HVAC Calcs
LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS JENSEN BEACH FLORIDA HVAC CALCULATIONS I hereby certify that these plans were made under my responsible charge. This document is electronically signed and sealed pursuant to Section 471.025 of the Florida Statutes and 61G15 of the Florida Administrative Code. John Langford, FL#69962 Mr E ��:N S .. �. No 99!'� ,STATE OF .-�4/ 07/20/14 JWL Engineering JOHN W. LANGFORD ENGINEERING, LLC 238 DOVER STREET Tel. (561) 237-5223 BOCA RATON, FL 334878 Fax. (561) 237-5680 DESIGNED BY: JWLE DATE: 25 MAR 2014 H VAC LOAD CALCULATIONS DRAWN BY: TL DATE: 25 MAR 2014 CHECKED BY: GC DATE: 16 MAY 2014 SIZE A CAGE CODE - DWG NO.. 14042-CAL-500-100-00 00 REV 00 ISSUED BY: JL DATE: 21 MAY 2014 SCALE: NONE STD PLANT SHT 1OF 38 File name: 14042-CAL-500-100-00 OO.doc DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE SHEET 2 OF 38 HVAC LOAD CALCS THIS PAGE IS INTENTIONALLY BLANK DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE SHEET 3 OF 38 HVAC LOAD CALCS REVISIONS REV REVISION DESCRIPTION APR'D BY APRV'D DATE 00 INITIAL ISSUE i i JL 20 JUN 2014 INDEX SHT REVISION DESCRIPTION 1 COVER SHEET 3 REVISION LIST 5 INDEX 7 CALCULATION DETAILS ENTIRE BLD AC 1-1 AC 1-2 AC 2-1 AC 2-2 DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE SHEET 4 OF 38 HVAC LOAD CALCS THIS PAGE IS INTENTIONALLY BLANK DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE HVAC LOAD CALCS SHEET 5 OF 38 REFERENCES NO. DESCRIPTION 1 ARCHITECTURAL FLOORiPLANS, DATED MAY 2014. 2 AMERICAN SOCIETY OF HEATING, REFRIGERATION & AIR CONDITIONING ENGINEERS (ASHRAE) ASHRAE HANDBOOK, FUNDAMENTALS, MANUAL `J' METHOD 3 FLORIDA BUILDING CODE. i GENERAL NO. DESCRIPTION COOLING AND HEATING LOADS HAVE BEEN CARRIED OUT TO SUIT REFERENCE (1) UPDATED 1 TO SUIT SITE VISIT DOCUMENTATION OF MODIFIED CONDITIONS 2 OUTSIDE AIR CALCULATIONS HAVE BEEN DEVELOPED IN ACCORDANCE WITH REFERENCE (3) DESIGN CRITERIA CRITERIA DESCRIPTION OPERATION YEAR-ROUND OUTDOOR CONDITIONS SUMMER: 90 deg DB, 78 deg WB; WINTER: 48 deg F DB; INDOOR CONDITIONS SUMMER: 75 deg F DB, 50% RH; WINTER: 70 deg F DB ASSUMPTIONS NO. DESCRIPTION 1. AS NOTED. DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE SHEET 6 OF 38 HVAC LOAD CALCS THIS PAGE IS INTENTIONALLY BLANK DWG NO.: 14042-CAL-500-100-00 00 LABARBIERA RESIDENCE SHEET 7 OF 38 HVAC LOAD CALCS i CALCULATION DETAILS i -- wrightsoft® Project Summary Entire House JWL ENGINEERING Job: 14042 Date: MAY 07, 2014 By: TL 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax: (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com 'Project, Information For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 F Outside db 90 'F Inside db 70 `F Inside db 75 'F Design TD 22 'F Design TD 15 F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 66205 Btuh Structure 82930 Btuh Ducts 15500 Btuh Ducts 10646 Btuh Central vent (0 cfm) 0 Btuh Central vent (0. cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 81704 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 89085 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 7707 Btuh Ducts 9035 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 6390 6390 Equipment latent load 16742 Btuh Volume (ft3) 76680 76680 Air changes/hour 0.28 0.15 Equipment total load 105826 Btuh Equiv. AVF (cfm) 358 192 Req. total capacity at 0.70 SHR 10.6 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref no.n/a Coil n/a AHRI ref no.n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total'cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -4- wrightsoft' Right -Suite® Universal 8.0.11 RSU14166 ACCK 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Pagel - Load Short Form Job: 14042 wrightsoft� Entire House Date: By: MAY 07, 2014 TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL 33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.cam Web: www.jwlengineering.com Project For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Design Information Htg Clg Infiltration Outside db (F) 48 90 Method Simplified Inside db (F) 70 75 Construction.quality Average Design TD (F) 2? 15 Fireplaces 0 Daily range I- L Inside humidity (%) 50 50 Moisture difference (gr/lb) 15 ICI 59 HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref no.n/a Coil n/a AHRI ref no.n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft?) (Btuh) (Btuh) (cfm) (cfm) AC 1-01 d 1320 18994 22064 1002 1002 AC 1-02 d 2137 25776 32975 1496 1496 AC 2-01 d 884 12804 13027 592 592 AC 2-02 d 2049 24130 28332 1285 1285 Entire House d 6390 81704 93576 4374 4808 Other equip loads 0 0 Equip. @ 0.95 RSM 89085 Latent cooling 16742 TOTALS ' 6390 1 81704 1 105826 4374 4808 it Calculations by ACCA to meet all requirements of Manual J 8th Ed. n� W1'ightSoft"' Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:14 AC +K ..._00 - HVAC LOADS\R00 - OPEN\14042_HVACi Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 1 Component Constructions Job: 14042 - wrightsoft- p Date: MAY 07, 2014 Entire House By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineeeing.com • • • For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Design • • • Location: Indoor: Heating Cooling West Palm Beach Intl AP, FL, US Indoor temperature (F) 70 75 Elevation: 20 ft Design TD (F) 22 15 Latitude: 27 N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 14.7 59.2 Dry bulb (F) 48 90 Infiltration: Daily range (F) - 13 (L ) Method Simplified Wet bulb (F) - 78 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft, Bluh/F1'-F ft`-F/Btuh BtuhfiF Btuh Btuhff Btu Walls 13A-4ocs' Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 5/8" gypsum n 1728 0.143 4.0 3.10 5363 2.71 4683 board int fnsh a 739 0.143 4.0 3.10 2295 2.71 2004 s 1807 0.143 4.0 3.10 5606 2.71 4895 w 1215 0.143 4.0 3.10 3769 2.71 3291 all 5489 0.143 4.0 3.10 17032 2.71 14874 Partitions 12C-Osw: Frm wall, stucco ext, r-13 cav ins, 2"x4" wood frm 618 0.091 13.0 1.97 1220 1.39 858 Windows 1 glazing, clr giz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no n 90 1.100 0 23.9 2158 27.2 2460 brk frm mat, 1/8" thk; 2 ft overhang (5 ft window ht, 2 ft sep.) s 25 1.100 0 23.9 597 27.2 680 all 115 1.100 0 23.9 2755 27.2 3140 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no n 21 1.100 0 23.9 493 27.2 562 brk frm mat, 1/8" thk; 19.6 ft overhang (8 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no n 21 1.100 0 23.9 493 27.2 562 brk frm mat, 1/8" thk; 26 ft overhang (8 ft window ht, 2 ft sep.) a 16 1.100 0 23.9 382 27.2 435 all 37 1.100 0 23.9 875 27.2 997 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no e 7 1.100 0 23.9 172 64.8 466 brk frm mat, 1/8" thk; 2 ft overhang (3.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no a 18 1.100 0 23.9 430 27.2 490 brk frm mat, 1/8" thk; 13 ft overhang (4.5 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no a 66 1.100 0 23.9 1575 64.8 4275 brk frm mat, 1/8" thk; 2 ft overhang (6.6 ft window ht, 2 ft sep.) s 20 1.100 0 23.9 473 27.2 539 all 86 1.100 0 23.9 2048 56.1 4813 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 105 1.100 0 23.9 2506 46.1 4841 brk frm mat, 1/8" thk; 6.6 ft overhang (7 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 73 1.100 0 23.9 1739 27.2 1981 brk frm mat, 1/8" thk; 13 ft overhang (7.6 ft window ht, 2 ft sep.) ACCAd- wrightsoft" Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 1 Q f I glazing, clr giz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 90 1.100 0 23.9 2148 64.8 5829 brk frm mat, 1/8" thk; 2 ft overhang (9 ft window ht; 2 ft sep.) 1 glazing, cir glz, mtl no brk frm mat, 1/8" thk; 1 glazing, clr glz, mtl no a 194 .1.100 0 23.9 4619 32.9 6372 brk frm mat, 1/8" thk; 11.6 ft overhang (9 ft window, ht, 2 ft sep.) 1 glazing, clr glz, mtl no.brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 90 1.100 0 23.9 2148 27.2 2448 brk frm mat, 1/8" thk; 26 ft overhang (9 ft window ht, 2 ft sep.) i 1 glazing, clr giz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no s 8 1.100 0 23.9 191 27.2 218 brk frm mat, 1/8" thk; 2 ft overhang (4 ft window ht) 2 ft sep.) 1 glazing, cir glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no s 21 1.100 0 23.9 501 27.2 571 brk frm mat, 1/8" thk; 19.6 ft overhang (6 ft window. ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no s 27 1.100 0 23.9 644 27.2 734 brk frm mat, 1/8" thk; 26 ft overhang (6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no s 37 1.100 0 23.9 875 27.2 997 brk frm mat, 1/8" thk; 2 ft overhang (8 ft window ht,12 ft sep.) 1 glazing, cir giz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir giz, mtl no w 14 1.100 0 23.9 329 64.8 894 brk frm mat, 1/8" thk; 2 ft overhang (4.6 ft window hit, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no w 28 1.100 0 23.9 659 40.4 1116 brk frm mat, 1/8" thk; 6 ft overhang (4.6 ft window fit, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no w 14 1.100 0 23.9 329 27.2 375 brk frm mat, 1/8" thk; 16 ft overhang (4.6 ft window ht, 2 ft sep.) 1 glazing, cir giz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no w 83 1.100 0 23.9 1969 64.8 5343 brk frm mat, 1/8" thk; 2 ft overhang (6 ft window ht,;2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w 48 1.100 0 23.9 1146 46.1 2213 brk frm mat, 1/8" thk; 6 ft overhang (6 ft window ht,!2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w 65 1.100 0 23.9 1657 50.0 3264 brk frm mat, 1/8" thk; 6 ft overhang (7.6 ft window ht, 2 ft sep.) 1 glazing, clr giz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no w 131 1.100 0 23.9 3115 52.3 6829 brk frm mat, 1/8" thk; 6 ft overhang (9 ftwindow ht, 12 ft sep.) I i 8Acw-2w: Sky glazing, small, wood curb, no shaft I'gt shaft, wd sash; 2 0 1.160 0 25.2 10 194 78 ft overhang (1 ft window ht, 2 ft sep.) Doors (none) Ceilings 16X19-Otd: Attic ceiling, tile, slate, concrete roof mat, r-20 roof ins, 3673 0.408 19.01 1.23 4514 1.31 4799 1/2" gypsum board int fnsh Floors 19C-19cscp: Flr floor, frm flr, 6" thkns, carpet flr fnsh, r-2 ext ins, r-19 1647 0.049 30.0 0.37 607 0.26 425 cav ins, tight crwl ovr, r-11 wall insul 22A-wpl: Bg floor, light dry soil, on grade depth, hrd, wd flr fnsh i 141 0.989 0 21.5 3035 0 0 i a. -FJF,- wrightsoft- Right -Suite® Univeirsal 8.0.11 RSU14166 ACOI 2014-Jul-15 09:00:15 ..._00 - HVAC LOADS\R00 - OPEN\14042_HVACI Calcs_06-07-14_1100.rup I Calc = MA Front Door faces: Page 2 -- wrightsoft- Project Summary AC 1-01 JWL ENGINEERING Job: 14042 Date: MAY 07, 2014 By: TL 238 DOVER STREET, BOCA RATON, FL 33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales..@jwlengineering.com Web: www.jwlengineering.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: -Desi . n 4riformation e Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 F Outside db 90 'F Inside db 70 F Inside db 75 'F Design TD 22 'F Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 15744 Btuh Structure 19766 Btuh Ducts 3249 Btuh Ducts 2298 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 18994 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 21005 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1728 Btuh Ducts 1918 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2 1320 1320 Equipment latent load 3645 Btuh . Volume ft') 15840 15840 Air changes/hour 0.30 0.16 Equipment total load 24650 Btuh Equiv. AVF (cfm) 80 43 Req. total capacity at 0.70 SHR 2.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trade Trade Model Cond AHRI ref no. Coil AHRI ref no. Efficiency 80AFUE Efficiency 0 SEER Heating input 0 Btuh Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total cooling 0 Btuh Actual air flow 1002 cfm Actual air flow 1002 cfm Air flow factor 0.053 cfm/Btuh Air flow. factor 0.039 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.86 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. - wr!ahtsoft:- Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 . HVAC LOADS\R00 - OPEN\14042_HVAC Caics_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 2 -- wrightsoft- Project Summary VAV 1-01A JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL 33487 Phone: Job: 14042 Date: MAY 01, 2014 By: TL. 237-5223 Fax (561) 237-5680 Email: sales@jwlenginee6ng.com Web: www.jwlengineedng.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Outside db 48 F Inside db 70 F Design TD j 22 'F Heating Summary Structure 14964 Btuh Ducts 1025 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 5989 Btuh Infiltration Method Construction quality Fireplaces Heati m Area (ftz) 42? Volume (ft3) 514,' Air changes/hour 0.3, Equiv. AVF (cfm) 2! Heating Equipment Su Make n/a Trade n/a Model n/a AHRI ref no.n/a Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat n/E Calculations Simplified Average 0 Cooling 429 5142 0.18 16 mary n/a 0 Btuh 0 F 0 cfm 0 cfm/Btuh 0 in H2O Summer Design Conditions Outside db 90 `F Inside db 75 'F Design TD 15 `F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 7242 Btuh Ducts 842 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 7696 Btuh Latent Cooling Equipment Load Sizing Structure 626 Btuh Ducts 622 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 1248 Btuh Equipment total load 8944 Btuh Req. total capacity at 0.70 SHR 0.9 ton Cooling Equipment Summary Make n/a Trade n/a , Cond n/a Coil n/a AHRI ref no.n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 by ACCA to meet all requirements of Manual J 8th Ed. CA -�- wr19htsc ft Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVACI Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 6 Q -- wrightsoft- Project Summary VAV 9-01 B JWL ENGINEERING Job: 14042 Date: MAY 07, 2014 By: TL 238 DOVER STREET, BOCA RATON, FL 33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineering.com �Project Information For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Design 1nfbrmati6n Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 F Outside db 90 'F Inside db 70 c Inside db 75 'F Design TD 22 'F Design TD 15 `F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Structure 5038 Btuh Ducts 1040 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 6078 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Heating Cooling Area (ftz) 273 273 Volume (ft3) 3270 3270 Air changes/hour 0.47 0.25 Equiv. AVF (cfm) 26 14 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref no.n/a Efficiency n/a Heating input Heating output 0 Btuh Temperature rise 0 'F Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat n/a Sensible Cooling Equipment Load Sizing Structure 9391 Btuh Ducts 1092 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 9979 Btuh Latent Cooling Equipment Load Sizing Structure 551 Btuh Ducts 396 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 947 Btuh Equipment total load 10926 Btuh Req. total capacity at 0.70 SHR 1.2 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a AHRI ref no.n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. '4 C� -�- wrightsoft' Right -Suite@) Universal 8.0.11 RSU14166 .._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Cale = MJ8 Front Door faces: 2014-Jul-15 09:00:15 Page 7 I Project Summary Job: 14042 -- wrightsoft� Date: MAY 07, 2014 VAV 1-01 C By: TL JWL ENGINEERING i 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com For: Notes: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Winter Design Conditions Summer Design Conditions Outside db 48 'F Outside db 90 `F Inside db 70 'F Inside db 75 'F Design TD 22 F Design TD 15 F Daily range L Relative, humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 5742 Btuh Structure 9740 Btuh Ducts 1185 Btuh Ducts 1132 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 6928 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 10350' Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 551 Btuh Ducts , 899 Btuh Heating Cooling Central vent (0 cfm) .0 Btuh Area 619 619 Equipment latent load 1450 Btuh Volume e ft3) 7428 7428 Air changes/hour 0.21 0.11 Equipment total load 11800 Btuh Equiv. AVF (cfm) 26 14 Req. total capacity at 0.70 SHR 1.2 ton i Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref no.n/a Coil n/a AHRI ref no.n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F,, Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a I Load sensible heat ratio 0 II Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. wrightsofV Right -Suite@ ACCN .._00 - HVAC LOADS\R00 - OPEN\14042_1- ;rsal 8.0.11 RSU14166 Calcs_06-07.14_1100.rup Calc = MJ8 Front Door faces: 2014-Jul-15 09:00:15 Page 8 Load Short Form Job: 14042 WI'19 htSOfto Date: MAY 07, 2014 AC 1-01 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax: (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com Project• • For: LABARBI ERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL OesignAnformation. Htg Clg Infiltration Outside db (F) 48 90 Method Simplified Inside db (F) 70 75 Construction quality Average Design TD (F) 22 15 Fireplaces 0 Daily range - L Inside humidity (%) 50 50 Moisture difference (gr/lb) 15 59 HEATING EQUIPMENT Make Trade Model AHRI ref no. Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 80 AFU E 0 Btuh 0 Btuh 0 'F 1002 cfm 0.053 cfm/Btuh 0 in H2O COOLING EQUIPMENT Make Trade Cond Coil AHRI ref no. Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 0 SEER 0 Btuh 0 Btuh 0 Btuh 1002 cfm 0.039 cfm/Btuh 0 in H2O 0.86 ROOM NAME Area Htg load CIg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) VAV 1-01A p 429 5989 8084 316 312 VAV 1-01B p 273 6078 10482 321 404 VAV 1-01 C p 619 6928 10872 365 419 AC 1-01 d 1320 18994 22064 1002 1002 Other equip loads 0 0 Equip. @ 0.95 RSM 21005 Latent cooling 3645 TnTAIS I320 18994 24650 10 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -Pp- wrightsofV Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:14 ACCK ..._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 2 I Component Constructions Job: 14042 - - wrightsoft� AC 1-01 Date: ML Y 07, 2014 I Y: JWL ENGINEERING I 238 DOVER STREET, BOCA RATON, FL33481 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineering.com For: LABARBIERA RESIDENCE LOT 35 b IAMOND SANDS, JENSEN BEACH, FL Location: r West Palm Beach Intl AP, FL, US Elevation: 20 ft Latitude: 27 N Outdoor: Heating) Cooling Dry bulb (F) 48 90 Daily range (F) - 13 (L ) Wet bulb (F) - 78 Wind speed (mph) 15.0 7.5 i i Indoor: Heating Cooling Indoor temperature (F) 70 75 Design TD (F) 22 15 Relative humidity (%) 50 50 Moisture difference (gr/lb) 14.7 59.2 Infiltration: Method Simplified Construction quality Average Fireplaces 0 Construction descriptions or Area U-value Insul R Htg HTM Loss Cig HTM Gain ft2 BtuhHt'-F fP-FBWh Btuh/ft' Btuh Btuh/F1' Btuh Walls 13A-4ocs: Blk wall, stucco ext, r-4 ext bd ins, 8" t k, 5/8" gypsum n 81 0.143 4.0 3.10 252 2.71 220 board int fnsh a 90 0.143 4.0 3.10 279 2.71 244 s 698 0.143 4.0 3.10 2167 2.71 1892 w 395 0.143 4.0 3.10 1224 2.71 1069 all 1264 0.143 4.0 3.10 3922 2.71 3425 Partitions 12C-Osw: Frm wall, stucco ext, r-13 cav ins, 2"x4"wood frm 618 0.091 13.0 1.97 1220 1.39 858 Windows 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glaang, clr glz, mtl no n 21 1.100 0 23.9 493 27.2 562 brk frm mat, 1/8" thk; 26 ft overhang (8 ft window hi, 2 ft sep.) 1 glazing, cir glz, mtl no brk frm mat, 118" thk: 1 glazing, clr glz, mtl no s 20 1.100 0 23.9 473 27.2 539 brk frm mat, 1/8" thk; 2 ft overhang (6.6 ft window lit, 2 ft sep.) I . 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no a 90 1.100 0 23.9 2148 64.8 5829 brk frm mat, 1/8" thk; 2 ft overhang (9 ft window ht,12 it sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no s 8 1.100 0 23.9 191 27.2 218 brk frm mat, 1/8" thk; 2 ft overhang (4 ft window ht,12 ft sep.) I 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr giz, mtl no w 47 1.100 0 23.9 1110 64.8 3012 brk frm mat, 1/8" thk; 2 ft overhang (6 ft window ht,12 ft sep.) 1 glazing, cir glz, mtl no brk frm mat, 1/8" thk: 1 glalzing, cir glz, mtl no w 48 1.100 0 23.9 1146 46.1 2213 brk frm mat, 1/8" thk; 6 ft overhang (6 ft window ht, 12 ft sep.) I 1 glazing, cir glz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no w 27 1.100 0 23.9 644 52.3 1413 brk frm mat, 1/8" thk; 6 ft overhang (9 ft window ht, 12 ft sep.) Doors (none) -Pj4- wrightsaft- Right -Suite@ Uni ersal 8.0.11 RSU14166 ACCK._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front 2014-Jul-15 09:00:15 Door faces: Page 3 Ceilings 16X19-Otd:Attic ceiling, tile, slate, concrete roof mat, r-20 roof ins, 395 0.408 19.0 1.23 485 1.31 516 1/2" gypsum board int fnsh Floors 19C-19cscp: Fir floor, frm fir, 6" thkns, carpet fir fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insui 22A-wpl: Bg floor, light dry soil, on grade depth, hrd wd flr fnsh 357 0.049 30.0 87 0.989 0 0.37 132 0.26 92 21.5 1866 0 0 $C '4+*- wrightsoft- Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Caics_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 4 Project Summa Job: 14042 wrightsoft r Date: MAY 07, 2014 AC 1-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL I Notes: West Palm'Beach Intl AP, FL, US Winter Design Conditions Outside db 48 F Inside db 70 F Design TD 22 cF Heating Summary Structure 20214 Btuh Ducts : 5562 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping j 0 Btuh Equipment load 25776 Btuh Infiltration Method Simplified Construction quality Average Fireplaces 0 Heating Cooling Area (ftz) , 2137 2137 Volume (ft3) 25644 25644 Air changes/hour 0.24 0.13 Equiv. AVF (cfm) 103 55 Heating Equipment Summary Make Trade Model AHRI ref no. Efficiency Heating Input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 80 AFUE I 0 Btuh 0 Btuh 0 'F '1496 cfm 0.058 cfm/Btuh 0 in ,H2O Summer Design Conditions Outside db 90 'F Inside db 75 'F Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 29031 Btuh Ducts 3944 Btuh Central vent (0 cfm) '0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 31393 Btuh Latent Cooling Equipment Load Sizing Structure 2211 Btuh Ducts 3264 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 5475 Btuh Equipment total load 36867 Btuh Req. total capacity at 0.70 SHR 3.7 ton Cooling Equipment Summary Make Trade Cond Coil AHRI ref no. Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 0 SEER 0 Btuh 0 Btuh 0 Btuh 1496 cfm 0.042 cfm/Btuh 0 in H2O 0.86 ACC -PI -�- wrightsoft-' Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVACICalcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 3 - wrightsoft, Project Summary VAV 1-02A JWL ENGINEERING Job: 14042 Date: MAY 07, 2014 By: TL 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com Project Information For: LABARBIERA RESIDENCE 'LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Design Information Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 'F Outside db 90 'F Inside db 70 F Inside db 75 'F Design TD 22 'F Design TD 15 F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 7453 Btuh Structure 16980 Btuh Ducts 2051 Btuh Ducts 2307 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 9504 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 18361 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 925 Btuh Ducts 1124 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 736 736 Equipment latent load 2049 Btuh Volume (ft3) 8832 8832 Air changes/hour 0.29 0.16 Equipment total load 20411 Btuh Equiv. AVF (cfm) 43 23 Req. total capacity at 0.70 SHR 2.2 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref no.n/a Coil n/a AHRI ref no.n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -Pk- wr1,ahtsoft- Right -Suite@) Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS1R00 - OPEN114042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 9 i Project SUmma Job: 14042 -- wrightsoft- Date: MAY 07, 2014 VAV 1-02B By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineering.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 F Outside db 90 'F Inside db , 70 'F Inside db 75 'F Design TD 22 T: Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary 112761 Sensible Cooling Equipment Load Sizing Structure Btuh Structure 17630 'Btuh Ducts 3511 Btuh Ducts 2395 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 16272 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 19064 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1286 Btuh Ducts 2140 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ftz 1401 1401 Equipment latent load 3425 Btuh Volume (W) 16812 16812 Air changes/hour 0.21 0.11 Equipment total load 22489 Btuh Equiv. AVF (cfm) 60 32 Req. total capacity at 0.70 SHR 2.3 ton Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref no.n/a Coil n/a AHRI ref no.n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total cooling 0 Btuh Actual air flow 0 cfm Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat n/a Load sensible heat ratio 0 i Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. Ad- wrightsoft- Right -Suite@) Universal 8.0.11 RSU14166 ACCK 2014-Jul-15 09:00:15 .._00 - HVAC LOADS\R00 - OPEN114042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 10 9 . Load Short Form Job: 14042 WI'1 ht$Oft Date: MAY 07, 2014 AC 1-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax: (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com e-roject intormation For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Htg Clg Infiltration Outside db (F) 48 90 Method Simplified Inside db (F) 70 75 Construction quality Average Design TD (F) 22 15 Fireplaces 0 Daily range - L Inside humidity (%) 50 50 Moisture difference (gr/lb) 15 59 HEATING EQUIPMENT Make Trade Model AHRI ref no. Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 80 AFUE 0 Btuh 0 Btuh 0 'F 1496 cfm 0.058 cfm/Btuh 0 in H2O COOLING EQUIPMENT Make Trade Cond Coil AHRI ref no. Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 0 SEER 0 Btuh 0 Btuh 0 Btuh 1496 cfm 0.042 cfm/Btuh 0 in H2O 0.86 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) VAV 1-02A p 736 9504 19287 551 811 VAV 1-02B p 1401 16272 20025 944 843 AC 1-02 d 2137 25776 32975 1496 1496 Other equip loads 0 0 Equip. @ 0.95 RSM 31393 Latent cooling 5475 TnTAIQ 7147 7CZ77R 4QQr-7 4AaR 4Ana Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. r4+. 411_ wrightsoft- Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:14 ACCK ..._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 3 -- wrightsoft° Component Constructions Job: 14042 Date: MAY 07, 2014 AC 1-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www,jwlengineedng.com I Project• • For: LABARBIERARESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL D- • • • • Location: Indoor: Heating Cooling West Palm Beach Intl AP, FL, US Indoor temperature (F) 70 75 Elevation: 20 ft Design TD (F) 22 15 Latitude: 27 N Relative humidity (%) 50 50 Outdoor: Heating Cooling Moisture difference (gr/lb) 14.7 59.2 Dry bulb (F) 48 90 Infiltration: Daily range (F) - 13 ( L ) Method Simplified Wet bulb (F) - 78 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain tP BtuhAP-F ft'-'F/Btuh BtuhKe Btuh BtuhAt' Btuh Walls 13A-4ocs: Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 5/8" gypsum n 753 0.143 4.0 3.10 2337 2.71 2041 board int fnsh a 223 0.143 4.0 3.10 690 2.71 603 s 209 0.143 4.0 3.10 649 2.71 566 w 245 0.143 4.0 3.10 759 2.71 663 all 1429 0.143 4.0 3.10 4435 2.71 3873 Partitions (none) Windows 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no n 39 1.100 0 23.9 925 27.2 1054 brk frm mat, 1/8" thk; 2 ft overhang (5 ft window ht,; 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 16 1.100 0 23.9 382 27.2 435 brk frm mat, 1/8" thk; 26 ft overhang (8 ft window hi., 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no a 194 1.100 0 23.9 4619 32.9 6372 brk frm mat, 1/8" thk; 11.6 ft overhang (9 ft window:ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8"thk: 1 glazing, clr glz, mtl no a 90 1.100 0 23.9 2148 27.2 2448 brk frm mat, 1/8" thk; 26 ft overhang (9 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no s 27 1.100 0 23.9 644 27.2 734 brk frm mat, 1/8" thk; 26 ft overhang (6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing; clr glz, mtl no s 16 1.100 0 23.9 382 27.2 435 brk frm mat, 1/8" thk; 2 ft overhang (8 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w 36 1.100 0 23.9 859 64.8 2332 brk frm mat, 1/8" thk; 2 ft overhang (6 ft window ht,12 ft sep.) I 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w 104 1.100 0 23.9 2471 52.3 5416 brk frm mat, 1/8" thk; 6 ft overhang (9 ft window ht,12 ft sep.) I �h -` k- wrilghtsoft- Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ..._00 - HVAC LOADS1R00 - OPEN114042_HVA6 Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: I Page 5 Doors (none) Ceilings 16X19-Otd: Attic ceiling, tile, slate, concrete roof mat, r-20 roof ins, 1/2" gypsum board int fnsh Floors 19C-19cscp: Fir floor, frm fir, 6" thkns, carpet fir fnsh, r-2 ext ins, r-19 cav ins, tight crwl ovr, r-11 wall insul 346 0.408 19.0 1290 0.049 30.0 1.23 425 1.31 451 0.37 476 0.26 333 � Ad-wrightsoft" Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 6 Pro ect $umma d -�- W rightsoft® /� /+ � � Date: MAY e: MAY 07, 2o1a A C 2-01 , By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineenng.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Design Information Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 F Outside db 90 'F Inside db 70 'F Inside db 75 'F Design TD 22 ' Design TD 15 F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure '10973 Btuh Structure 11735 Btuh Ducts 1831 Btuh Ducts 1292 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 12804 Btuh Use manufacturer's data n ' Rate/swing multiplier 0.95 Infiltration Equipment sensible load 12402 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 1245 Btuh Ducts 1041 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ft2) 884 884 Equipment latent load 2286 Btuh Volume (ft3) 10611 10611 Air changes/hour 0.33 0.18 Equipment total load 14688 Btuh Equiv. AVF (cfm) 58 31 Req. total capacity at 0.70 SH.R 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trade Trade Model Cond AHRI ref no. Coil AHRI ref no. Efficiency 80AFUE Efficiency 0 SEER Heating input 0 'Btuh Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 0 'F Total cooling 0 Btuh Actual air flow 592 cfm Actual air flow 592 cfm Air flow factor 0.046 cfm/Btuh Air flow factor 0.045 cfm/Btuh Static pressure 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.85 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. -Pk- wriahtsoft Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ..._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 4 9 o Load Short Form Job: 14042 wri htsoft Date: MAY 07, 2014 A 2-01 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com Project• • For: LABARBI ERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Htg Clg Outside db (F) 48 90 Method Inside db (F) 70 75 Construction quality Design TD (F) 22 15 Fireplaces Daily range - L Inside humidity (%) 50 50 Moisture difference (gr/lb) 15 59 HEATING EQUIPMENT Make Trade Model AHRI ref no. Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 80 AFU E 0 Btuh 0 Btuh 0 1= 592 cfm 0.046 cfm/Btuh 0 in H2O Infiltration Simplified Average 0 COOLING EQUIPMENT Make Trade Cond Coil AHRI ref no. Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 0 SEER 0 Btuh 0 Btuh 0 Btuh 592 cfm 0.045 cfm/Btuh 0 in H2O 0.85 ROOM NAME Area Htg load Clg load Htg AVF CIg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) HER W.I.0 110 829 626 38 28 HIS W.I.0 90 779 512 36 23 MASTER BATH 228 2421 2544 112 116 MASTER BEDROOM 456 8776 9346 406 424 AC 2-01 d 884 12804 13027 592 592 Other equip loads 0 0 Equip. @ 0.95 RSM 12402 Latent cooling 2286 Tr1TA1 C! 1 OOA 1 470r%A 4AGOO Grl7 =nn Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. ' wrightsc3fft- Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:14 ACC, ..._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 4 Component Constructions Job: 14042 - d- wrightsoft , /� /+ Date: MAY 07, 2014 AC 2-01 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineering.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Design Conditions Location: Indoor: Heating Cooling West Palm Beach Intl AP, FL, US Indoor'temperature (F) 70 75 Elevation: 20 ft Design TD (F) 22 15 Latitude: 27 N Relative humidity (%) 50 50 Outdoor: Heating! Cooling Moisture difference (gr/lb) 14.7 59.2 Dry bulb (F) 48 1 90 Infiltration: Daily range (F) - 13 ( L ) Method Simplified Wet bulb (F) - 78 Construction quality Average Wind speed (mph) 15.0 I i 7.5 Fireplaces 0 Construction descriptions' I Or Area U-value Insul R Htg HTM Loss fl' Btuh&-F tP-FBtuh Btuhff Btuh Cig HTM Gain BtuhM2 Btuh Walls I 13A-4ocs: Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 5/8" gypsum board intfnsh Partitions (none) Windows' i 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 2 ft overhang (5 It window ht, l2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 2 ft overhang (3.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 13 ft overhang (4.5 ft window,ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 6.6 ft overhang (7 ft window hit, 2 ft sep.) I 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 19.6 ft overhang (6 ft window �ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk; 2 ft overhang (8 ft window ht, 2 ft sep.) Doors (none) Ceilings n 425 0.143 4.0 3.10 1319 2.71 1152 e 212 0.143 4.0 3.10 657 2.71 574 s 264 0.143 4.0 3.10 819 2.71 715 all 901 0.143 4.0 3.10 2795 2.71 2441 n 13 1.100 0 23.9 308 27.2 351 s 13 1.100 0 23.9 298 27.2 340 all 25 1.100 0 23.9 607 27.2 691 e 7 1.100 0 23.9 172 64.8 466 e 18 1.100 0 23.9 430 27.2 490 e 105 1.100 0 23.9 2506 46.1 4841 s 21 1.100 0 23.9 501 27.2 571 s 21 1.100 0 23.9 493 27.2 562 16X19-0td: Attic ceiling, tile, slate, concrete roof mat, r-20 roof ins, 884 0.408 19.0 1.23 1087 1.31 1155 1/2" gypsum board int fnsh ! -'-F'- wrightsc ft" Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 -, HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 7 Floors 22A-wpl: Bg floor, light dry soil, on grade depth, hrd wd flr fnsh 47 0.989 0 21.5 1004 44- wrightsoft" Right -.Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ..._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 8 Pro ect SUmma Job: 14042 - wrightsoft© ry Date: MAY 07, 2014 AC 2-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedn§.com ,Project• 1 I For: LABARBI ERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Weather: West Palm Beach Intl AP, FL, US Winter Design Conditions Summer Design Conditions Outside db 48 'F Outside db 90 'F Inside db 70 'F Inside db 75 'F Design TD 22 F Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure �9273 Btuh Structure 24897 Btuh Ducts 4857 Btuh Ducts 3435 Btuh Central vent (0 cfm) 0 .Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24130 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 26972 Btuh Method i Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2524 Btuh Ducts 2812 Btuh Heating Cooling Central vent (0 cfm) 0 Btuh Area (ftz) 2049 2049 Equipment latent load 5336 Btuh Volume (ft3) 24585 24585 Air changes/hour 0.29 0.15 Equipment total load 32308 Btuh Equiv. AVF (cfm) 117 63 Req. total capacity at 0.70 SHR 3.2 ton Heating Equipment Summary Cooling Equipment Summary Make Make Trade Trade Model Cond AHRI ref no. Coil AHRI ref no. Efficiency 80AFUE Efficiency 0 SEER Heating input 0 Btuh Sensible cooling 0 Btuh Heating output 0 Btuh Latent cooling 0 Btuh Temperature rise 1 0 'F Total cooling 0 Btuh Actual air flow 1285 cfm Actual air flow 1285 cfm Air flow factor 0.053 cfm/Btuh Air flow,factor 0.041 cfm/Btuh Static pressure 1 0 in H2O Static pressure 0 in H2O Space thermostat Load sensible heat ratio 0.84 i Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. i C� Ad- wrightsoft- Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ..._00 - HVAC LOADS\R00 - OPEN\14042_HVACI Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 5 I i - wrightsoft° Project Summary VAV 2-02A JWL ENGINEERING Job: 14042 Date: MAY 07, 2014 By: TL 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Weather: West Palm Beach Intl AP, FL, US Winter,Design Conditions Outside db 48 F Inside db 70 F Design TD 22 '17 Heating Summary Structure 9490 Btuh Ducts 2391 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 11882 Btuh Infiltration Method Construction quality Fireplaces Area (ftz) Volume (ft') Air changes/hour Equiv. AVF (cfm) Simplified Average 0 Heating Cooling 1075 1075 12903 12903 0.24 0.13 51 27 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref no.n/a Efficiency n/a Heating input Heating output 0 Btuh Temperature rise 0 F Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat n/a Summer Design Conditions Outside db 90 'F Inside db 75 'F Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 12646 Btuh Ducts 1745 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 13700 Btuh Latent Cooling Equipment Load Sizing Structure 1102 Btuh Ducts 1476 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 2578 Btuh Equipment total load 16278 Btuh Req. total capacity at 0.70 SHR 1.6 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a AHRI ref no.n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. C� -�- wrightsc ft- Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Cato = MJ8 Front Door faces: Page 11 i Project Summary 7 wrightsoft VAV 2-02B Job: 14042 Date: MAY 07, 2014 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineering.com For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Notes: Winter Design Conditions Outside db 48 1= Inside db 70 F Design TD 22 F Heating Summary Structure 19783 Btuh Ducts 2465 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Piping 0 Btuh Equipment load 12249 Btuh I Infiltration Method Construction quality Fireplaces West Palm Beach Intl AP, FL, US Slmpllfled Average 0 Heating Cooling Area (ft2) 974 974 Volume (ft3) 11682 11682 Air changes/hour 0.34 0.18. Equiv. AVF (cfm) 66 35 Heating Equipment Summary Make n/a Trade n/a Model n/a AHRI ref no.n/a Efficiency n/a Heating input Heating output 0 Btuh Temperature rise 0 'F Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Space thermostat . n/a Calculations Summer Design Conditions Outside db 90 'F Inside db 75 'F Design TD 15 'F Daily range L Relative humidity 50 % Moisture difference 59 gr/lb Sensible Cooling Equipment Load Sizing Structure 17704 Btuh Ducts 2443 Btuh Central vent (0 cfm) 0 Btuh Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 19180 Btuh Latent Cooling Equipment Load Sizing Structure 1422 Btuh Ducts 1336 Btuh Central vent (0 cfm) 0 Btuh Equipment latent load 2758 Btuh Equipment total load 21938 Btuh Req. total capacity at 0.70 SHR 2.3 ton Cooling Equipment Summary Make n/a Trade n/a Cond n/a Coil n/a AHRI ref no.n/a Efficiency n/a Sensible cooling 0 Btuh Latent cooling 0 Btuh Total cooling 0 Btuh Actual air flow 0 cfm Air flow factor 0 cfm/Btuh Static pressure 0 in H2O Load sensible heat ratio 0 by ACCA to meet all requirements of Manual J 8th Ed. -Pp- wrightsoft- Right -Suite® Universal 8.0.11 RSU14166 ACCA ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC,Calcs_06-07A4_1100.rup Cale = MJ8 Front Door faces: 2014-Jul-15 09:00:15 Page 12 9 Load Short Form Job: 14042 wri htsoft Date: MAY 07, 2014 AC 2-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com iLroject intormation For: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Htg Clg Outside db (F) 48 90 Method Inside db (F) 70 75 Construction quality Design TD (F) 22 15 Fireplaces Daily range - L Inside humidity (%) 50 50 Moisture difference (gr/lb) 15 59 HEATING EQUIPMENT Make Trade Model AHRI ref no. Efficiency Heating input Heating output Temperature rise Actual air flow Air flow factor Static pressure Space thermostat 80 AFU E 0 Btuh 0 Btuh 0 `F 1285 cfm 0.053 cfm/Btuh 0 in H2O Infiltration Simplified Average 0 COOLING EQUIPMENT Make Trade Colid Coil AHRI ref no. Efficiency Sensible cooling Latent cooling Total cooling Actual air flow Air flow factor Static pressure Load sensible heat ratio 0 SEER 0 Btuh 0 Btuh 0 Btuh 1285 cfm 0.041 cfm/Btuh 0 in H2O 0.84 . ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft2) (Btuh) (Btuh) (cfm) (cfm) VAV 2-02A p 1075 11882 14391 633 595 VAV 2-02B p 974 12249 20147 652 832 AC 2-02 d 2049 24130 28332 1285 1285 Other equip loads 0 0 Equip. @ 0.95 RSM 26972 Latent cooling 5336 T(1TA1 Q OnA0 7A1411 474110 170r, 1009Z Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. A—Z:. -Fk- wrightSaft- Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:00:14 ACCI, ..._00 - HVAC LOADMR00 - OPEN114042_1-1VAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 5 VAV 2-02B p 974 12249 20147 652 832 Other equip loads 0 0 Equip. @ 0.95 RSM 19180 Latent cooling 2758 Tr)TAI C 07A -l))no 74044 ace own Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. A� -Fk wrightSOft- Right -Suite® Universal8.0.11 RSU14166 AXN ..._00 - HVAC LOADS1R00 - OPEN114042_HVAC'Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: 2014-Jul-15 09:00:14 Page 14 Component Constructions Job: 14042 -]- wrightsoft- p Date: MAY 07, 2014 AC 2-02 By: TL JWL ENGINEERING 238 DOVER STREET, BOCA RATON, FL33487 Phone: (561) 237-5223 Fax (561) 237-5680 Email: sales@jwlengineering.com Web: www.jwlengineedng.com Project• • For: LABARBI ERA RESIDENCE LOT 35 DIAMOND SANDS, JENSEN BEACH, FL Location: West Palm Beach Intl AP, FL, US Elevation: 20 ft Latitude: 27 N Outdoor: Heating Dry bulb (F) 48 Daily range (`F) - Wet bulb (F) - Wind speed (mph) 15.0 Indoor: Indoor temperature (F) Design TD (F) Relative humidity (%) Cooling Moisture difference (gr/lb) 90 Infiltration: 13 ( L ) Method 78 Construction quality 7.5 Fireplaces Heating Cooling 70 75 22 15 50 50 14.7 59.2 Simplified Average 0 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain fN Btuh/W-F ft-FBtuh Btuh/fP Btu BtuhtW Btu Walls 13A-4ocs: Blk wall, stucco ext, r-4 ext bd ins, 8" thk, 5/8" gypsum n 469 0.143 4.0 3.10 1454 2.71 1270 board int fnsh a 215 0.143 4.0 3.10 668 2.71 583 s 636 0.143 4.0 3.10 1972 2.71 1722 w 576 0.143 4.0 3.10 1786 2.71 1560 all 1895 0.143 4.0 3.10 5880 2.71 5135 Partitions (none) Windows 1 glazing, clr glz, mtl no brk frm mat, 118" thk: 1 glazing, clr glz, mtl no n brk frm mat, 1/8" thk; 2 ft overhang (5 ft window ht, 2 ft sep.) s all 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no n brk frm mat, 1/8" thk; 19.6 ft overhang (8 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no e brk frm mat, 1/8" thk; 2 ft overhang (6.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no e brk frm mat, 1/8" thk; 13 ft overhang (7.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w brk frm mat, 1/8" thk; 2 ft overhang (4.6 ft window ht, 2 ft sep.) ' 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w brk frm mat, 1/8" thk; 6 ft overhang (4.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, clr glz, mtl no w brk frm mat, 1/8" thk; 16 ft overhang (4.6 ft window ht, 2 ft sep.) 1 glazing, clr glz, mtl no brk frm mat, 1/8" thk: 1 glazing, cir glz, mtl no w brk frm mat, 1/8" thk; 6 ft overhang (7.6 ft window ht, 2 ft sep.) 39 1.100 0 23.9 925 27.2 1054 13 1.100 0 23.9 298 27.2 340 51 1.100 0 23.9 1223 27.2 1394 21 1.100 0 23.9 493 27.2 562 66 1.100 0 23.9 1575 64.8 4275 73 1.100 0 23.9 1739 27.2 1981 14 1.100 0 23.9 329 64.8 894 28 1.100 0 23.9 659 40.4 1116 14 1.100 0 23.9 329 27.2 375 65 1.100 0 23.9 1557 50.0 3264 -fk- wrightsoft" Right -Suite@ Universal 8.0.11 RSU14166 2014-Jul-15 09:00:15 .._00 - HVAC LOADS%R00 - OPEN114042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: Page 9 8Acw-2w: Sky glazing, small, wood curb, no shaft Igt shaft, wd sash; 2 ft overhang (1 ft window ht, 2 ft sep.) Doors (none) Ceilings 16X19-Otd:Attic ceiling, tile, slate, concrete roof mat, r-20 roof ins, 1/2" gypsum board int fnsh Floors 22A-wpl: Bg floor, light dry soil, on grade depth, hrd wd fir fnsh 0 1.160 0 2048 0.408 19.0 8 0.989 0 C�-� wrightsoft^ Right -Suite® Universal 8.0.11 RSU14166 ._00 - HVAC LOADS\R00 - OPEN\14042_HVAC Calcs_06-07-14_1100.rup Calc = MJ8 Front Door faces: 25.2 10 194 78 1.23 2517 1.31 2676 21.5 166 0 0 2014-Jul-15 09:00:15 Page 10 Level 2 Level 7 CM MHz a E) STORKiEi PO OLSTORAGE �tM � RANA�E AGAR GARAGE STORAGE4 BdJUS STORAGE STORAGE2 FQYER'. ': �awtW4rS- . STORAGE5 STORAGE3 Job #: 14042 JWL ENGINEERING Scale: 1 : 196 Performed by TL for: Page 2 LABARBIERA RESIDENCE 238 DOVER STREET Right -Suite@ Universal LOT 35 DIAMOND SANDS BOCA RATON, FL 33487 2 8.0.111R15 14166 2 JENSEN BEACH, FL Phone: (561) 237-5223 Fax: (561) 237-5680 www. wlen meerin com sales wlen meerin com •••042_HVAC Calcs_06-07-14_1100.r... 1 9• 9• @1 9• 9• Job #: 14042 Performed by TL for: LABARBIERA RESIDENCE LOT 35 DIAMOND SANDS JENSEN BEACH, FL Level 3 JWL ENGINEERING 238 DOVER STREET BOCA RATON, FL 33487 Phone: (561) 237-5223 Fax: (561) 237-5680 www.jwlengineering.com sales@jwlengineering.com Scale: 1 : 196 Page 3 Right -Suite® Universal 8.0.11 RSU14166 2014-Jul-15 09:01:02 VAC Calcs 06-07-14 1100.r.