HomeMy WebLinkAboutAvalon Custom HVAC LT 7 MANUAL J & MAN. D DUCT SUMMARY[44] (2)Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Load Short Form 01/06/2020Date:ENTIRE BUILDING CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Information
InfiltrationClgHtg
SimplifiedMethod9143Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1627Design TD (°F)
L-Daily range
5050Inside humidity (%)
5922Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make n/a Make n/a
Trade n/a Trade n/a
Model n/a Cond n/a
AHRI ref n/a Coil n/a
AHRI ref n/a
Efficiency n/a Efficiency n/a
Heating input Sensible cooling Btuh0
Heating output Btuh0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0
Actual air flow cfm0 Actual air flow cfm0
Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0
Static pressure in H2O0 Static pressure in H2O0
Space thermostat n/a Load sensible heat ratio 0
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
1st Flr AHU 1521 25358 22753 368 1000
2nd Flr AHU 1139 20677 20744 231 1000
ENTIRE BUILDING 2659 46035 43496 599 2000
Other equip loads 0 0
Equip. @ 1.00 RSM 43496
Latent cooling 8187
TOTALS 2659 46035 51683 599 2000
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Load Short Form 01/06/2020Date:1st Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Information
InfiltrationClgHtg
SimplifiedMethod9143Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1627Design TD (°F)
L-Daily range
5050Inside humidity (%)
5922Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Trane Make Trane
Trade Trade TRANE
Model Cond 4TTR6030J1
AHRI ref Coil TEM6A0B30H21++TDR
AHRI ref 8626669
Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER
Heating input kW7.7 Sensible cooling Btuh25404
Heating output Btuh26273 Latent cooling Btuh3796
Temperature rise °F65 Total cooling Btuh29200
Actual air flow cfm368 Actual air flow cfm1000
Air flow factor cfm/Btuh0.015 Air flow factor cfm/Btuh0.044
Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.87
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Dining 120 4798 3555 70 156
Master Bdrm 330 7066 5709 103 251
Master WIC 57 893 411 13 18
Kitchen 268 643 2215 9 97
Master Bath 117 1352 1675 20 74
WC Rm 15 0 0 0 0
Laundry 55 1457 1643 21 72
G Hall 23 0 0 0 0
Foyer 150 2486 1405 36 62
Study 222 5356 5014 78 220
Bath 4 84 1307 1125 19 49
1st flr stairs 79 0 0 0 0
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
1st Flr AHU 1521 25358 22753 368 1000
Other equip loads 0 0
Equip. @ 1.00 RSM 22753
Latent cooling 3529
TOTALS 1521 25358 26281 368 1000
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Load Short Form 01/06/2020Date:2nd Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Information
InfiltrationClgHtg
SimplifiedMethod9143Outside db (°F)
AverageConstruction quality7570Inside db (°F)
0Fireplaces1627Design TD (°F)
L-Daily range
5050Inside humidity (%)
5922Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Trane Make Trane
Trade Trade TRANE
Model Cond 4TTR6030J1
AHRI ref Coil TEM6A0B30H21++TDR
AHRI ref 8626669
Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER
Heating input kW7.7 Sensible cooling Btuh24236
Heating output Btuh26273 Latent cooling Btuh4964
Temperature rise °F104 Total cooling Btuh29200
Actual air flow cfm231 Actual air flow cfm1000
Air flow factor cfm/Btuh0.011 Air flow factor cfm/Btuh0.048
Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.82
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Bedrm 3 WIC 48 786 754 9 36
2nd Flr Stairs 79 0 0 0 0
Loft 247 3358 3666 38 177
2nd flr hall 49 0 0 0 0
Bath 3 47 590 600 7 29
Bath 2 54 597 607 7 29
Bedroom 2 209 2525 2682 28 129
Bedroom 3 150 2616 2761 29 133
Family 256 4386 4476 49 216
FAMILY RM CLG.0 5820 5196 65 251
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 5
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
2nd Flr AHU 1139 20677 20744 231 1000
Other equip loads 0 1195
Equip. @ 1.00 RSM 21938
Latent cooling 4658
TOTALS 1139 20677 26596 231 1000
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Building Analysis 01/06/2020Date:ENTIRE BUILDING CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Conditions
Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US
1627Design TD (°F)ft30Elevation:
5050Relative humidity (%)°N28Latitude:
Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating
Infiltration:9143Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality78-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
OtherCeilings
Floors
Infiltration
Ducts
% of loadBtuhBtuh/ft²Component
17.882092.6Walls
35.81650327.9Glazing
1.254913.4Doors
7.032441.5Ceilings
13.562352.92.9Floors
13.662701.8Infiltration
10.95025Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.046035Total
Cooling
Walls
Glazing Other
Ceilings
Infiltration
Ducts
Internal Gains
% of loadBtuhBtuh/ft²Component
15.768242.2Walls
44.81949332.9Glazing
1.459614.6Doors
7.331911.5Ceilings
0.31200.1Floors
4.218440.5Infiltration
7.93449Ducts
00Ventilation
18.37980Internal gains
00Blower
0Adjustments
100.043496Total
Latent Cooling Load = 8187 Btuh
Overall U-value = 0.254 Btuh/ft²-°F
ERROR: negative wall area in Bedroom 3 - check windows.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Building Analysis 01/06/2020Date:1st Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Conditions
Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US
1627Design TD (°F)ft30Elevation:
5050Relative humidity (%)°N28Latitude:
Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating
Infiltration:9143Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality78-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing
DoorsCeilings
Floors
Infiltration
Ducts
% of loadBtuhBtuh/ft²Component
18.145972.8Walls
31.2791927.9Glazing
2.254913.4Doors
4.912321.5Ceilings
20.752473.53.5Floors
11.529051.8Infiltration
11.52908Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.025358Total
Cooling
Walls
Glazing Doors
Ceilings
Infiltration
Ducts
Internal Gains
% of loadBtuhBtuh/ft²Component
16.737982.3Walls
42.3961433.9Glazing
2.659614.6Doors
5.312131.5Ceilings
000Floors
3.88540.5Infiltration
8.11848Ducts
00Ventilation
21.24830Internal gains
00Blower
0Adjustments
100.022753Total
Latent Cooling Load = 3529 Btuh
Overall U-value = 0.235 Btuh/ft²-°F
Data entries checked.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Building Analysis 01/06/2020Date:2nd Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
Design Conditions
Location:CoolingHeatingIndoor:7570Indoor temperature (°F)Vero Beach Muni, FL, US
1627Design TD (°F)ft30Elevation:
5050Relative humidity (%)°N28Latitude:
Outdoor:59.422.0Moisture difference (gr/lb)CoolingHeating
Infiltration:9143Dry bulb (°F)
SimplifiedMethod)L(15-Daily range (°F)
AverageConstruction quality78-Wet bulb (°F)
0Fireplaces7.515.0Wind speed (mph)
Heating
Walls
Glazing Ceilings
Floors
Infiltration
Ducts
% of loadBtuhBtuh/ft²Component
17.536122.4Walls
41.5858427.8Glazing
000Doors
9.720121.5Ceilings
4.89881.61.6Floors
16.333641.8Infiltration
10.22117Ducts
00Piping
00Humidification
00Ventilation0Adjustments
100.020677Total
Cooling
Walls
Glazing Ceilings
OtherInfiltration
Ducts
Internal Gains
Blower
% of loadBtuhBtuh/ft²Component
13.830262.0Walls
45.0987932.0Glazing
000Doors
9.019791.5Ceilings
0.51200.2Floors
4.59890.5Infiltration
7.31601Ducts
00Ventilation
14.43150Internal gains
5.41195Blower
0Adjustments
100.021938Total
Latent Cooling Load = 4658 Btuh
Overall U-value = 0.275 Btuh/ft²-°F
WARNING: window to floor area ratio = 27.1% - more than 25%.
ERROR: negative wall area in 2nd Flr Stairs - check windows.
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Project Summary 01/06/2020Date:ENTIRE BUILDING CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949
Notes:
Design Information
Vero Beach Muni, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75
Design TD °F27 Design TD °F16Daily range L
Relative humidity %50Moisture difference gr/lb59
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh41010 Structure Btuh40047
Ducts Btuh5025 Ducts Btuh3449Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0
Humidification Btuh0Blower Btuh0
Piping Btuh0Equipment load Btuh46035 Use manufacturer's data y
Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh43496
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh5565
Ducts Btuh2622Central vent (0 cfm) Btuh0
CoolingHeating26592659Area (ft²) Equipment latent load Btuh8187
3092630926Volume (ft³)Air changes/hour 0.210.41 Equipment Total Load (Sen+Lat)Btuh51683
Equiv. AVF (cfm) 108211 Req. total capacity at 0.84 SHR ton4.3
Heating Equipment Summary Cooling Equipment Summary
Make n/a Make n/aTrade n/a Trade n/a
Model n/a Cond n/aAHRI ref n/a Coil n/a
AHRI ref n/aEfficiency n/a Efficiency n/a
Heating input Sensible cooling Btuh0Heating output Btuh0 Latent cooling Btuh0
Temperature rise °F0 Total cooling Btuh0Actual air flow cfm0 Actual air flow cfm0
Air flow factor cfm/Btuh0 Air flow factor cfm/Btuh0Static pressure in H2O0 Static pressure in H2O0
Space thermostat n/a Load sensible heat ratio 0
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Project Summary 01/06/2020Date:1st Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949
Notes:
Design Information
Vero Beach Muni, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75
Design TD °F27 Design TD °F16Daily range L
Relative humidity %50Moisture difference gr/lb59
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh22449 Structure Btuh20905
Ducts Btuh2908 Ducts Btuh1848Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0
(none) (none)Humidification Btuh0Blower Btuh0
Piping Btuh0Equipment load Btuh25358 Use manufacturer's data y
Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh22753
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh2222
Ducts Btuh1306Central vent (0 cfm) Btuh0
CoolingHeating (none)15211521Area (ft²) Equipment latent load Btuh3529
1520515205Volume (ft³)Air changes/hour 0.200.39 Equipment Total Load (Sen+Lat)Btuh26281
Equiv. AVF (cfm) 5098 Req. total capacity at 0.87 SHR ton2.2
Heating Equipment Summary Cooling Equipment Summary
Make Trane Make TraneTrade Trade TRANE
Model Cond 4TTR6030J1AHRI ref Coil TEM6A0B30H21++TDR
AHRI ref 8626669Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER
Heating input kW7.7 Sensible cooling Btuh25404Heating output Btuh26273 Latent cooling Btuh3796
Temperature rise °F65 Total cooling Btuh29200Actual air flow cfm368 Actual air flow cfm1000
Air flow factor cfm/Btuh0.015 Air flow factor cfm/Btuh0.044Static pressure in H2O0.70 Static pressure in H2O0.70
Space thermostat Load sensible heat ratio 0.87
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Project Summary 01/06/2020Date:2nd Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:Avalon by the Beach Lot 7, St Lucie County, FL 34949
Notes:
Design Information
Vero Beach Muni, FL, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F43 Outside db °F91Inside db °F70 Inside db °F75
Design TD °F27 Design TD °F16Daily range L
Relative humidity %50Moisture difference gr/lb59
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh18561 Structure Btuh19143
Ducts Btuh2117 Ducts Btuh1601Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0
(none) (none)Humidification Btuh0Blower Btuh1195
Piping Btuh0Equipment load Btuh20677 Use manufacturer's data y
Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh21938
Method Latent Cooling Equipment Load SizingSimplified
Construction quality Average0Fireplaces Structure Btuh3342
Ducts Btuh1316Central vent (0 cfm) Btuh0
CoolingHeating (none)11391139Area (ft²) Equipment latent load Btuh4658
1572115721Volume (ft³)Air changes/hour 0.220.43 Equipment Total Load (Sen+Lat)Btuh26596
Equiv. AVF (cfm) 58113 Req. total capacity at 0.83 SHR ton2.2
Heating Equipment Summary Cooling Equipment Summary
Make Trane Make TraneTrade Trade TRANE
Model Cond 4TTR6030J1AHRI ref Coil TEM6A0B30H21++TDR
AHRI ref 8626669Efficiency 100 EFF Efficiency 14.0 EER, 16.5 SEER
Heating input kW7.7 Sensible cooling Btuh24236Heating output Btuh26273 Latent cooling Btuh4964
Temperature rise °F104 Total cooling Btuh29200Actual air flow cfm231 Actual air flow cfm1000
Air flow factor cfm/Btuh0.011 Air flow factor cfm/Btuh0.048Static pressure in H2O0.50 Static pressure in H2O0.50
Space thermostat Load sensible heat ratio 0.82
Job #: 191242
Performed by CJH for:
Gelcorp. Industries Avalon by the Beach Custom Home
Avalon by the Beach Lot 7
St Lucie County, FL 34949
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104
Port St Lucie, FL 34952
Scale: 1 : 101
Page 1
Right-Suite® Universal 2019
19.0.21 RSU25986
2021-Mar-09 13:35:24
...lon Custom HVAC calcs.S.LT 7.rup
N
Level 1
Family
Kitchen
Dinin g
Master Bdrm
Master WIC
Master Bath
WC Rm
LaundryG Hall
Garage
Fo yer
Study
Bath 4
1st flr stairs
Job #: 191242
Performed by CJH for:
Gelcorp. Industries Avalon by the Beach Custom Home
Avalon by the Beach Lot 7
St Lucie County, FL 34949
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104
Port St Lucie, FL 34952
Scale: 1 : 101
Page 2
Right-Suite® Universal 2019
19.0.21 RSU25986
2021-Mar-09 13:35:24
...lon Custom HVAC calcs.S.LT 7.rup
N
2ND Flr
Bedroom 3
Bedrm 3 WIC
2nd Flr Stairs
Loft
2nd flr hall Bath 3
Bath 2
Bedroom 2
FAMILY RM CLG.
Bold/italic values have been manually overridden
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Duct System Summary 01/06/2020Date:1st Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
CoolingHeating
External static pressure in H2O0.70in H2O0.70
Pressure losses in H2O0.21in H2O0.21
Available static pressure in H2O0.49in H2O0.49
Supply / return available pressure 0.282 / 0.208 in H2O in H2O0.282 / 0.208
Lowest friction rate in/100ft0.080in/100ft0.080
Actual air flow cfm1000cfm368
Total effective length (TEL) ft612
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st4295.041.0VlFx0x06.00.08449191125cBath 4
st3250.038.6VlFx0x08.00.098156703555cDining
st4320.032.1VlFx0x06.00.08062361405cFoyer
st4310.039.2VlFx0x07.00.0819792215cKitchen
st3260.09.3VlFx0x06.00.10572211643cLaundry
st3250.018.1VlFx0x06.00.10574201675cMaster Bath
st3230.036.6VlFx0x08.00.106125512855cMaster Bdrm
st3225.047.1VlFx0x08.00.104125512855cMaster Bdrm-A
st3240.024.3VlFx0x04.00.1071813411cMaster WIC
st4300.051.5VlFx0x010.00.080220785014cStudy
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st4 Peak AVF 142 429 0.080 515 11.1 12x10 RectFbg st1
st3 Peak AVF 226 571 0.098 685 11.8 12x10 RectFbg st1
st1 Peak AVF 368 1000 0.080 643 15.2 14x16 RectFbg
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb2 0x 1350 343 109.7 0.190 436 12.0 x0 0 VlFx rt1
rb5 0x 780 220 259.6 0.080 404 10.0 x0 0 VlFx rt4
rb4 0x 1550 437 251.5 0.083 409 14.0 x0 0 VlFx rt4
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1 Peak AVF 368 1000 0.080 571 15.2 14x18 RectFbg
rt4 Peak AVF 233 657 0.080 563 13.0 12x14 RectFbg rt1
Bold/italic values have been manually overridden
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
191242Job:Duct System Summary 01/06/2020Date:2nd Flr AHU CJHBy:
The EARTHWORKS Group
7410 S US Hwy 1 Suite 104, Port St Lucie, FL 34952
Project Information
Gelcorp. Industries Avalon by the Beach Custom HomeFor:
Avalon by the Beach Lot 7, St Lucie County, FL 34949
CoolingHeating
External static pressure in H2O0.50in H2O0.50
Pressure losses in H2O0.21in H2O0.21
Available static pressure in H2O0.29in H2O0.29
Supply / return available pressure 0.143 / 0.147 in H2O in H2O0.143 / 0.147
Lowest friction rate in/100ft0.067in/100ft0.067
Actual air flow cfm1000cfm231
Total effective length (TEL) ft430
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk
st2180.020.8VlFx0x05.00.071297607cBath 2
st2180.023.4VlFx0x05.00.070297600cBath 3
st2175.025.8VlFx0x05.00.071369754cBedrm 3 WIC
st2180.031.4VlFx0x08.00.067129282682cBedroom 2
st2175.027.1VlFx0x08.00.071133292761cBedroom 3
st2160.027.7VlFx0x08.00.076125332598cFAMILY RM CLG.
st2140.035.5VlFx0x08.00.081125332598cFAMILY RM CLG.-A
st2150.030.7VlFx0x08.00.079108242238cFamily
st2135.033.2VlFx0x08.00.085108242238cFamily-A
st2175.030.2VlFx0x07.00.07088191833cLoft
st2165.021.0VlFx0x07.00.07788191833cLoft-A
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st2 Peak AVF 231 1000 0.067 643 15.7 16x14 RectFbg
2021-Mar-09 13:34:11
Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4
...P\submitted\Avalon Custom HVAC calcs.S.LT 7.rup Calc = MJ8 Front Door faces: S
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk
rb3 0x 350 159 143.5 0.103 454 8.0 x0 0 VlFx rt2
rb1 0x 380 169 218.4 0.067 384 9.0 x0 0 VlFx rt6
rb8 0x 1580 672 212.9 0.069 481 16.0 x0 0 VlFx rt6
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt2 Peak AVF 231 1000 0.067 571 15.7 14x18 RectFbg
rt6 Peak AVF 196 841 0.067 476 18.0 0x0 VinlFlx rt2