Loading...
HomeMy WebLinkAboutGas Riser GAS ISOMETRIC RISER DIAGRAM Linda Sinkula 3104 NW Radcliffe Way Palm City, Florida 34990 Gas Codes Based on 402.4 Series FBC Codes Gas Piping Codes based on NFPA 54/58 Codes. Type of Gas: 500g LP Tank Pipe Sizing for trench: 45’ ¾ PE @ 10psi Appliances: 20kw Gen @ 337,500BTU Excel Electric LLC 1391 SW Bellevue Ave Port St Lucie, FL 34953 Phone: 772-529-1091 Email: ExcelOffice77@gmail.com Qualifier: Ronnie Kellar LP Gas State License # LI 45010 Tank will comply with all setbacks of 10 feet from sources of ignition, property line elements and the residence 500g LP Tank Anchored/Anode 1st Stage Reg 20Kw Gen ¾ Shut off ¾ Riser 2nd Stage Reg Up to 45’ of ¾ PE @ 10psi