Loading...
HomeMy WebLinkAboutProject InformationCompliance R pl S CReport ManuaompJob: Lot 24 Block 5 Waterston... -F- wrightsoft® p Date: NOVEMBER 3, 2010 Entire House By. Dcs DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 i Project Information For: ADAM HOMES 5364 Vespera Street, Cocoa, FL 32926 Cooling Equipment Design Conditions Outdoor design DB: 90.4OF Sensible gain: 20544 Btuh Entering coil DB: 76.4°F Outdoor design WB: 77.4OF Latent gain: 4174 Btuh Entering coil WB: 63.3OF Indoor design DB: 75.0 OF Total gain: 24718 Btuh Indoor FIR 50% Estimated airflow: . 947 cfm Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 00 Actual airflow: 947 cfm Sensible capacity: 22276 Btuh 108%of load Latent capacity: 5040 Btuh 121 % of load Total capacity: 27317 Btuh 111%of load SHR: 82% Design Conditions Outdoor design DB: 41.0 cF Heat loss: 23104 Btuh Entering coil DB: 69.5 OF Indoor design DB: 70.0 OF I Manufacturer's Performance Data at Actual Design Conditions Equipment type: SpIitASHP Manufacturer: Carrier Model: 25HBC530AP03+FX4DNF031 L00 Actual airflow: 947 cfm Output capacity: 27529 Btuh 119% of load Capacity balance: 36 °F Supplemental heat required: 0 Btuh Economic balance: -99 OF Backup equipment type: Elec strip Manufacturer: Model: Actual airflow: 947 cfm Output capacity: 5.7 kW 840/.of load Temp. rise: 19 OF I Meets all requirements ofACCA Manual S. C Wrlghtso'Ft' 2021-Feb-1508:43:59 n�i•�•/O.h AIm 4M1� empM Riglt-Srite® Uriversal 202121.0.02 RSU23828 Page w aterstone1635BGR\Lot24BIk5Waterstcne1635BGR.rp Calc=MJ8 House faces: W Project Summary Job: Lot 24 Block 5 Watersto... 1- wrightsofte n Date: NOVEMBER 3, 2010 Entire House By: Des DEL -AIR HEATING AND AIR CONDITIONING ~ 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Proiect Information For: ADAM HOMES 5364 Vespera Street, Cocoa, FL 32926 Notes: REVISED 3-26-12 SGT REVISED 8-18-15 JA L. S. 2-15-21 VWK Design Information I Weather: St Lucie Co Intl, FL, US Winter Design Conditions Summer Design Conditions Outside db 41 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 29 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 57 grAb Heating Summary Sensible Cooling Equipment Load Sizing Structure 19720 Btuh Structure j 15845 Btuh Ducts 3384 Btuh Ducts 4698 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm)i 0 Btuh none Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 23104 Btuh Use manufacturer's data y Rate/swin multiplier 1.00 Infiltration EquipmenKsensible load 20544 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 3039 Btuh Ducts 1135 Btuh Central vent (0 cfm)J 0 Btuh Heating Cooling Area (none) (ft2) 1639 163g Equipment latent load 4174 Btuh Volume (ft3) 15827 15827 Air changes/hour 0.38 0.20 Equipment Total Load (Sen+Lat) 24718 Btuh Equiv. AVF (cfm) 100 53 Req. total capacity at 0.75 SHR 2.3 ton Heating Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIER Trade CARRIER Model 25HBC530AP03 Cond 25HBC530AP03 AHRI ref 204840289 Coil FX4DNF031 L00 AHRI ref 204840289 Efficiency 8.5 HSPF Efficiency 12.5 EER,15 SEER Heating input Sensible cooling 21300 Btuh Heating output 28200 Btuh @ 470F Latent cooling j 7100 Btuh Temperature rise 27 OF Total cooling 28400 Btuh Actual airflow 947 cfm Actual airflow 947 cfm Airflowfactor 0.041 cfm/Btuh Airflowfactor 0.046 cfm/Btuh Static pressure 0.40 in H2O Static pressure 0.40 in H2O Space thermostat Load sensible heat ratio 0.83 Capacity balance point = 36 OF Backup: ` Input = 6 kW, Output =19353 Btuh,100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. w ` -ilk =i ntsoft- ^� Right-Sute®Uriversal 2021 21.0.02 RSU23828 2021-Feb-1508:43:59 'C':'A ...aterstone1635BGR'Lor24Blk5Waterstone1635BGR.np CaIc=MJ8 Hoisefaces: W Page 1 +-wrightsoftm Right-JO Worksheet Job: Lot 24 Block 5 Waterston 16... Entire House Date: NOVEMBER 3, 2010 By: DCS DEL -AIR HEATING AND AIR IONING 531 CODISCO WAY, SANFORD, FL 32771 PhCo . 4077-3T-2665 1 Room name Entire House FAM 2 3 Exposed wall Room height 179.9 ft 38.9 ft 4 Room dimensions 9.7 it d 10.7 ft heaU000l 5 Room area 16350 ftz 456.0 ft z 1.0 x 456.0 ft Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz4� (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blkwall,stu000ext' V�j/---G 2A26v,,', ; 0.201 -.0.330 n, n 5:83 957 �'- 4.06 8.52 484 7 ; 412 0 2404 66 1674 ' "'' 110 , 110 �'�641 —447 ' G 2A 2ov _ 58 0. 0 0 0 _�0.330 _ n . 957 8:52 �65 0 620 . ; 552 0 �' 0 11 Blk wall, stucco ext 10C-m 0201 0.550 a a 5.83 15.95 4.06 40.83 348 18 P65 0 1546 287 1077 735 180 18 _�_..-� 13 0 !t)0 - '-756 287 -0 526 735 2A 2ov 0.330 a 957 22.43 32 2 310 726 32 2 310 726 2A 2ov Bill wall stuao ex<.- 0 330 0 201 e _ s , 9 57 5 83 22.91 4 06 32 '{384 1 „ " 368 310 " 2144 742 1493 0 0 0 .0 0 0 0 0 2A 2ov_ = ° 0330 ms._ _ 957_ _ _ .852 .mac ]6 162155 138 _ „_0 '_ _ _ ?a0 ._�. , 0 �0. Blk wall, stucco e)d 2A-2om 0201 0.330 w w 5.83 9.57 4.06 20.92 182 16 127 1 741 155 516 339 70 0 31 0 183 0 . 127 0 26-2fv 0.330 w 9.57 9.72 5 5 48 49 2B-2fv 0.330 w 9.57 24.77 13 3 128 332 5 13 5 3 48 128 49 332 P 11JO _ j2C OW �, 0600, 0091 �0032 wv 1740 26q 1758 131 20 174 20 174 352 459 356 228 20 30 _ 20 30 352 79 356 w39, C 166 30ad 22<ripl_:`�.:�w_ 093 28;68 169 0.00a635 1768 1768 180 _ 1641 5i80 r 2987 .v.,_ _ 484 « 4g4 450 819 _0.989 .�.._, 0 _„a 456 wo39 1116, 0` a rv. -.-.� -.. Y....__,....�....«...-...-._,._ ....._....1..._._..� .,.. �..__.. ..,r =..,,.k _ — ,i-,._...,.1a. w.a..{'....._tuu._. i. s....u.ra._4 ....._..r +....i+.,. ...c..._.... w.�...,.E.,..,-. ..,..x.e.....»,..adx....�....-..-.. ..�.�v..w3.t ,... .. _-�_.._�-.._.. �.�.__.-....� � __ _ ..-.._..,..-__..tee - ._��. .�.�_ ._............ _ .�._.. -..-.«. «..�...._.. _ �.-.�._ ..�_�£ ........� .+..-._-.. fix... «......._,. »•--� ,...-...:-e.s....=..J $.t r ._..u.. +3F.Jw"S,v`.xi°a ... ....... � .va.,.ws a. �✓.i.,c .m1. ,... ��� ^..'..` ,........w w. ... .. ', .: .. .. .w nr .,_...-n}_.... .i .-._a..r.. ._.._.+._-. 77 _ _71- „W 6 c) AED excursion 0 35 Envelope loss/gain 16525 12003 4350 4121 12 a) Infiltration 3195 893 823 230 b) Room ventilation 0 0 0 0 13 Internal gains: Oocupants@ 230 5 1150 3 690 Appliances/other 1800 0 Subtotal (lines 6 to 13) 19720 15845 5172 5041 Less Vernal load 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 19720 15845 5172 5041 15 Duct loads 17°/ 30 % 3384 4698 17% 30 % 888 1495 Total room load 23104 20544 6060 6535 Air required (cfm) 947 947 248 301 Calculations approved byACCA to meet all requirements of Manual J 8th Ed -rid-Wr➢g~� 2021-Feb-1508:43:59 �P. Right-Sute®Uriversal 2021 21.0.02 RSU23828 Page 1 aterstone1635BGR\Lot24Blk5Waterstone1635BGR.nQ Calc=W8 Housefaces: W +1wrightsoft9 Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR IONING 531 CODISCO WAY, SANFORD, FL 32771 Phho OND3T-2665 Job: Lot 24 Block 5 Waterston 16... Date: NOVEMBER 3, 2010 By- DCS 1 Room name BR 4 BR 3 2 Exposed vvall 11.0 ft 24.0 ft 3 Room height 8.9 ft heaUcool 8.9 It heat/cool 4 Room dimensions 1.0 x 140.5 It 1.0 x 133.0 It 5 Room area 140.5 ftz 133.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz 'n (Btuhlftz) or perimeter (ft) (Btuh), or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat 'Cool Gross N/P/S Heat Cool 6 Blk wall, stucco eM - 0 2201 " n 5b3 w 4.06 0 '' 0 0- 0 - "0 '� t.,0 0 2A 2ov. '0.330 n 9.57 8.52 8520 0 0 0 0 0 0 0 0, 0 2A-2ov 0.201 - e - 5.83 _ 4.06 88 72 Blk wall, stucco e# �LL 419 292 80 y- 64 �372 259 11 10C-m 0.550 a 15.95 40.83 0 0 0 0 0 0 0 0 2A 2ov 0.330 a 9.57 22.43 0 0 0 0 0 0 0 0 2A 2ov Blk wall,stucoo extext� `. 0.330 0201 a s 9.57 583 22.91 4.06 16 F 0 0 0 155 0 371 0 16 ° 112 0 ' 1 2 155 653 371 `455 .2A 2ov ., _ _,. a 0 330 ._-_s _ � :9 57_ _w w 8.52 _ �. 0 ._.<, m ,_0 Blk wall, stucco ext 2A-2om 0.201 0.330 w w 5.83 9.57 4.06 20.92 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 26-21v 0.330 w 9.57 9.72 0 0 0 0 0 0 0 2B-2fv 0,330 w 9.57 24.77 0 0 0 0 0 0 0 0 0 11,10 0600 w 1740 17.58 0 0 0 0 0 0 0 0 P j2C Osw 0091 i 264 131 0 0 0. ;` 0 0_ C , t 16B-30ad X 0 032 „ ^ 0 93 1 69 158 158, 147 267 151 151 141 256 _..�_... F 224,ip1 _..�__,...�,.:.�.� ,._.�...._ 0,989 _. 28.68 tea. 6.66 .`.�.-.;�741, _� i -.: � •' _ a.�..�'w,.:688 p 77, _ __._..._. ._...vim.....,_ _ �.. .. ` u...._. ..__...._+_.. _.._.�.> ..._ .. � .,.._.o ........ ..,._._..u... �.w.... .__•_-....�. 77 N �.._... e,....-. ....�_.. ate- ,.._. - -- ..-... _ t _ _ _._ 6 c) AED excursion 82 66 Envelope lo&gain 1036 1012 2009 1406 12 a) Infiltration 201 56 439 123 b) Room ventilation 0 0 0 .0 13 Internal gains: Occupants Ca) 230 0 0 0 0 Applianoes/other 0 0 Subtotal (lines 6 to 13) 1237 1068 2447 1529 Less extemalload 0 0 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1237 1068 2447 1529 15 Ductloads 17% 30% 212 317 17% 30% 420 453 Total room load 1449 i 1385 2867 1982 Air required (cfm) 59 64 118 91 ACCA to -�- wriigF�tsoTt- . Right-Sute@Uriversal202l 2l.O.O2 RSU23828 aterstore1635BGR\Lot24Blk5Waterstore1635BGR.np Calc=WB Horsefaces: W J 8th Ed. 2021-Feb-15 08:43:59 Page 2 +wrightsoft, Right-JM Worksheet Job: Lot 24 Block 5 Waterston 16... Entire House Date: NOVEMBER 3, 2010 DEL -AIR HEATING AND AIR By: DCs 531 CODISCO WAY SANFORD, FL 32771 pSgNDITIONING 1 Room name DIN BATH 2 3 Exposed wall Room height 11.0 It 12.0 It heaklool 6.0 It 4 Room dimensions 9.0 x 12.0 It 8.5 It heat/000l 5 Roam area 108.0 ft2 48.0 ft 2 8.0 x 6.0 ft Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft -f) (Btuh/ft2) or perimeter (ft) (Btuh)� or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat iCool Gross N/P/S Heat Cool 6Blk wall; stu000 eM, 2A 2ov '' 0201 0.330 n : n 5 83 9,57 4.06 8.52 120 �`" 88 0 511 356 ,' 0 'b "p p II--CG 0 0 0 0 0 0 0 11 Blk wall, stuao eM 10C-m ;ti , E 0:330 0201 0.550 : n _ a a __r` 967 5.83 15.95 8 52 4.06 40.83 �w _ 32 0 0 0 0 310 0 0+ 0 276 0 0 0 0 0 _ 0 �0 2A-2ov 0.330 a 9.57 22.43 0 0 0 0 0 0 0 0 0 0 0 1�l` ^ 2A 2ov Blk wall stuao ext 0 330 0 201 a s 9.57 5 88 22.91 4;06 0 s 0 0 "` 0 0 0 0 0 0 48 0 , 748 0 280 0 "` 195' 2A 2ov. y:0330 s.. r. 9:57_ 852 . a 0 �_ 0 ° 0 0 0 MO Blk wall, slu000 ext 2A-2om 0.201 0.330 w w 5.83 957 4.06 20.92 0 0 0 0 _,0 0 0 ..:' 0 0 ._ 0 0 � 0 -.,. 0 , 0 2B-21v 0.330 w 9.57 9.72 0 0 0 0 2B-21v ' 0 0 0 0 0 0 0 0.330 w 957 24.77 0 0 0 0 0 0 0 0 P 11.10 12C Oswr 0600 0091 w 1740 2.64 1758 131 0 0 0 50 0 0 _ 0 0 0 0 0 0 0 0 p F' --..�-..22AW1,.....:s.�,.._........� 16B 30ad ,0032 a„D989 - 093 28,68 1.69 OOb. 118 08 118 12 110 199 55 55 _�'p 51 �93 �...._,_._._..t -7 .. _.-.. w_�.._-._._.�.._...�. .. t.... L_ .... „ ...e...., .,...,.... ..w.t.,.b.....,...a.....+__.. ,.+aw .e...m.,...It , 3 w.. t' ..,.ram .W:,l..a.......... ...f...w-.+.i3..h w ......«.. ,4L%W.z......._...- ...L u.«+r+-Jva.. r.....w.,_ .✓. _.tea__..,,.. .-_...,_-.�-_..._...,-...--__...._-_•_ _. _..,_.,_.v..,..,.: _...�..._�-_._F_ ...,.__...,.�M G._...�.»-�..., ....._.e,.:.,-.,._....v ....,.....a_..�..:-'�.:..r......_..._.-_ Y^- 6 c) AED excursion40 Envelope loss/gain 1274 791 503 276 12 a) Infiltration 274 77 110 31 b) Room ventilation 0 1 0 0 0 13 Internal gains: Occupants@ 230 1 230 0 p Appliances/other 0 0 Subtotal (lines 6 to 13) 1549 ; 1098 612 307 Less external load 0 0 Lesstransfer 0 0 0 0 Redistribution 0 0 0 p 14 Subtotal 1549 1098 0 612 0 307 15 Dud loads 171/. 30% 266 325 17% 30%1 105 91 Total room load Air required (cfm) 1814 1423 718 398 74 661 29 18 Calculations approved byACCA to meet all requirements of Manual J 81h Ed -*- wrigi�tsa7ft- Right-Su2021-Feb-1508:43:59te®Uriversal 2021 21.0.02 RSU23828 Page 3 aterstone1635BGR\Lot24Blk5Waterstone1635BGR.np Calc=W8 Hoisefaces: W -+'�Fwrightsoft`° Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 24 Block 5 Waterston 16... Date: NOVEMBER 3, 2010 By: DCS 1 Room name M BR Krr 2 Exposed wall 15.0 It ft 3 Room height 11.0 It heaV000l 10.0 It heaticool 4 Room dimensions 1.0 x 200.0 It 1 1.0 x 127.5 It 5 Room area 200.0 ft2 127.5 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (Btuh/ftz� (Btuh/ft2) or perimeter (ft) (Btuh)i or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blkwall stuocoext 0201 n 583 4:06 150 118 ` 686 , ' 478 0 0 0 0 2A 2ov 0330 h 957 852 0 0 . 0" 0- 0 0 0 0 2A 2ov �e' �« 0 �0 �� � 310 � ,E 'F76 „ 0 0 11 Blk wall, stucco ext 10C-m 0.201 0.550 a 523 15.95 4.06 40.83 0 0 0 0 0 1 0 0 � 0 0 . _ _ �� 0 0 . 0 0 � � 0 0 2A-2ov 0.330 a 9.57 22.43 0 0 0 0 0 0 0 0 2A 2ov 0.330 e 9 57 22.91 0 0 0 0 0 0 0 0 VVa�lI ! Blk wall stuao ext 0 201 s' 5.83 4 08 0 0 0 R 0 0 0 -0 0' G .2A 2ov._, _. _,, _"L0.330 _ Blk wall, stucco ext 2A-2om 0.201 0.330 w w 5.83 9.57 4.06 20.92 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2B-2fv 0.330 w 9.57 9.72 0 0 0 0 0 0 0 26-21V 0.330 w 9.57 24.77 0 0 0 1 0 0 0 0 0 0 111,10 0600 w 1740 1758 0 0 0 0 0 0 0 0 _s�2:s4 3.,31_ t_ _AO 0 0 . ._0 Q n 'Q'0. C 16B 30ad 0.032 0.93 1.69 224 224 208 378 128 n 128 118 215 F 22A tpl _ 0 989 28 68 0 00 r { 200 � 15 "'�430 ,,��, u _ « _ _. _ _ w ,r k_. w_ _v w _ _. u �_-: ....r ..,_.,.w-...+..._._._......,_.-.,....�_ .__.....,._.e._ u_w.s ems.._.. .>a .... ,.wv« .,.,m« ..._....«A .uv...a-J':«..._-,,. ._..�,� i 1,...-....-.a3«. - ....e..,:_ _ .+a.,.x........ 77 17 Y�__ ._.....,_........_. ..._.-..-.«....- _ .......,...mw,. .a ..,a_.,_ w.n,.. r.,..«-w...v_...x;n.... .... Srv.... .,,.�.._, �:.i. <...... ,r..w.�.,�...,Y ...,..«,,:c.c. . �..A,,...,�,t. .........,1...- ,.....cw._ ..`.._�._.......w_.e._...._ _.-.,..A«. �.« ..,....u.. ...-iWs.a., d3.�...r.0 v.�m....u,.....w ...«,. I 71 6 c) AED excursion -52 -50 Envelope lose/gain 1634 1080 118 165 12 a) Infiltration 343 96 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: OccupantsQa 230 1 230 0 0 Appliances/other 0 1200 Subtotal (lines 6 to 13) 1976 1406 118 1365 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1976 1406 118 1365 15 Ductloads 17% 30% 339 417 17% 30% 20 405 Total room load 2315 1823 139 1770 Air required (cfm) 95 84 6 82 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -f�+ wNrigfftUsoit- Right-Sute®Uriversal 2021 21.0.02 RSU23828 � 2021-Feb-1508:43:59Page 4 aterstone1635BGR1Lot24Blk5Waterstone1635BGR.rLp Calc=MJ8 Hoisefaces: W - - wrightsoft9 Right-M Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 24 Block 5 Waterston 16... Date: NOVEMBER 3, 2010 By: DCS 1 Room name BR 2 UTIL 2 Exposed wall 28.0 It 6.0 ft 3 Room height 8.5 ft heaVcool 8.0 It heat/cool 4 Room dimensions 12.0 x 16.0 It 1.0 x 48.0 It 5 Room area 192.0 ftz 48.0 ftz Ty Construction U-value Or HTM Area (ft2) Load Area (ftz) Load number (Btuhfit -9 (BtuhRtz) 1 or perimeter (ft) (Btuh) ! or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 ItjJ '� wall slu000 eM j j 2BIAk _ _. 0330 .n 8 _ $ 52 0 .w w 0 _ _ 0 . _0 0 0_. 11 VVV���I�///----GG Blk vrall, stucco exi 10C-m 0.201 0.550 a a 5.83 15.95 4.06 40.83 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2A-2ov 0.330 a 9,57 22.43 0 0 0 0 0 0 0 0 2A 2ov 0.330 a 9.57 22.91 0 0 0 0 0 0 0 0 Blkwall s`tucooext >" 0201 s; 5.83 406 128 11112 `, 652 ( 454 0 , ' 0 0-7 __.G .2A _ .m0330 ._. s �9:57 _. _8.52 _.. 16 _._ .: 16 �.� 155 , x' . 138 w �0 . _ 0 0 Blk well, stucco ext 2A-2om 0201 0.330 w w 5.83 9.57 4.06 20S2 0 0 0 0 0 0 0 0 .0 0 _ 0 0 0 0 0 0 2B-2fv 0.330 w 9.57 9.72 0 0 0 0 0 0 0 213-2ty 0.330 w 9.57 24.77 0 0 0 0 0. 0 0 0 0 F : 111,10� 12Cµ0sw: 0600 » _0091' _w 17.40 ;�264 17.58 J 31_96 _0 _0 .� v_ �96 0 253 0 126 0 4$ 0 r._� 48 0 .'� 127_ 0 .63 C F. 1613-30ad '22A.1� _ _. 0032 0 9$9 0.93 .286t3 1.69 O.QQ 219 219 204 803 371 *' 0 48 48 45 gi _ _ _! w192 _.,.28 ._ w >_ l72 0_ .._._... ....n.tm.3... a._....e.-..w. _ .w_..,._.. v., wr„_..-.T.ul u3..s..... '�. A.........ss � w�',�. _...sd.- 0...1 .uti«..+....�.t.. ._..m_.n+.,� T .a.........».. 1'. �............. - ,-... .. - --.L------- _ ._. _ 6 c) AED excursion 41 26 Envelope lossigain 2067 1047 343 118 12 a) Infiltration 292 8 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliancestother 0 600 Subtotal (lines 6 to 13) 2359 1129 343 718 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 2359 1129 343 718 loads 17 % 30 % 405 335 17 % 30 % 59 213 1Dud 1 Total room load 2764 1464 402 930 Air required (cfm) 113 1 1 67 116 43 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed -�"}�- wrigf�tsoTt^ Rigfd-Sute®Uriversal 2021 21.0.02 RSU23828 ' 2021-Feb-1508.43:59 Page 5 aterstone1635BGR1Lot24Blk5Waterstone1635BGR.nis Q Calc=MJB Floefaces: W +.wrightsofta Right-JO Worksheet Entire House DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 Job: Lot 24 Block 5 Waterston 16... Date: NOVEMBER 3, 2010 By: DCS 1 Room name M BATH M WIC 2 Exposed wall 33.0 ft 6.0 It 3 Room height 8.0 ft hen of 8.0 it heat/cool 4 Room dimensions 1.0 x 135.0 ft 1.0 x 47.0 ft 5 Room area 135.0 ftz 47.0 ft2 Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load number (BtuM-T) (Btuh/ftz) or perimeter (ft) (Btuh)i or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VL�I--G Blk wall, stu000 ext 2A 2ov _ Y2A-2ov t 0 201 D 330 nT, rr 75,83 957 4,06 8'52 104 7 M 97 0 566_ 66 394 58 0 0 > . p e 0 '0 �0 { ; -" 0 _.. W0330 n957 .� 8�52 ti 11 Blk wall, stu000 ext 10C-m 0.201 0.550 epLL a 5.83 15.95 4.06 40.83 0 0 0 0 0 0 0 0 0- 0 0 0 w 0 0 0 0 2A-2ov 0.330 a 9.57 22.43 0 0 0 0 0 0 0 0 2A 2ovTM� 0.330 e 9.57 22.91 0 0 0 1 0 0 0 0 0 yVj!! Blk'wall,stuocoext. 0201 s' 5'83 406 48 48 280 $V = 195 _, A330 ,>_sn. t0 .n Blk wall, stucco ext 2A-2om 0.201 0.330 w w 5.83 9.57 4.06 20.92 112 16 96 1 558 155 ! 389 339 0 0 0 0 0 0 0 0 2B-2fv 0.330 w 9.57 9.72 0 0 0 0 0 0 0 0 21321v 0.330 w 9.57 24.77 0 0 0 0 0 0 0 0 11J0 0.600 w 17.40 17.58 0 0 0 0 0 0 0 0 P `12C _�0 C 16830ad 0 032 _0 93 1 69 135 135 _ 125 1 228 47 47 44 79 F 22A.ipl` 0. �0989 : 28;68, 900 135 33 _._. . _ n._ ._...s_._.....:._..k_..,,...�.w�....,..x..�_�,,..- _e-.._...�;r.,�._�� _ s...�.,._�v.._v. ...,,..- _._..,.:.._.._.:._.- _.._..v...._ .....,sk.__.��.,..... ,._,_.,...u-.�.._.. .,,�,� ,�..�.M a.�____.a,_..�,.._:..:.._o_._._..._.._ ......................w.,.�..>,.,..�...�,:..,.:_: .o .^:r ..e........, ,.,a.._..:._,.o,......_._....,_._... w.wt. az...,., �,.. t.,.... .z-.: ,.. .«. _.,..,_ «,.,,... e.. o-.zr,.. _...,_.✓ ,..c,._,..�..,e_ .. ... ,,,.._, ., .., .> .._,......t+�.,., m...�...,ax....., _....—_ .,._.,,.....��....�-.w_... ....�.. ,........._..�.,� ..._.3... .....,,,,.._... ...<..,v.,.. _ .»n ,. rux .. ..._.-.. ,,.a... �.,..,...._., �. ...aaa..,. .w.o ..,.,v .�. ,,..r ..r...s c..z..... ..,..._ ....... _..-. _.+, ��.,...z..a......r�.._....,_...._ ..�.r...m_,_ ..,,s_..«xtt _.,,...w ...n ...r,.w.. _...c..a.,:.f�..:,..., ...a,.x...ra.w. w.....e... t,:.......#,..,.-.....au Y..,.w........ x.n..a.�ea.r- f ,...+....,u «. a., �w�,._... ,...._..........._.�._ a..x.f�...v> x ...�. ._.....,�_ �.s..a..... L.a.&.ffi..a� ti�.„w., ......,tn.w ..�..... .... .... u..�. ...,...�. .w.a« _ ,»...., _,.....> . _..... ..,.......„.....u�x.r ...�u...rrort v-«._nd. .. .. _„......es.r _....,.._t. _,».�.....«... ..raw.ae�..o ,....,.aw.. o.ws'* s..... _.,..<..v..ay. ._„y........ .K..._._..._ .�.w.2.....,._, .0....... .........o� _.....�,.�-...r _..,.x...........»+.+.=-.;Y9 $ ... ,......, a.....,i ta- .. 4-,.}:a.+... w ._....K_ ...+a-....»..._....+...vx. _,� .........� ss..n+,�« _vt4..a.va._m.. , x.,.wrs... r 2_a:..+.:9...� t,'� n1� . ........a....n.= ......._......4. -...�,.1r W.....+. r.. 6 c) AED excursion 119 -11 Envelope lossIgain 2697 1723 495 264 12 a) Infiltration 603 169 110 31 b) Room ventilation 0 0 0 0 13 Internal gains: OccupantsQa 230 0 1 0 0 0 Appliancestother 0 0 Subtotal (lines 6 to 13) 3300 1891 605 294 Less external load 0 I 0 0 0 Less transfer 0 0 0 0 Redistribution 6 0 0 0 14 Subtotal 3300 1891 605 294 15 Ductloads 17% 30% 566 561 17% 30%1 104 87 Total room load 3866 2452 709 381 Air required (cfm) 158 113 29 18 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. AC-�'I.►- wrGgiatsoTt- 2021-Feb-1508:43:59 C@ Right-SuteOUriversal 2021 21.0.02 RSU23828 Page 6 aterstone1635BGR\Lot24Blk5Waterstone1635BGR.rup Calc=MJ8 House faces: W g Duct System Summary Job: Lot 24 Block 5 Waterston ... - wrightsoft® Date: NOVEMBER 3, 2010 Entire House By. Dc3 DEL -AIR HEATING AND AIR CONDITIONING 531 CODISCO WAY, SANFORD, FL 32771 Phone:407-333-2665 For: ADAM HOMES 5364 Vespera Street, Cocoa, FL 32926 External static pressure Pressure losses Available static pressure Supply/ return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.256 in/100ft 947 cfm 133 ft Cooling 0.40 in H2O 0.06 in H2O 0.34 in H2O 0.170 / 0.170 in H2O 0.256 in/100ft 947 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mal Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 718 29 18 0.414 4.0 Ox 0 VI Fx 12.1 70.0 BR 2 h 2764 113 67 0.319 6.0 Ox 0 VI Fx 21.7 85.0 st1 BR 3 h 2867 118 91 0.404 6.0 Ox 0 VI Fx 14.1 70.0 BR 4 c 1385 59 64 0.462 6.0 Ox 0 VI Fx 3.6 70.0 DIN h 1814 74 66 0.414 6.0 Ox 0 VIFx 12.1 70.0 FAM c 6535 248 301 0.429 9.0 Ox 0 VI Fx 9.2 70.0 Krr c 1770 6 82 0.445 6.0 Ox 0 VI Fx 6.3 70.0 M BATH h 3866 158 113 0.256 7.0 Ox 0 VI Fx 32.7 100.0 s2 M BR h 2315 95 84 0.274 7.0 Ox 0 VI Fx 24.2 100.0 st2 M W IC h 709 29 18 0.260 4.0 Ox 0 VI Fx 30.7 100.0 st2 UTIL c 930 16 43 0.327 4.0 Ox 0 VI Fx 19.1 85.0 st1 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 282 215 0.256 639 9.0 0 x 0 VinlFlx st1 st1 PeakAVF 412 325 0.256 525 12.0 0 x 0 VinlFlx - wrightsoft- M,••�.e,.•t-��m�•. Rigk-Sute®Uriversa1202121.0.02RSU23828 aterstone1635BGR\Lot24BIk5Waterstone1635BGR.rLp Calc=MJ8 House faces: W 2021-Feb-15 08:44:00 Page 1 Name Grille Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Mat Trunk rbi Ox0 947 947 0 0 0 0 Ox 0 MR wrightsoft- 2021-Feb-15 08:44:00 AM. •t• ,.• •� - � .m Rlgtt-Sute®Uriversal 2021 21.0.02 RSU23828 Page 2 ACCK ..aterstonL1635BGR\Lot248lk5Waterstonel635BGR.rLp Calc=W8 Hoisefaces: W 2020 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CIRITERIA TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA i Project Name: Lot 24 Block 5 Waterstone 1635 BGR Builder Name: ADAM HOMES Street: 5364 Vespera Street Permit Office: City, State, Zip: Fort Pierce , FL , 34951 Permit Number: Y Owner: Jurisdiction: 661000 w Design Location: FL, ST_LUCIE_CO_INTL v COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements 9 Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity sealed. with a material having a thermal resistance of R-3 Knee walls shall be sealed. per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim, joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to (including insulation. maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation and cantilevered shall be permitted to be in contact with the top side floors) of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottbm to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation, insulation a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spac as. , Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building shall be sealed to the finished surface. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring andlplumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind D*120na and wiring. Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall on exterior wall tubs shall separate them from the showers and tubs. be insulated. Electrical/phone box or The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC supply and return register boots that penetrate building thermal envelope shall be sealed to the sub -floor, wall covering or Concealed When required to be sealed, concealed fire sprinklers shall only be sprinklers sealed in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids i nkler cover plates and walls or ce4lonas. a. ni auuuwn, uiaNcUUUii U1 iUy wails span ue hi accordance with the provisions Or II:G-4UU. 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 1 of 1 FORM R405-2020 RESIDENTIAL ENERGY CONSERVATION CODE DOW ENTATION CHECKLIST Florida Department of Business and Profession a I Regulation Simulated Performance Alternative (Performanlce) Method I Applications for compliance with the 2020 Florida Building Code, Energy Conservation via the Residential Simulated Performance Alternative shall include: ❑ This checklist ❑ Form R405-2020 report ❑ Input summary checklist that can be used for field verification ❑ Energy Performance Level (EPL) Display Card (one page) ❑ HVAC system sizing and selection based on ACCA Manual S or per ❑ Mandatory Requirements (five pages) Required prior to CO: four pages/may be greater) provided in Section R403.7 ❑ Air Barrier and Insulation Inspection Component Criteria checklist (Table R402.4.1.1 - one page) ❑ A completed 2020 Envelope Leakage Test Report (usually one page); exception in R402.4 allows dwelling units of R-2 Occupancies and multiple attached single family dwellings to comply with Section C402.5 ❑ if Form R405 duct leakage type indicates anything other than "default leakage" then a completed 2020 Duct Leakage Test Report - Performance Method (usually olne page) 2/15/2021 8:47:45 AM EnergyGauge@ USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 1 Envelope Leakage Test Report (Blower Door Test) Residential Prescriptive, Performance or ERI Method Compliance 2020 Florida Building Code, Energy Conservation, 7th Edition Jurisdiction: 661000 Permit #: y . J.ob Information Builder: ADAM HOMES Community: Lot: 24-5 Address: 5364 Vespera Street City: Fort Pierce State: FL Zip: 34951 A LeakageTest Results' ,Passing results must meet either the Peiformance, Prescrrptrve, or ERIalVlethod 0 PRESCRIPTIVE METHOD The building or dwelling umt=shall be tested and venfied`as havrrig an air.leakage°rate of not exceecJmg changes pet hour at'a pressure of 0 `2 inch w g:,(50 Pascals) in CUmate Zones 0 PERFORMANCE or ERI�METHOD The building or dwelling urnt shall be tested and venfiedas having an air Leakage rate of not exceeding ";the s#lected ACH(50)ivalue, as shown an Form R405r2020 (Performance) or R49t; 2020,(ERI} secfipn lali led as it filtration,'sub'sect on A' 1 5- `. AGH(50) specred prr Form R405 2020 Energy Ca(c (Performance)s or R406>2020 (ERI) t 7000 x 60 _ 15860 = Method for calculating building volume: CFM(50) Building Volume ACH(50) O Retrieved from architectural plans PASS Code software calculated i When ACH(50) is less than 3, Mechanical Ventilation installation Q Field measured and calculated must be verified by building department. R402.4.1.2 Testing. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals) Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues.or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to thecode official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. During testing: 1. Exterior windows and doors, fireplace and. stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. l-estl5ng' Company Company Name: Phone: I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code Energy Conservation requirements according to the compliance method selected abode. Signature of Tester: Date of est: Printed Name of Tester: License/Certification #: Issuing Authority: 2/15/2021 8:48:35 AM EnergyGaugeO USA 7.0.00 - FlaRes202O FBC 7th Edition (21 20) Compliant Software Page 1 of 1 1 I Florida Building Code, Energy Conservation,) 7th Edition (2020) Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods ADDRESS: 5364 Vespera Street Permit Number: Fort Pierce , FL , 34951 MANDATORY REQUIREMENTS - See individual code sections for full details. SECTION R401 GENERAL R401.3 Energy Performance Level (EPL) display card (Mandatory) The building official shall require that an energy performance level (EPL) display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law ❑ (Section 553.9085, Florida Statutes) requires the EPL display card to be included as an addendum to each sales contract for both presold and nonpresold residential buildings. The EPL display card contains information indicating the energyi performance level and efficiencies of components installed in a dwelling unit. The building official shall verify that the EPL display card completed and signed by the builder accurately reflects the plans and specifications submitted to demonstrate code compliance for the building. A copy of the EPL display card can be found in Appendix RD. SECTION R402 BUILDING THERMAL ENVELOPE ❑ R402.4 Air leakage (Mandatory). The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements of Sections R402.4.1 through R402.4.5. I Exception: Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted to comply with Section C402.5. ❑ R402.4.1 Building thermal envelopeThe building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealing methods between dissimilar materials shall allow for differential expansion and contraction. ❑ R402.4.1.1 Installation. The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordance with the manufacturer's instructions and the criteria listed in Table R402.4.1.1, as applicable to the method of construction. Where required by the code official, an approved third party shall inspect all components and verify compliance. ❑ R402.4.1.2 Testing. The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g) or (1) or an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. Exception: Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existing buildings in which the new construction is less than 85 percent of the building thermal envelope. i During testing: 1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures. 2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures. 3. Interior doors, if installed at the time of the test, shall be open. 4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. 5. Heating and cooling systems, if installed at the time of the test, shall be turned off. 6. Supply and return registers, if installed at the time of the test, shall be fully open. ❑ R402.4.2 Fireplaces. New wood -burning fireplaces shall have tight -fitting flue dampers or doors, and outdoor combustion air. Where using tight -fitting doors on factory -built fireplaces listed and labeled in accordance with UL 127, the doors shall be tested and listed for the fireplace. Where using tight -fitting doors on masonry fireplaces, the doors shall be listed and labeled in accordance with UL 907. ❑ R402.4.3 Fenestration air leakage. Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square foot (1.5 L/s/m2), and swinging doors.no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or AAMA/ WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer. i Exception: Site -built windows, skylights and doors. 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 1 of 5 MANDATORY REQUIREMENTS - (Continued) R402.4.4 Rooms containing fuel -burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it passes through conditioned space to a minimum of R-8. Exceptions: 1. Direct vent appliances with both intake and exhaust pipes installed continuous, to the outside. 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of lithe Florida Building Code, Residential. R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage between conditioned and unconditioned spaces. All recessed luminaires shall be IC -rated and labeled as having an air leakage rate not more than 2.0 cfm (0.944 Us) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling: covering. R403.1 Controls. SECTION R403 SYSTEMS R403.1.1 Thermostat provision (Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. R403.1.3 Heat pump supplementary heat (Mandatory). Heat pumps having supplementary' electric -resistance heat shall have controls that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load. 0 R403.3.2 Sealing (Mandatory) All ducts, air handlers, filter boxes and building cavities thatiform the primary air containment passageways for air distribution systems shall be considered ducts or plenum chambers, shall be constructed and sealed in accordance with Section C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(0, (g) or (i), Florida Statutes, to be "substantially leak free" in accordance with Section R403.3.3. R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent of the design airflow rate when tested in accordance with ASHRAE 193. R403.3.3 Duct testing (Mandatory). Ducts shall be pressure tested to determine air leakage by one of the following methods: 1. Rough -in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test. 2. Postconstruction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the entire system, including the manufacturer's air handler enclosure. Registers shall be taped or otherwise sealed during the test. Exceptions: 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope. 2. Duct testing is not mandatory for buildings complying by Section 405 of this code. Duct leakage testing is required for Section R405 compliance where credit is taken for leakage, and a duct air leakage Qn to the outside of less than 0.080 (where Qn = duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals) is indicated in the compliance report for the proposed design. A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. R403.3.5 Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums. ❑ R403.4 Mechanical system piping insulation (Mandatory). Mechanical system piping capable of carrying fluids above 105°F (41 °C) or below 55°F (13°C) shall be insulated to a minimum of R-3. Fi R403.4.1 Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted. R403.5.1 Heated water circulation and temperature maintenance systems (Mandatory). If heated water circulation systems are installed, they shall be in accordance with Section R403.5.1.1. Heat trace temperature maintenance systems shall be in accordance with Section R403:5.1.2. Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible. ❑ R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump. The system return pipe shall be a dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited. Controls for circulating hot water system pumps shall start the pump based on the identification of ajdemand for hot water within the occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at; the desired temperature and when there is no demand for hot water. R403.5.1.2 Heat trace systems. Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systems shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the times when heated water is used in the occupancy. 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes202O FBC 7th Edition (2020) Compliant Software Page 2 of 5 MANDATORY REQUIREMENTS - (Continued) R403.5.5 Heat traps (Mandatory). Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heat traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a downward and upward bend of at least 3'% inches (89 mm) in the hot water distribution line and cold water line located as close as possible to the storage tank. R403.5.6 Water heater efficiencies (Mandatory). R403.5.6.1.1 Automatic controls. Service water -heating systems shall be equipped with automatic temperature controls capable of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature setting range shall be from 100°F to 140°F (38°C to 60°C). R403.5.6.1.2 Shut down. A separate switch or a clearly marked circuit breaker shall be provided to permit the power supplied to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s) of combustion types of service water -heating systems to be turned off. Fi R403.5.6.2 Water -heating equipment. Water -heating equipment installed in residential units shall meet the minimum efficiencies of Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the appropriate water -heating category. Solar water heaters shall meet the criteria of Section R403.5.6.2.1. R403.5.6.2.1 Solar water -heating systems. Solar systems for domestic hot water production are rated by the annual solar energy factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors, and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar water -heating systems should meet the following criteria: 1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and 2. Be installed at an orientation within 45 degrees of true south. R403.6 Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential, or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation including: Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating. R403.6.1 Whole -house mechanical ventilation system fan efficacy.When installed to function as a whole -house mechanical ventilation system, fans shall meet the efficacy requirements of Table R403.6.1. Exception: Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole -house mechanical ventilation, the air handler shall be powered by an electronically commutated motor. R403.6.2 Ventilation air. Residential buildings designed to be operated at a positive indoor pressure or for mechanical ventilation shall meet the following criteria: 1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications. 2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas. 3. If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum of R-19, space permitting, or R-10 otherwise. R403.7 Heating and cooling equipment. ❑ R403.7.1 Equipment sizing (Mandatory). Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on the equipment loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies, based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions described in Section R302.1. This Code does not allow designer safety factors, provisions for future expansion or other factors that affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed. TABLE R403.6.1 WHOLE -HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY FAN LOCATION AIRFLOW RATE MINIMUM (CFM) MINIMUM EFFICACY a (CFM/WATT) AIRFLOW RATE MAXIMUIV (CFM) HRV or ERV Any 1.2 cfm/watt Any Range hoods Any 2.8 cfm/watt I Any In -line fan Any 2.8 cfm/watt Any Bathroom, utility room 10 1.4 cfm/watt <90 Bathroom, utility room 90 2.8 cfm/watt Any For SI: 1 cfm = 28.3 L/min. a. When tested in accordance with HVI Standard 916 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 3 of 5 MANDATORY REQUIREMENTS . (Continued) R403.7.1.1 Cooling equipment capacity. Cooling only equipment shall be selected so that its total capacity is not less than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in Section R403.7, or the closest available size provided by the manufacturer's product lines. The corresponding latent capacity of the equipment shall not be less than the calculated latent load. The published value for AHRI total capacity is a nominal, rating -test value and shall not be used for equipment sizing. Manufacturer's expanded performance data shall be used to select cooling -only equipment. This selection shall be based on the outdoor design dry-bulb temperature for the load calculation (or entering water temperature for water -source equipment), the blower CFM provided by the expanded performance data, the design value for entering wet -bulb temperature and the design value for entering dry-bulb temperature. Design values for entering wet -bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space. Exceptions: 1. Attached single- and multiple -family residential equipment sizing may be selected so that its cooling capacity is less than the calculated total sensible load but not less than 80 percent of that load. 2. When signed and sealed by a Florida -registered engineer, in attached single- and multiple -family units, the capacity of equipment may be sized in accordance with good design practice. R403.7.1.2 Heating equipment capacity. R403.7.1.2.1 Heat pumps. Heat pump sizing shall be based on the cooling requirements as calculated according to Section R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if the design heating load is 1.15 times greater than the design cooling load. R403.7.1.2.2 Electric resistance furnaces. Electric resistance furnaces shall be sized within 4 kW of the design requirements calculated according to the procedure selected in Section R403.7.1. EJ R403.7.1.2.3 Fossil fuel heating equipment. The capacity of fossil fuel heating equipment with natural draft atmospheric burners shall not be less than the design load calculated in accordance with Section R403.7.1. I R403.7.1.3 Extra capacity required for special occasions. Residences requiring excess cooling or heating equipment capacity on an intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to prevent continuous space cooling or heating within that space by one or more of the following options: 1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas. 2. A variable capacity system sized for optimum performance during base load periods is utilized. ❑ R403.8 Systems serving multiple dwelling units (Mandatory). Systems serving multiple dwelling units shall comply with Sections C403 and C404 of the Florida Building Code, Energy Conservation —Commercial Provisions in lieu of Section R403. R403.9 Snow melt and ice system controls (Mandatory) Snow- and ice -melting systems, supplied through energy service to the building, shall include automatic controls capable of shutting off the system when the pavement temperature is above 50°F (10°C), and no precipitation is falling and an automatic or manual control that will allow shutoff when the outdoor temperature is above 40°F (4.8°C). ❑ R403.10 Pools and permanent spa energy consumption (Mandatory). The energy consumption of pools and permanent spas shall be in accordance with Sections R403.10.1 through R403.10.5. R403.10.1 Heaters. The electric power to heaters shall be controlled by a readily accessible on -off switch that is an integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the power to the heater. Gas -fired heaters shall not be equipped with continuously burning ignition pilots. R403.10.2 Time switches. Time switches or other control methods that can automatically turn off and on according to a preset schedule shall be installed for heaters and pump motors. Heaters and pump motors that have built-in;time switches shall be in compliance with this section. Exceptions: 1. Where public health standards require 24-hour pump operation. 2. Pumps that operate solar- and waste -heat -recovery pool heating systems. 3. Where pumps are powered exclusively from on -site renewable generation. 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 4 of 5 QR403.10.3 Covers. Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor -retardant cover on or at the water surface or a liquid cover or other means proven to reduce heat loss. Exception: Where more than 70 percent of the energy for heating, computed over an operation season, is from site -recovered energy, such as from a heat pump or solar energy source, covers or other vapor -retardant means shall not be required. R403.10.4 Gas- and oil -fired pool and spa heaters. All gas- and oil -fired pool and spa heaters shall have a minimum thermal ❑ efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool heaters fired by natural or LP gas shall not have continuously burning pilot lights. ❑ R403.10.5 Heat pump pool heaters. Heat pump pool heaters shall have a minimum COP of;4.0 when tested in accordance with AHRI 1160, Table 2, Standard Rating Conditions -Low Air Temperature. A test report from an !independent laboratory is required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard. R403.11 Portable spas (Mandatory).The energy consumption of electric -powered portable spas shall be controlled by the requirements of APSP-14. MR403.13 Dehumidifiers (Mandatory If installed, a dehumidifier shall conform to the following irequirements: 1. The minimum rated efficiency of the dehumidifier shall be greater than 1.7 liters/ kWh if the total dehumidifier capacity for the house is less than 75 pints/day and greater than 2.38 liters/kWh if the total dehumidifier capacity1for the house is greater than or equal to 75 pints/day. 2. The dehumidifier shall be controlled by a sensor that is installed in a location where; it is exposed to mixed house air. 3. Any dehumidifier unit located in unconditioned space that treats air from conditioned space shall be insulated to a minimum of R-2. 4. Condensate disposal shall be in accordance with Section M1411.3.1 of the Florida Building Code, Residential. R403.13.1 Ducted dehumidifiers. Ducted dehumidifiers shall, in addition to conforming to the requirements of Section R403.13, conform to the following requirements: 1. If a ducted dehumidifier is configured with return and supply ducts both connected into the supply side of the cooling system, a backdraft damper shall be installed in the supply air duct between the dehumidifier inlet and outlet duct. 2. If a ducted dehumidifier is configured with only its supply duct connected into the supply side of the central heating and cooling system, a backdraft damper shall be installed in the dehumidifier supply duct between the dehumidifier and central supply duct. 3. A ducted dehumidifier shall not be ducted to or from a central ducted cooling system on the return duct side upstream from the central cooling evaporator coil. 1 4. Ductwork associated with a dehumidifier located in unconditioned space shall be insulated to a minimum of R-6. SECTION R404 ELECTRICAL POWER AND LIGHTING SYSTEMS R404.1 Lighting equipment (Mandatory). Not less than 90 percent of the lamps in permanently installed luminaires shall have an efficacy of at least 45 lumens -per -watt or shall utilize lamps with an efficacy of not less than 65 lumens -per -watt. R404.1.1 Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot lights. I 2/15/2021 8:48 AM EnergyGauge® USA 7.0.00 - FlaRes2020 FBC 7th Edition (2020) Compliant Software Page 5 of 5