‐ 1 ‐ | Page
sparc design 3021 Jupiter Park Circle Suite 102 Jupiter Florida
561.203.7539 www.sparcdesign.us
February 25,2021
St. Lucie County
Planning & Development Services
Building and Code Regulation Division
2300 Virginia Avenue
Fort Pierce, Florida 34982
RE: Harbour Ridge Yacht and Country Club
Lakeside Activity Center
Permit Comments
sparc design project P2019.137
Dear Plan reviewers:
In regard to the permit comments for the above referenced project, I am writing to clarify the comments
received on August 4,2020. Response and comments are listed below.
Plans Examiner - Plumbing
1. Comment: NEED 1 HI AND LOW DRINKING FOUNTAIN PER 410.3 FLORIDA PLUMBING CODE 6TH EDITION
Response: P000 and P101 are revised to include Hi/Lo drinking fountain requirement.
2. Comment: A DRY WELL CAN ONLY BE USED FOR CONDENSATE DISPOSAL. NEED A SEWER LINE AND
CONNECTION FOR THE DRINKING FOUNDTAINS OR AN APPROVED SYSTEM PER CHAPTER 13 OF THE
FLORIDA PLUMBING CODE 2017 6TH EDITION.
Response: The drywell usage here is intended for clear-water waste which we propose is similar to
the condensate. The nearest building sewer is much too far from the drinking fountain locations to
be able to meet the required invert elevation. Calling for a sewer line connection would prompt
the project to have a lift station installed for (2) drinking fountains. We are proposing the dry well
usage as an alternative design solution similar to a remote park structure where it is not feasible to
have a sewer connection. See attached for a certification letter from the civil engineer regarding
the soils being acceptable for the drywell application.
Plans Examiner Review
1. Comment: PLEASE PROVIDE USE AND OCCUPANCY CLASSIFICATION FOR PICKLEBALL COURT AND
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES, PER 302.1 AND TABLE 2902.1 RESPECTIVELY OF THE
FLORIDA BUILDING CODE 6TH EDITION, 2017.
‐ 2 ‐ | Page
sparc design 3021 Jupiter Park Circle Suite 102 Jupiter Florida
561.203.7539 www.sparcdesign.us
Response: Plumbing fixture occupancy table added to Sheet A000 Project information sheet.
Occupancy for the existing sales center building to remain and the pickleball courts are included.
Sports courts are calculated at 100sf/person, which amounts to approximately 8 players/court. This
allows for (2) sets of teams per court for occupancy.
Sincerely,
Sean P Sukhu, Partner
1655 27th Street, Suite 2 Vero Beach, Florida 32960
Phone: (772) 567-5300 Fax: (772) 794-1106
mastmolr@bellsouth.net
MASTELLER & MOLER, INC.
~ CIVIL ENGINEERS ~
February 26, 2021
Andy Wentz
St. Lucie County Plans Examiner Plumbing
2300 Virginia Avenue
Fort Pierce, Florida 34982
RE: Harbor Ridge Recreation Site
Dear Andy:
This letter is intended to serve as the Engineer’s Certification that based on my review of the
results of a recent soils exploration performed by KSM Engineering in the proposed drywell
locations, the soils are acceptable for drywell applications for the drinking fountains.
Please let me know if you have any questions.
Sincerely,
MASTELLER & MOLER, INC.
FEB 26 2021
Stephen E. Moler, PE
FL PE # 33193
Vice President
SEM/sh
file #1902
(SLC_Cert_DryWell_21-0226.docx)
PROPOSED PICKLE
BALL COURTS
PROPOSED PICKLE
BALL COURTS PROPOSED PICKLE
BALL COURTS
PROPOSED SHADE
STRUCTURE
PROPOSED SHADE
STRUCTURE
EXISTING DOG PARK
EXISTING LAKESIDE
ACTIVITY CENTER
PHASE 2
P000
PLUMBING NOTES, LEGENDS,
SCHEDULES & DETAILS
AAV AIR ADMITTANCE VALVE
ACW AUTOMATIC CLOTHES WASHER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
CI CAST IRON
CFU COLD WATER FIXTURE UNIT
CO CLEANOUT
COND CONDENSATE
CTG CLEANOUT TO GRADE
CM COFFEE MAKER
CW COLD WATER
DFU DRAINAGE FIXTURE UNIT
DW DISHWASHER
EFD EMERGENCY FLOOR DRAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FF FINISHED FLOOR
FLR FLOOR
GWH GAS WATER HEATER
HB HOSE BIBB
HC HANDICAP
HFU HOT WATER FIXTURE UNIT
HW HOT WATER
HWR HOT WATER RECIRC.
IE INVERT ELEVATION
LAV LAVATORY
NTS NOT TO SCALE
OD ROOF OVERFLOW DRAIN
RD ROOF DRAIN
RE RELOCATE EXISTING
REF REFERENCE
REF REFRIGERATOR
RO REVERSE OSMOSIS
SK SINK
SH SHOWER
SST STAINLESS STEEL
TFU TOTAL FIXTURE UNIT
TUB BATH TUB
UR URINAL
VTR VENT TO ROOF
WC WATER CLOSET
WCO WALL CLEANOUT
PLUMBING ABBREVIATIONS
NOTE: NOT ALL ABBREVIATIONS MAY APPLY TO PLANS
ALL EQUIPMENT SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN
INSTALLATION INSTRUCTIONS.
CONTRACTOR SHALL COORDINATE SPECIFIC REQUIREMENTS OF EQUIPMENT WITH MANUFACTURER SHOP
DRAWINGS.
MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES IN THEIR
LATEST REVISIONS.
PLUMBING NOTES, LEGENDS, SCHEDULES & DETAILSP000
FLOOR PLANS & ISOMETRICSP101
1.ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE CODES AS SHOWN.
2.THE PLUMBING CONTRACTOR SHALL BE HELD TO HAVE VERIFIED ALL EXISTING CONDITIONS, INCLUDING SITE VISITATION, AND REVIEW OF AS
BUILT DOCUMENTATION AS APPLICABLE PRIOR TO BIDDING, ORDERING, FABRICATION OR INSTALLATION OF ANY MATERIALS OR EQUIPMENT ON
THIS PROJECT.
3.UNLESS OTHERWISE SPECIFIED, ALL MATERIALS SHALL BE NEW. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A
FIRST CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE. ALL EXCAVATION AND BACK FILL AS REQUIRED FOR
THIS PHASE OF CONSTRUCTION SHALL BE A PART OF THIS CONTRACT.
4.REQUIRED INSURANCE SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
DAMAGE FOR THE DURATION OF THE WORK.
5.PLUMBING CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND TESTS, PLUMBING CONTRACTOR TO OBTAIN PERMIT
AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT. PLUMBING CONTRACTOR MUST BE PRESENT FOR ALL
INSPECTIONS OF HIS WORK BY REGULATORY AUTHORITIES.
6.DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE TO BE READ IN CONJUNCTION WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL AND
STRUCTURAL DRAWINGS AND ARE CONSIDERED TO BE ONE SET OF DOCUMENTS. BENDS OFFSETS AND TRANSITIONS WILL BE REQUIRED TO
PROVIDE AND INSTALL A COMPLETE AND FUNCTIONAL SYSTEM AND SHALL BE PROVIDED BY THE PLUMBING CONTRACTOR AT NO ADDITIONAL
COST. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES, PIPING, EQUIPMENT, ETC.
7.CONTRACTOR SHALL SUBMIT FOR APPROVAL ELECTRONIC PDF COPIES OF MANUFACTURER DRAWINGS FOR ALL PLUMBING FIXTURES AND
EQUIPMENT INCLUDED IN CONTRACT. ALL MATERIAL SHALL BE NEW FROM A U.S. MANUFACTURER OF GOOD QUALITY. ALL WORK SHALL BE
PERFORMED IN A WORKMANLIKE MANNER BY SKILLED TRADESMEN.
8.ENGINEER OF RECORD RECOGNIZES THE GENERAL CONTRACTOR AND ALL OTHER CONTRACTORS TO BE LICENSED IN THE STATE OF FLORIDA.
GENERAL CONTRACTOR SHALL CONSIDER THE PROJECT AS ONE SET OF DOCUMENTS. GENERAL CONTRACTOR SHALL PROVIDE AN ENTIRE SET OF
DOCUMENTS SHOWING ALL TRADES TO EACH SUBCONTRACTOR PRIOR TO BIDDING AND CONSTRUCTION. GENERAL CONTRACTOR SHALL
COORDINATE WITH ALL OTHER CONTRACTORS TO INFORM ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR CONFLICTS ON THE DOCUMENTS
PRIOR TO SUBMITTING FINAL BID AND COMMENCING ANY WORK. CONTRACTOR SHALL MAKE HIMSELF AVAILABLE FOR REVIEWING DOCUMENTS
WITH ARCHITECT/ENGINEER UPON REQUEST
9.THE GENERAL CONTRACTOR SHALL PROVIDE IN WRITING ON COMPANY LETTER HEAD ALL ITEMS VALUE ENGINEERED OR OMITTED FROM ENTIRE
PROJECT. THIS DOCUMENT SHALL HAVE DETAILED DESCRIPTION AND TRANSPARENCY OF ALL ITEMS IN EACH DISCIPLINE AND TRADE.
INFORMATION SHALL BE PROVIDED TO ARCHITECT AND ENGINEER FOR REVIEW PRIOR TO SUBMITTING FINAL BID. CONTRACTOR SHALL MAKE
HIMSELF AVAILABLE FOR REVIEWING DOCUMENTS WITH ARCHITECT/ENGINEER/OWNER UPON REQUEST.
10.ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. REPORT ANY
DISCREPANCY TO ENGINEER/ARCHITECT PRIOR TO BEGINNING CONSTRUCTION.
11.VERIFY LOCATION, SIZE, DIRECTION OF FLOW AND INVERTS OF ALL EXISTING UTILITIES PRIOR TO BEGINNING OF CONSTRUCTION. ADVISE
ENGINEER OF ANY DISCREPANCIES.
12.WATER DISTRIBUTION PIPING SHALL BE PEX, PVC, OR HDPE.
13.ALL PVC SHALL BE SOLID CORE NO CELLULAR CORE.
14.ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS AND APPROPRIATELY MARKED ACCESS PANELS. COORDINATE LOCATIONS
WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION.
15.PLUMBING CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1)
YEAR FROM DATE OF ACCEPTANCE BY OWNER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL
INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED.
16.UNLESS OTHERWISE INDICATED ON THE PLAN, THE SOIL, WASTE AND STORM WATER PIPING SHALL BE PVC ABOVE SLAB AND PVC BELOW SLAB
AND FOR VENT PIPE ABOVE A TRAP. PVC MAY NOT BE USED THROUGH RATED ASSEMBLIES OR IN RETURN AIR PLENUMS. WASTE PIPING FOR
WATER DISCHARGED FROM DISHWASHER OR ANY APPLIANCE HANDLING WASTE WATER OVER 140° SHALL HAVE A DRAIN TEMPERING VALVE TO
PRIOR TO ITS DISCHARGE ONTO THE MAIN BUILDING WASTE LINE.
17.PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES.
18.ALL CONTROL VALVES SHALL BE TAGGED AND MARKED. A REPRODUCIBLE DIAGRAM LOCATING ALL VALVES SHALL BE PROVIDED FOR
OWNER/OPERATOR.
19.PROVIDE ANGLE STOPS ON ALL WATER SERVICE LINES TO FIXTURES FOR INDIVIDUAL SHUT-OFF.
20.DRYWELL LOCATIONS INDICATED ON THE CONSTRUCTION DOCUMENTS ARE APPROXIMATE. THE CONTRACTOR SHALL COORDINATE WITH THE
ARCHITECT AND THE CIVIL ENGINEER PRIOR TO PLACEMENT AS REQUIRED.
21.PLUMBING CONTRACTOR SHALL PROVIDE ENGINEER WITH AS-BUILT DRAWINGS UPON COMPLETION.
22.UNLESS OTHERWISE SPECIFIED, THE PLUMBING CONTRACTOR SHALL PROVIDE MOTOR STARTERS AS REQUIRED FOR ALL PLUMBING RELATED
EQUIPMENT. THE STARTERS SHALL BE MATCHED TO THE EQUIPMENT AND THE SERVICE VOLTAGE. PHASE LOSS MONITORS/PROTECTION SHALL BE
REQUIRED ALL THREE PHASE EQUIPMENT. COORDINATE PRIOR TO ORDERING/PURCHASING/INSTALLATION.
23.CONTRACTOR SHALL SUBMIT FOR APPROVAL (BEFORE ORDERING OR INSTALLING SUCH UNITS) TO THE MECHANICAL ENGINEER A TYPED LIST OF
ALL BACKFLOW PREVENTERS TO BE USED FOR PROJECT.
24.ALL PIPING TO BE TESTED IN ACCORDANCE WITH SECTION 312 OF THE FLORIDA PLUMBING CODE.
1-800-432-4770
Sunshine State One Call of Florida, Inc.
It's the Law!
before you dig
Call 48 hours
GENERAL PLUMBING NOTES
ADDITIONAL NOTES
FLORIDA FIRE PREVENTION CODE, 6TH EDITION (2017)
FLORIDA BUILDING CODE PLUMBING, 6TH EDITION (2017)
FLORIDA BUILDING CODE, 6TH EDITION (2017)
APPLICABLE BUILDING CODES
PLUMBING SHEET INDEX
PLUMBING SYMBOL LEGEND
NOTE: NOT ALL SYMBOLS MAY APPLY TO PLANS
SANITARY DRAIN
SANITARY VENT
GREASE WASTE DRAIN
STORM WATER DRAIN
CONDENSATE DRAIN
COLD WATER SUPPLY PIPE
HOT WATER SUPPLY PIPE
HOT WATER RECIRCULATION
PIPE
140°F HOT WATER SUPPLY
PIPE
EXISTING PIPE
DEMOLISHED PIPE
DOMESTIC WATER DOWN
DOMESTIC WATER UP
FULL-OPEN VALVE
CONNECT TO EXISTING AT THIS
LOCATION
POINT OF DEMO
X"Ø STM
X"Ø SAN
X"Ø GW
X"Ø HWR
X"Ø HW
X"Ø HW 140
X"Ø CW
X"Ø VNT
FULL-OPEN VALVE W/
ACCESS DOOR
WATER SUPPLY PIPE WITH
CAPPED END
X"Ø COND
PRESSURE RELIEF
VENT LINE
X"Ø PRL
Project Number:
PROJECT ISSUE DATES:
SHEET NUMBER
DATE:
architecture
3021 Jupiter Park Circle
Suite 102
Jupiter, FL 33458
t 561.203.7539
sparcdesign
planning
interiors
www.sparcdesign.us
Jupiter Commerce Park
SEAN PATRICK SUKHUAR97488HARBOUR RIDGE YACHTAND COUNTRY CLUBLAKESIDE ACTIVITY CENTERPALM CITY, FLORIDAAA26003806SHEET NAME
2019.137
2020.03.27
2020.03.27ISSUED FOR BID/PERMIT
This Document is an instrument of
service and the property of
Sun Patrick Architecture, INC. AA26003806
and shall remain their property. This document is
not suitable for use on other projects or in other
locations. Publication is expressly limited to the
original site for which it was prepared.
2020 Sun Patrick Architecture, INC.C
This item has been electronically signed
and sealed by Sean Sukhu, R.A. on
the date and/or time stamp shown
using a digital signature
Printed copies of this document are not
considered signed and sealed and
the signature must be verified on
any electronic copies.
PLUMBING PLAN VIEW
SCALE: 1/128"=1'-0"1
1,2,3
P101
N1 1/4" PVC DRAIN
1 1/4" PVC
AIR GAP
TO DRYWELL
1 DRINKING FOUNTAIN DETAIL
DRY WELL DETAIL2
1-1/2"Ø PVC COND.
(UNDERGROUND ONLY)
MIRAFI FILTER CLOTH
#57 DRAINFIELD ROCK
UP TO WITHING 3" OF INVERT
55 GALLON HVY PE
DRUM W/REMOVABLE
LID (MARMON CLAMP).
OPEN BOTTOM.
ABOVEGROUND COND. PIPE MATERIAL SHALL BE PER GENERAL NOTES.
30x30x3" CONC. COVER WITH 2
3 8" STAINLESS STEEL HANDLES
EMBEDDED
GRADE
FROM
DRINKING
FOUNTAIN
PLUMBING SCOPE OF WORK:
THE PLUMBING CONTRACTOR SHALL FIELD VERIFY ALL EXISTING DOMESTIC WATER RUNS PRIOR TO COMMENCING
WORK. NOTIFY ENGINEER OF RECORD IF EXISTING CONDITIONS DO NOT SUPPORT THE DESIGN INTENT.
THE PLUMBING SCOPE OF WORK INCLUDES BUT IS NOT LIMITED TO:
1.INSTALLATION OF NEW REDUCED PRESSURE ZONE (RPZ) UP-STREAM FROM PREVIOUS.
2.INSTALLATION OF NEW WATER FOUNTAINS AND DRY WELLS.
3.PROVIDE NEW SANITARY PIPING SYSTEM TO NEW FIXTURES.
4.PROVIDE NEW COLD WATER SUPPLY LINES OFF OF EXISTING MAINS TO WATER FOUNTAINS.
PLUMBING BOX
RGD
Consulting Engineers
2151 S. ALT A1A, SUITE 2000, JUPITER, FL 33477 (561) 743-0165
These Drawings are NOT VALID for any purpose which requires the original
signature and seal of the engineer unless the original signature and seal are affixed.
Drawings not signed and sealed by the engineer shall not be submitted to any
authority or used for any purpose where signed and sealed documents are required.
Mechanical ElectricalStructural
made in the usa
ww w .rgdengineers.com
Plumbing
DATE 9.8.2020
ROBERT DAVENPORT P.E.
FLORIDA P.E. NO. 31932
MECHANICAL ENGINEER
CERT OF AUTH 5454
PROJECT #: 19-1168
Fire Protection ROBER T G . DAVE
N
P
ORTROBER T G .DAVE
N
P
ORTL IC E NSELICENSE
PROFE
S
SIONA L E N G INEERPROFE
S
SIONA L E N G INEERFLOR I D AFLORIDA
No. 31932
STATE OF
1
BLDG DEPT 20.09.081
PROPOSED PICKLE
BALL COURTS
PROPOSED PICKLE
BALL COURTS
PROPOSED PICKLE
BALL COURTS
PROPOSED SHADE
STRUCTURE
PROPOSED SHADE
STRUCTURE
EXISTING DOG PARK
EXISTING LAKESIDE
ACTIVITY CENTER
PHASE 2
HCEWC-1
1
EWC-1
1
DRY WELL
DRY WELL
EXISTING WATER
FOUNTAIN TO REMAIN
SANITARY KEY NOTES:
1.DRINKING FOUNTAIN DISCHARGE TO DRYWELL. COORDINATE FINAL LOCATION WITH ARCH. REFER
TO DETAIL; P000-1.
#
PROPOSED PICKLE
BALL COURTS
PROPOSED PICKLE
BALL COURTS
PROPOSED PICKLE
BALL COURTS
PROPOSED SHADE
STRUCTURE
PROPOSED SHADE
STRUCTURE
EXISTING DOG PARK
EXISTING LAKESIDE
ACTIVITY CENTER
PHASE 2
EXISTING 1"Ø BACKFLOW
PREVENTER TO REMAIN
THROUGHOUT PHASE 1
FOR CONTINUATION
REFERENCE CIVIL
3/4"Ø CW
EWC-1
HCEWC-1
2"Ø CW - EXISITING2"Ø CW
1
2 3/4"Ø CW3
3/4"Ø CW
EXISTING WATER
FOUNTAIN TO REMAIN
DOMESTIC WATER KEY NOTES:
1.PROVIDE 2"Ø LEAD FREE BACKFLOW PREVENTER TO ADD REDUCED PRESSURE ZONE (RPZ).
COORDINATE MAKE AND MODEL WITH UTILITY.
2.PROVIDE 2"Ø WATER SERVICE. CAP-AND-CUT FOR FUTURE SERVICE TO PHASE 2 BUILDING.
3.PROVIDE NON-METALLIC BOX FOR ACCESS BELOW GRADE SHUT-OFF VALVE FOR DOMESTIC
WATER.
#
P101
SANITARY FLOOR PLAN
SCALE: 1/32" = 1'-0"1
FLOOR PLANS & ISOMETRICS
Project Number:
PROJECT ISSUE DATES:
SHEET NUMBER
DATE:
architecture
3021 Jupiter Park Circle
Suite 102
Jupiter, FL 33458
t 561.203.7539
sparcdesign
planning
interiors
www.sparcdesign.us
Jupiter Commerce Park
SEAN PATRICK SUKHUAR97488HARBOUR RIDGE YACHTAND COUNTRY CLUBLAKESIDE ACTIVITY CENTERPALM CITY, FLORIDAAA26003806SHEET NAME
2019.137
2020.03.27
2020.03.27ISSUED FOR BID/PERMIT
This Document is an instrument of
service and the property of
Sun Patrick Architecture, INC. AA26003806
and shall remain their property. This document is
not suitable for use on other projects or in other
locations. Publication is expressly limited to the
original site for which it was prepared.
2020 Sun Patrick Architecture, INC.C
This item has been electronically signed
and sealed by Sean Sukhu, R.A. on
the date and/or time stamp shown
using a digital signature
Printed copies of this document are not
considered signed and sealed and
the signature must be verified on
any electronic copies.
DOMESTIC WATER FLOOR PLAN
SCALE: 1/32" = 1'-0"2N DOMESTIC WATER ISOMETRIC PLAN
N.T.S3
N3/
4
"
Ø
C
W
E
W
C
-
1
H
C
E
W
C
-
1
2"Ø
C
W -
E
XI
SI
TI
N
G
2"
Ø
C
W
3/4"Ø
C
W
3/
4
"
Ø
C
W
RGD
Consulting Engineers
2151 S. ALT A1A, SUITE 2000, JUPITER, FL 33477 (561) 743-0165
These Drawings are NOT VALID for any purpose which requires the original
signature and seal of the engineer unless the original signature and seal are affixed.
Drawings not signed and sealed by the engineer shall not be submitted to any
authority or used for any purpose where signed and sealed documents are required.
Mechanical ElectricalStructural
made in the usa
ww w .rgdengineers.com
Plumbing
DATE 9.8.2020
ROBERT DAVENPORT P.E.
FLORIDA P.E. NO. 31932
MECHANICAL ENGINEER
CERT OF AUTH 5454
PROJECT #: 19-1168
Fire Protection ROBER T G . DAVE
N
P
ORTROBER T G .DAVE
N
P
ORTL IC E NSELICENSE
PROFE
S
SIONA L E N G INEERPROFE
S
SIONA L E N G INEERFLOR I D AFLORIDA
No. 31932
STATE OF
BLDG DEPT 20.09.081
1
1
1
THIS ITEM HAS BEENELECTRONICALLY SIGNED ANDSEALED BY LEONARD A. TYLKA JR.,P.E. USING A DIGITAL SIGNATUREAND DATE. PRINTED COPIES OFTHIS DOCUMENT ARE NOTCONSIDERED SIGNED AND SEALEDAND THE SIGNATURE MUST BEVERIFIED ON ANY ELECTRONICCOPIES.Digitally signed by Leonard A Tylka Jr. Date: 2021.01.23 09:18:25 -05'00'