HomeMy WebLinkAboutAvalon Custom HVAC LT 7 MANUAL J & MAN. D DUCT SUMMARY[44] (2)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Load Short Form 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make n/a Make n/a Trade n/a Trade n/a Model n/a Cond n/a AHRI ref n/a Coil n/a AHRI ref n/a Efficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0 Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0 Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0 Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) 1st Flr AHU 1521 25358 22753 368 1000 2nd Flr AHU 1139 20677 20744 231 1000 ENTIRE BUILDING 2659 46035 43496 599 2000 Other equip loads 0 0 Equip. @ 1.00 RSM 43496 Latent cooling 8187 TOTALS 2659 46035 51683 599 2000 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Load Short Form 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade Trade TRANE Model Cond 4TTR6030J1 AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669 Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW7.7 Sensible cooling Btuh25404 Heating output Btuh26273 Latent cooling Btuh3796 Temperature rise °F65 Total cooling Btuh29200 Actual air flow cfm368 Actual air flow cfm1000 Air flow factor cfm/Btuh0.015 Air flow factor cfm/Btuh0.044 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.87 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Dining 120 4798 3555 70 156 Master Bdrm 330 7066 5709 103 251 Master WIC 57 893 411 13 18 Kitchen 268 643 2215 9 97 Master Bath 117 1352 1675 20 74 WC Rm 15 0 0 0 0 Laundry 55 1457 1643 21 72 G Hall 23 0 0 0 0 Foyer 150 2486 1405 36 62 Study 222 5356 5014 78 220 Bath 4 84 1307 1125 19 49 1st flr stairs 79 0 0 0 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 1st Flr AHU 1521 25358 22753 368 1000 Other equip loads 0 0 Equip. @ 1.00 RSM 22753 Latent cooling 3529 TOTALS 1521 25358 26281 368 1000 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Load Short Form 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Information InfiltrationClgHtg SimplifiedMethod9143Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1627Design TD (°F) L-Daily range 5050Inside humidity (%) 5922Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Trane Make Trane Trade Trade TRANE Model Cond 4TTR6030J1 AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669 Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW7.7 Sensible cooling Btuh24236 Heating output Btuh26273 Latent cooling Btuh4964 Temperature rise °F104 Total cooling Btuh29200 Actual air flow cfm231 Actual air flow cfm1000 Air flow factor cfm/Btuh0.011 Air flow factor cfm/Btuh0.048 Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.82 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Bedrm 3 WIC 48 786 754 9 36 2nd Flr Stairs 79 0 0 0 0 Loft 247 3358 3666 38 177 2nd flr hall 49 0 0 0 0 Bath 3 47 590 600 7 29 Bath 2 54 597 607 7 29 Bedroom 2 209 2525 2682 28 129 Bedroom 3 150 2616 2761 29 133 Family 256 4386 4476 49 216 FAMILY RM CLG.0 5820 5196 65 251 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 5 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 2nd Flr AHU 1139 20677 20744 231 1000 Other equip loads 0 1195 Equip. @ 1.00 RSM 21938 Latent cooling 4658 TOTALS 1139 20677 26596 231 1000 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Building Analysis 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing OtherCeilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 17.882092.6Walls 35.81650327.9Glazing 1.254913.4Doors 7.032441.5Ceilings 13.562352.92.9Floors 13.662701.8Infiltration 10.95025Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.046035Total Cooling Walls Glazing Other Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 15.768242.2Walls 44.81949332.9Glazing 1.459614.6Doors 7.331911.5Ceilings 0.31200.1Floors 4.218440.5Infiltration 7.93449Ducts 00Ventilation 18.37980Internal gains 00Blower 0Adjustments 100.043496Total Latent Cooling Load = 8187 Btuh Overall U-value = 0.254 Btuh/ft²-°F ERROR: negative wall area in Bedroom 3 - check windows. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Building Analysis 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing DoorsCeilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 18.145972.8Walls 31.2791927.9Glazing 2.254913.4Doors 4.912321.5Ceilings 20.752473.53.5Floors 11.529051.8Infiltration 11.52908Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.025358Total Cooling Walls Glazing Doors Ceilings Infiltration Ducts Internal Gains % of loadBtuhBtuh/ft²Component 16.737982.3Walls 42.3961433.9Glazing 2.659614.6Doors 5.312131.5Ceilings 000Floors 3.88540.5Infiltration 8.11848Ducts 00Ventilation 21.24830Internal gains 00Blower 0Adjustments 100.022753Total Latent Cooling Load = 3529 Btuh Overall U-value = 0.235 Btuh/ft²-°F Data entries checked. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Building Analysis 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 Design Conditions Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US 1627Design TD (°F)ft30Elevation: 5050Relative humidity (%)°N28Latitude: Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating Infiltration:9143Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality78-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts % of loadBtuhBtuh/ft²Component 17.536122.4Walls 41.5858427.8Glazing 000Doors 9.720121.5Ceilings 4.89881.61.6Floors 16.333641.8Infiltration 10.22117Ducts 00Piping 00Humidification 00Ventilation0Adjustments 100.020677Total Cooling Walls Glazing Ceilings OtherInfiltration Ducts Internal Gains Blower % of loadBtuhBtuh/ft²Component 13.830262.0Walls 45.0987932.0Glazing 000Doors 9.019791.5Ceilings 0.51200.2Floors 4.59890.5Infiltration 7.31601Ducts 00Ventilation 14.43150Internal gains 5.41195Blower 0Adjustments 100.021938Total Latent Cooling Load = 4658 Btuh Overall U-value = 0.275 Btuh/ft²-°F WARNING: window to floor area ratio = 27.1% - more than 25%. ERROR: negative wall area in 2nd Flr Stairs - check windows. Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Project Summary 01/06/2020Date:ENTIRE BUILDING CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh41010 Structure Btuh40047 Ducts Btuh5025 Ducts Btuh3449Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 Humidification Btuh0Blower Btuh0 Piping Btuh0Equipment load Btuh46035 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh43496 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh5565 Ducts Btuh2622Central vent (0 cfm) Btuh0 CoolingHeating26592659Area (ft²) Equipment latent load Btuh8187 3092630926Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh51683 Equiv. AVF (cfm) 108211 Req. total capacity at 0.84 SHR ton4.3 Heating Equipment Summary Cooling Equipment Summary Make n/a Make n/aTrade n/a Trade n/a Model n/a Cond n/aAHRI ref n/a Coil n/a AHRI ref n/aEfficiency n/a Efficiency n/a Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0 Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0 Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0 Space thermostat n/a Load sensible heat ratio 0 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Project Summary 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh22449 Structure Btuh20905 Ducts Btuh2908 Ducts Btuh1848Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh0 Piping Btuh0Equipment load Btuh25358 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh22753 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh2222 Ducts Btuh1306Central vent (0 cfm) Btuh0 CoolingHeating (none)15211521Area (ft²) Equipment latent load Btuh3529 1520515205Volume (ft³)Air changes/hour 0.200.39 Equipment Total Load (Sen+Lat)Btuh26281 Equiv. AVF (cfm) 5098 Req. total capacity at 0.87 SHR ton2.2 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTrade Trade TRANE Model Cond 4TTR6030J1AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW7.7 Sensible cooling Btuh25404Heating output Btuh26273 Latent cooling Btuh3796 Temperature rise °F65 Total cooling Btuh29200Actual air flow cfm368 Actual air flow cfm1000 Air flow factor cfm/Btuh0.015 Air flow factor cfm/Btuh0.044Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.87 Bold/italic values have been manually overridden Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Project Summary 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949 Notes: Design Information Vero Beach Muni, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75 Design TD °F27 Design TD °F16Daily range L Relative humidity %50Moisture difference gr/lb59 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh18561 Structure Btuh19143 Ducts Btuh2117 Ducts Btuh1601Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0 (none) (none)Humidification Btuh0Blower Btuh1195 Piping Btuh0Equipment load Btuh20677 Use manufacturer's data y Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh21938 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3342 Ducts Btuh1316Central vent (0 cfm) Btuh0 CoolingHeating (none)11391139Area (ft²) Equipment latent load Btuh4658 1572115721Volume (ft³)Air changes/hour 0.220.43 Equipment Total Load (Sen+Lat)Btuh26596 Equiv. AVF (cfm) 58113 Req. total capacity at 0.83 SHR ton2.2 Heating Equipment Summary Cooling Equipment Summary Make Trane Make TraneTrade Trade TRANE Model Cond 4TTR6030J1AHRI ref Coil TEM6A0B30H21++TDR AHRI ref 8626669Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER Heating input kW7.7 Sensible cooling Btuh24236Heating output Btuh26273 Latent cooling Btuh4964 Temperature rise °F104 Total cooling Btuh29200Actual air flow cfm231 Actual air flow cfm1000 Air flow factor cfm/Btuh0.011 Air flow factor cfm/Btuh0.048Static pressure in H2O0.50 Static pressure in H2O0.50 Space thermostat Load sensible heat ratio 0.82 Job #: 191242 Performed by CJH for: Gelcorp. Industries Avalon by the Beach Custom Home Avalon by the Beach Lot 7 St Lucie County, FL 34949 The EARTHWORKS Group 7410 S US Hwy 1 Suite 104 Port St Lucie, FL 34952 Scale: 1 : 101 Page 1 Right-Suite® Universal 2019 19.0.21 RSU25986 2021-Mar-09 13:35:24 ...lon Custom HVAC calcs.S.LT 7.rup N Level 1 Family Kitchen Dinin g Master Bdrm Master WIC Master Bath WC Rm LaundryG Hall Garage Fo yer Study Bath 4 1st flr stairs Job #: 191242 Performed by CJH for: Gelcorp. Industries Avalon by the Beach Custom Home Avalon by the Beach Lot 7 St Lucie County, FL 34949 The EARTHWORKS Group 7410 S US Hwy 1 Suite 104 Port St Lucie, FL 34952 Scale: 1 : 101 Page 2 Right-Suite® Universal 2019 19.0.21 RSU25986 2021-Mar-09 13:35:24 ...lon Custom HVAC calcs.S.LT 7.rup N 2ND Flr Bedroom 3 Bedrm 3 WIC 2nd Flr Stairs Loft 2nd flr hall Bath 3 Bath 2 Bedroom 2 FAMILY RM CLG. Bold/italic values have been manually overridden 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Duct System Summary 01/06/2020Date:1st Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0.21in H2O0.21 Available static pressure in H2O0.49in H2O0.49 Supply / return available pressure 0.282 / 0.208 in H2O in H2O0.282 / 0.208 Lowest friction rate in/100ft0.080in/100ft0.080 Actual air flow cfm1000cfm368 Total effective length (TEL) ft612 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st4295.041.0VlFx0x06.00.08449191125cBath 4 st3250.038.6VlFx0x08.00.098156703555cDining st4320.032.1VlFx0x06.00.08062361405cFoyer st4310.039.2VlFx0x07.00.0819792215cKitchen st3260.09.3VlFx0x06.00.10572211643cLaundry st3250.018.1VlFx0x06.00.10574201675cMaster Bath st3230.036.6VlFx0x08.00.106125512855cMaster Bdrm st3225.047.1VlFx0x08.00.104125512855cMaster Bdrm-A st3240.024.3VlFx0x04.00.1071813411cMaster WIC st4300.051.5VlFx0x010.00.080220785014cStudy Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st4 Peak AVF 142 429 0.080 515 11.1 12x10 RectFbg st1 st3 Peak AVF 226 571 0.098 685 11.8 12x10 RectFbg st1 st1 Peak AVF 368 1000 0.080 643 15.2 14x16 RectFbg 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb2 0x 1350 343 109.7 0.190 436 12.0 x0 0 VlFx rt1 rb5 0x 780 220 259.6 0.080 404 10.0 x0 0 VlFx rt4 rb4 0x 1550 437 251.5 0.083 409 14.0 x0 0 VlFx rt4 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 368 1000 0.080 571 15.2 14x18 RectFbg rt4 Peak AVF 233 657 0.080 563 13.0 12x14 RectFbg rt1 Bold/italic values have been manually overridden 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S 191242Job:Duct System Summary 01/06/2020Date:2nd Flr AHU CJHBy: The EARTHWORKS Group 7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952 Project Information Gelcorp. Industries Avalon by the Beach Custom HomeFor: Avalon by the Beach Lot 7, St Lucie County, FL 34949 CoolingHeating External static pressure in H2O0.50in H2O0.50 Pressure losses in H2O0.21in H2O0.21 Available static pressure in H2O0.29in H2O0.29 Supply / return available pressure 0.143 / 0.147 in H2O in H2O0.143 / 0.147 Lowest friction rate in/100ft0.067in/100ft0.067 Actual air flow cfm1000cfm231 Total effective length (TEL) ft430 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk st2180.020.8VlFx0x05.00.071297607cBath 2 st2180.023.4VlFx0x05.00.070297600cBath 3 st2175.025.8VlFx0x05.00.071369754cBedrm 3 WIC st2180.031.4VlFx0x08.00.067129282682cBedroom 2 st2175.027.1VlFx0x08.00.071133292761cBedroom 3 st2160.027.7VlFx0x08.00.076125332598cFAMILY RM CLG. st2140.035.5VlFx0x08.00.081125332598cFAMILY RM CLG.-A st2150.030.7VlFx0x08.00.079108242238cFamily st2135.033.2VlFx0x08.00.085108242238cFamily-A st2175.030.2VlFx0x07.00.07088191833cLoft st2165.021.0VlFx0x07.00.07788191833cLoft-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st2 Peak AVF 231 1000 0.067 643 15.7 16x14 RectFbg 2021-Mar-09 13:34:11 Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4 ...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb3 0x 350 159 143.5 0.103 454 8.0 x0 0 VlFx rt2 rb1 0x 380 169 218.4 0.067 384 9.0 x0 0 VlFx rt6 rb8 0x 1580 672 212.9 0.069 481 16.0 x0 0 VlFx rt6 Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt2 Peak AVF 231 1000 0.067 571 15.7 14x18 RectFbg rt6 Peak AVF 196 841 0.067 476 18.0 0x0 VinlFlx rt2