Product Evaluation Report
GULF COAST.SUPPLY& MANUFACTURING, LLC
26 Ga. GulfRib4N1 Roof Panel over 15132"Plywood
Florida Product Approval #11651.22 R2
Florida Building Code 2014
Per Rule 61 G20-3
Method: 1 -D
Category: Roofing
Subcategory: Metal Roofing
Compliance Method: 61 G20-3.005(1)(d)
NON HVHZ
Product Manufacturer:
Gulf Coast Supply & Manufacturing, LLC.
14429 SW 2nd Place, Suite G30
Newberry, FL 32669 �GI�
,k
' \ sF tit
'*: No. 75519 •:_
Engineer Evaluator:
Dan Kuhn, P.E. #75519
Florida Evaluation ANE ID: 10743 ?0•, STATE OF
,c
Validator: S�oNAL EN
Locke Bowden, P.E. #49704 ''''"� '''%%
9450 Alysbury Place o613°���5
Montgomery, AL 36117
Contents:
Evaluation Report Pages 1 - 5
FL#11651.22 R2•JUNE 15,2015
PRODUCT
• • , EVALUATION REPORT
FLORIDA Gulfc>
SUPPLY & MANUFACTURING
GULFRITM
26 GUAGE GULFRIB TM PANEL . . . .
FLORIDA PRODUCT APPROVAL NO. 11651.22 R2
TM
Compliance Statement: The product as described in this report has demonstrated compliance with the
Florida Building Code 2014, Sections 1504.3.2.
Product Description: GulfRibTM, 3/a" Rib Roof Panel, Minimum 26 Ga. Steel, 36" Coverage,
through fastened roof panel over minimum 15/32" Plywood Decking. Non
Structural application.
Panel Material/Standards: Material: Minimum 26 Ga. Steel,ASTM A792 or ASTM A653 G90 conforming to
Florida Building Code 2014 Section 1507.4.3.
Paint Finish Optional
Yield Strength: Min. 80.Oksi
Corrosion Resistance: Panel Material shall comply with Florida Building Code
2014, Section 1507.4.3.
Panel Dimension(s): Thickness: 0.018" Minimum
Width: 36" Coverage
Rib Height: 3/a" Major Rib at 9" O.C.
Panel Fastener: #9-15x1.5" HWH with sealing washing or approved equal
11/a" minimum penetration through plywood.
Corrosion Resistance: Per Florida Building Code 2014, Section 1506.6, 1507.4.4
Substrate Description: Minimum 15/32" thick,APA Rated plywood over supports at maximum 24" O.C.
Design of plywood and plywood support re outside the scope of this evaluation.
Must be designed in accordance w/Flo r 2014.
Design Uplift Pressures: Table"A"
Maximum Total Uplift D�esiq�n Pr�essu1AIM.2�5 psf ®� 59.25 psf
Fastener Pattern fil .9"-911=911--911, _ t5"-2.5"-6.5"-
"6.5"-2.5"-6.5"
Fastener Pattern Spacing
Design Pressure includes a Safety F tor;=2.0.
FL#11651.22 R2•JUNE 15,2015
PRODUCT EVALUATION .
i
FLORIDA • . GuIX66st
SUPPLY & MANUFACTURING
kL TM
GULFIFD\� I •
' :TUPANEL OVER PLYWOOD
FLORIDA PRODUCT APPROVAL NO. 11651.22 R,2
17
Code Compliance: The product described herein has demonstrated compliance with the
Florida Building Code 2014, Sections 1504.3.2.
Evaluation Report Scope: The product evaluation is limited to compliance with the structural wind load
requirements of the Florida Building Code 2014, as relates to Rule 61 G20-3.
Performance Standards: The product described herein has demonstrated compliance with:
• UL 580-06-Test for Uplift Resistance of Roof Assemblies
• UL 1897-04-Uplift Test for Roof Covering Systems.
Reference Data: 1. UL 580-94/1897-98 Uplift Test
Force Engineering &Testing, Inc. (FBC Organization#TST 5328)
Report No. 117-0062T-07A, B, Dated 02/19/2007
2. Certificate of Independence
By Dan Kuhn, P.E. (FL#75519)@ Kuhn Engineering, LLC
(FBC Organization#ANE ID: 10743)
Test Standard Equivalence: 1. The UL 580-94 test standard is equivalent to the UL 580-06 test standard.
2. The UL 1897-98 test standard is equivalent to the UL 1897-04 test
standard.
Quality Assurance Entity: The manufacturer has established compliance of roof panel products in
accordance with the Florida Building Code and Rule 61 G20-3.005(3)for
manufacturing under a quality assurance program audited by an approved quality
assurance entity.
Minimum Slope Range: Minimum Slope shall comply with Florida Building Code 2014, including
Section 1507.4.2 and in accordance with Manufacturers recommendations. For
slopes less than 3:12, lap sealant must be used in the panel side laps.
Installation: Install per Manufacturer's recommended details.
Underlayment: Shall comply with Florida Building Code 2014 section 1507.4.5.1 and 1507.4.5.2.
FL#11651.22 R2•JUNE 15,2015
PRODUCT • .
KUHN •
FLORIDA PRODUCT APPRMFAL GuIfCod t
SUPPLY & MANUFACTURING
RITM
• • _ . . . .
FLORIDA PRODUCT APPROVALNO 11651.22 F;
TM
Roof Panel Fire Classification: Fire classification is not part of this acceptance.
Shear Diaphragm: Shear Diaphragm values are outside the scope of this report.
Design Procedure: For roofs within the parameters listed on the load table,fastening pattern must
at a minimum meet those listed for the applicable wind zone. For all roofs outside
the parameters listed on the load table, design wind loads shall be determined
for each project in accordance with FBC 2014 Section 1609 or ASCE 7-10
using allowable stress design.The maximum fastener spacing listed herein shall
not be exceeded.This evaluation report is not applicable in High Velocity
Hurricane Zone. Refer to current NOA or HVHZ evaluation report for use of this
product in High Velocity Hurricane Zone.
FL#11651.22 R2•JUNE 15,2015
o
Gulfcoayf
SUPPLY & MANUFACTURING
7 TIVI
GULFRU
+ ' iTIVI • • •
TM
ENGINEER LOAD TABLE:26 Ga. GulfRibTM Panel over 15/32" Plywood
BLilld)ngs havingaRoof�(uleanHelghts.20 '�,YRoof Saope�2 %12� 12 s/12 Gable or Hip Roof,U1/md,}Speed120 a
180rnph; Exposure C Risk Ca e"gory llnc sedBuildm°g;basedon'Flonda�Bu)I�d ngCo'tle201 ; � FDN
120 130 140 150 160 170 180
WIIND FASTENER SUBSTRATE
(MIN.1/4"
SPEED penetration) (MIN.15/32") ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER ON CENTER
SPACING SPACING SPACING SPACING SPACING SPACING SPACING
ZONE 1 #9 15X1 5 rPlywootlY 2 T1fPE 1, i24' TYPE 1" 24 2 T1Y1PE�1 2 TYPE 1 4 PTYPE 1 24 fiTY E 1y 24 TYPE 1
ZONE 2 #9-15x1.5" Plywood 24",TYPE 1 24 TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 1 24",TYPE 2
ZONE 3 ' #9-15x1 5" PlyvvOOd 24 TYPE 1 24'- TYPE 1 24 TYPE 1 12 TYPE 2 12TYPE 2 �1 2, 4TYPE42 12 �TgYP.E 2
1.)PANEL DESCRIPTION:GULFRIBTM, MIN.26 GA.,GRADE 80,36"COVERAGE,3/4"TALL.
• 2.)PANEL FASTENER:#9-15X1.5" HWH WITH SEALING WASHER OR APPROVED EQUAL
3.)MAXIMUM ALLOWABLE PANEL UPLIFT PRESSURE:69.25 PSF @ 24" O.C.FASTENER SPACING TYPE I FASTENER PATTERN, 159.25
PSF @ 12" O.C. FASTENER SPACING TYPE 2 FASTENER PATTERN BASED ON TAS 125, UL 580/UL 1897 TESTING.
4.)PLYWOOD DECKING:MIN.75/a2"THICK PLYWOOD MUST BE DESIGNED IN ACCORDANCE WITH FLORIDA BUILDING CODE 2014.
5.)ROOF SLOPE:ON ROOF SLOPES LESS THAN 3:12, LAP SEALANT MUST BE USED IN PANEL SIDE LAPS.
6.)LOAD TABLE BASED ON WIND PRESSURES CALCULATED PER ASCE 7-10(KD=0.85)MULTIPLIED BY 0.6 PER FLORIDA BUILDING
CODE 2014
ZONE 2 HIP ROOF a Note:Dimension(a)is defined as 10%of the minimum width of the building or
---------AE /
ZONE 1� 40%of the mean height of the roof,whichever is smaller,however,(a)cannot be
1-11 — a less than either 4%of the minimum width of the building or 3 feet.
TYPE 1 FASTENER PATTERN
RIAt Panel Lap
/ZONE 1 L t.Tape Seal for use on Slopes less than 3:12
(1)#9-15 x 1-1/2•w/Sealer Washer Q 24.O.C.Max-----
TYPE 2 FASTENER PATTERN
ZONE2 GABLE ROOF (-6.5" 2.5"{-6.5"—{2.5"1
-6.5" 2.5 1
-6.5" 2.5"
I I
I I /
RIDGE L Cont.Tape Seal for use on Slopes less than 3:12
l (1)#9-15 x 1-1/2°w/Sealer Washer Q 10 O.C.Max.
,--——————--————————————-
a
ZONE 1
I I
+----------------------1
ZONE 3 EAVE
FL#11651.22 R2•JUNE 15,2015