Review Type Status Reviewed By Date Started Date Completed Date Released
ADDRESSING ASSIGNMENT COMPLETE Lori Bender 11/23/2020 11/24/2020 11/24/2020
Comment:
DOCUMENTS MISSING PENDING Karen Nielsen 11/18/2020
11/18/2020 Comment: CONTRACTOR TO UPDATE WORKERS COMP INSURANCE
11/18/2020 Comment: RECORDED NOC
11/18/2020 Comment: ELECTRICAL SUB
11/18/2020 Comment: PLUMBING SUB
11/18/2020 Comment: MECHANICAL SUB
11/18/2020 Comment: ROOFING SUB
11/18/2020 Comment: VEG PERMIT SCANNED IN LASERFISHE, FEES LOADED. EV
FORWARDED VEG PERMIT AND SURVEY TO ERD.
11/23/2020 Comment: COPY RECEIPT FOR PAID UTILITIES WATER AND SEWER.
ENVIRONMENTAL REVIEW COMPLETE Lynn Swartzel 11/23/2020 11/23/2020 11/23/2020
Comment:
FRONT COUNTER REVIEW COMPLETE Karen Nielsen 11/18/2020 11/18/2020 11/18/2020
Comment:
NOTIFIED FOR PICK UP PENDING
Comment:
Email:Paul@Trmcorpfl.Com
REVIEW COMMENTS
Page 1
PE REVIEW COMMENTS (2)INCOMPLETE Jpi, Inc-Andrew 1/13/2021
12/8/2020 Comment: THE DESIGN LOCATION ON THE ENERGY CALCULATION IS INCORRECT. CORRECT AND RESUBMIT. 107
FBC 6TH ED 2017
12/8/2020 Comment: SOFFIT DETAIL SF01D2 IS MISSING FROM PLANS CORRECT AND RESUBMIT 107 FBC 6TH ED 2017
12/8/2020 Comment: SUBMIT A COPY OF THE SOIL REPORT 107 FBC 6TH ED 2017
12/8/2020 Comment: SUBMIT PLANS FOR THE FIRE SPRINKLER SYSTEM 107 FBC 6TH ED 2017
1/13/2021 Comment: *SHEET L1- THERE ARE TWO LINTEL SCHEDULES WITH CONFLICTING SIZES & REINFORCING
REQUIREMENTS. ([A]107.2.1)
1/13/2021 Comment: *E1.0- NO SMOKE OR CO DETECTOR IN BEDROOM ON THE FIRST FLOOR, LABELED AS STUDY ON A1.0.
THE LAYOUT OF THIS ROOM IS THAT OF A SLEEPING ROOM. (R314, R315)
1/13/2021 Comment: *PLEASE PROVIDE AN ELECTRIC PANEL SCHEDULE AND ELECTRIC LOAD CALCULATIONS. ([A]107.2.1)
1/13/2021 Comment: *PLEASE PROVIDE A PLUMBING RISER DIAGRAM. ([A]107.2.1)
1/13/2021 Comment: *PLEASE PROVIDE THE MANUAL D WITH DUCT SIZE TABLE & DUCT LAYOUT. ([A]107.2.1)
1/13/2021 Comment: *PLEASE SEE TABLE R302.1, RATED EAVE OR BLOCKING REQUIRED WHEN LESS THAN 3 FEET FROM
PROPERTY LINE. SPRINKLED BUILDING REQUIRED.
1/13/2021 Comment: *PROVIDE POSITIVE DRAINAGE AWAY FROM THE STRUCTURE. (R401.3)
1/13/2021 Comment: *PLEASE SHOW THE FLOOD ZONES ON THE SURVEY. ([A]107.2.1)
1/13/2021
Comment: *PRODUCT APPROVALS EXPIRED ([A]107.2.1)
17-0614.16- WINDOWS, MULLIONS, FIXED GLASS- EXPIRED, NEED SEPARATE PRODUCT APPROVAL FOR
EACH PRODUCT
17-0420.12- SLIDING DOORS- EXPIRED
1/13/2021 Comment: *SHEET A1.1, SUSPENDENDED AIR HANDLER AND 50 GALLON WATER HEATER- PLEASE SHOW LOADING
FOR THE ON THE TRUSS DRAWINGS. PROVIDE DETAILS FOR HANGING EQUIPMENT. ([A]107.2.1)
PLANNING REVIEW PENDING Bethany Grubbs
Comment:
PLANS EXAMINER REVIEW COMPLETE Joseph Fersch 11/24/2020 1/13/2021 1/13/2021
Comment:
ZONING REVIEW INCOMPLETE Lydia Galbraith 11/23/2020
11/23/2020
Comment: THE SURVEY HAS AN INCORRECT FLOOD PANEL AND YEAR. THE SURVEY WILL NEED THE FLOOD
INFORMATION FROM THE MAPS OF 2020.
PLEASE PROVIDE CORRECTED SURVEY.
11/24/2020 Comment: PLEASE BE AWARE THAT ABOVE COMMENTS ARE ZONING REVIEW COMMENTS ONLY. THE PLANNING
DEPARTMENT AND PLANS EXAMINER MIGHT HAVE ADDITIONAL COMMENTS.