September 9, 2014
To: St. Lucie County, Planning 4 Zoning
Re: LaBarbiera Residence
Lot 35 Diamond Sands
8224 S. Ocean Drive
Jensen Beach, Fl. 34957
Permit # 1407-0469
I
Dear Plans Reviewer:
In reference to the Plan Review Coml ents by Planning & Zoning staff completed, I am respectfully submitting
this letter addressing the comments as well as (2) Two Signed and Sealed, Revised copies of the affected sheets as
outlined below. All affected sheets have been clouded as Delta #1 in the Title Block of each sheet:
Plans Examiner:
Comment #1: Please remove all references to future habitable space uses below FFE/ DFE, as this is prohibited
by FBC 3109.4.2, R3i22.3.4, & R322.3.5.
Response #1: Please see revised sheets A001 a, A001 b, P201, & P202 showing the removal of habitable space
below FFE/ DFE.
Comment #6: Please correct garage separation note on sheet A001b regarding ceiling drywall type &
thickness.
Responseg& Please see revised sheet A 001b for revised notes regarding garage separation.
Comment #7: Please show all a/c. generator, pool & all other equipment pads elevated above BFE.
Response #7: Please see revised sheets A001 b, 4301, A302, A303, A304, & A501 for added notes equipment.
pads elevated above �FE.
Comment #8: Please note all wall & floor finishes used below BFE must be flood resistant material.
Response #8: Please see revised shi ets A001 a, A001 b, A801, & A802 for added notes regarding flood resistant
material:.
Zoning Review:
Comment # 1: Garage slab not meeting the min. elevation required by FDEP permit.
Response #1: The FDEP permit did not indicate correctly the garage slab elevation however, in the approved
plans stamped by FDEP the garage slab is noted to be 5.84 N.A. V.D. and the upper slab to be 7.01
N.A. V.D.
42 N. SWINTON AVE, SUITE 1
DELR.AY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 - Fax
www.STOFFT.com
AA0003379
l
II
I���IRANDALL STOFFT
III ARCHITECTS
distinctive inspirational architecture
Comment #2: Height restrictions will be calculated from the min. required height. of first structural beam + 2'
beam allowance + 35' max. height (151.51 NAVD + 2' + 35' = 52.51' NAVD mean height highest roof.
I
Response 92: Spoke to Ms. Galbraith regarding this comment. It was intended to be used if the garage floor slab
needed to be raised per comment #1 above. The garage slab does need to be raised, therefore, this comment is no
longer pertains.
This concludes our responses associated with Revision #1.
Please feel free to contact this office with any questions or concerns related to this submittal.
Sincerel
i
Randall E. Stofft, AIA
President
RES. Donald W. Durante
42 N. SWINTON AVE, SUITE I
DELRAY BEACH, FLORIDA 33444
561-243-0799 - PHONE
561-243-0299 -FAX
2
www.STOFFT.com
A A 00033.9
-i
ENGINEERING -
Planning & Development Services
Building & Code Regulations Division
2300 Virginia Avenue
Fort Pierce, FL 34982
John W. Langford Engineering, LLC
238 Dover Street, Boca Raton, FL 33487
Tel (561) 237-5223 Fax (561) 237-5680
www.iwlengineering.com
September 3, 2014
RE:14042/PERMIT 1407-0469; LABARBIERA JENSEN; PLUMBING COMMENTS DATED 08-01-14,
Dear Whom it May Concern:
In response to comments generated regarding the piping plans for the referenced project, please see the below
responses.
Plumbing Comments
1. The ground level should not have habitable space please remove future bedrooms, wic and bathrooms
from the plans. First habitable floor should be above 15.51'navd.and bathrooms from the .plans. First
habitable floor should be above 15.51'navd..
Response: Please see updated plans on sheets P201, 202 that have removed reference to future
services in question.
f
Please let me know if there are any 'questions or concerns.
Sincerely,
John Langrora, rt
President
JWL Engineering
it
14042_LET-J L-W C_0001
cc/file;