Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
MANJ (3)
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Load Short Form Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor: 2825 Brocksmith Rd, Ft. Pierce, FL 34945 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond 14ACXS036-230A** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.3 Sensible cooling Btuh24220 Heating output Btuh24887 Latent cooling Btuh10380 Temperature rise °F20 Total cooling Btuh34600 Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.050 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Dining/Foyer 216 3664 2043 165 103 Master Bath 218 3365 1745 152 88 Wtr Clst 26 375 158 17 8 WIC 98 1392 587 63 29 Pantry 23 0 0 0 0 Laundry 68 739 1037 33 52 Master Suite 243 3615 2436 163 122 Bed 3 161 2483 1436 112 72 Den 165 1436 832 65 42 Bed 2 180 3050 1696 137 85 Bath 2 81 1897 778 85 39 Lin 2 8 0 0 0 0 Hall 63 0 0 0 0 Living Room 369 2896 6535 130 328 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E Linen 8 0 0 0 0 Kitchen 223 687 3690 31 185 Entire House 2147 25598 22972 1153 1153 Other equip loads 1640 871 Equip. @ 0.95 RSM 22747 Latent cooling 7241 TOTALS 2147 27239 29988 1153 1153 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Building Analysis Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor: 2825 Brocksmith Rd, Ft. Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Other Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 18.049092.7Walls 6.016238.8Glazing 1.64333.7Doors 7.821201.0Ceilings 23.062692.92.9Floors 13.436432.1Infiltration 24.26600Ducts 00Piping 00Humidification 6.01640Ventilation0Adjustments 100.027239Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 12.529701.6Walls 12.8305416.6Glazing 1.84373.7Doors 13.131291.5Ceilings 000Floors 4.19670.6Infiltration 31.07394Ducts 3.7871Ventilation 21.15020Internal gains 00Blower 0Adjustments 100.023844Total Latent Cooling Load = 7241 Btuh Overall U-value = 0.082 Btuh/ft²-°F Data entries checked. 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Component Constructions Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor: 2825 Brocksmith Rd, Ft. Pierce, FL 34945 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Block R-9 Wall: Blk wall, Stuc Ext, 8" thk, R-9 Foam Fill, 1/2" Gyp Bd 7732.589.00.089300n 4951.65 411.65642.589.00.08925ne 3621.655672.589.00.089220e 411.65642.589.00.08925se 7641.6511942.589.00.089463s 6801.6510632.589.00.089413w 23821.6537232.589.00.0891445all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 5891.4611862.9411.00.101404 Windows Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.25 ft window ht, 1 ft sep.); 6.8 ft head ht 3487.174088.4100.29049n 2169.331958.4100.29023s 5657.876038.4100.29072all Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.17 ft window ht, 1 ft sep.); 6.8 ft head ht 2917.4138.1200.2802ne 2213.0138.1200.2802se 5015.2278.1200.2803all Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.17 ft window ht, 1 ft sep.); 6.8 ft head ht 5921.7228.1200.2803e Impact: Impact; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 5.4 ft overhang (5.83 ft window ht, 1 ft sep.); 6.8 ft head ht 37614.62178.4100.29026e Impact: Impact; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (1.33 ft window ht, 1 ft sep.); 6.8 ft head ht 718.89658.1200.2808s Impact: Impact; NFRC rated (SHGC=0.26); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 10.4 ft overhang (8 ft window ht, 1 ft sep.); 6.8 ft head ht 79411.06899.5700.33072w Doors 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E Fbrgls Door 1793.731773.697.00.12748e 793.73793.697.00.12721s 1793.731773.697.00.12748w 4373.734333.697.00.127117all Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 5/8" Gyp Bd 0.0342147 31291.4621200.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00626928.700.989219 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Project Summary Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor:2825 Brocksmith Rd, Ft. Pierce, FL 34945 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18998 Structure Btuh15578 Ducts Btuh6600 Ducts Btuh7394Central vent (51 cfm) 1640 Btuh Central vent (51 cfm) Btuh871 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh27239 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh22747 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3009 Ducts Btuh2243Central vent (51 cfm) Btuh1989 CoolingHeating Outside air21472147Area (ft²) Equipment latent load Btuh7241 2143621436Volume (ft³)Air changes/hour 0.160.32 Equipment Total Load (Sen+Lat)Btuh29988 Equiv. AVF (cfm) 57114 Req. total capacity at 0.70 SHR ton2.7 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond 14ACXS036-230A**AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 10259480Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.3 Sensible cooling Btuh24220Heating output Btuh24887 Latent cooling Btuh10380 Temperature rise °F20 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.045 Air flow factor cfm/Btuh0.050Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Entire House Dining/Foyer 2 Exposed wall 218.6 ft 31.5 ft 3 Room height 10.0 ft 11.3 heat/coolft 4 Room dimensions ft12.0x18.0 5 Room area 2147.3 ft²216.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 349 300 773 495 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 49 0 408 348 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 26 25 64 41 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 2 0 13 29 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 296 220 567 362 203 130 334 214 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 3 0 22 59 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 26 15 217 376 26 15 217 376 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 48 48 177 179 48 48 177 179 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 26 25 64 41 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 2 1 13 22 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 516 463 1194 764 0 0 0 0 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 8 8 65 71 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 23 19 195 216 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 21 21 79 79 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 533 413 1063 680 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 72 69 689 794 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 48 48 177 179 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 404 404 1186 589 153 153 448 223 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 2147 2147 2120 3129 216 216 213 315 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 2147 219 6269 0 216 32 903 0 6 c) AED excursion 1139 -36 Envelope loss/gain 15355 9591 2293 1269 12 a) Infiltration 3643 967 424 113 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 4 920 0 0 Appliances/other 4100 0 Subtotal (lines 6 to 13)18998 15578 2717 1382 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 2 3 14 Subtotal 18998 15578 2719 1385 15 Duct loads 35%47%6600 7394 35%47%945 657 Total room load 25598 22972 3664 2043 Air required (cfm)Air required (cfm)1153 1153 165 103 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Master Bath Wtr Clst 2 Exposed wall 29.1 ft 3.5 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft217.6x1.0 ft26.1x1.0 5 Room area 217.6 ft²26.1 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 23 23 60 38 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 26 25 64 41 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 2 0 13 29 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 93 90 233 149 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 3 0 22 59 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 26 25 64 41 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 2 1 13 22 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 102 79 204 130 33 33 84 54 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 23 19 195 216 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 218 218 215 317 26 26 26 38 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 218 29 834 0 26 4 100 0 6 c) AED excursion -30 -3 Envelope loss/gain 1916 1011 210 89 12 a) Infiltration 566 150 68 18 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)2482 1161 278 107 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 15 22 0 0 14 Subtotal 2497 1184 278 107 15 Duct loads 35%47%868 562 35%47%97 51 Total room load 3365 1745 375 158 Air required (cfm)Air required (cfm)152 88 17 8 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 3...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name WIC Pantry 2 Exposed wall 13.0 ft 0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft13.0x7.5 ft9.0x2.5 5 Room area 97.5 ft²22.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 121 121 311 199 0 0 0 0 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 98 98 96 142 23 23 22 33 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 98 13 373 0 23 0 0 0 6 c) AED excursion -10 -1 Envelope loss/gain 781 331 22 32 12 a) Infiltration 252 67 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)1033 398 22 32 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 -22 -32 14 Subtotal 1033 398 0 0 15 Duct loads 35%47%359 189 35%47%0 0 Total room load 1392 587 0 0 Air required (cfm)Air required (cfm)63 29 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 4...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Laundry Master Suite 2 Exposed wall 8.5 ft 31.5 ft 3 Room height 9.3 heat/coolft 9.8 heat/coolft 4 Room dimensions ft8.0x8.5 ft18.0x13.5 5 Room area 68.0 ft²243.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 176 168 434 278 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 8 8 65 71 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 132 84 217 139 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 48 48 177 179 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 79 79 232 115 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 68 68 67 99 243 243 240 354 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 68 9 244 0 243 32 903 0 6 c) AED excursion -18 -43 Envelope loss/gain 543 196 2036 977 12 a) Infiltration 0 0 644 171 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 500 500 Subtotal (lines 6 to 13)543 696 2681 1648 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 7 2 3 14 Subtotal 548 703 2683 1652 15 Duct loads 35%47%190 334 35%47%932 784 Total room load 739 1037 3615 2436 Air required (cfm)Air required (cfm)33 52 163 122 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 5...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Den 2 Exposed wall 25.0 ft 11.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft160.5x1.0 ft11.0x15.0 5 Room area 160.5 ft²165.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 107 91 234 150 102 86 222 142 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 16 0 136 116 16 0 136 116 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 126 126 369 183 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 161 161 158 234 165 165 163 240 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 161 25 717 0 165 11 315 0 6 c) AED excursion -25 -14 Envelope loss/gain 1614 657 836 484 12 a) Infiltration 223 59 213 57 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1837 967 1050 541 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 5 7 16 23 14 Subtotal 1843 974 1066 564 15 Duct loads 35%47%640 462 35%47%370 268 Total room load 2483 1436 1436 832 Air required (cfm)Air required (cfm)112 72 65 42 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 6...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 2 Exposed wall 27.5 ft 18.0 ft 3 Room height 9.3 heat/coolft 9.3 heat/coolft 4 Room dimensions ft180.0x1.0 ft9.0x9.0 5 Room area 180.0 ft²81.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 116 100 258 165 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 16 0 136 116 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 84 62 161 103 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 21 21 79 79 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 140 140 359 230 84 84 216 138 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 180 180 178 262 81 81 80 118 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 180 28 789 0 81 18 516 0 6 c) AED excursion -30 -14 Envelope loss/gain 1720 744 1051 425 12 a) Infiltration 534 142 349 93 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)2253 1135 1401 517 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 10 15 7 10 14 Subtotal 2264 1150 1408 528 15 Duct loads 35%47%787 546 35%47%489 250 Total room load 3050 1696 1897 778 Air required (cfm)Air required (cfm)137 85 85 39 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 7...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Lin 2 Hall 2 Exposed wall 0 ft 0 ft 3 Room height 8.0 heat/coolft 9.3 heat/coolft 4 Room dimensions ft3.0x2.5 ft18.0x3.5 5 Room area 7.5 ft²63.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 8 8 7 11 63 63 62 92 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 8 0 0 0 63 0 0 0 6 c) AED excursion 0 -2 Envelope loss/gain 7 11 62 89 12 a) Infiltration 0 0 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)7 11 62 89 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution -7 -11 -62 -89 14 Subtotal 0 0 0 0 15 Duct loads 35%47%0 0 35%47%0 0 Total room load 0 0 0 0 Air required (cfm)Air required (cfm)0 0 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 8...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Living Room Linen 2 Exposed wall 15.0 ft 0 ft 3 Room height 11.8 heat/coolft 9.3 heat/coolft 4 Room dimensions ft18.0x20.5 ft3.0x2.5 5 Room area 369.0 ft²7.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Block R-9 WallBlock R-9 Wall 0.0890.089 nn 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2900.290 nn 8.418.41 7.177.17 0 0 0 0 0 0 0 0 .WW Block R-9 WallBlock R-9 Wall 0.0890.089 nene 2.582.58 1.651.65 0 0 0 0 0 0 0 0 .GG ImpactImpact 0.2800.280 nene 8.128.12 17.4417.44 0 0 0 0 0 0 0 0 11 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ee 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ee 8.128.12 21.7121.71 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ee 8.418.41 14.5914.59 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ee 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 sese 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 sese 8.128.12 13.0413.04 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ss 2.582.58 1.651.65 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2800.280 ss 8.128.12 8.898.89 0 0 0 0 0 0 0 0 GG ImpactImpact 0.2900.290 ss 8.418.41 9.339.33 0 0 0 0 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ss 3.693.69 3.733.73 0 0 0 0 0 0 0 0 WW Block R-9 WallBlock R-9 Wall 0.0890.089 ww 2.582.58 1.651.65 177 105 271 173 0 0 0 0 GG ImpactImpact 0.3300.330 ww 9.579.57 11.0311.03 72 69 689 794 0 0 0 0 DD Fbrgls DoorFbrgls Door 0.1270.127 ww 3.693.69 3.733.73 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 369 369 364 538 8 8 7 11 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 369 15 430 0 8 0 0 0 6 c) AED excursion 1431 0 Envelope loss/gain 1754 2936 7 11 12 a) Infiltration 369 98 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)2123 4394 7 11 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 26 37 -7 -11 14 Subtotal 2150 4431 0 0 15 Duct loads 35%47%747 2103 35%47%0 0 Total room load 2896 6535 0 0 Air required (cfm)Air required (cfm)130 328 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-25 18:41:14Right-Suite® Universal 2021 21.0.03 RSU27054 Page 9...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Right-J® Worksheet Oct 23, 2020Date:Entire House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen 2 Exposed wall 5.0 ft 3 Room height 9.3 heat/coolft 4 Room dimensions ft223.0x1.0 5 Room area 223.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area Load number (Btuh/ft²-°F)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 W Block R-9 Wall 0.089 n 2.58 1.65 0 0 0 0 .G Impact 0.290 n 8.41 7.17 0 0 0 0 .W Block R-9 Wall 0.089 ne 2.58 1.65 0 0 0 0 .G Impact 0.280 ne 8.12 17.44 0 0 0 0 11 W Block R-9 Wall 0.089 e 2.58 1.65 0 0 0 0 G Impact 0.280 e 8.12 21.71 0 0 0 0 G Impact 0.290 e 8.41 14.59 0 0 0 0 D Fbrgls Door 0.127 e 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 se 2.58 1.65 0 0 0 0 G Impact 0.280 se 8.12 13.04 0 0 0 0 W Block R-9 Wall 0.089 s 2.58 1.65 0 0 0 0 G Impact 0.280 s 8.12 8.89 0 0 0 0 G Impact 0.290 s 8.41 9.33 0 0 0 0 D Fbrgls Door 0.127 s 3.69 3.73 0 0 0 0 W Block R-9 Wall 0.089 w 2.58 1.65 0 0 0 0 G Impact 0.330 w 9.57 11.03 0 0 0 0 D Fbrgls Door 0.127 w 3.69 3.73 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 -2.94 1.46 47 47 137 68 C Attic, Shngl Roof, R 0.034 -0.99 1.46 223 223 220 325 F On Grade Depth, Tile 0.989 -28.68 0.00 223 5 143 0 6 c) AED excursion -65 Envelope loss/gain 500 328 12 a) Infiltration 0 0 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 2 460 Appliances/other 1700 Subtotal (lines 6 to 13)500 2488 Less external load 0 0 Less transfer 0 0 Redistribution 10 14 14 Subtotal 510 2502 15 Duct loads 35%47%177 1188 Total room load 687 3690 Air required (cfm)31 185 2021-Mar-25 18:41:15 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Duct System Summary Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor: 2825 Brocksmith Rd, Ft. Pierce, FL 34945 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.461 / 0.239 in H2O in H2O0.461 / 0.239 Lowest friction rate in/100ft0.267in/100ft0.267 Actual air flow cfm1153cfm1153 Total effective length (TEL) ft262 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2120.043.7VlFx0x06.00.282471031897hBath 2 st2125.046.8VlFx0x07.00.2681021653050hBed 2 st1100.030.2VlFx0x06.00.354871342483hBed 3 st2125.046.9VlFx0x05.00.26850781436hDen st195.026.4VlFx0x06.00.38062991832hDining/Foyer st3120.042.9VlFx0x06.00.28362991832hDining/Foyer-A st195.015.9VlFx0x06.00.416111191845cKitchen st3120.032.0VlFx0x06.00.304111191845cKitchen-A st195.018.1VlFx0x05.00.40863401037cLaundry st3120.043.3VlFx0x07.00.282197783267cLiving Room st2120.046.3VlFx0x08.00.277197783267cLiving Room-A st3120.045.4VlFx0x07.00.2791051823365hMaster Bath st3125.047.7VlFx0x06.00.26773981808hMaster Suite st3120.040.3VlFx0x06.00.28873981808hMaster Suite-A st3120.035.7VlFx0x05.00.29635751392hWIC st3120.040.5VlFx0x04.00.2871020375hWtr Clst Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 423 396 0.268 776 10.0 0x0 VinlFlx st1 st3 Peak AVF 669 666 0.267 852 12.0 0x0 VinlFlx st1 st1 Peak AVF 1384 1384 0.267 783 18.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Mar-25 18:41:15 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 2 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 2710 182 86.6 0.276 496 10.0 x0 0 VlFx rb3 0x 1650 102 89.4 0.267 373 9.0 x0 0 VlFx rt1 rb4 0x 780 50 85.6 0.279 222 8.0 x0 0 VlFx rt1 rb2 0x 1340 87 87.6 0.272 385 8.0 x0 0 VlFx rt1 rb1 0x 7360 963 56.1 0.425 545 18.0 x0 0 VlFx rt1 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1113 1202 0.267 680 18.0 0x0 VinlFlx 2021-Mar-25 18:41:15 Right-Suite® Universal 2021 21.0.03 RSU27054 Page 1 ...ts\Wrightsoft HVAC\TBD Brocksmith Rd(Wells).rup Calc = MJ8 Front Door faces: E 1355Job:Manual S Compliance Report Oct 23, 2020Date:Entire House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Wells Residence, Groza Builders, IncFor: 2825 Brocksmith Rd, Ft. Pierce, FL 34945 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh23844Sensible gain:°F90.4Outdoor design DB: °F64.0Entering coil WB:Btuh7241Latent gain:°F77.4Outdoor design WB: Btuh31085Total gain:°F75.0Indoor design DB: cfm1153Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: 14ACXS036-230A**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer: cfm1153Actual airflow: % of load102Btuh24220Sensible capacity: % of load143Btuh10380Latent capacity: %70SHR:% of load111Btuh34600Total capacity: Heating Equipment Design Conditions °F68.2Entering coil DB:Btuh27239Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1153Actual airflow: °F50Temp. rise:% of load91kW7.3Output capacity: Meets all requirements of ACCA Manual S.