HomeMy WebLinkAboutProduct Approval EVALUATION REPORT OF UNION CORRUGATING COMPANY 1 26 GA.ADVANTAGE-LOK II' FLORIDA BUILDING CODE 7TH EDITION(2020) FLORIDA PRODUCT APPROVAL FL 20484.2-R2 ' ROOFING t,j METAL ROOFING REVIEWED FOR Prepared For: CODE COMPLIANCE Union Corrugating Coma 701 S. King St. p ST' -..1CIE COUNTY Fayetteville,NC 28301 BOCC Telephone: (910)483-0479 ���� Fax: (910)483-1091 Fil+- Cop-., Prepared By: Bala Sockalingam,Ph.D.,P.E. Florida Professional Engineer#62240 1216 N Lansing Ave.,Suite C Tulsa,OK 74106 Telephone: (918)492-5992 FAX: (866)366-1543 This report consists of Evaluation Report(3 Pages including cover) ;JIM11111,t Installation Details (1 Page) 1epti'SGGKAL/ty '''�` moo`°`r.Q'•'�G�N SF•��?j�'=_ w��`:• No 62240 f~ .L Report No. C2401-2 p-a'• pF '. ``w Date: 10.10.2020 �T aT E .,C p F1 n lca 1cj . 2'z2 4 FL 20484.2-R2 C2401-2 10.10.2020 Page 2 of 3 Manufacturer: Union Corrugating Company Product Name: Advantage-Lok II Panel Pao Description: Max. 16" wide coverage with 1" high ribs Materials: Minimum 26 ga., 50 ksi steel. Galvanized coated steel (ASTM A653) or Galvalume coated steel (ASTM A792) or painted steel (ASTM A755). Corrosion resistant as per FBC 2020 Section 1507.4.3. Deck Description: Min. 7/16" thick OSB or min. 15/32" thick APA rated plywood or min. 3/4' thick wood plank (min SG of 0.42) for new and existing constructions. Designed by others and installed as per FBC 2020. New Underlayment: Minimum underlayment as per FBC 2020 Section 1507.4.5.1. V/,/Required for new construction. Existing Underlayment: One layer of asphalt shingles over one layer of#30 felt. For reroofing (Optional) construction only. Slope: 1/2:12 or greater in accordance with FBC 2020 Section 1507.4.2. Requires applied lap sealant for roof slopes less than 2:12. Design Uplift Pressure: 30.0 psf at panel fastener spacing of 13-7/8" o.c. along seam (Factor of Safety=2) 63. sf at anel fastener spacing of 9-1/4" o. seam 8.5 psf at pane as ene mg o - 8" o.c. along seam 112.5 psf at seam fastener spacing of 4-5/8" o.c. along seam with 3/16" diameter bead adhesive in panel seam 131.5 psf at seam fastener spacing of 4-5/8" o.c. along seam into min. 15/32" thick APA rated plywood with retainer strap Panel Attachment: #10-12 pancake head wood screws along panel seam. Fasteners are corrosion resistant as per FBC 2020 Section 1507.4.4. Fastener shall be of sufficient length to penetrate through the deck a minimum of 3/8". Retainer Strap: 5" wide, 24 ga., 50 ksi strap fastened to deck with 2 rows of#10-12 x 1" long pancake head screws at 12" o.c. spacing and 6" staggered. The strap is continuous over the entire corner or edge roof zones. Prior to the panel installation, two rows of 3/8" bead of adhesive are field applied along the length of the strap and a row of 3/8" bead of adhesive on the male leg of panel. Seam Adhesive: Sikaflex-201 or APS 500 Advance Polymer Sealant. In lieu of Sikaflex or APS sealant, adhesive with greater or equal tensile properties may be used. FL 20484.2-R2 C2401-2 10.10.2020 Page 3 of 3 Test Standards: Roof assembly tested in accordance with UL580-06 `Uplift Resistance of Roof Assemblies' & UL1897-04 `Uplift Tests for Roof Covering Systems' or TAS 125-03 `Standard Requirements for Metal Roofing Systems'. Test Equivalency: The test procedures in UL 1897-04 comply with test procedures prescribed in UL 1897-12. Code Compliance: The product described herein has demonstrated compliance with FBC 2020 Section 1507.4. Product Limitations: Design wind loads shall be determined for each project in accordance with FBC 2020 Section 1609 or ASCE 7-16 using allowable stress design. The maximum fastener spacing listed herein shall not be exceeded. This evaluation report is not applicable in High Velocity Hurricane Zone. Refer to current NOA for use of this product in High Velocity Hurricane Zone. Fire classification is not within scope of this Evaluation Report. Refer to FBC 2020 Section 1505 and current approved roofing materials directory or ASTM E108/UL790 report from an accredited laboratory for fire ratings of this product. Supporting Documents: UL580&UL1897 Test Reports PRI Construction Materials Technologies UCC-006-02-1 Rev 1,Reporting Date 2/10/12 TAS 125 Test Report Farabaugh Engineering and Testing Inc. Project No. T302-16, Reporting Date 11/16/16, Revised Date 1/18/17 Project No. T303-16,Reporting Date 11/16/16,Revised Date 1/18/17 Project No. T304-16, Reporting Date 11/16/16,Revised Date 1/18/17 DMMN Bl: IIELCED BY: NEW UNDERLAYMENT SEE DETAILS 1 & 2 PANEL OVERLAP PANEL FASTENER ROOF PANEL PDT di a,E'$ 0 MAX. 13-7/8" O.C. I i EXISTING UNDERLAYMENT OSB 7/16" THICK (MIN.) OR n (OPTIONAL) EXISTING SHINGLES DECK ATTACHMENT AND BE PLYWOOD 15/32" THICK (MIN.) - RAFTER/JOIST/TRUSS (OPTIONAL) SUPPORTS MUST DESIGNED AND INSTALLED AT MAX. 24 O.C. BY OTHERS A TYPICAL PANEL INSTALLATION X-SECTION NEW UNDERLAYMENT 3/8" BEAD OF (2) 3/8" BEAD OF #10-12 X 1" SCREWS PANEL FASTENER ROOF PANEL ADHESIVE ADHESIVE 2 ROWS STAGGERED 0 MAX. 4-5/8" O.C. 0 6" O.C. i- O U I,pj W N'o If I H VfU N Z II n RETAINER STRAP PLYWOOD 15/32" THICK (MIN.) ii ZE,.i� DECK ATTACHMENT AND 5" WIDE, 24 GA 0 Y-? SUPPORTS MUST BE U 6 o DESIGNED AND INSTALLED RAFTER/JOIST/TRUSS Z BY OTHERS AT MAX. 24' O.C. i oCy'o^ PANEL INSTALLATION WITH RETAINER STRIP MIN 26 GA. PANEL w z'# z Li #10-12 PANCAKE HEAD a a x WOOD FASTENER ALLOWABLE UPLIFT PRESSURE Y NEW UNDERLAYMENT = n EXISTING SHINGLES FASTENER MINIMUM SEAM RETAINER PRESSURE (OPTIONAL) SPACING SUBSTRATE ADHESIVE STRIP (pSF) ¢ a ' -—-—-— —-—' ALONG RIB DIAMETER z a � 13-7/8" 7/16" OSB NONE NONE 30.0 0 2 � 9-1/4" 7/16" OSB NONE NONE 63.5 ¢ 3" EXISTING UNDERLAYMENT 4-5/8" 7/16" OSB NONE NONE 78.5N (OPTIONAL) DETAIL 1 OSB 7/16" THICK (MIN.) OR 4-5/8" 7/16" OSB 3/16" NONE 112.5 N - a PLYWOOD 15/32 THICK (MIN.) 4-5/8" 15/32" PLY 3/8" 1 REQUIRED 1315 gi SIKAFLEX 201 MIN 26 GA. PANEL OR EQUIVALENT 3/16 BEAD GENERAL NOTES: #10-12 PANCAKE HEAD 1. ARCHITECTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE WOOD FASTENER FLORIDA BUILDING CODE (FBC). NEW UNDERLAYMENT 2. ROOF PANELS ARE SHALL BE 26 GA EFFECTIVE COVERING WIDTH OF EXISTING SHINGLES OF PANEL = 16". 3. THE ROOF PANELS SHALL BE INSTALLED OVER SHEATHING & STRUCTURE AS (OPTIONAL) SPECIFIED ON THIS DRAWING. 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT. THIS PANEL SYSTEM MAY NOT BE INSTALLED WHEN THE REQUIRED DESIGN WIND LQADS ARE GREATER THAN THE ALLOWABLE WIND LOAD TABLE. 5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING & THE FLORIDA EXISTING UNDERLAYMENT BUILDING CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM AA N (OPTIONAL) DETAIL 2 OSB 7/16" THICK (MIN.) OR REQUIREMENTS OF THIS DRAWING & THE CODE, THE CODE SHALL CONTROL. C2401-2 PLYWOOD 15/32" THICK (MIN.) 6. RAFTERS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS REQUIRED FOR EACH APPLICATION AND ARE THE RESPONSIBILITY OF OTHERS. SHEET No. 1 of 1 i�a 5T. LUCIE .. ST LUCIE COUNTY ROOFING PERMIT INFORMATION SHEET a Florida Building Code 7th Edition (2020) Based on Section 1525 of the Florida Building Code-Build INSTRUCTION PAGE COMPLETE THE NECESSARY SECTIONS OF THE UNIFORM ROOFING SHEET APPLICATION FORM AND ATTACH THE REQUIRED DOCUMENTS AS NOTED BELOW: Required Sections of Attachments Required Roof System the Permit Application See List Below Form Low Slope Application A,B,C 1,2,3,4,5.6,7 Prescriptive BUR-RAS 150 A,B,C 2,4,5,6,7 Asphaltic Shingles A,B,D 1,2.4,5,6,7 Concrete or Clay Tile A,B,D,E 1,2,3,4,5,6,7 Metal Roofs A,B,D 1,2,3,4,5,6,7- Wood Shingles and A,B,D 1,2,4,5,6,7 Shakes Other As Applicable 1,2,3,4,5,6,7 ATTACHMENTS REQUIRED As Applicable): 1. Fire Directory Listing Page 2. From Product Approval: Front Page Specific System Description Specific System Limitations General Limitations Applicable Detail Drawings 3, Design Calculations per Chapter 16,or if applicable, RAS 127 or RAS 128 4. Other Component of Product Approval 5. Municipal Permit Application 6. Owners Notification for Roofing Considerations(Reroofing Only) 7, Any Required Roof Testing/Calculation Documentation Form RooflnfoFeb21 Rev Feb 18,2021 ST. L' UCIE V'VORKS Section A (General Information). Master Permit No. Process No. Ito✓.✓a✓L 6 L/17— /�Contractors Name: o Jd S p,AJ License# tlp ��.• ,�, Job Address M ROOF CATEGORY Lt�ow Slope ❑Mechanically Fastened Tile ❑Mortar/Adhesive Set Tiles ❑Asphaltic Shingles ❑Metal Panel/Shingles ❑Wood Shingles/Shakes ❑ Prescriptive BUR-RAS 150 ROOF ROOF TYPE. C9Aew roof ❑ Repair ❑ Maintenance ❑ Reroofing QWrrecovering ROOF SYSTEM INFORMATION Low Slope Roof Area(SF) V5`0 Steep Sloped Roof Area(SF) Total(SF) 2 if O Section B(Roof Plan) Sketch Roof Plan: Illustrate all levels and sections, roof drains, scuppers, overflow scuppers and overflow drains. Include dimensions of sections and levels, clearly identify dimensions of elevated pressure zones and location of parapets. I i I I i i I i i I i 1 ST. LUCIE WORKS Section C (Low Slope Roof) Surfacing: Fill in specific roof assembly components and identify Fastener Spacing for Anchor/Base Sheet Attachment: manufacturer Zone 1':_.._."oc @ Lap,#Rows ® goo (If a component is not used,identify as"NA") Zone 1:—"oc @ Lap,#Rows ® `0 System Manufacturer: /4 tkiAA 1C IMA rAl Zone 2:—" oc @ Lap,#Rows ® 00 Zone 3:�"oc @ Lap,#Rows ®�`0 Product Approval No.: �' ���� �2 Number of Fasteners Per Insulation Board: Design Wind Pressures, From RAS 128 Or Calculations: Zone 1': Zone 1: Zone 2: Zone 3:�� Zone 1': Zone 1: Zone 2: Zone 3: Illustrate Components Noted and Details as Applicable: Max. Design Pressure, from the specific product approval Woodblocking, Gutter, Edge Termination, Stripping, system: Z-6 U Flashing, Continuous Cleat, Cant Strip, Base Flashing, Counterflashing,Coping, Etc. ., Deck: Indicate: Mean Roof Height, Parapet Height, Height of Base Type: m t-nt L Flashing,Component Material, Material'Thickness, Fastener Type,FastenerSpacing or Submit Manufacturers Details that Gauge Thickness: _y Comply with RAS 111 and Chapter 16.. Slope: Anchor/Base Sheet& No. df Ply(s): Anchor/Base Sheet Fa�t FT ener/Bondin M ter'al: f .Aa Insulation Base Layer: Base Insultation Size and Thickness: Parapet Base Insulation Fastener/Bonding Material: Height Top Insulation Layer: Top Insulation Size and Thickness: FT. Top Insulation Fastener/Bonding Material: Mean Base Sheet(s)& No.of Ply(s): Roof Base Sheet Fastener/Bonding Material: Height Ply Sheet(s)'&No. of Ply(s): Ply Sheet Fastener/Bonding Material: Top Ply: Top Ply Fastener/Bonding Material: ST. L'UCIE WORKS Section D (Steep Slope Roof System) !}I,4-TIC A4LT? ZS L4 /�T Roof System Manufacturer: u,�,..�Qrr 'JAC,7( Notice of Acceptance Number: Minimum Design Wind Pressures, If Applicable(From RAS 127 or Calculations): -`7 Zone 1: Zone 2e: Zone 2n: Zone 2r:_Zone 3e�JZone 3r: (Z I C Deck Type: ( S L Side G-P Type Underlayment: Roof Slope: 12 Insulation: �R Fire Barrier: Ridge Ventilation? Fastener Type &Spacing: 3 141 Adhesive Type: Type Cap Sheet Mean RoaF Height: Roof Covering: Type&Size Drip Edge: ST. LUCIE WORKS Section E(Tile Calculations) /L)/ For Moment based the systems,choose either Method 1 or 2.Compare the values for Mr with the values from Mf.If the Mf values are greater than or equal to the Mrvalues,for each area of the roof,then the tile attachment method is acceptable. Method 1'Moment Based Tile Calculations Per RAS 12T (Zone 1 : x k = _�-Mg ;M„ Product Approval Mi (Zone 2e: _ X k ` -a_M9: =Mra Product Approval Mf (Zone 2n: x k = _�-Mg Man Product Approval Mf (Zone 2r. X k = _�-Mg: =Mar Product Approval Mf (Zone 3e: x k = _)-Mg: =Mt3, Product Approval Mf (Zone 3r. x k = ---J-Mg: =Mr& Product Approval Mf- Method 2"Simplified Tile Calculations Per Table Below" Required Moment of Resistance(Mr) From Table Below Product Approval Mf Mr required Moment Resistance* ft oof Slope 15' 20' 25' 30' 40' 34.4 36.5 38.2 39.7 42.2 32.2 34.4 36.0 37.4 39.8 4:12 30.4 32.2 33.8 35.1 37.3 5:12 28.4 30.1 31.6 32.8 34.9 6:12 26.4 28.0 29.4 30.5 32.4 7:12 24.4 25.9 27.1 28.2 30.0 *Must be used in conjunction with a list of moment based the systems • For Uplift based the systems use Method 3. Compare the values for F'with the values for Fr If the F'values are greater than or equal to the Fr values,for each area of the roof,then the tile attachment method is acceptable. Method 3"Uplift Based Tile Calculations Per RAS 12T (Zone 1: x L =x W:= -W: cos r =Fri Product Approval F' (Zone 2e: x L =x W:= )-W: cos r =Fr2e Product Approval F' (Zone 2n: x L =x W:= )-W: cos r =Fr2n Product Approval F' (Zone 2r: x L =x W:= -W: cos r =Fr2r Product Approval F' (Zone 3e: x L =x W:= )-W: cos r =Fr3e Product Approval F' (Zone 3r: x L =x W:= -W: cos r =Fr3r Product Approval F' Where to Obtain Information Description Symbol Where to find Design Pressure From applicable table in RAS 127 or by an engineering analysis g Zones 1,Ze,2n,2r,3e,3r prepared by PE based on ASCE 7 Mean Roof Height H Job Site Roof Slope 0 Job Site Aerodynamic Multiplier a Product Approval Restoring Moment due to Gravity M, Product Approval Attachment Resistance Mf Product Approval Required Moment Resistance Mg Calculated Minimum Attachment Resistance F' Product Approval Required Uplift Resistance Fr Calculated Average Tile Weight W Product Approval Tile Dimensions L=length W=width Product Approval All calculations must be submitted to the building official at the time of permit application.