ENGINEER EVALUATE TEST CONSULT
EVALUATION REPORT
Eagle Roofing Products, LLC
1575 East Country Road 470
Sumterville, FL 33585
(800) 400-3245
Evaluation Report E1322.09.06-R6
FL7473-R9
Date of Issuance: 02/24/2009
Revision 6: 09/28/2020
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 7th Edition (2020) Florida Building Code sections noted herein.
DESCRIPTION: Eagle Roof Tiles
LABELING: Labeling shall be in accordance with the requirements of the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance or production facility location(s) changes, or Code provisions that relate to the product(s) change.
Acceptance of our Evaluation Reports by the named client constitutes agreement to notify NEMO ETC, LLC of any
changes to the product(s), the Quality Assurance or the production facility location(s). NEMO ETC, LLC requires a
complete review of its Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Florida Product Approval Number (FL#) preceded by the words “NEMO|etc. Evaluated” may be
displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its
entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 5.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 09/28/2020. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. NEMO ETC, LLC does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. NEMO ETC, LLC is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing produ cts for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
©2019 NEMO ETC, LLC
NEMO|etc.
NEMO ETC, LLC Evaluation Report E1322.09.06-R6
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL7473-R9
Eagle Roofing Products, LLC Revision 6: 09/28/2020
Page 2 of 5
ROOFING SYSTEM EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub-Category: Roofing Tiles
Compliance Statement: Eagle Roof Tiles, as produced by Eagle Roofing Products, LLC, have demonstrated compliance
with the following sections of the 7th Edition (2020) Florida Building Code through testing in accordance with the
following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set
forth herein.
2. STANDARDS:
Section Property Standard Year
1507.3.5, R905.3.5 Material standard ASTM C1492 2003(2009)
1507.3.7, R905.3.7 Application FRSA/TRI (09-18) 2018
1504.2.1.1 Overturning Moment SSTD 11 1997
3. REFERENCES:
Entity Examination Reference Date
ATL (TST3782) ASTM C1492 RT0310.01-17, 02-17, 03-17 03/15/2017
ATL (TST3782) ASTM C1492 – Freeze/thaw RT0706.01-17, 02-17, 03-17 09/25/2017
Tile Roof Industry Alliance SSTD 11 Membership Letter 11/29/2005
Tile Roof Industry Alliance Membership confirmation tileroofing.org Current
Intertek/ATI (QUA1844) Quality Assurance Inspection Report 05/28/2020
Intertek/ATI (QUA1844) Quality Assurance Florida BCIS Current
4. PRODUCT DESCRIPTION:
Product Material Standard Plant(s)
4.1 Low Profile Concrete Tile ASTM C1492, Type III Sumterville, FL
NEMO|etc.
NEMO ETC, LLC Evaluation Report E1322.09.06-R6
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL7473-R9
Eagle Roofing Products, LLC Revision 6: 09/28/2020
Page 3 of 5
Product Material Standard Plant(s)
4.1 Low Profile Concrete Tile ASTM C1492, Type III Sumterville, FL
4.2 Medium Profile Concrete Tile ASTM C1492, Type II Sumterville, FL
4.3 High Profile Concrete Tile ASTM C1492, Type II Sumterville, FL
5. LIMITATIONS:
5.1 This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions (i.e., Broward and Miami-Dade
Counties).
5.3 This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.4 This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 or R902 for requirements
and limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations
concerning the use of foam plastic insulation.
5.5 This Evaluation Report does not include evaluation of roof edge termination.
5.6 Refer to FBC 1511 or R908 for requirements and limitations regarding recover installations.
NEMO|etc.
NEMO ETC, LLC Evaluation Report E1322.09.06-R6
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL7473-R9
Eagle Roofing Products, LLC Revision 6: 09/28/2020
Page 4 of 5
5.6.1 For mechanically attached components over existing roof decks, fasteners shall be tested in the existing deck for
withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum
requirements for the system. Testing shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard
TAS 105.
5.7 ”Color-Bonded” or “Slurry-Coated” tiles are limited to use on projects in areas subjected to weathering indices of 50
or less (negligible weathering), as outlined in Figure 1 of ASTM C1492-03(2009)i, reproduced below for reference.
This limitation does not apply to the “Color-Through” product offering.
5.8 All components in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
6. INSTALLATION:
6.1 Eagle Roof Tiles may be mechanically fastened, mortar-set or adhesive-set. Installation shall comply with
manufacturer’s current published instructions, but not less than the requirements of FBC 1507.3 and the FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition.
6.2 Underlayment:
Underlayment shall hold current Florida Product Approval for use with tile roofing systems. The underlayment
Product Approval shall specify allowable method(s) of tile installation (mechanical attachment, mortar-set or
adhesive-set) for use with the specific underlayment. The underlayment Product Approval shall specify attachment
methods for the underlayment system to resist wind uplift design loads in accordance with Table 1A of FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or the critical (highest) design
pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
6.3 Tile Attachment:
6.3.1 Mechanically Attached Tile:
Wind load resistance shall be in accordance with Table 3 of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile
Installation Manual, Sixth Edition to resist the Uplift Moment determined in Table 2HB, 2HC, 2HD, 2GB, 2GC or 2GD
of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or FBC 1609.5.3.
6.3.2 Mortar-Set Tile:
Wind load resistance shall be in accordance with Table 2HB, 2HC, 2HD, 2GB, 2GC or 2GD of FRSA/TRI Florida High
Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or FBC 1609.5.3 in conjunction with the mortar
manufacturer’s Product Approval.
6.3.3 Adhesive-Set Tile:
Wind load resistance shall be in accordance with Table 2HB, 2HC, 2HD, 2GB, 2GC or 2GD of FRSA/TRI Florida High
Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition or FBC 1609.5.3 in conjunction with the adhesive
manufacturer’s current Product Approval. Refer to the current version of the referenced Florida Product Approval
for paddy-placement details and performance data.
NEMO|etc.
NEMO ETC, LLC Evaluation Report E1322.09.06-R6
Certificate of Authorization #32455 7TH EDITION (2020) FBC NON-HVHZ EVALUATION FL7473-R9
Eagle Roofing Products, LLC Revision 6: 09/28/2020
Page 5 of 5
TILE ADHESIVES FOR ADHESIVE-SET TILE SYSTEMS
Manufacturer Product(s) Florida Product Approval
DAP Foam, Inc.
“Touch N’ Seal Storm Bond Roof Tile Adhesive” FL14506
“Touch N’ Seal Storm Bond 2 Two-Component Roof Tile
Adhesive” FL21374
DuPont de Nemours, Inc. “TILE BOND™ Roof Tile Adhesive” FL22525
ICP Adhesives & Sealants, Inc. “POLYSET® AH-160” FL6332
“POLYSET® RTA-1” FL6276
6.3.4 Hip and Ridge Tile:
Tile shall be installed in accordance with FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual,
Sixth Edition. For hip and ridge tile installations atop hip and ridge metal, refer to the hip and ridge metal
manufacturer’s current Product Approval (e.g., FL5374) or test report in accordance with SSTD 11 for allowable loads
to resist those determined in accordance with Table 1A of FRSA/TRI Florida High Wind Concrete and Clay Roof Tile
Installation Manual, Sixth Edition.
7. LABELING:
7.1 Each unit shall bear the imprint or identifiable marking of the manufacturer’s name or logo. Tile lots shall be labeled
in accordance with the requirements of the Accredited Quality Assurance Agency noted herein.
7.2 Tile not tested for freeze-thaw shall state clearly that the lot has not been tested for freeze-thaw acceptance on all
lot tags or certification.
8. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
9. MANUFACTURING PLANTS:
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer to
Section 4 herein for products and production locations having met codified material standards.
10. QUALITY ASSURANCE ENTITY:
Architectural Testing, Inc., and Intertek Company – QUA1844; (847) 718-6307; naura.alcheikh@intertek.com
- END OF EVALUATION REPORT -
i ASTM C1492-03(2009), Standard Specification for Concrete Roof Tile, © ASTM International