PECGA LLC dba Palmer Engineering Company
March 22, 2021
Ms. Joy Racines
SageNet
10205 East 61st Street
Tulsa, OK 74133
RE: 1.2M Antenna on Free Standing Pipe Mast and Concrete Pier
Dollar General Store 08736
3751 Virginia Avenue
Fort Pierce, FL 34981
PEC Project #: 21099 .
Dear Ms. Racines:
Palmer Engineering Company has evaluated the use of a 1.2M antenna on a Free Standing
Pipe Mast and Concrete Pier for the above referenced location. The loading criteria used for .
our evaluation is as follows:
Code: 2020 Florida Building Code &ASCE 7-16
Ultimate Wind Speed: 160 mph (3-sec gust)
ASD Wind Speed (Survival): 123 mph (3-sec gust)
Risk Category: "I"
Exposure Category: "C"
Maximum height to center of antenna: 8'-0" above ground surface
Based on the above criteria, the mount shown on sheets S-1 and S-2 will safely support the
1.2M antenna. See enclosed sheets S-1 and S-2 for mast size and anchorage requirements.
This is a site specific design.
If you have any questions regarding this matter please contact this office.
Sincerely, IM
Palmer Engineering Company �,l�Q CENSFAq���/�
FLORIDA COA No. 7331 ` <
No. 59718
STATE
0�� OR
A
Baku Patel, P.E. II1
President THIS DOCUMENT HAS BEEN WET SIGNED AND
SEALED BY BAKULESH M.PATEL,FLORIDA
P.E.No.59718ON MARCH 22,.2021.
Attachments:Drawings - 2 pages SCANNED IMAGES,COPIES,AND/OR FACSIMILES
ARE NOT CONSIDERED SIGNED AND SEALED.
Calculations - 5 pages
www.pecga.com
Atlanta Office
3585 Habersham at Northlake,Building N
Tucker,Georgia 30084
o:(770)908-9908/ f:(770)9,08-9919
PALMERPROJECT DOLLAR GENERAL STORE 08736, FORT PIERCE, FL
w~nq PROJECT NO. 21099
com 7 p" SHEET NO. S-1 OF 2
PECGA LLC oba Palmer Engineering Company
3585 Habersham at Northlake,Tucker,Georgia 30084 CALCULATED BY MDE/MJ DATE 03-22-2021
P:(770)908-9908 F:(770)908-9919 www.pecga.com
FLORIDA COA No. 7331
1.2M ANTENNA
2 z" STD. PIPE \\\ -77
(2.88 O.D.) MAST
PIPE TRANSITION
ADAPTER �\
V)
• 0
LL
I O
4" STD. PIPE I ►-
(4.50" O.D.) MAST
I =
I I
TOP OF FOOTING
EL. +0'-3" ABOVE I o
FINISH GRADE
SLOPE
FINISH GRADE
o I w
;i I LU
U
Z
O
DRILL 6" DIA. HOLE THRU PIPE I 1O
I U
AND INSERT"' DIA. ALL-THREAD I O
ROD w/ NUTS EA. SIDE OF PIPE. a
ALL-THREAD ROD IS REQUIRED TO
PREVENT ROTATION
2'-0"
DIAMETER OF CONCRETE
ANTENNA ELEVATION
SCALE: N.T.S.
NOTES:
1. SEE SHEET S-2 FOR GENERAL NOTES. Na. 59718
2. FIELD VERIFY ANTENNA DIRECTION.
STATE
\
O
NAL
THIS DOCUM YIgS�64E T SIGNED AND
SEALED BY BAKULESH M.PATEL,FLORIDA
P.E.No.59718 ON MARCH 22,2021.
SCANNED IMAGES,COPIES,AND/OR FACSIMILES
ARE NOT CONSIDERED SIGNED AND SEALED
PALMERPROJECT DOLLAR GENERAL STORE 08736, FORT PIERCE, FL
RMEMIN kmdno PROJECT NO. 21099
PECGA LLC dba Palmer Engineering Company
SHEET NO. S-2 OF 2
3585 Habersham at Northlake,Tucker,Georgia 30084 CALCULATED BY MDE/MJ DATE 03-2272021
P:(770)908-9908 F:(770)908-9919 www.pecga.com
FLORIDA COA No. 7331
GENERAL NOTES:
1) CONTRACTOR SHALL PROVIDE ADEQUATE BRACING OR SHORING FOR ALL
WORK DURING THE CONSTRUCTION PERIOD.
2) IF, AFTER EXCAVATION, THE CONDITION OF THE SOIL INDICATES A SAFE
BEARING CAPACITY OF LESS THAN 2000 PSF OR OR A LATERAL PASSIVE SOIL
BEARING CAPACITY OF LESS THAN 150 PSF PER FT.,THE ENGINEER SHALL BE
NOTIFIED AND THE FOUNDATION REVISED IF NECESSARY.
3) ALL CONCRETE SHALL BE NORMALWEIGHT (150 PCF) 2500 PSI COMPRESSIVE
STRENGTH AT 28 DAYS. THE CONCRETE SLUMP SHALL BE 4"TO 6".
4) STRUCTURAL STEEL DETAILING , FABRICATION, AND ERECTION SHALL BE IN
ACCORDANCE WITH THE LATEST EDITION OF THE "MANUAL OF STEEL
CONSTRUCTION" OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION.
5) STRUCTURAL PIPE STEEL SHALL CONFORM TO ASTM A53 GRADE B. ALL OTHER
STRUCTURAL STEEL SHALL CONFORM TO ASTM A36 UNLESS NOTED ,
OTHERWISE.
6) ALL-THREAD STEEL RODS SHALL BE 2" DIAMETER CONFORMING TO ASTM A307.
7) ALL WELDS SHALL BE MADE'BY AN AWS CERTIFIED WELDER USING E70XX
WELDING RODS.
8) THE ANTENNA MOUNT ILLUSTRATED ON THESE STRUCTURAL DRAWINGS HAS
BEEN PREPARED IN ACCORDANCE WITH THE 2020 EDITION.OFTHE FLORIDA
BUILDING CODE AND ASCE 7-16 BASED ON THE FOLLOWING LOAD CRITERIA.
WIND LOAD
ULTIMATE WIND SPEED 160 MPH (3-SECOND GUST)
ASD WIND SPEED (SURVIVAL_) 123 MPH (3-SECOND GUST)
EXPOSURE CATEGORY C
RISK CATEGORY I
THESE DRAWINGS ARE FOR ONE ANTENNA ONLY \\\0
1,I t 4.
TO BE INSTALLED AT'DOLLAR GENERAL STORE 08736 \N����'�CEN
3751 VIRGINIA AVENUE, FORT PIERCE, FL 34981 .
REUSE OF THIS DRAWING IN ANY FORM IS
STRICTLY PROHIBITED WITH0,UTTHE WRITTEN APPROVAL No. 59718
OF PALMER ENGINEERING COMPANY 4
RI STATE(�-
THI ALE)BY UEI MA T.1,ORIDAD
P.E.No.59718 ON MARCH 22,2021.
SCANNED IMAGES,COPIES,AND/OR FACSIMILES
ARE NOT CONSIDERED SIGNED AND SEALED
PALMER Dollar Store General08736 03/22/2021
��■ engineering Fort Pierce, FL
M company
Dollar General Store 08736,Fort Pierce,FL
Calculated By:MDE
Checked By:MJ
The following analysis forthe antenna mountwas based on the loading criteria specified in the FBC 2020
and ASCE 7-16.
1.2 m antenna on free standing pipe mast and concrete pier
Antenna and mount data d:= 1.2•m
Mast height(above ground) h = 8:5--ft
Antenna and mount weight Want:' 60-lb
Mast weight4"std_pipe(4.50"od) Wmst 10.8•plf
Total weight Wtot Want+Wmst-h Wtot= 151.8Ib
Antenna height(above grade) H:= h H= 8.5 ft
2
Antenna area Af:_ n.d Af= 12.174 ft2
4
Antenna shape factor Cf:= 1.2 G:= 0.85
Ultimate wind speed(risk category 1) Vuit:= 160•mph
ASDwind speed(survival) Vasd Vult-N5.6 Vasd= 123.935•mph
Wind speed(operational) Vo:= 50•mph
Allowable rotation 'Ra 0.15•deg
Wind load
Exposure coefficient(exposure C) or:= 9.5 Z9 := 90Q
Z:= I15•ft if H< 15•ft Z= 15ft
H otherwise
2
a
KZ:_'2.01• Z KZ:= 0.7 if KZ<0.7 KZ= 0.849
Z9•ft
KZ otherwise
Wind pressure coefficients Kzt:= 1.0 Kd := 0.85
1 of 5
r
IIIIIII&M_J�n�qiLMER Dollar Store General08736 03/22/2021
WM■ neering Fort Pierce, FL
®' company
2
ASD velocity pressure Vasd
city p qz:_ 0.00256 Kz Kzt•Kd'(mph) 'psfqz= 28.373 psf
( V 12
qzo:= 0.00256•Kz•Kzt•Kd•I mphJ. psf qzO= 4.618•psf.
ASD design wind load F,:= qz•G•Cf•(Af+ 0.5•ft•h) Fw= 475.302 lb
Fwo:= gzo•G•Cf•(Af+ 0.5•ft•h) Fw.= 77.36lb
Seismic load
Exempt from Seismic Design perASCE 7-10 Section 13.1.4 Item 5.Mechanical and electrical
components in Seismic Design Category A,B or C provided that the component importance factor,Ip,is
equal to.1.0.
Short period design spec response acc Sds 0.053
1-sec period design spec response acc Sd1 0.045
Therefore,seismic design,categoryA
Component importance factor I P,:= 1.0
Check stem 2.5"std pipe(2.88"od) I := 1.45•in4 J := 2.89•in4 Z:= 1.37•in3.
Yield stress Fy:_,35•ksi Q:= 1.67
Modulus of elasticity E:= 29000•ksi
Shear modulus of elasticity G:= 11000•ksi
Stem moment Ms:= F,•1.5•ft Ms= 712.953•ft•lb
Allowable moment Ma:_ Fy•Z Ma= 2392.715•ft•lb
SZ
Load ratio f s = 0.298 I <1.0 OK
ML�_ -
Operational flexural rotation Rsf:= Rsf= 0.017•deg
2•E•I
Fw,-(0.2•d)•1.5•ft
Operational torsional rotation Rst:_ G•J Rst= 0.024-deg
2 of 5
P M ER Dollar Store General 08736 03/22/2021
®■ �ngmet'ring Fort Pierce, FL
company
Check mast4"std pipe(4.50"od) 'I := 6.82•in4 J := 13.6•in4 Z:= 4.05•in3
Mast moment Mm:= F,•(h— 1.5•ft) + MS Mm= 4040.067•ft•lb
Fy•Z
Allowable moment Ma'.— Ma= 7073.353•ft•Ib
Load ratio , m = 0.571 ` <1.0 OK
Ma i
Operational flexural rotation
FWa•(h— 1.5•ft)2 (FWo•1.5•ft)-(h— 1.5•ft)
Rmf:_ + Rmf= 0.113-deg .
2•E•1 E•1
Operational torsional rotation Rmt FWo•(0.2•d),•(h+ 1•ft— 1.5•ft) Rmt= 0.027•deg
G•J
Operational rotation
2 2
Ro:_ �(R.f+ Rmf) + (Rst+ Rmt) Ro = 0.14•deg
R�
Deflection ratio - = 0.93—� <1.0 OK
Ra
3 of 5
PALMER Dollar Store General 08736 03/22/2021
��■ engineering Fort Pierce, FL
■ �'� company
Embedment Program
*User Instructions: P=applied lateral force(lbs)
H=effective height(ft)
b=diameter of caisson(ft)
p=allowable lateral soil bearing pressure
per foot of depth(psf/ft)
q=maximum allowable lateral soil
bearing pressure(psf)
1.Type in values of P,H,b,p,and q
2.Values are automatically computed.for embedment and M
d(P,H,b,p,q) := d<- 1
e<-- 0
while l d- el > 0.01001
CA<- 2.34• P 1 if �•d•p>-q
q•b 3
P
A <-2.34• otherwise
1
3
e<- d 1
d <- 2 �1 +FI + 4.36•Al
Fv, h
P :_ — P = 475.302 H:_ - H= 8.5
lb ft
Pier diameter,ft b:= 2.0
Lateral soil bearing pressure,psf per ft p',:= 300
Soil bearing pressure,psf q:= 2000
1.00•P•(H+ d(P,H,b,p,q))
3
M :_
1000
Embedment depth,ft d(P,H,b,p,q) = 4.2171
ASD moment,ft-kip M = 4.708
Load ratio M ft kip - 0.666 <1.0 OK
Ma —
4 of 5
PALMER Dollar Store General 08736 03/22/2021
®■ engineering Fort Pierce, FL
coniparly
Embedment Program
*User Instructions: P=applied lateral force(lbs)
H=effective height(ft)
b=diameter of caisson(ft)
p=allowable lateral soil bearing pressure
per foot of depth(psf/ft)
q=maximum allowable lateral soil
bearing pressure(psf)
1.Type in values of P,H,b,p,and q
2.Values are automatically computed for embedment and M
d(P,H,b,p,q) := d 1
e 0
while I d- el > 0.0001
CA<-- 2.34• F if •d•p>-q
q•b 3
P
A<- 2.34• otherwise
1
Tdb
3
e<-- d 11
d� 2 �1 + 1 + 4.36•AJ
Fwo h
P :_ — P = 77.36 H:_ - H= 8.5
lb ft
Pier diameter,ft b= 2
Lateral soil bearing pressure,psf per ft p:= 150
Soil bearing pressure,psf q:= 2000
1.00•P• H+
C d(P,H,b,p,q)1
J
3
M :_
1000
Embedment depth,ft ;Id(P,H,b,p,q) = 2.795;
ASD moment,ft-kip M = 0.73
Load ratio M ft kip - 0.103 j <1.0 OK
l—Ma
5of5