HomeMy WebLinkAboutAPPROVED Carports Anywhere - K Sparacio - 602410-Rev1 - Digital Sealed 1. THESE PLANS PERTAIN ONLY TO THE STRUCTURE, INCLUDING MAIN WIND FORCE RESISTING SYSTEM, COMPONENTS AND
CLADDING, AND BASE RAIL ANCHORAGE. OTHER DESIGN ISSUES, INCLUDING BUT NOT LIMITED TO PLUMBING, ELECTRICAL,
INGRESS/EGRESS, PROPERTY SET—BACKS, FINISH FLOOR ELEVATION AND SLOPE, OR OTHER LOCAL ZONING REQUIREMENTS Aga
ARE THE RESPONSIBILITY OF OTHERS.
2. THIS STRUCTURE IS DESIGNED AS A NON—HABITABLE UTILITY/STORAGE BUILDING (RISK CATEGORY 1) CAPABLE OF
SUPPORTING DEAD LOAD OF THE STRUCTURE AND APPLICABLE LIVE AND WIND LOADS. IMPROVEMENTS NOT SPECIFICALLY
ADDRESSED HEREIN, INCLUDING DOORS, WINDOWS, OR OTHER COMPONENTS NOT LISTED IN THE FBC APPROVED PRODUCTS
LIST, AND NOT PROVIDED AND INSTALLED BY CARPORTS ANYWHERE, INC., WHICH EXERT ADDITIONAL LOADS ON THE CODE INFORMATION
STRUCTURE SHALL BE AT THE OWNER'S RISK. CARPORTS ANYWHERE NOR THE ENGINEERING DESIGN SHALL NOT BE CODE VERSION FBC 2020 7th Edition,
RESPONSIBLE FOR STRUCTURAL DAMAGE OR FAILURE DUE TO THE APPLICATION OF ADDITIONAL LOADS. ASCE-7-16
3. THIS BUILDING IS EXEMPT FROM THE FBC ENERGY CONSERVATION CODE PER SECTION C101.4.2. MANUFACTURER CARPORTS ANYWHERE
4. ALL STEEL TUBING SHALL BE 50 KSI STEEL AND MEETS/EXCEEDS GALVANIZATION PER ASTM A1003/A1003M-15. BUILDING TYPE UTILITY STRUCTURE
5. PLUMBING, ELECTRICAL, INGRESS/EGRESS, PROPERTY SET—BACKS, AND/OR OTHER LOCAL CODE REQUIREMENTS ARE THE CONSTRUCTION TYPE II—B
RESPONSIBILITY OF THE OWNER. RISK CATEGORY I
6. ROOF AND WALL SHEATHING SECURED WITH #12-14x3/4" SELF—DRILLING SCREWS WITH SEAL WASHERS ® 6" O.C. MAX.
7. FIELD FRAMING CONNECTIONS SECURED WITH #12-140/4" SELF—DRILLING SCREWS. FIRE PROTECTION NONE
8. ALL SHOP FRAMING CONNECTIONS ARE TO BE WELDED. NO WELDING ONSITE. ALL WELDING DONE IN SHOP BY A CERTIFIED FIRE SUPPRESSION SYSTEM NONE
WELDER. OCCUPANCY UTILITY, U
9. CONCRETE EXPANSIONS ANCHORS ARE TO BE MINIMUM 1/2" DIAMETER & 2,500LB TENSILE STRENGTH. WIND SPEED Vult-150mph
10. 12 OR 14GA. FRAMING IS 2.5"x2.5" TUBE STEEL. NIPPLES ARE 2.25"x2.25" TUBE STEEL.
EXPOSURE B
ENCLOSURE OPEN
16'-0" '-0" 8 INTERNAL PRESSURE COEFF. +/— 0.0
IMPORTANCE FACTOR 1.0
FRAME FRAME FRAME FRAME
OUT OUT OUT OUT ROOF DEAD LOAD 10PSF
ROOF LIVE LOAD 20PSF OR 3001b P.L.
FLOOR DEAD LOAD 1OPSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 1,440 SQ. FT.
GROUND ANCHOR WITHIN 6" OF REVISIONS
EACH POST. ANCHOR SECURED
WITH A" GRADE 5 BOLT MINIMUM BASE AIL REV DESCRIPTON DATE BY
WITH 2" WASHERS 1 NO WINDOWS 3/3/21 MTB
Ground Anchor Length _I�RIADEIII=III III=III=III=I
=1 — =1�=
(all building widths<_30') Wind Speed (mph) ��� ��� ASPHALT OR
DOUBLE 4" HELIX EARTH MINIMUM SOIL
Soil Type <-140 145-155 160-170 175-180 BEARING CAPACITY
AUGER GROUND ANCHOR
500 PSF (TYP.)
z Very dense and/or cemented sand,coarse gravel, 30" 30" 48" 4$" (SEE CHART FOR LENGTH)
O cobbies, preloaded silts,clays and coral
ry Medium dense coarse sands,sandygravels, 30" 48" 48" 60" DRAWN BY: MTB
ry y GROUND ANCHOR BASE DATE: / ,
ve stiff silts and clays 1 30 21
Loose to medium dense sands,firm to stiff „ 4810
6010
6010
LOCA19
RAIL DETAIL 01 WagonWheel Lane, Port St. Lucie
SIZE:clays, silts,and alluvial fill
60'L X 24'W X 10'H
Loose sands,firm clays, silts,and alluvial fill 4$" 60" 6010* 6011* W 1T!'Bq//���
*-2 anchors per post unless soil changes to a more desireable type at halfdepth or shallower. _\OENSF '•�0 ��
ii
z NO.64608 Z
i-10 ': STATE OF 44,
FRAME FRAME FRAME FRAME FRAME ��j S�S'� "'
OUT OUT OUT OUT OUT �4/1 I;it,`�����
Id
—2'-6" s'—o" I 2'—s" I s'—o" -4-2'-6" s'—o" 2'—s" I s'—o" I 2'—s" I s'—o" 2'—s"—I 0
6 -°" uu Digitally signed
a by Matthew li
Baldwin
Date: 2021 .03.03
09:54:57 -05'00'
z Matthew T. Baldwin P.E.
Florida License #64608
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND Q
Sheet: CA—
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES �F 4
1�
3
CODE INFORMATION
CODE VERSION FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
i o 0 CONSTRUCTION TYPE II—B
RISK CATEGORY I
FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
EXPOSURE B
ENCLOSURE OPEN
INTERNAL PRESSURE COEFF. +/— 0.0
IMPORTANCE FACTOR 1.0
3'-11 3'-11 3'-11 12'-0" 3'-11 3'-11 3'-11 ROOF DEAD LOAD 10PSF
24'-0" 24'-0" ROOF LIVE LOAD 0PSF OR 3001b P.L.
FRONT END WALL REAR END WALL FLOOR DEAD LOAD 10PSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 1,440 SQ. FT.
REVISIONS
3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 3'-11 REV DESCRIPTON DATE BY
O.C. MAX. 1 NO WINDOWS 3/3/21 MTB
'-0"
0 FOUT
0 0
FRAME FRAME FRAME FRAME
OUT OUT OUT o
DRAWN BY: MTB
DATE: 1/30/21
LocAT9601 WagonWheel Lane, Port St. Lucie
SIZE: 601 X 24'W X 10'H
0'-0"
LEFT SIDE WALL
3'-11 11 3'-11 3-11 3'-11 R" 3'-11 3-11 " 3'-11 3-11 3-11 3-11 3-11 " 3'-11 3-11 3-11 " 3-11
W
FRAME FRAME FRAME FRAME FRAME U`
OUT OUT OUT OUT OUT 0 z
I —
0
Q
LL-
2'-6" 2'-6"
W
1'-10" 11 1'-4 " 1'-44" 11" 1'-10" 2" I�2'-3 "
Matthew T. Baldwin P.E.
0'-0" W Florida License #64608
RIGHT SIDE WALL PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES (/) Sheet: CA-2 OF 4
CARPIORTSANYWHEPS
CODE INFORMATION
CODE VERSION FBC 2020 7th Edition,
ASCE-7-16
MANUFACTURER CARPORTS ANYWHERE
BUILDING TYPE UTILITY STRUCTURE
CONSTRUCTION TYPE II—B
0 o RISK CATEGORY I
0 o FIRE PROTECTION NONE
FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
EXPOSURE B
ENCLOSURE OPEN
INTERNAL PRESSURE COEFF. +/— 0.0
IMPORTANCE FACTOR 1.0
ROOF DEAD LOAD 1OPSF
24'-0" 24'-0"
ROOF LIVE LOAD 20PSF OR 3001b P.L.
FRONT END WALL REAR END WALL FLOOR DEAD LOAD 1OPSF
FLOOR LIVE LOAD 50PSF
"R"RATING OF WALLS,FLOOR,ROOF N/A
MODULES PER BUILDING 1
HURRICANE PROTECTION USAGE NO
HURRICANE SHELTER USAGE NO
SQUARE FOOTAGE 1,440 SQ. FT.
REVISIONS
REV DESCRIPTON DATE BY
1 NO WINDOWS 3/3/21 MTB
o FRAME FRAME FRAME FRAME
I OUT OUT OUT OUT
0
DRAWN BY: MTB
DATE: 1/30/21
LocAT9601 WagonWheel Lane, Port St. Lucie
SIZE: 60'L X 24'W X 1O'H
LEFT SIDE WALL
r-
IMF
Im
ly
FRAME FRAME FRAME FRAME FRAME
OUT OUT OUT OUT OUT
o
o W
z
W
MattheW T. BaldWin P.E.
RIGHT SIDE WALL E0-0 W Florida License #64608
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES (/) Sheet: CA-3 OF 4
MINIMUM 6" TS NIPPLE. NIPPLE MINIMUM 6" TS NIPPLE. NIPPLE
SECURED TO WALL POST WITH
SECURED TO WALL POST WITH MINIMUM 6" TS NIPPLE. NIPPLE
PSC)R#5EWS
-14xi" SELF—DRILLING (4)#12-14xj" SELF—DRILLING SECURED TO WALL POST WITH
SCREWS A(412-14x " SELF—DRILLING
NIPPLE TO 2"x2"x2" 16 GA. ANGLE CLIP 2"x2"x2" 16 GA. ANGLE CLIPEWS
TBASE RAIL NIPPLE TO 336" SECURED WITH (4) #12-14x " ��
T
BASE RAI O SELFSECURDRILLING ITH SCREWS-14x SELF—DRILLING SCREWS CODE INFORMATION
2"x2"x2" 16 GA. ANGLE CLIP
SECURED WITH (4) #12-14xi" SINGLE OR DOUBLETS CODE VERSION FBC 2020 7th Edition,
�i III—III—III—III— -I �—III—III—III— —III- SELF—DRILLING SCREWS HEADER ASCE-7-16
SINGLE OR DOUBLETS
NIPPLE THEADER MANUFACTURER CARPORTS ANYWHERE
" BASE RAI BUILDING TYPE UTILITY STRUCTURE
INTERMEDIATE POST TO CONSTRUCTION TYPE II—B
RISK CATEGORY I
POST TO BASE RAIL END POST TO BASE RAIL HEADER/BASE RAIL/OR HEADER CONNECTION HEADER CONNECTION DETAIL FIRE PROTECTION NONE
CONNECTION CONNECTION WINDOW RAIL DETAIL DETAIL OPTION 1 OPTION 2 FIRE SUPPRESSION SYSTEM NONE
OCCUPANCY UTILITY, U
WIND SPEED Vult-150mph
2"x2"x2" 16 GA. ANGLE CLIP SECURED EXPOSURE B
WITH (4) #12-14xi" SELF—DRILLING ENCLOSURE OPEN
SCREWS 26 GAUGE ROOF SHEATHING INTERNAL PRESSURE COEFF. +/— 0.0
VARIES SECURED WITH (1)#12-14x "
NIPPLE fie'' SELF—DRILLING SCREWS ® IMPORTANCE FACTOR 1.0
TO TRUSS '2-1-2-1' (6" O.C. (9" O.C. MAX.)) ROOF DEAD LOAD 1OPSF
-- ----- STD. MAX. SPACING
2"x2"x2" 16 GA. 48" MAX• -"-- ROOF LIVE LOAD OPSF OR 3001b P.L.
ANGLE CLIP 3" MIN. MINIMUM 6" TS FLOOR DEAD LOAD 1OPSF
N 1—
R WITH 4 L NIPPLE. NIPPLE r __ __
FLOOR LIVE LOAD 50PSF
SECURED W O SECURED TO WALL ---
#12-14xi" POST WITH _ -"- _- "R"RATING OF WALLS,FLOOR,ROOF N/A
SELF—DRILLING (4)#12-14xi" ---"- _ _-- MODULES PER BUILDING 1
SCREWS SELF—DRILLING ___----" HURRICANE PROTECTION USAGE NO
1—�JSTD. MAX. SPICING SCREWS 1" 16 GAUGE FURRING CHANNEL
48" O.C. MAX. SECURED WITH HURRICANE SHELTER USAGE NO
(n — SQUARE FOOTAGE 1,440 SO. FT.
o VARIES (2)#12-14x1" SELF DRILLING
SCREWS TO EACH RAFTER. REVISIONS
NON—STRUCTURAL SIDE WALL ROLL—UP REV DESCRIPTON DATE BY
HEADER OR WINDOW DOOR/FRAME OUT POST TO TRUSS ROOF PANEL CONNECTION 1 NO WINDOWS 3/3/21 MTB
RAIL TO POST DETAIL HEADER DETAIL CONNECTION VERTICAL SHEATHING OPTION
INSTALL PER MANUFACTURERS INSTRUCTIONSr" 4
2"
#14x1" 16 GA.
#12-14xi" SELF—DRILLINGANNEL BRACE, MIN.
SELF—DRILLING SCREWS SCREWS ® 6" O.C. P TO 7' POST, MIN. DRAWN BY:
CAP 10" O.C. MAX., 3" MAX. & 6" MAX. VER 7' POST. MIN. MTB
MAX. FROM CORNERS FROM CORNERS MAX. 60' FROM DAB 1/30/21
HORIZONTALLY/ 4" MAX. . (EXCLUDEFROM CORNERS �ocA IVERTICALLY WALLS). SECURED �9I601 WagonWheel Lane, Port St. Lucie
INTERIOR (4)#12-14xi" SIZE:
DRILLING SCREWS. 60'L X 24'W X 1O'H
EXTERIORMINIMUM 6 TS NIPPLE. NIPPLE
22 SECURED TO WALL POST WITH
(4)#12-14xi" SELF—DRILLING
DOOR FRAME TO POST SCREWS
CONNECTION ROLL—UP DOOR TO BOX EAVE RAFTER TO
POST CONNECTION POST CONNECTION DETAIL
APPROVED PRODUCTS APPROVAL NO.
Design Pressures - 150 mph Basic Wind Speed ROOF SHEATHING Carports Anywhere FL27402.1
Zone Hampton Rib Roof Panel
WALL SHEATHING Carports Anywhere FL27403.1
Roof Wall Hampton Rib Wall Panel
1 2n 2r 2e 3r 3e 4 5
15.0 16.7 15.0 15.0 21.1 21.1 21.1 23.9
-18.0 1 -41.3 1 -34.4 1 -18.0 1 -66.5 1 -57.1 -22.7 1 -28.3
cn
Q Matthew T. Baldwin P.E.
Florida License #64608
PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED AND ci w
THE SHA AUTHENTICATION CODE MUST BE VERIFIED ON ANY ELECTRONIC COPIES I- Sheet: CA-4 OF 4