Comment: SUBMIT DUPLICATE,SCALED FLOOR PLANS FOR THE DWELLING[SEE FBC 107.2.1 j *SHOW ALL DUCT
10/11/2017 SIZES,DROP LOCATIONS,ROOM REGISTER SIZING,ALL BALANCED RETURN AIR SIZING CALCULATIONS,
EQUIPMENT LOCATIONS,METHOD OF TIE DOWN FOR THE MECHANICAL COMPRESSOR MEETING THE 160
M.P.H.WIND SPEED,
Comment: SUBMIT DUPLICATE ENERGY CALCULATIONS[WHICHEVER COMPLIES j W/ORIGINAL SIGNATURES BY
10/11/2017 THE PREPARER AND THE CONTRACTOR W/EPL CARDS*WILL NOT BE REQUIRED*WILL ACCEPT
VERIFICATION OF INSULATION FROM NICOLE B.
Comment:
PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE SUBMITTED
DOCUMENTS.ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS
PLEASE NOTE:(1)ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE,(Z)ALL CHANGES WILL BE REQUIRED TO BE CLOUDED:
10/11/2017 ON THE PLANS AND(3)THE CONTRACTOR WHEN RESUeM(TTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE CONTRACTOR PREFERS,A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE ANY COMMENT NOT ADDRESED MAYBE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.
LUCIE COUNTY RESOLUTION#13-196
COMMENTS SENT
f
i
f Goa e �
4 pannrng!; :�oveto mer ser►Ices 5ubl" REVIEW COMME TS
� 8iilding•�Cork Ragulation Dvisiarta
2300YirginlaAVaswe,
Folt Pierce,FL 349$2;;_
Fhaee{T77j462 2772< ax 1j772�462.64.3
C Page.I
I
PROPERTY INFORMATION
Address: 151 Se Bonita Ct Owner(s):
Aline Odwazna/William Odwazna ;
,
City/State7 Zip: Port St Lucie, FI 34983
Parcel#: 3419-540-0285-000/5 Jurisdiction: SAINT LUCIE COUNTY
Zoning: RS-4 Lot#: 18 Block: 51
APPLICATION INFORMATION
Permit Number: 1710-0006 Stories: Automatic Sprinkler System? No
Permit Type: MECHANICAL/HVAC RESID-FIRST TIME INSTALLATION
i.
CIONTRACTOR INFORMATION
Contractor Name: Nathaniel Mejia Fax Number:
Business Name: Mejia A/C And Heating LIc
sine Buss Addr: ?add—��s�,nn�eiv�l
Email: Mejiasabana@G mail.Corn
I
City/State/Zip:
10Q
REVIEWS AND
Review Tvoe �V' O LA Reviewed By Date Started Date Completed Date Released
I
FRONT COUNTER I �I l Lashahna Ingram 10/2/2017 10/2/2017 10/21201.7
l V
PLANS EXAMINER REVIEW INCOMPLETE Joe Cicio 10/11/2017
Comment: SUBMIT AN ELECTRICAL PERMIT FOR THE WIRING CONNECTIONS TO THE NEW MECHANICAL SYSTEM W/
10/11/2017 PANEL BREAKDOWN*NEEDS ELECTRICAL CONTRACTOR TO APPLY FOR PERMIT*.SUBMIT WIRING
SCHEMATICS IN DUPLICATE
10/11/2017 Comment: SUBMIT DUPLICATE MANUAL J CALCULATIONS W/ALL EQUIPMENT SPECIFICATIONS*SEE FBCR M 1401.3
10/1'1/2017 Comment: SUBMIT DUPLICATE MANUAL D DUCT-SIZING CALCULATIONS W/CFM CALC[ROOM X ROOM]*FBCR M
} 1601.1
Comment: SUBMIT DUPLICATE,SCALED FLOOR PLANS FOR THE DWELLING[SEE FBC 107.2.1] 'SHOW ALL DUCT
10/11/2017 SIZES,DROP LOCATIONS,ROOM REGISTER SIZING,ALL BALANCED[RETURN AIR SIZING CALCULATIONS,
EQUIPMENT LOCATIONS,METHOD OF TIE DOWN FOR THE MECHANICAL COMPRESSOR MEETING THE 160
M.P.H.WIND SPEED,
Comment: SUBMIT DUPLICATE ENERGY CALCULATIONS[WHICHEVER COMPLIES]W/ORIGINAL SIGNATURES BY
10/11/2017 THE PREPARER AND THE CONTRACTOR W/EPL CARDS*WILL NOT BE REQUIRED*WILL ACCEPT
VERIFICATION OF INSULATION FROM NICOLE B.
Comment: n,-
PLEASE NOTE THAT THE COMMENTS ARE FOR THE CLARIFICATION OR CORRECTION OF THE SUBMITTED -`
DOCUMENTS.ADDITIONAL REVIEW MAY BE REQUIRED AFTER SUBMITTING CORRECTED DOCUMENTS
PLEASE NOTE:(1)ALL REVIEW COMMENTS WHEN ANSWERED WILL REQUIRE A COVER LETTER
ADDRESSING WHERE THE CHANGES WERE MADE,(2)ALL CHANGES WILL BE REQUIRED TO BE CLOUDED•>_`-
10/11/2017 ON THE PLANS AND(3)THE CONTRACTOR WHEN RESUBMITTING WILL BE REQUIRED TO INSERT THE
NEW UPDATED PAGES INTO THE PLANS OR IF THE.CONTRACTOR PREFERS,A REVISED COMPLETE SET
OF PLANS CAN BE SUBMITTED
PLEASE NOTE ANY COMMENT NOTAODRESED MAYBE SUBJECT TO AN ADDITIONAL REVIEW FEE PER ST.'
LUCIE COUNTY RESOLUTION#13-196
COMMENTS SENT
I
Pianntng>><Development Setvtces REVIEW COMMENTS
i�(3u(tding 8!;Code.Regutation�tJyta(ona
2300;1/irginla%venue;
Fort Pierce,FL`;:34982,..
Phone{772�462 2172 Pik(772y462 6443
Page 2
10/11/2017 Comment: COMMENTS E-MAILED AS OF THIS DATE
I '
i
Joe Cido
From: quickcalcs@aol.com
Sent: Friday, October 27, 2017 9:14 AM
To: Joe Cicio
Subject: Permit#1710-0006 151 SE Bonita Court
Attachments: 151 SE BONITA CT..pdf
I
Joe,
4ave attached the construction component page showing that we used R-19 for ceiling insulation , R-4 for wall
insulation and single clear windows.
T,anks,
Nicole Blackwell
Quick Calcs, Inc.
772-466-6799
I
I
I
: I
I
I
i
j
1
I
I
' C
I
® i
Joe Cicio
From: quickcalcs@aol.com
Sent: Monday, October 30, 2017 10:21 AM
To• Joe Cicio
Suibject: Re: Permit#1710-0006 151 SE Bonita Court
Joe,
Sorr I was out of the office Friday. Yes I have seen the R-4 and R-19 in ceiling.
Y, Y 9
Thanks,
Nicole
Q 1 ick Calcs
---F-Original Message-----
From: Joe Cicio <cicioj@stlucieco.org>
To: 'quickcalcs@aol.com' <quickcalcs@aol.com>
Sent: Fri, Oct 27, 2017 9:20 am
Subject: RE: Permit#1710-0006 151 SE Bonita Court
Nicole, I need your e-mail to state that you have witnessed the r-4 walls and R-19 ceilings
For the big house it will be o.k. to add the gallons together and show the one heater
Thanks
Joe
From: quickcalcs@aol.com [mailto:quickcalcs@aol.com]
Sent: Friday, October 27, 2017 9:14 AM
To:Joe Cicio<cicioi@stlucieco.org>
Subject: Permit#1710-0006 151 SE Bonita Court
Joe,
I have attached the construction component page showing that we used R-19 for ceiling insulation , R-4 for wall
insulation and single clear windows.
Thanks,
Nicole Blackwell
Quick Calcs, Inc.
772-466-6799
Pie ase Note:Florida has very broad public records laws.Most written communications to or from County officials regarding County business are public records
available to the public and media upon request.it is the policy of St.Lucie County that all County records shall be open for personal inspection,examination and
or copying.Your e-mail communications will be subject to public disclosure unless an exemption applies to the communication.If you received this email in error:
please notify the sender by reply e-mail and delete all materials from all computers.
I
I 1
i
f 0 = 7r.vt
X �
I
I
I
1
I
i
t
l
_
S
f
t
_ T
d®
lak6
k �
ve-.
s VT
it
� r