Florida Product Approval Number 17796.04-R2
Manufacturer:
Atlantic Metal II of Vero Beach .Inc
4310 45th Street, Vero Beach, FL ''
www.atlanticmetal2.com V]EWEY W
� !
(772)257-573000DE CO f
Metal Roofing Panels • ISM LME COUNT'l'`
Accessories • Custom Metal IFabri
btuc C
. 1 I
Product: Nail strip standing seam,panel with nominal rib height,of 1.0" and max panel width of 16".
Material: 24ga or thicker steel with yield strength of at least 50ksi, and cF&dCrQ PYnce per FBC
1507.4.3.
RECEIVED I
Fastener: #10 x 1 pancake-style fastener, compliant with FBC 15106.6.
Substrate/Deck: Minimum 15/32"thick plywood. MAR 2 5 2021!
Underlayment: Comply with FBC 1507.1.1 where required.
ST. Lucie County, Per I ittin!g
Slope: Comply with FBC 1507.4.2 where required.
Max.Allowable Loads&Installation Requirements: l
Method A: 59.75psf I Install (1)#10 x 1"fastener in panel slot at 16"
O.C.
� �--
Method B: 101 psf I Install (1)#10 x 1"fastener in panel slot at 6.75"
o.c
Method C: 153.512sf I Install (1)#10 x 1"fastener in panel slot at I
6.75"o.c AND (2)#10x1" eclipse head fastener in pan of panel atr
12"o.c. i
Factor of Safety of 2.0 applied to calculate allowable loads.
� I
Compliance statement: This product as described has demonstrated compliance with Florida Buildings
Code 2020, Section 1504.3.2 (non-HVHZ), as required by Rule 61 G20-3, method 1 D !
��ttllit���
Evaluated By: E
David Eng PE P..........
'
Timberlake Cove, LLC DavidEEng I� '
3324 W Univ.Ave#206, Gainesville FL 32607 1��?62o:1o.07 oo:zi:sa+o No.81377
roci�
PE Lic. No: 81377
CA Lic. NO: 33344 This item has been digitally signed and CC—
www.TimberLakeCove.com sealed by D.E.Eng,PE,on the date - Q STATE OF !(��
indicated. Printed copies of this document %%� •. F�OR10P.•' \��
are not considered signed and sealed and i/ 0 �
the signature must be verified on any 'ass/CINAL
electronic copies �i
I � I
FL • • , ,
I
. I i,
i
A NTI
AL
ET
Technical Documentation: of Vero Beach,Inc.
This product has been tested to the UL 580 standard by Force Engineering
(TST-5328), report 72-0314T-06.As referenced in FL 177 I6.04-R1
Certification of Independence: David Eng, PE and Timberlake Cove, LLC do not have, nor
will acquire a financial interest in any company manufacturing or distributing products under
this evaluation.The same entities do not have, nor will acquire, a financial interest in any
other entity involved in the approval process of the product.
Exclusions&Limitations: Design of deck and roof structure(to include deck attachment) !
shall be completed by others. Fire classification and shear diaphragm design are outside the
scope of this evaluation.Accelerated weathering/salt spray is outside the scope of this
evaluation. Installation shall be subject to the local building code and authority having
jurisdiction;this report shall not be construed to supersede local codes in force.
This report is limited to compliance with structural wind load requirements of FBC 1504.3.2,
as required by Rule 61 G20-3. Neither Timberlake Cove northe manufacturer shall be
responsible for any conclusions, interpretations, or designs made by others based on this
evaluation report.This report is limited solely to documenting compliance with Rule 61 G20-
3, and makes no express or implied warranty regarding performance of this product.
Design Process:The load tables in this report provide several prescriptive options for the
fastening requirement for the applicable wind loads for roofs within the parameters
described. For roofs outside of the listed parameters, design wind loads shall be determined
as required by FBC 1609, ASCE 7, or other design code iri'force, using allowable stress. j
These load tables are based on ASCE 7-16. Use of these tables assumes that the structure is:
• Enclosed and conforms to wind-borne debris provisions and is a regular shaped building
• Is not subject to across-wind loading,vortex shedding, or instability; nor does it have a site
location for which channeling or buffeting warrant consideration
Engineering analysis may be completed by other licensedengineers for project specific
approval by local authorities having jurisdiction j
!
Load Tables: NOTE:ASCE 7-16 and FBC 2020 adopt a 7-zone concept. For the load tables
below,the worst case was taken for each zone and reported using the standard zones 1-2-3:
Zone 1 includes zones 1 and 1'
Zone 2 includes zones 2e, 2r, and 2n
Zone 3 includes zones 3e and 3r
Combining these zones creates a clear, simple scheme, at the expense of some design
efficiency. Contact the manufacturer for further information, or consult a licensed design
professional.
I
FL
i
i
h
• • / ®
®a Tables,
P
AN
ME AL
of Vero Beach,Inc:
eJ i
Instructions:
Iff , 2
2
2 ' 2 3 a
Select the appropiate load table that applies totheI
2 1 j 2 2 1g � a StrUCtU e In question. I
' 2' i Determine the design wind speed for the project
1 I2 1
2; location.
a 31 2 2 3 a
r Use the attachment method indicated for that
--
a' HIP ROOF 1 GABLE ROOF (aL windspeed within each roof zone.
a tG"bOFLE/STWiOVTA:ONEnSiOROROan_P.}nGtEYERISSktLLFRHUTNO See Note on previous page.
"'Te'[RwCRa:MSIG5'ROA -TgL02-.ftLE YOR JFl,9e,1)
OATS 4''TCRL�.y�O By p[StWy OR OT!1t'R>oF+UG.gy[COpE
ROOF ZONES FOR GENERIC BUILDING
Use this load table for structures which meet the following criteria: Use this load table for structures which meet the following criteria:
Are located in Exposure B area Are located in B,C,or D exposure area
Have either a flat roof,or gable/hip roof with max slope of 12:12 Have either a flat roof,or gablelhip roof with max slope of 12:12
Have a mean Roof Height of 30 feet or less Have a mean Roof Height of 30 feet or less
FL17796.04: 24 a 1,0 Nail Stri on 15/32" PI ood FL17796.04: 24 a 1,0 Nail Strip on 15/32" Plywood ;
Wind 105 110 120 130 140 150 160 170 180 190 200 Wind 1105 110 120 130 140 150 160 170 180 1901200
Zone 1: A A A A A A A A 13 8 B:, Zone 1: A A A A 8 B B B C C ) C
Zone 2: A A A A A B . B 13 B C C' Zone 2: 1 A A B B B R
Zone 3: A A A A `r B B; B. :B C;.- C C:, Zone 3: +B ='_B B B C C ., C , NR�NR Nl ,NR
Use this load table for structures which meet the following criteria: Use this loadltabie for structures which meet the following criteria:
Are located in Exposure B area Are located in B,C,or D exposure area i
Have either a flat roof less than 7°,hip roof with Have either ajflat roof less than 7°,hip roof with
max slope of 12:12,or gable roof with slope between 4,4:12& 12:12 max slope of 12:12,or gable roof with slope between 4,4:12&12:12
Have a mean Roof Height of 30 feet or less Have a mean Roof Height of 30 feet or less
FL17796.04: 24 a 1.0 Nail Strip on 15/32" PI ood FL17y96.04: 24ga 1.0 Nail%ri on 15/327 PI ood
Wind 105 110 120 130 140 150 160 170 180 190 200 Wind 105 110 120 130 140 150 160 170 180 190 1200
Zone 1: A A A A A A A A A B B Zone 1: ';A A A A A B B B B
Zone 2: A A A A A A B B B S B Zone 2: A A A B -B B C C C C 11lR,.
Zone 3: A A A A B ,C -C-;,- C„ Zone 3: A B B B C C
METHOD A METHOD B METHOD C j
/--FEMALE LEG SNAPS FEMALE LEG SNAPS !
✓ ONTO MALE LEG ONTO PAALE LEG � — —FLMA11 I.FGjSNAPS
ONTO A;ALE LEG
I h19 FASr�NF-.R
OYP),12"O.0 41AX
r.70 FASTENER,7G"O C r;tAX n70 FASTENER,6 75"O C t;4AX �
f�— 'M I-ASI I NER,6/6"Q C N1AX
NR: NOT'RATED _ }
CONSULT DESIGN �ror
PROFESSIONAL AS NEEDED k
FL
96 ® `.