HomeMy WebLinkAboutFire Alarm Sequence of OperationFIRE ALARM SEQUENCE OF OPERATIONS
1. The fire alarm system shall operate as follows:
A. Activation of alarms- Activation of a manual pull station, water
flow switch, smoke detectors, and heat detectors shall:
1.) Identify the individual station on the system control panel
and sound the alarm at the control panel.
2.)Sound audible alarms and activates strobes
3.)Transmit alarm signal to the monitoring station and they will
dispatch the fire dept.
B. Activation of any supervisory circuit shall cause the following
actions and indications:
1) Display the origin of the supervisory condition report on the
LCD of the alarm control panel.
2) Activate supervisory audible and visual signals at the control
panel.
3) Transmit supervisory signal to the monitoring station and
the monitoring station will call the premise contact.
C. Activation of trouble signals on the control panel shall cause
the following actions and indications.
L) Display on the control panel LCD the origin of the trouble
condition.
2.) Activate trouble audible and visual signals at the control
panel and remote annunciator if any.
3.) Transmit the trouble signal to the monitoring station and
notification will be sent to all person's on the contact list.