Loading...
HomeMy WebLinkAboutProject InformationManual S Compliance Report Job: Lot 22Block 5Watersone... - 1- wrightsofte Date: Entire House By: Dcs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM For: ADAMS HOMES FEB 2 2021 5367 Vespera Street, Fort Pierce, FL 34951 ST. Lucie County, Permitting Cooling, Equipment Design Conditions Outdoor design DB: 90.4 OF Sensible gain: 26027 Btuh Entering coil DB: 76.4°F Outdoor designWB: 77.4°F Latentgain: 4767 Btuh Entering coilWB: 63.2OF Indoor design DB: 75.0 OF Total gain: 30794 Btuh Indoor RH: 50% Estimated airflow: 1167 cfm Manufacturer's Performance Data at Actual Design Conditions . Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Sensible capacity: 28185 Btuh 108%of load Latent capacity: 5115 Btuh 107%of load Total capacity: 33301 Btuh 108% of load SHR: 85% Design Conditions Outdoor design DB: 41.0 OF Heat loss: 28570 Btuh Indoor design DB: 70.0 °F Manufacturer's Performance Data at Actual Design Conditions Equipment.type: SpIitASHP Manufacturer: Carrier Model: 25HBC537AP03+FX4DNF037L00 Actual airflow: 1167 cfm Output capacity: 31707 Btuh 111 % of load Supplemental heat required: 0 Btuh Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 1167 cfm Output capacity: 7.6 kW 91%of load Temp. rise: 20 of Meets all requirements ofACCA Manual S. Entering coil DB: 69.5OF Capacity balance: 36 OF Economic balance: -99 of wrightsoft, 2021-Jan-28 08:42:07 �� .M,..• o.kn.wm.,.�mam Rig14-Sute®Urrversal202121.0.02RSU23828 Page %4CCA...aterstone1820BGR\Lot22BIk5Waterstone1820BGR.rr{: Calc=MJ8 Front Door faces: S Component Constructions Job: Lot 22 Block 5 Watersone ... Wrightsoft® Date: Entire House By: DCs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM •ject intormation For: ADAMS HOMES 5367 Uespera Street, Fort Pierce, FL 34951 Design Conditions Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (OF) 70 75 Elevation: 26 ft Design TD (OF): 29 15 Latitude: 28 °N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 2.4 56.9 Dry bulb (OF) 41 90 Infiltration: Daily range (T) - 15 (L ) Method Simplified Wet bulb (T) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft� Btuh/ftzT ftz'F/Btuh Btulvt' Btuh Btuh/ft2 Btuh Walls 16B-19ad: Knee wall, asphalt shingles roof mat, r-19 kw ins, 1/2" gypsum board int fnsh Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 1 /2" gypsum board int fnsh Partitions 12C-Osw: Frm wall, 1 /2" gyp.bd ext, r-13 cav ins, 1 /2" gypsum board int fnsh, 2N4" wood frm, 16" o.c. stud n 20 0.049 19.0 1.42 28 2.59 52 e 20 0.049 19.0 1.42 28 2.59 52 s 20 0.049 19.0 1.42 28 2.59 52 w 20 0.049 19.0 1.42 28 2.59 52 all 80 0.049 19.0 1.42 114 2.59 207 n 317 0.201 4.1 5.83 1846 4.06 1286 e 534 0.201 4.1 5.83 3113 4.06 2168 s 127 0.201 4.1 5.83 737 4.06 514 w 611 0.201 4.1 5.83 3561 4.06 2481 all 1588 0.201 4.1 5.83 9258 4.06 6449 270 0.091 13.0 2.64 713 1.31 354 Windows 10C-v: 2 glazing, clr low-e outr, air gas, vnl frm mat, dr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.70); 10.5 ft overhang (6.7 ft window ht, 0.5 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 It overhang e (5.3 ft window ht, 0.8 ft sep.); 6.67 ft head ht W all 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" n thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 11.5 ft overhang (5.3 ft window ht, 0.5 ft sep.); 6.67 ft head ht 18 0.550 0 16.0 285 16.2 289 33 0.330 0 9.57 313 8.52 279 49 0.330 0 9.57 469 22.4 1096 49 0.330 0 9.57 469 22.4 1096 131 0.330 0 9.57 1251 18.9 2470 33 0.330 0 9.57 313 8.52 279 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" e 7 0.330 0 9.57 66 21.8 151 thk; NFRC rated (SHGC=0.23); 50% drapes, medium; 1.33 ft overhang (3.2 It window ht, 0.8 ft sep.); 6.67 ft head ht 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 16 0.330 0 9.57 156 8.91 146 thk; NFRC rated (8HGC=0.21); 50% drapes, medium; 1 ft overhang (5.3 ft window ht, 3.9 ft sep.); 6.67 ft head ht W rightsoft- 2021-JarF28 08:42:07 Right-Sute®Uriversal2021 21.0.02 RSU23828 Page 1 aterstone1820BGR\Lot22BIk5Waterstone1820BGR.rLQ Calc=MJB FrordDoorfaces: S 2A-2ov: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 16 0.330 0 9.57 156 9.17 150 thk; NFRC rated (SHGC=0.21); 50% drapes, medium; 1 ft overhang (5.3 ft window ht, 5.3 ft sep.); 6.67 ft head ht 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl fret mat, clr innr, 1/4" gap, 1/8" s 7 0.330 0 9.57 67 11.6 81 thk; NFRC rated (SHGC=0.31); 9 ft overhang (1.4 ft window ht, 0.5 ft sep.); 6.67 ft head ht F 2B-2fv: 2 glazing, clr low-e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8" s 13 0.330 0 9.57 128 9.72 130 thk; NFRC rated (SHGC=0.31); 50% drapes, medium; 9 ft overhang (6.7 ft window ht, 2 ft sep.); 6.67 ft head ht Doors 11 JO: Door, mtl fbrgl type s 20 0.600 6.3 17.4 355 17.6 359 Ceilings 16B-30ad: Attic ceiling, asphalt shingles roof mat, r-30 ceil ins, 1 /2" 1835 0.032 30.0 0.93 1703 1.69 3100 gypsum board int fnsh Floors 22A-tpl: Bg floor, light dry soil, on grade depth 212 0.989 0 28.7 6080 0 0 Wright90ft`° 2021-Jarr2808:42:07 �'� Rigl6-Sute®Uriversal202121.0.02RSU23828 Page f�.CA ...aterstone1820BGR\ ot22BIk5Waterstone1820BGR.nQ Calc=MJ8 Frort Door faces: S Project Summary Job: . Lot 22 Block 5 Watersone ... -- wrightsoft® Entire House By: ocs DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phore:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM roject information For: ADAMS HOMES 5367 Vespera Street, Fort Pierce, FL 34951 Notes: JA8-18-15 Change to 3.0 ton 2/16/16 S. Finch L. S. 1-28-21 VW K Design,• • Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 ` OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference; 57 gr/Ib Heating Summary Structure 24350 Btuh Ducts 4220 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 28570 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Heating Coolingg Area (ft2) 1820 1820 Volume (ft3) 18350 18350 Airchanges/hour 0.38 0.20 Equiv. AVF (cfm) 116 61 Heating Equipment Summary Make Carrier Trade CARRIER Model 25HBC537AP03 AHRI ref 204837926 Efficiency 8.5 HSPF Heating Input Heating output 34600 Btuh @ 47°F Temperature rise 27 OF Actual air flow 1167 cfm Airflowfactor 0.041 cfm/Btuh Static pressure 0.30 in H2O - Space thermostat Capacity balance point = 36 OF Backup: Input = 8 kW, Output = 25920 Btuh,100 AFUE Sensible Cooling Equipment Load Sizing Structure 20250 Btuh Ducts 5777 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data y Rate/swina multipplier 1.00 Equipment sensib16 load 26027 Btuh Latent Cooling Equipment Load Sizing Structure 3364 Btuh Ducts 1403 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 4767 Btuh Equipment Total Load (Sen+Lat) 30794 Btuh Req. total capacity at 0.75 SHR 2.9 ton Cooling Equipment Summary Make Carrier Trade CARRIER Cond 25HBC537AP03 Coil FX4DNF037L00 AHRI ref 204837926 Efficiency 12.5 EER,16 SEER Sensible cooling 26250 Btuh Latentcooling 8750 Btuh Total cooling 35000 Btuh Actual airflow 1167 cfm Airflowfactor 0.045 cfm/Btuh Static pressure 0.30 in H2O Load sensible heat ratio 0.85 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -r4- wrightsoft® 2021-JarF2808:42:07 - ^ - • mwM Right-Sute®Urrversal 2021 21.0.02 RSU23828 Page 1 aterstore1820BGR\Lot22BIk5Waterstore1820BGR.rye Calc=MJ8 FrordDoorfaces: S -�- wrightsoft, Right-M Wolrksheet Job: Lot 22 Block 5 Watersone 182... Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 Room name Entire House BDRM2 2 Exposed wall 212.0 It 36.0 It 3 Room height 10.0 It d 10.0 It heaV000l 4 Room dimensions 13.0 x 13.0 ft 5 Room area 1835.0 ftz 169.0 ftz Ty Construction U-value Or HTM (ft) Area z Load Area (ft2) Load number (Btuh/ftZT) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 60049 : nnv. J.;4? ..� :?.5.9 20 .?Q �28 = 52 _,. 0 a� 0 . 0 ' Blk wall, stucco ext 0.201 n 5.83 4.06 400 317 1846 1286 _ 130 _. _ 114 663 461 10C-v 0.550 n 15.95 1620 18 0 285 289 0 0 0 0 2A-2ov 0.330 n 9.57 8.52 33 0 313 279 16 0 156 139 11 2A-2ov 0.330 n 9.57 8.52 33 0 313 279 0 0 0 0 iN _ 16B 19ad, k 0048 _..0 _ems Blk wall, stucco e)d 201 a 5.83 4.06 590 534 3113 2168 100 100 583 406 2A 2ov 0.330 a 9.57 21.79 7 1 66 151 0 0 0 0 2A 2ov 0.330 e 9.57 22.35 49 3 469 1096 0 0 0 0 W 166y19ad wym _ 0049 s w. �] 42 2.59 , z _20; 20 n 28 . 52 0 ..4 Q u Q . _.. 0. BIk wall, stucco ext 0.201 s 5.83 4.06 200 127 737 514 0 0 0 0 2A-2ov 0.330 s 9.57 8.91 16 5 156 146 0 0 0 0 2A-2ov 0.330 s 9.57 9.17 16 0 156 150 0 0 0 0 2B-2fv 0.330 s 9.57 11.58 7 7 67 81 0 0 0 0 2B-2fv 0.330 s 9.57 9.72 13 13 128 130 0 0 0 0 11 JO s, 17.40 17.58 20 20 355 359 0 0 0 0 .. W r1.6B 19ad _ _0.600 _ _. 0049 .Z =42 _ .2w =b .._...; .20 =w =52 " o .. 5,ate D = ' ;Q w. M w..0; V)/ Blk wall stucco ext 0.201 w 5.83 4.06 660 611 3561 2481 130 130 758 528 I-G 2ov 0 330 w 957 2235 49 3 469 1096 0 0 0 P 12C Oswt __ s 0 091, 2.641:31. z ., 2F70 270713 , 354 , _ „A -0 _-.0 _ 0':0: C 1613-30ad 0.032 0.93 1.69 1835 1835 1703 3100 169 169 157 286 ;6080 _ w ,_- .._r:__ .vim._. ... ..,__..._.,.._..._........-.._._..�..... _..v_,..... _:..,.z.._. <. _..,..,_... m...... ..s{_,..,x....: _. sr ... �. -- ..m..,._,- ._.e._..�_ ... _...+._v. .,»:_.b,1a.'.zau� <.,. .....o.< �. • .� ..5..,...wa..e.._..., _�......,,.._w.,_ .: ye_ w. _.._.s�.� -.-:..-»._ _... us..,. _,.. .,„c�.u...e ....._ LIT ..0 .... .._.n,.. ,... ..._.vti...a_.� .. _[x:......�.� w.u.,, .r....�..M......,. -.eu..u£rt. ...,......1. .. .�.-,~ a......-.. _ ia.»......+,. w.-.s..mL..w'.n. 4z .,.�..ewi,.....,a ........ a..,s ._._. �Sfii, 2'"k7 ;.:......a., ....-...... ..... ..................t... .^^h--- ^.^,.. Wit; C..'. ,.''4 _ ""'_i YI 6 c) AED excursion 0 -108 Envelope loss/gain 20646 14165 3349 1712 12 a) Infiltration 3704 1035 691 193 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliancestother 3900 300 Subtotal (lines 6 to 13) 24350 20250 4040 2205 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 24350 20250 4040 2205 15 Dud loads 17% 29% 4220 5777 170/6 29% 700 629 Total room load 28570 26027 4740 2834 Air required (cfin) 1167 1167 194 127 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -ria- wrigFr,tsoft 2021-Jan-2808.42,07 Right-Sdte®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstore1B20BGR\Lot22Blk5Waterstone1820BGR.nQ Calc=MJS FrordDoorfaces: S - - wrightsoft, Right-M Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM Job: Lot 22 Block 5 Watersone 182... Date: By: DCS 1 Room name BATH 2 BDRM3 2 ENosed wall 6.0 it 13.0 it 3 Room height 10.0 it heaV000l 10.0 it heaU000l 4 Room dimensions 13.0 x 6.0 it 13.0 x 13.0 ft 5 Roam area 78.0 ft2 169.0 112 Ty Construction U-value Or HTM Area (ft2) Load Area (ftz) Load number (Btuh/ft2-`F) (Btuh/112) or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Coal Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W ::16&19ad � _. 00_49 wall, stucco ext 0.55 n 5.95 0 0 0 0 0 0 0 0 10C-v 10 0.550 n 15.95 620 1620 0 0 0 0 0 0 0 0 2A-2ov 0,330 n 9.57 8.52 0 0 0 0 0 0 0 0 11 2A 2ov 0.330 n 9.57 8.52 0 0 0 0 0 0 0 0 W 16 6-i 9acl7 a `N 0 049 ,.._c 1' l 2 59 2_, ,.. 'a0 w o �0 ._., � � A _.,., � _0 �.�.-21 -1-1 � 0 ._ � ;0 µM Y ' 4: V�1 Blk vdl slucoo ext 0.201 a 5.83 4.06 0 0 0 0 0 =10 ry0 LL 0 2A 2ov 0.330 a 9.57 21.79 0 0 0 0 0 0 0 0 2A 2ov 0.330 e_ 9.57 22.35 0 0 0 0 0 0 0 0 _ W . _ ,�__...._0 Blk wall, stucco ext 0201 s 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 8.91 0 0 0 0 0 0 0 0 2A2ov 0.330 s 9.57 9.17 0 0 0 0 0 0 0 0 2B-2fv 0.330 s 9.57 11.58 0 0 0 0 0 0 0 0 2B-2fv 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11JO 0600 s 1740 1758 0 0 0 0 0 0 0 0 W__>_. a16679ad. 00Q9 w 1:42 M259 �. '0:._�,z;�'�°0 2 0 }v.< 0. s0;' Q e0.. 0 w_ Blk wall, stucco ext 0.201 w 5.83 4.06 60 60 350 244 . ,. 130 114 _ 663 461 2A-2ov 0.330 w 9.57 22.35 0 0 0 0 16 1 156 365 P.w_ `_ a12C Osri' „0091 I]EI 0 f_0 _� Q 7 C _ 16B-30ad 0.032 _ 0.93 1.69 78 78 72 w 132 ww a _0 169 .�,_,.�_Q' 169 157 _ 286 F _ 224,ip1 0989 __. 6 0 ' ,_ _78 w.�_, _� _.1.7.2 .._ ;169.__ r n-77 v_,:-,, -177 77 ' s.,.�s _+�.. ,. ..,w�f-m ....,._�...._...a,..... Wiz... ...�.:�a..,.. .A,..,�sr ,.�.>......,�...._...;: .....,...�..e.......,.:,>.......r..,._:3:Wz 6 c) AED excursion -191 148 Envelope loss(gain 594 356 1349 1260 12 a) Infiltration 115 32 249 70 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 300 Subtotal (lines 6 to 13) 709 389 1598 1630 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 709 389 1598 1630 15 Duct loads 17% 29% 123 111 17% 29%1 277 465 Total room load 832 499 1875 2095 Air required (cfm) 34 22 77 94 Calculations approved WACCA to meet all reauirements of Manual J 8th Ed. �- wrigtitsoft� 2021-Jan-2808:42:07 ACCA Right-Srite®Urrversal 2021 21.0.02 RSU23828 Page 2 aterstore1820BGR\Lot22Blk5Waterstone1820BGR.rup Cale =MJ8 Front Door faces: S -- wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 22 Block 5 Watersone 182... Date: By: DCS 1 Roam name DINING/FOYER DENBDRM4 2 Exposed wall 25.0 It 31.0 It 3 Room height 10.0 It heaU000l 10.0 ft heaU000l 4 Room dimensions 1.0 x 276.0 ft 13.0 x 13.0 It 5 Room area 276.0 ft' 169.0 ft2 Ty Construction U-value Or HTM Area (ft) Load Area (ft') Load number (Btuh/ft- F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PB Heat Cool 6 W a1.6Bk19ad: 0049 n w 1,.42 2:59. 0 2= 0 0 _ _ Blk wall, stu000 end 0.201 . n 5.83 . 4.06 .:f 0 i.� 0 0 ., w.0O 0 0 .n' . 0 u _ 0 0 vv 1OC-v 0.550 n 15.95 1620 0 0 0 0 0 0 0 0 2A-2ov 0.330 n 9.57 8.52 0 0 0 0 0 0 0 0 112A 2ov 0.330 n 9.57 8.52 0 0 0 0 0 0 0 0 �,-179049 a 1;42.f 7 . 4r 0 f 2 ' 0 .12 = 0 =0 170 a `.0 -TaLEZ Zm:Z V+/ Blk wall, stu000 eM 0.201 a 5.83 4.06 0 0 0 0 50 50 291 203 2A-2ov 0.330 a 9.57 21.79 0 0 0 0 0 0 0 0 2A 2ov 0.330 e 9.57 22.35 0 0 0 0 0 0 0 0 0 ` � Q Blk wall, stucco ext 0.201 s 5.83 4.06 w _ 70 a� 29 170 119 130 - 97 567 395 2A-2ov 0.330 s 9.57 8.91 0 0 0 0 16 5 156 146 2A-2ov 0.330 s 9.57 9.17 0 0 0 0 16 0 156 150 26-2tv 0230 s 9.57 11.58 7 7 67 81 0 0 0 0 2B-2fv 0.330 s 9.57 9.72 13 13 128 130 0 0 0 0 11JO 0600 s 1740 17.58 20 20 359 0 0 0 W _ �16Bz19ad= w w�. 0049 wk 142 2: Z6 � 0._..�� _355 � 0 3 �� � ...d^0 _0 �_..: VI! a Bilk wall, stucco e)d _ 0.201 _, w w 5.83 4.06 �..���... 110 77 451 314 _.:��„a..i...0 130 130 :� ._•..r��0.Z= 758 528 -G 2A 2ov 0.330 w 9.57 22.35 2 313 730 0 0 0 _, Osw _ ., 009]. A 264; . 131i _33 ��.3,e70 .2,.,,�RK�70 Z ,_ 185 �.,, -�92 0 - ,.7 -0 , wQ ;0 _ . r C 16B-30ad 0.032 0.93 1.69 276 276 256 466 169 169 157 286 F : _ ipl 0989 28;68 0.00 _. Emm25 717 29= F-I-i-� Z ;0 _v. . w276 -E •Tt z�.. �a_..�..._,..._ .....,..�..u.._..3 ...waa:e ..�..,,._a''.0 c.....u___._. ...... ,._t.,J,_,_ _. _ �..,; .. �r...e.......,.e..- ....,..3�...,. ..�3� ,.,.t..._ :.'�iv......c,....�... _..-......_a,.. .max..... ... . C✓.� .c................ _�...d_.o.. �i ..._...,.....�.. __.- "."� •`-;-_ �'3 my � ^c # } '.: ......%.0 - -..,....�.. Lw.r..�...........-.[.,. ,!.n.s_.w...... ._. " t .v�..+_u. ».u.....-..x,.m� ..-...-.... u..a ._.�i.L'....k:di «a- .G ...�... -..,�.._..,«�.,�,�.Y. a...� .kw1,,....w.,,;,,... n....,o..+...a. .-. R ...e...._. ,..'-1.-."".Y „.,.. ....... T T 11", �.qc.....-_n,. ..._,. .._.».. _r_n_�-..._...+..A_ .�»u_ -' ,�.�... LL-.t. _w.........vey •.,.,.«...Civ.w. ?a..".� .n f .n`.'s..`_'s-..w.c,v.. �r ..,..vu.._. k _...._ � 4,...c..._ .o..�.m.,z d_ �.._._-...,gib r ..s .,._....... �,.t-u....,. r.... s.. �.....ss......C_,. .,,...:.`-.L.^,um. ' ... .ca,n .«...,.... u011-1.... Srz s. ..�a.....a.m .r...r «. �4 6 c) AED excursion 254 -30 Envelope losstgain 2642 25451 2975 1677 12 a) Infiltration 345 97 595 166 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 1 230 0 0 Appliancestother 0 300 Subtotal (lines 6 to 13) 2987 2871 3570 2143 Less mdemal load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2987 2871 3570 2143 151 Dudloads 17% 2 61 518 819 17% 299/6 619 611 Total room load 3505 3690 4189 2755 Air required (dm) 143 165 171 124 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rkwrigftitscwt- 2021-Jarr2808:42:07 Aft: ' Right-Suite@Uriversal202121.0.02RSU23828 Page alerstonel820BGR\Lot22BIk5Waterstone1820BGR.np Calc=MJ8 Frort Door faces: S wrightsoftn Right-JO Worksheet Job: Lot22 Block 5 Watersone 182... Entire House Date: DEL AIR HTG, A/C & REFRIG. INC By: DCS 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Fax:407-333-3853 Web: W W W.DELAIR.COM 1 Room name FAMILY RM MSTR BDRM 2 Exposed wall 13.0 ft 41.0 It 3 Room height 10.0 ft heat/000l 10.0 ft heat/cool 4 Room dimensions 13.0 x 22.0 ft 14.0 x 17.0 it 5 Room area 286.0 ftz 238.0 ftz Ty Construction U-value Or HTM Area (ft) Load Area (ftz) Load number (Btuh/ftz-9 (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W ... 16B 19ad > Blk wall, stucco e)d 0.201 n 5.83 4.06 130 79 463 323 140 124 721 502 WW 10C-v 0.550 n 15.95 1620 18 0 285 289 0 0 0 0 2A-2ov 0.330 n 9.57 8.52 0 0 0 0 16 0 156 139 112A-2ov 0.330 n 9.57 8.52 33 0 313 279 0 0 0 0 0 Q Blk wall, slucoo ext 0.201 a 5.83 4.06 0 0 0 0 ,: _H? m 170 .w 154 896 624 2A 2ov 0.330 e 9.57 21.79 0 0 0 0 0 0 0 0 2A 2ov 0.330 a 9.57 22.35 0 0 0 0 16 1 156 365 2:59.12 =4 4,,° -r }. 0' Do 2� 0 Blk wall, stucco e)d 0.201 s 5.83 4.06 0 0 : 0 _52 0 0 0 0 - :.;z. 0 2A-2ov 0.330 s 9.57 8.91 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 9.17 0 0 0 0 0 0 0 0 2B-2fv 0.330 s 9.57 11.58 0 0 0 0 0 0 0 0 2B-2fv 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11 JO 0.600 s 17AO 17.58 0 0 0 0 0 0 0 0 W 7"' 166-19ad -__ � =6:0 _. C _ 0 1.A2 =Z,2''59 =20 =:O =28 =0 =..A 0, =0 " _ �0 ZE,. E;:4: Blk wall, stucco ext 0.201 w 5B3 4.06 0 0 0 0 100 100 583 406 2A 2ov 0.330 w 9.57 22.35 0 0 0 0 0 0 0 0 P 2--12C Qsw ,. -61 1 ' ss 2:64 1 1.31, O ] f + :.0 i" 0. 7 6 71 U w C u 16B-30ad 0.032 0.93 1.69 �� _ 286 . , 286 265 _0 483 238 238 221 .402 F 22Q Oel." `.1a0 989 ' 28 6$ 0 R0 2$6T u373 'w.0 ?38 _ 1176 _ ._ _ _.., . M ,gip .41; 2-2 r .1 1.-.._. r, ...._.._± .i.s..1�___�_`_._.......,...a. ..,._, ..,._...... ..... ..,.,._...�... .a..�,,.,:.s .rcr...,..... ,.._. _ _.r,�„u..a.� ....,:: ' sa..�'� .......�._...,., .,..-h.�...._. ...e, .._.e."._.._.� _.._..._.._.-. .,.,.,.....,,._,.. _�.. _..._ ..�.....a....M .„ate..,.,; a>r., >... .,...._.... _a,....:..... _....I:..._.rnM__�.:..t ... _ .w.,. u_...i...... ...'.v: ......,.`P«'✓. „r.. .v.x_..#...... .7.iv..n»e,....., ..at,':r.Y .«.k.-...r.. ..J2......,.",.„_.. ..... ka....x...,.. ?.........a. .. w... ...... ...ww,,,.r�+e,... �a.d.,... - .h..-.w.. �.e.,...., - ..m-._5... ....ww.ew. tv.....aav vai..a�., cz.... ..a. - . _....-..u.... ..w .._ - .....w rt �...; L......-`.. .r- ....,-..da...mwn a......i..I . =...-�.+..._... .r../e.�. a„ pw+ .a s'cu.e i.. .:7-- m=«..}w. 6 c) AED excursion -139 -139 Envelope losstgain 1813 1441 3909 2300 12 a) Infiltration 403 113 787 220 b) Roomventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 1 230 Appliancestother 600 600 Subtotal (lines 6 to 13) 2216 2844 4696 3350 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2216 2844 4696 3350 15 Ductloads 17% 29% 384 811 17% 29% 814 956 Total room load 1 2600 3655 5510 4305 Air required (dm) I 106 164 1 225 193 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -rk- wr➢ghtsoR- 2021-Janr2808:42:07 Right-Suite®Universal 2021 21.0.02 RSU23828 Page 4 aterstone1820BGR\Lo122Blk5Waterstone18208GR.rp Calc=MJ8 Frond Door faces: S - wrightsoft® Right-JO Worksheet Entire House • DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 22 Block 5 Watersone 182... Date: By: DCS 1 Room name M BATH M WIC 2 Bposed wall 12.0 ft 0 It 3 Room height 10.0 ft heaUcool 10.0 ft heaV000l 4 Room dimensions 1.0 x 119.0 $ 7.0 x 7.0 ft 5 Room area 119.0 ft2 49.0 ft2 Ty Construction U-value Or HTM Area (ftz) Load Area (ft2) Load number (Btuh4[z ) (Btuh/112) or perimeter (ft) (13 h); or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W , 166 19ad' w 0 049 n a mg z - z.�0, � - -� ° ?-• wall, stucco ext _ 0.201 n 5.95 ...�ra_259,,.,��......�0.r�,_��.rsx,0wr.v..,:-.�.OH�,,x:..�.0.:; 620 0 0 0 0 0 a.,...._d.'0 0 .�..°I..Q 0 w �..�.,:.0. 0 10C-v 1 O 0.550 n 15.95 1620 0 0 0 0 0 0 0 0 2A-2ov 0.330 n 9.57 8.52 0 0 0 0 0 0 0 0 11 2A 2ov 0.330 n 957 8.52 0 0 0 0 0 0 0 0 W _ 16B 19ac1 z.. '`� .u£0049 e ` 142 259 11217- Blk wall, stu000 e)d 0.201 a 5.83 4.06 120 113 659 459 0 0 0 0 2A 2ov 0.330 a 9.57 21.79 7 1 66 151 0 0 0 0 2A 2ov 0.330 a 9,57 22.35 0 0 0 0 0 0 0 0 W 166.._19ad"� Blk vuall, stucco ext 0.201 s 5.83 4.06 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 957 8.91 0 0 0 0 0 0 0 0 2A-2ov 0.330 s 9.57 9.17 0 0 0 0 0 0 0 0 213-2tv OZ30 s 9.57 11.58 0 0 0 0 0 0 0 0 213-2tv 0.330 s 9.57 9.72 0 0 0 0 0 0 0 0 11JO 0600 s 17AO 17.58 0 0 0 0 0 0 0 0 ,W .; z16619ad " 0049zww � T.• u72:59 =M0.". Q 5ma "� ZU� 5 b.. , d =0 : t M M. Q. tl�1 Blk vuall, stucco ext 0.201 w 5.83 4.06 0 0 0 0 0 0 0 0 -G 2A 2ov 0.330 w 9.57 22.35 0 0 0 0 0 0 0 0 4_Osw%��.��...�.,:_,IIi�. 1:3j:.1 M� ==.0 =!� 0. 1 ;-=0 Ezm'..-�.Q M .P C 168-30ad ,<,.,...,;009J.= 0.032 0.93 .Z..._ 1.69 119 119 110 201 49 49 45 , .'0. 83 z:Q;00 119 L? 34 } bE 0 49 '. � Q _7 4 0 z.x. .. , ,?`D �..,. u �,�..cLm,...r.:''�' .�......,...,...n +., �.�,. r t'�,. _.....,.� _ "_�": .: ..,�+�.,,.� ,:..s.X .a< �.nla.& h ..a �,.. x-^+ »...f,: `a:`,- ;,^-max ..�..�,_,..., , ,�..,-,..a�w -°,r ,,......_d,3.�xa...e `-i„^�'" �- `"""' "^ '� r �,"`-t^'" ';� -Y � ,�, �"""--'^.,s r^• � nay ..Q :Z,.a:.:.�,a #wQ'&'.... 7" �.,?„3;>ns may. " ..,,,.,.,n.. ..�.,..,.,..b�....... �,.r.....:,...._ .'�.,-......,:�.:; a.,....z:sa._zfa.:.' '#'". ,Y°2vJ4' , w.. Y,b...., _,.t. . _:G ,€d»�Gi' m'A. ,. .�...�5 av I GYP' i" ^Ae„ ._.T..,,...r-.. ._..-..,aa�.w.�,s.m.,us-w.�.....,aS,.....��r.;...at ..,�� �.,....s.fµ. >.:�x...0 ...e-..✓.:L2:`...`,.,�.,. �,,,.._�.,.w. ,S�.l.`...,,...<.�� r�atabdk.::.,...A.r.. .w.-,t'u faw<.e�n` .�F1,..�v.X,a�.iiY<ti .,...�.�.ez�3Y,.a'*� _._ri€ .:✓i -i1'.._, rwT.9 � sfit?.,..�3„Pwm,F`. Rf,.w.du.w ".."'T G.?�: .,.^� Y a3S awd ss. �vw.::ti �..4L<s ftLw.ci •. `o'Y ^^`-,.'np'_d' *^+rz -m,.� t ""-9^` w.wp ".,.�. .P4 'T. ...'v-�+T.'. ^�,`,pa.' i�ry '+"'�^ a'^' �'....,.,m.wL.�,l 'r 6 e) AED excursion 1 -4 Envelope loss/gain 1180 810 45 79 12 a) Infiltration 230 64 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancesbther 0 0 Subtotal (lines 6 to 13) 1410 1 875 45 79 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 ' 0 0 0 14 Subtotal 1410 875 45 79 15 Duct cads 17% 29°/ 244 250 17% 29% 8 23 Total room load 1655 1124 53 101 Air required (cfm) 68 50 2 5 Calculations approved byACCAto meet all requirements of Manual J 8th Ed. -*- wr➢ghtsoft� Right-SuteC�Uriversal202121.0.02RSU23828 2021-Jarr2808:42:07Page5 aterstone1820BGRUt22BIk5Waterstone1820BGR.rp Calc=MJ8 Front Door faces: S -�- wrightsoft, Right-JO Worksheet Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY, SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM Job: Lot 22 Block 5 Watersone 182... Date: By. DCS 1 Room name KrrCHENuNOOK LAUNDRY 2 Exlmsed wall 29.0 ft 6.0 ft 3 Room height 10.0 ft heat/cool 10.0 It heaV000l 4 5 Room dimensions Room area 1.0 x 246.0 ft 246.0 ft2 6.0 x 6.0 ft 36.0 ftz Ty Construction U-value Or HTM Area (ft2) Load Area (ftz) Load number (Btuh4t2-fl (Btuh4t2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VU 16619.dT 0049 VVV���/// BIk wall, stucco e)d 10C-v 0.201 0.550 n n 5.83 15.95 4.06 1620 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 11 W` y/ 2A-2ov 2A-2ov 166-19ad_ =�' BIk wall, stucco ext 0.330 0.330 r.11 0.201 n n e-. a 9.57 9.57 5.83 8.52 8.52 2:59 4.06 0 0 `� . . 0 150 0 0 ~.vM.+ 0 117 0 0 -� 0 684 0 0 _ _,. 0. 476 0 0 = j 0 0 L- :.�A 0 0 0 �=-=X 0 0 0 =0 0 0 2A 2ov 2A 2ov 0230 _ 0.330 a e; . 9.57 9.57_ 21.79 22.35 0 33 0 r_ 2 0 313 0 _ 730 0 0 0 0 0 0 0 0 BIk wall, stucco ext 2A-2ov 2A-2ov 0.201 0.330 0.330 s s S 5.83 9.57 9.57 4.06 8.91 9.17 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 26-2fv 2B-2(v 0.330 0.330 s s 9.57 9.57 11.58 9.72 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 W W 11JO 16B-19ad� `_,_ BIk wall, stu000 ext 0.600 _ .0 049: 0201 s w.n w 17.40 =A4=n2 5.83 17.58 4.06 0 ..:�_ o 0 0 ..==a 0 0 ==0 0 1 0 � 0 0 0 �:< 0 0 0 =Z. 3 0 0 =..n.,,,.,=......ZQ 0 ...._, ;:t). 0 0 L.-G_ Pr C 2A2ov 12C_Osuv ' .166-30ad~ _ 0330 ". 0 091. _ �Yµ0.032 w a ' 9.57 ,_.. 264:. 0.93 2235 1 3 ' 1.69 0 , 140 246 __0 . ,-' 140 246 0 �., 369 228 T 0 �. -;�:183 416 _0 � " =Q 36 _ 0 ' _._.,. 60 36 .0 _ �. 58 33 0 -.29. 61 . _. �0 989 _; 28_68' �0.00 _ 246 -_ _' 4 .R_ 44 =:� 0 __.,=36 : 6 = ; 172 'a -6 - -. _. _._...._.....L.... _.w_... ,_.a...._,.. go-_.. ..v...zJ.:r. «._._r..'«.::i �_. ,.,,....._.,..,.>.......a_.-.,,.u... ..s...a..._..v.�. ...�.z..w,>°«i:.:, ..a,........_..L.:, _u-......�....E...,....._:.....�.....:._,.Cs:+`.:s+_w . ....._s,...a..ss.:»: u.o,,..,...+ .�.:.J ;......._s._._... -sw>.:._...,. _ �_...tl......a..............._...-.d _....w u. 'Tw ...x....._. w..oa,dL�Y ,...�...... �3.«+.. _.+-.... .�....�..k.�. ....�...v.o- c....... 6 c) AED excursion 74 -35 Envelope loss/gain 2426 1879 364 105 12 a) Infiltration 288 80 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancesrother 1200 600 Subtotal (lines 6 to 13) 2714 3160 364 705 Less external load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2714 3160 364 705 15 Ductloads 17% 29% 470 901 1 -.1 29% 63 201 Total room load 3184 4061 427 906 Air required (cfm) 130 182 17 41 Calculations approved bvACCAto meet all reauirements of Manual J 8th Ed. -rid- 2021 -Jan-28 08.42:07 Right-Sute®Universal 2021 21.0.02 RSU23828 Page 6 aterstone1820BGR\Lot22BIk5Waterstone1820BGR.np Cale =MJ8 Front Door faces: S -- wrightsoft® Duct System Summary Entire House DEL AIR HTG, A/C & REFRIG. INC 531 CODISCOWAY,,SANFORD,FL32771 Phone:407-333-2665 Fax:407-333-3853 Web:WWW.DELAIR.COM iLroject intormation For: ADAMS HOMES 5367 Vespera Street, Fort Pierce, FL 34951 Job: Lot 22 Block 5 Watersone ... Date: By: DCS Heating Cooling External static pressure 0.30 in H2O 0.30 in H2O Pressure losses 0.06 in H2O 0.06 in H2O Available static pressure 0.24 in H2O 0.24 in H2O Supply / return available pressure 0.120 / 0.120 in H2O 0.120 / 0.120 in H2O Lowest fricti on rate 0.212 in/100ft 0.212 in/100ft Actual airflow 1167 cfm 1167 cfm Total effective length (TEL) 113 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH 2 h 832 34 22 0.278 4.0 Ox 0 VI Fx 16.3 70.0 BDRM2 h 4740 194 127 0.258 8.0 Ox 0 VIFx 22.9 70.0 BDRM3 c 2095 77 94 0.305 6.0 Ox 0 VIFx 8.6 70.0 DENBDRM4 h 4189 171 124 0.288 7.0 Ox0 VIFx 13.2 70.0 DINING/FOYER c 3690 143 165 0.314 7.0 Ox0 VIFx 6.5 70.0 FAMILYRM C 3655 106 164 0.233 7.0 Ox 0 VIFx 17.9 85.0 sti KrrCHEN/NOOK C 4061 130 182 0.228 8.0 Ox 0 VIFx 20.1 85.0 sti LAUNDRY c 906 17 41 0.223 4.0 Ox 0 VIFx 22.7 85.0 sti M. BATH h 1655 68 50 0.224 5.0 Ox 0 VI Fx 22.2 85.0 st1 KWIC c 101 2 5 0.225 4.0 Ox 0 VI Fx 21.9 85.0 st1 MSTRBDRM h 5510 225 193 0.212 8.0 Ox0 VIFx 28.2 85.0 sti Supply Trunk Detail Table Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk sti PeakAVF 549 635 0.212 594 14.0 0 x 0 VinlFlx : * wrightsoft® 2021 -Jan-28 08.42,08 I. ........, Right-Sute®Uriversal2021 21.0.02 RSU23828 Page 1 ACCK aterstone1820BGR\Lot228Ik5Waterstone1820BGR.rLp Calc=MJB FrordDoorfaces: S Return Branch Detail Table Name Grille Size (in) Htg (cfm) Cig (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rbi Ox 0 1167 1167 0 0 0 0 Ox 0 VIFx t wrightsoft® 2021-Jarf2808:42:08 aM,,.t•, w� . gym, ., Ngtd-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 aterstone1820BGRIot22BMWaterstone1820BGR.np Calc=MJ8 Front Door faces: S 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: Lot 22 Block 5 Waterstone 1820 BGR Builder Name: ADAMS HOMES Street: 5367 Vespera Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y U Owner: Jurisdiction: 661000 = Design Location: FL, ST LUCIE_CO_INTL U COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall requirements The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with; a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/doorjambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim' joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and'plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or cemlonas. a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400. 1/28/2021 8:57 AM EnergyGauge® USA 7.0.00 -. FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST Florida Department of Business and Professional Regulation Simulated Performance Alternative (Performance) Method Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification (usually four pages/may be greater) ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7 ❑ Mandatory Requirements (five pages) Required prior to CO: ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ If Form R405 duct leakage type indicates anything other than "default lea kage° then a completed 2020 Duct Leakage Test Report - Performance Method (usually one page) 1/28/2021 8:56:14 AM EnergyGauge@ USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: Job Information. Builder: ADAMS HOMES Community: Lot: 22-5 Address: 5367 Vespera Street City: Fort Pierce State: FL Zip: 34951 Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERf Method O PRESCRIPTIVE METHOD=The building or dwellingaunit shall.be teste&and verrfied as.having an air leakage rate of natexceeding 7 air ho changeIi ur at a pressure of 0.2 inch w g��(50,Pascals)'in' Clii-nate Zones 1 and 2 0. PERFORMANCE or•ERI METHOD -The building or dwelling unitshall be tested andyenfied as having an air leakage rate ofnot,ezceeding; the selected ACH(50);valUe, as shown,pn Form R405 2020. (Performance) gr.R4o6=2020'(ERI) 'section Iabeletl as`infiltration„,sub=section AGH50. &H(50) :specified on Form R4054020-Energy Calc (Performance), or- R406-2020 (ER!): 7.000 x 60 _ 18200 — Method for calculating building volume: CFM(50) Building Volume ACH(50) Q Retrieved from architectural plans 1-1 PASS Code • software calculated When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. Testing Company° Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected above. Signature of Tester: Date of Test: Printed Name of Tester: License/Certification #: Issuing Authority: 1/28/2021 8:57:11 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 Florida Building Code, Energy Conservation, 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5367 Vespera Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL' display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shallbe fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or door's, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. Exception: Site -built windows, skylights and doors. 1/2812021 8:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 5 . MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or • enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. SECTION R403 SYSTEMS R403.1 Controls. ❑ R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. ❑ R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities that form the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constrdcted and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. ❑ R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory forbuildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. ❑ R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41°C) or below 55°F (13°C) shall be insulated to a minimum of R-3. R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. ❑ R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403.5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall "❑ be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 1/28/2021 8:56 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) • ❑ R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3 % inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). ❑ R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). ❑ R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. ❑ R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. ❑ R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with atilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. ❑ R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. ❑ R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. ❑ R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based ❑ on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMU (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any. For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 1/28/2021 8:56 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS - (Continued) EiR403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the 2. calculated total sensible load but not less than 80 percent of that load. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. El R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. ❑ R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8'C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. EiR403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 1/28/2021 8:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 4 of 5 ElR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed, over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. ❑ R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. Fi R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. F1 R403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following requirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. F1 R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS 1I R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. 1/28/2021 8:56 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 5 of 5