HomeMy WebLinkAboutLORI GROVE - FULL - R0_signedT01 01 VICINITY 02 AERIAL LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA PROJECT INFORMATION DISTRICTS COUNTY: ST LUCIE COUNTY JURISDICTION: ST. LUCIE COUNTY DESIGN SPECS WIND EXPOSURE: B WIND SPEED (MPH): 160 SNOW LOAD (PSF): 0 GOVERNING CODES BUILDING: FBC 2020/ASCE 7-16 ELECTRICAL: NEC 2017 FIRE: FFPC 2020/NFPA 2018 SYSTEM SIZE (KWDC): 19.76 # PANELS: 52 PANEL: BLK-G9380 INVERTER(S):YSE7600H-US VOLTAGE (V): 240 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SHEET INDEX T01COVER S01LAYOUT SF01FIRE SAFETY SP01-SPxxATTACHMENT PLAN SA01-SAxxATTACHMENT DETAIL SD01-SDxxSTRUC DATASHEETS E01LINE DIAGRAM EL01LABELS ED01-EDxxELEC DATASHEETS S01 ROOF 1 MEAN HEIGHT:12'MATERIAL: METALSHAPE: GABLEATTACHMENT: (1) S5!-PROTEARAIL: (492') IRONRIDGE-XR100MAX POINT DEADLOAD: 26 lbsMAX ANCHOR LOAD: -189 lbfMIN SAFETY FACTOR: 2.92 FRAMING RAFTER/TRUSS SIZE: MIN 2X4RAFTER/TRUSS SPACING: 24" OC ARRAY(S) MODULES: (52) BLK-G9380ARRAY AREA: 1061 SQFT 01 PLAN VIEW 02 SYSTEM SUMMARY 03 NOTES 04 CERTIFICATION INV -INVERTER/COMBINER PM -POWER METER ACD -AC DISCONNECT MP -MAIN PANEL/DISC -1,2e -OTHER GENERAL 1.1 EXISTING VENTS, SKYLIGHTS OR EXHAUST OUTLETS SHALL NOT BE COVERED BY THE SOLAR PV SYSTEM. 1.2 MODULES SHALL NOT OVERHANG ANY RIDGE, HIP OR ROOF EDGE. 1.3 CONTRACTOR SHALL NOTIFY ENGINEER/DESIGNER OF ANY CHANGES. AN ANALYSIS OF THE ROOF CONSTRUCTION AT THE REFERENCED PROPERTY WAS DONE AND IT HAS BEEN DETERMINED THAT THE STRUCTURE IS ADEQUATE TO SUPPORT THE ADDITIONAL SOLAR PV LOAD. BASED ON OUR REVIEW, THE EXISTING MEMBERS COMPLY WITH FBC 2020/ASCE 7-16 DESIGN SPAN RATINGS WITH SUFFICIENT CAPACITY TO SUPPORT THE NEW LOADS IMPOSED BY THE PROPOSED SOLAR ARRAY. THE SPECIFICATIONS SHOWN IN THIS CONSTRUCTION PLAN WERE DESIGNED PER FBC 2020/ASCE 7-16 FOR A WIND SPEED OF 160 MPH, EXPOSURE CATEGORY B FOR RISK CATEGORY II BUILDING WITH 0 PSF SNOW LOAD. PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 3 31 33 3 333 3 3 31 311 31 31 31313131 SF01 01 FIRE SAFETY OFFSETS NFPA 1 11.12.2.2.2 FOR RESIDENTIAL HOMES .1 PATHWAYS: NOT LESS THAN TWO 36IN WIDE PATHEWAYS ON SEPARATE ROOF PLANES FROM GUTTER TO RIDGE, SHALL BE PROVIDED ON ALL BUILDINGS. ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLANE WITH A PV ARRAY, A 36IN WIDE PATHWAY FROM GUTTER TO RIDGE SHALL BE PROVIDED ON THE SAME ROOF PLANE OR STRADDLING THE SAME AND ADJACENT ROOF ADJACENT ROOF PLANES. PATHWAYS SHALL BE LOCATED IN AREAS WITH MINIMAL OBSTRUCTIONS SHUCH AS VENT PIPES, CONDUIT, OR MECHANICAL EQUIPMENT. .2 33 PERCENT RULE: FOR PV ARRAYS OCCUPYING UP TO 33 PERCENT OF THE PLAN VIEW ROOF AREA, A MINIMUM 18IN PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. FOR PV ARRAYS OCCUPYING MORE THAN 33 PWECENT OF THE PLAN VIEW AREA, A MINIMUM OF 36IN PATHWAY SHALL BE PROVIDED ON EITHER SIDE OF A HORIZONTAL RIDGE. PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 3 31 33 3 333 3 3 31 311 31 31 31313131 SP01 01 ATTACHMENT PLAN (METAL ROOF) PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 LEGEND PARAMETERS ARRAY MODULE: (52) BLK-G9380TOTAL AREA: 1061.46 SQFT HARDWARE RAIL:ATTACHMENT:ANCHORAGE: 492' IRONRIDGE-XR100(1) S5!-PROTEARIB/SEAM FRAMING SIZE:MIN. 2X4SPACING: 24" OC ROOF MEAN HEIGHT: 12'MATERIAL: METAL (9" OC RIBS/SEAMS)SHAPE:GABLE GEOGRAPHY EXPOSURE CAT: BWIND SPEED: 160 MPHSNOW LOAD: 0 LBS LOAD CALCS PER ASCE 7-16 & SEAOC PV2-2017 DEAD LOAD CALC LOADS:Panel = 43lbsAnchors = 1.2lbsRail = 0.72lbs/ftMisc = 1.6lbs/panel DEADLOAD PER ROW, Fdr:Fdr = (lbs/panel*#panels/row) +(lbs/ft-rail*ft-rail/row)*2 +(lbs/anchor*#anchors/row) +(misc-lbs/panel*#panels/row) (lbf) DIST DEADLOAD, Fdd:Fdd = Fdr/(area/panel*#panels/row) (psf) DEADLOAD PER ANCHOR, Fda:Fda = Fdr/(#anchors/row) (lbs) FLUSH MOUNTED PANELS ON ANY ROOF CRITERIA:- Panels parallel to roof surface- Max height of panel above roof, h1 & h2 OF 10"- Min panel gap of 0.25"- Min edge distance 2*h2- Max panel chord length of 6.7' UPLIFT ON ONE PANEL, Fup = P*A (lbf)Per ASCE 2.4, 26.10.2 & 29.4.4P = pasd = 0.6*p = 0.6*qh*(GCp)*(YE)*(Ya), A = load area UPLIFT PER ROW, Fur = SUM(Fup(0):Fup(n)) (lbf)Where Fup(0):Fup(n) = loads from first to last panel in row UPLIFT PER ANCHOR, Fua = Fur/(#ANCHORS/ROW) (lbf) LOAD PER ANCHOR, Fa = 0.6*Fda + Fua (lbf) SAFETY FACTOR, SF = Ftest/Fa VELOCITY PRESSURE qh = 0.00256*Kz*Kzt*Kd*Ke*V^2 = 32 (lb/sqft)Where Kz = 0.57, Kzt = 1, Kd = 0.85, Ke = 1, V = 160 EXT PRESSURE COEFFICIENT, GCp:GCp varies per roof & zone, 30.3-2A-I to 30.3.7: Aeff = 5.1 sqft EXPOSURE FACTOR, YE:YE = 1.5 for uplift loads on panels that are exposed and within a distance 1.5Lp from the end of a row at an exposed edge of the array; YE = 1.0 elsewhere for uplift loads and for all downward loads, as illustrated in Fig. 29.4-7. A panel is defined as exposed if d1 to the roof edge > 0.5h and one of the following applies: 1. d1 to the adjacent array > max (4h2, 4 ft (1.2m) or 2. d2 to the next adjacent panel > max (4h2, 4 ft (1.2m). Per SEAOC 5.3.3 2*h2 may be used instead of 1.5Lp for flush mounted panels. PRESSURE EQUALIZATION FACTOR, Ya:Ya is given as 0.7 per SEAOC 5.3.5 with h2 = 6" & panel gap = 0.37" ZONES f0: 1' (Flat)f1: 1 (Flat)f2: 2 (Flat)f3: 3 (Flat)g1: 1 (Gable)g2e: 2e (Gable)g2n: 2n (Gable)g2r: 2r (Gable)g3r: 3r (Gable)g3e: 3e (Gable)h1: 1 (Hip)h2r: 2r (Hip)h2e: 2e (Hip)h3: 3 (Hip) ROW: 0 Z: g1 P: -20 psf Fup: -408 lbf 00 13.6" ROW: 1 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -817 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 10 Z: g1 P: -20 psf Fup: -408 lbf 11 22.25" ROW: 2 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.86 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 20 13.6" ROW: 3 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 30 Z: g1 P: -20 psf Fup: -408 lbf 31 Z: g1 P: -20 psf Fup: -408 lbf 32 22.25" Z: g1 P: -20 psf Fup: -408 lbf 40 Z: g1 P: -20 psf Fup: -408 lbf 41 Z: g1 P: -20 psf Fup: -408 lbf 42 Z: g1 P: -20 psf Fup: -408 lbf 43 Z: g1 P: -20 psf Fup: -408 lbf 44 12" ROW: 5 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1633 lbf #ANCHORS: 1 LOAD/ANCHOR, Fa: -107 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.15 DIST LOAD, Fdd: 2.82 psf POINT LOAD, Fda: 16.43 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 50 Z: g1 P: -20 psf Fup: -408 lbf 51 Z: g1 P: -20 psf Fup: -408 lbf 52 Z: g1 P: -20 psf Fup: -408 lbf 53 20.35" Z: g1 P: -20 psf Fup: -408 lbf 60 Z: g1 P: -20 psf Fup: -408 lbf 61 Z: g1 P: -20 psf Fup: -408 lbf 62 22.25" ROW: 7 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -550 lbf SF: 4.9 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 70 Z: g1 P: -20 psf Fup: -408 lbf 71 Z: g1 P: -20 psf Fup: -408 lbf 72 22.25" ROW: 8 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.86 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 80 13.6" NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -408 lbf #ANCHORS: 4 LOAD/ANCHOR, Fa: -94 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.86 DIST LOAD, Fdd: 2.66 psf POINT LOAD, Fda: 13.58 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg ROW: 4 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -2042 lbf #ANCHORS: 18 LOAD/ANCHOR, Fa: -104 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.3 DIST LOAD, Fdd: 2.82 psf POINT LOAD, Fda: 16.01 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg ROW: 6 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -550 lbf SF: 4.9 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg ROW: 9 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 90 Z: g1 P: -20 psf Fup: -408 lbf 91 Z: g1 P: -20 psf Fup: -408 lbf 92 22.25" ROW: 10 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -2042 lbf #ANCHORS: 10 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 100 Z: g1 P: -20 psf Fup: -408 lbf 101 Z: g1 P: -20 psf Fup: -408 lbf 102 Z: g1 P: -20 psf Fup: -408 lbf 103 Z: g1 P: -20 psf Fup: -408 lbf 104 22.25" ROW: 11 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1633 lbf #ANCHORS: 8 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 110 Z: g1 P: -20 psf Fup: -408 lbf 111 Z: g1 P: -20 psf Fup: -408 lbf 112 Z: g1 P: -20 psf Fup: -408 lbf 113 22.25" PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SP02 ROW: 12 Z: g1 P: -20 psf Fup: -408 lbf 120 Z: g1 P: -20 psf Fup: -408 lbf 121 Z: g1 P: -20 psf Fup: -408 lbf 122 22.25" ROW: 13 Z: g1 P: -20 psf Fup: -408 lbf 130 Z: g1 P: -20 psf Fup: -408 lbf 131 Z: g1 P: -20 psf Fup: -408 lbf 132 22.25" ROW: 14 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -112 lbf TEST LOAD/ANCHOR: -550 lbf SF: 4.9 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 140 Z: g1 P: -20 psf Fup: -408 lbf 141 Z: g1 P: -20 psf Fup: -408 lbf 142 22.25" NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg ROW: 15 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1429 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -133 lbf TEST LOAD/ANCHOR: -550 lbf SF: 4.15 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -30 psf Fup: -613 lbf 150 Z: g1 P: -20 psf Fup: -408 lbf 151 Z: g1 P: -20 psf Fup: -408 lbf 152 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1225 lbf #ANCHORS: 6 LOAD/ANCHOR, Fa: -189 lbf TEST LOAD/ANCHOR: -550 lbf SF: 2.92 DIST LOAD, Fdd: 2.54 psf POINT LOAD, Fda: 25.95 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg 22.25" ROW: 16 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -1429 lbf #ANCHORS: 11 LOAD/ANCHOR, Fa: -133 lbf TEST LOAD/ANCHOR: -550 lbf SF: 4.15 DIST LOAD, Fdd: 2.81 psf POINT LOAD, Fda: 17.2 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -30 psf Fup: -613 lbf 160 Z: g1 P: -20 psf Fup: -408 lbf 161 Z: g1 P: -20 psf Fup: -408 lbf 162 22.25" ROW: 17 NOM SPAN: 45" MAX SPAN: 4" MAX CANTILEVER: 23" UPLIFT/ROW, Fur: -817 lbf #ANCHORS: 8 LOAD/ANCHOR, Fa: -93 lbf TEST LOAD/ANCHOR: -550 lbf SF: 5.89 DIST LOAD, Fdd: 2.85 psf POINT LOAD, Fda: 14.53 lbs ROOF PITCH: 20-27 deg PANEL TILT: 0 deg Z: g1 P: -20 psf Fup: -408 lbf 170 Z: g1 P: -20 psf Fup: -408 lbf 171 10.05" SA01 BLK-G9380 72.4 IN 40.6 IN 5.9-17.7 IN 0-21.7 IN GENERAL 1.1 DESIGNED PER FBC 2020/ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES. 1.2 CONTRACTOR IS RESPONSIBLE FOR INSTALLING PV MODULES, RACKING & RACKING SUPPORTS IN ACCORDANCE WITH THE MANUFACTURER INSTALLATION INSTRUCTIONS NOT SHOWN IN THIS PLAN. 1.3 WITHDRAWAL VALUES GIVEN PER NDS 2015 BASED ON SG OF 0.5 OR MANUFACTURER SUPPLIED 3RD PARTY UPLIFT TESTING REPORTS WITH APPLICABLE SAFETY FACTORS. 1.4 ALL PENETRATIONS SHALL BE FLASHED OR SEALED IN A MANNER THAT PREVENTS MOISTURE FROM ENTERING THE WALL AND ROOF. 1.5 THE SUPPORTING ROOF STRUCTURE SHALL BE CONVENTIONAL WOOD FRAMED CONSTRUCTION WITH PRE-ENGINEERED TRUSSES OR ROOF FRAMING MEMBERS AT A SPACING OF 24 IN MAXIMUM ON CENTER. 1.6 EXISTING STRUCTURE IS ASSUMED TO BE IN COMPLIANCE WITH APPLICABLE BUILDING CODES AT THE TIME OF CONSTRUCTION. 1.7 CONTRACTOR SHALL NOTIFY ENGINEER OF ANY CONDITION CHANGES. 01 ANCHORAGE DETAIL 02 NOTES 03 ANCHOR DETAIL 04 RAIL & CLAMPS DETAIL 05 MODULE DETAILS PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SD01 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 SD02 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 E01 GENERAL 1.1 CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH FBC 2020/ASCE 7-16 AND NEC 2017 REQUIREMENTS AND EQUIPMENT INSTALLATION INSTRUCTIONS NOT SHOWN IN THIS PLAN. 1.2 CONDUCTOR TYPES SHALL MEET THE REQUIREMENTS PER NEC 310.10 BASED ON INSTALLATION LOCATION. 1.3 DIRECT-CURRENT PV SOURCE AND OUTPUT CONDUCTORS INSIDE A BUILDING SHALL BE CONTAINED IN METAL RACEWAYS, 690.31(G). 1.4 ALL EQUIPMENT SHALL BE LISTED PER NEC 690.4(B). 1.5 CONDUCTORS ARE SIZED BASED ON RACEWAYS NOT EXPOSED TO DIRECT SUNLIGHT UNLESS STATED OTHERWISE. 10% OF CIRCUIT LENGTH CAN BE EXPOSED DIRECT SUNLIGHT UP TO 10FT, NEC 310.15(A)(2). 1.6 PV SOURCE AND OUTPUT CIRCUIT CONDUCTORS ARE SIZED TO BE EXPOSED TO DIRECT SUNLIGHT GREATER THAN 10% OF THEIR LENGTH WHEN INSTALLED IN RACEWAYS ½” OR GREATER ABOVE ROOF. ADJUSTMENTS ARE BASED ON MAX STRING CURRENT OF 15A & AMBIENT TEMPERATURE OF 35C PER NEC 310.15(B)(2)(A) & 310.15(B)(3)(C). SYSTEM 2.1 THE OUTPUT VOLTAGE OF THE OPTIMIZERS ARE REGULATED BY THE INVERTER AND ARE NOT IMPACTED BY THE NUMBER OF MODULES IN THE STRING. THE CONTINUOUS CURRENT OF A SINGLE STRING IS EQUAL TO THE MAXIMUM OUTPUT CURRENT OF THE OPTIMIZER OF 15A. 2.2 THE INVERTER IS EQUIPPED WITH A RAPID SHUTDOWN FEATURE WHICH CONFORMS TO NEC 690.12. 2.3 THE INVERTER IS NON-ISOLATED AND UNGROUNDED. NEITHER THE NEGATIVE NOR POSITIVE CONDUCTOR IS GROUNDED AND HAS A COMMON AC AND DC EQUIPMENT GROUNDING TERMINAL THEREFORE NO DC GEC IS REQUIRED. 2.4 INTERCONNECTION SHALL BE MADE BY LINE-SIDE-TAP PER ARTICLE 705.12(A) USING INSULATED, PIERCING CONNECTORS UL LISTED FOR THIS PURPOSE AND LOCATED WITHIN CODE COMPLIANT ENCLOSURE. TAP CONDUCTORS SHALL BE NO MORE THAN 10FT PER 705.31. 2.5 INTEGRATED DC DISCONNECT AND AFCI IS PROVIDED WITH INVERTER. GROUNDING 3.1 ALL EQUIPMENT SHALL BE PROPERLY GROUNDED PER THE REQUIREMENTS OF NEC ARTICLES 250 & 690. 3.2 FRAMED PV MODULES SHALL BE BONDED TOGETHER USING LUGS OR RACKING INTEGRATED GROUNDING CLAMPS. 3.3 EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED PER NEC 250.120(C), SIZED PER 690.45 & BE A MINIMUM OF #6 WHEN EXPOSED TO DAMAGE. PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 CALCS BASED ON MAX CONDITIONS. CIRCUIT LENGTH BASED ON 1% VOLTAGE DROP. SEE NOTE 1.6 FOR RACEWAYS IN DIRECT SUNLIGHT. *CCC: CURRENT CARRYING CONDUCTORS 01 INVERTER RATINGS03 SYSTEM05 CONDUCTOR SCHEDULE06 ELECTRICAL LINE DIAGRAM07 *ENERAL NOTES MODULE RATINGS04 MAKE SOLAREDGE MODEL SE7600H-US SE7600H-US MAX INPUT POWER 11800 11800 W MAX INPUT VOLTAGE 480 480 V NOM INPUT VOLTAGE 400 400 V MAX INPUT CURRENT 20 20 A NOM AC VOLTAGE 240 240 V MAX AC CURRENT 32 32 A NOM AC POWER 7600 7600 W MAKE HANWHA MODEL BLK-G9380 RATED POWER 380 W VMPP 37.85 V IMPP 10.04 A VOC 45.04 V ISC 10.50 A TOTAL # MODS 52 TOTAL # INVERTERS 2 STC DC RATING 19.76 KW AC OUTPUT RATING 15.2 KW MIN STRING SIZE 8 MOD MAX STRING SIZE 15 MOD INVERTER 1:SE7600H-US # MODS 26 # STRINGS 2 STC DC RATING 9.88 KW DC/AC 130 % MPP CURRENT 20.00 A INVERTER 2:SE7600H-US # MODS 26 # STRINGS 2 STC DC RATING 9.88 KW DC/AC 130 % MPP CURRENT 20.00 A D INVERTER 2EGC BOND POINT, ROOF ARRAY RACKING SYSTEM, NOTE #3.2. B2 C1 JBOX 1 PH LOCKABLE FUSED AC DISCONNECT, 120/240V MIN 80A W/ 80A FUSES A: #10 PV WIRE, 600V RATED INVERTER 1B1 08 - 15 MODS 120/240V MIN 100A SUBPNL 40A-2P = = = = 15 SE P400 01 = = 40A-2P C2 ID RUN VOLTAGE (V) CURRENT (A) VD (%)LENGTH CONDUCTOR SIZE Ω/KFT CONDUIT SIZE #CCC EGC OCPD TERM (C)TEMP ADJ FILL ADJ BASE AMP DERATED AMP A STR - JBOX 400 15 1 108 PV WIRE #10 1.24 FREE AIR NA 2 #10 NA 75 0.96 1 35 35 B1 JBOX1 - INV 400 15 1 108 THHN/THWN-2 | PV WIRE #10 1.24 PVC/EMT/FMC MIN 3/4" 4 #10 NA 75 0.96 0.8 35 30.72 B2 JBOX2 - INV 400 15 1 108 THHN/THWN-2 | PV WIRE #10 1.24 PVC/EMT/FMC MIN 3/4" 4 #10 NA 75 0.96 0.8 35 30.72 C1 INV1 - PNL 240 32 1 48 THHN/THWN-2 #8 0.778 PVC/EMT/FMC/NMLT MIN 3/4" 3 #10 40 75 0.96 1 50 50 C2 INV2 - PNL 240 32 1 48 THHN/THWN-2 #8 0.778 PVC/EMT/FMC/NMLT MIN 3/4" 3 #10 40 75 0.96 1 50 50 D PNL - DISC 240 64 1 61 THHN/THWN-2 #4 0.308 PVC/EMT/FMC/NMLT MIN 1" 3 #8 80 75 0.96 1 85 85 E DISC - PCC 240 64 1 61 THHN/THWN-2 #4 0.308 PVC/EMT/FMC/NMLT MIN 1"3 NA 80 75 0.96 1 85 85 E M EXISTING 225A 120/240V PANEL EXISTING GROUNDING ELECTRODE LINE-SIDE-TAP, RE: NOTE 2.4 225A <=10FT 08 - 15 MODS 08 - 15 MODS 08 - 15 MODS EL01 NEC 690.13(B) LOCATION(S): 3, 4 NEC 690.13(B) LOCATION(S): 3, 4 NFPA 1 11.12.2.1.3, NEC 690.31(G)(3) LOCATION(S): 1, 2 NEC 705.12(B)(3) LOCATION(S): 5 NEC 690.54 LOCATION(S): 5 NFPA 1 11.12.2.1.4 LOCATION(S): 4, 5 NEC 690.53 LOCATION(S): 3 SYSTEM SERVICED BY: SOLAR SUN LLC 727-888-6000 SYSTEM SERVICED BY: SOLAR SUN LLC 727-888-6000 NFPA 1 11.12.2.1.4, NEC 690.56(B), 705.10 LOCATION(S): 5 NFPA 1 11.12.2.1.1.6, NEC 690.56(C)(3) LOCATION(S): 4 NFPA 1 11.12.2.1.1.1.1, NEC 690.56(C)(1) LOCATION(S): 5 GENERAL 1.1 LABEL MATERIALS SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT, NEC 110.21(B)(3). 1.2 EXACT MATERIALS USED ARE SUBJECT TO THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS SHALL BE A MINIMUM LETTER HEIGHT OF 3/8" AND PERMANENTLY AFFIXED. 01 LABELS 02 480 0 15 240 32 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 02 NOTES ED01 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840 ED02 PROJECT ID: CONTRACTOR:DESCRIPTIONDATE VERBY PAPER: ARCHB SCALE: NTS 03.22.21 RG 01 INITIAL DESIGN UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS3140 W KENNEDY BLVD #106, TAMPA FL 33609CA: 33343 A B C D E F 1 2 3 4 5 6 7 8 9 LORI GROVE 5306 PALMETTO DR, FORT PIERCE, FL 34982, USA 032221-MSS-GROVE SOLAR SUN LLC 6120 CENTRAL AVE, ST.PETERSBURG FL 33707 727-888-6000 I-EC13008840