HomeMy WebLinkAboutAvalon Custom Energy Calcs LT 23.SD[94]FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 1... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
RESIDENTIAL ENERGY CONSERVATION CODE DOCUMENTATION CHECKLIST
Florida Department of Business and Professional Regulation
Simulated Performance Alternative (Performance) Method
Applications for compliance with the 2017 Florida Building Code, Energy Conservation via the residential
Simulated Performance method shall include:
This Checklist
A FORM 405 report that documents that the Proposed Design complies with Section R405.3 of the Florida
Energy Code. This form shall include a summary page indicating home address, e-ratio and the pass or fail
status along with summary areas and types of components, whether the home was simulated as a worst-case
orientation, name and version of the compliance software tool, name of individual completing the compliance
report (one page).
An input summary checklist that can be used for field verification (usually 4 pages/may be greater).
Energy Performance Level (EPL) Display Card (one page)
HVAC system sizing and selection based on ACCA Manual S or per exceptions provided in Section R403.7
Mandatory Requirements (five pages)
Required prior to CO for the Performance method:
Air Barrier and Insulation Inspection Component Criteria checklist (Table 402.4.1.1 - one page)
A completed Form 2017 Envelope Leakage Test Report (usually one page). Section R402.4 or R402.4.1.2
exceptions may apply.
If FORM R405 duct leakage type indicates anything other than "default leakage", then a completed FORM R405
Duct Leakage Test Report (usually one page).
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 2... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
Builder Name:Avalon Beach Custom HomeProject Name:
Permit Office:Avalon by the Beach Lot #23Street:
Permit Number:St Lucie County, FL 32963City, State, Zip:
St Lucie CountyJurisdiction:Gelcorp. Industries Avalon by the Beach Custom HomeOwner:
(Florida Climate Zone 2)County:FL, St Lucie Co IntlDesign Location:
1. New construction or existing New (From Plans)Area(ft²)Insulation (R)9. Wall types (4360 ft²)
2. Single family or multiple family Single-Family
3111.004.1Blk wall, stucco ext, r-4 int. ba.
329.0019.0Frm wall, 5/8" gyp.bd ext, r-19b.
3. Number of units, if multiple family 1 160.0019.0Frm wall, 5/8" gyp.bd ext, r-19c.
4. Number of bedrooms 760.41other (see details)d.3
Area(ft²)Insulation (R)10. Ceiling types (2119 ft²)
5. Is this a worst case? Yes 2118.7520.0Attic ceiling, mtl roof mat, r-2a.
6. Conditioned floor area above grade (ft²) 2574.25 N/Ab.
N/Ac.0Conditioned floor area below grade (ft²)
Area(ft²)R11. Ducts7. Windows (603 ft²) Description Area (ft²)408.886.0Sup: 1st Flr AHU, Ret: 1st Flr AHU, AH: 1st Flr AHUa.
190.666.0Sup: 2nd Flr AHU Att, Ret: 2nd Flr AHU Att, AH: 2nd Flr AHUb.186.00Dbl, 1.010a. U-Factor:
0.33SHGC:
EfficiencykBtu/hr12. Cooling systems248.50Dbl, 1.050b. U-Factor:
SEER: 16.529.2Split air conditionera.0.26SHGC:
SEER: 16.529.2Split air conditionerb.144.00Dbl, 1.040c. U-Factor:
EfficiencykBtu/hr13. Heating systems0.29SHGC:
AFUE: 100.026.3Electric stripa.24.00Dbl, 1.030d. U-Factor:AFUE: 100.026.3Electric stripb.0.24SHGC:
14. Hot water systemsft1.739Area Weighted Average Overhang Depth:
Cap: 50 galElectric conventional (50 gal)a.0.288Area Weighted Average SHGC:
EF: 0.93
8. Floor types (2120.75 ft²) Insulation (R) Area (ft²) Conservation featuresb.
(None)1776.500.0Bg floor, light dry soil, on graa.
310.2519.0Flr floor, frm flr, 12" thkns, cb.
Ceiling Fan15. Credits34.0019.0Flr floor, frm flr, 12" thkns, tc.
110.80Total Proposed Modified Loads:Glass/Floor area: 0.234 PASS113.49Total Baseline Loads:
Review of the plans and specificationsI hereby certify that the plans and specifications covered by
this calculation are in compliance with the Florida Energy
Code.
covered by this calculation indicates
compliance with the Florida Energy
Code. Before construction is completed,
this building will be inspected forPREPARED BY:____________________________
compliance with Section 553.908
Florida Statutes.DATE:____________________________________
I hereby certify that this building, as designed, is in
compliance with the Florida Energy Code.
BUILDING OFFICIAL:______________________OWNER/AGENT:___________________________
DATE:__________________________________DATE:____________________________________
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
- Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project
requires an envelope leakage test report with envelope leakage no greater than 7.0 ACH50 (R402.4.1.2).
Christopher J Hammel
03-09-2021
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 3... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
Building Input Summary Report
PROJECT
Street addressAddress type:3Bedrooms:Avalon Beach Custom HomeTitle:
Lot#:1Bathrooms:FLAsBuiltBuilding Type:
Block/Subdivision:2574Conditioned Area:Gelcorp. Industries Avalon by the Beach Custom HomeOwner:
Platbook:2Total Stories:1# of Units:
Avalon by the BeachStreet:YesWorst Case:Builder Name:
County:0Rotate Angle:Permit Office:
St Lucie County, FL 32963City, State, Zip:NoCross Ventilation:St Lucie CountyJurisdiction:
NoWhole House Fan:Single-FamilyFamily Type:
Ocean/LakeTerrain:New (From Plans)New/Existing:
SuburbanShielding:2020Year Construct:
Comment:
CLIMATE
Daily TempDesignHeatingInt Design TempDesign TempIECC
RangeMoistureDegree DaysSummerWinter2.5 %97.5 %ZoneTMY SiteDesign Location
Low57486757090412FL_Vero_Beach_MuniFL, St Lucie Co Intl
BLOCKS
VolumeAreaName#
ft³14399.50ft²1053.752nd Flr AHU1
ft³18424.00ft²1520.501st Flr AHU2
SPACES
HeatedCooledFinishedInfil IDBedroomsOccupantsKitchenVolumeArea#
YesYesYes102Noft³5632.00ft²256.00Family1
YesYesYes100Yesft³5901.50ft²268.25Kitchen2
YesYesYes100Noft³1200.00ft²120.00Dining3
YesYesYes111Noft³3300.00ft²330.00Master Bdrm4
YesYesYes100Noft³570.00ft²57.00Master WIC5
YesYesYes100Noft³1170.00ft²117.00Master Bath6
YesYesYes100Noft³150.00ft²15.00WC Rm7
YesYesYes100Noft³552.50ft²55.25Laundry8
YesYesYes100Noft³227.50ft²22.75G Hall9
YesYesYes100Noft³1502.50ft²150.25Foyer10
YesYesYes100Noft³2220.00ft²222.00Study11
YesYesYes100Noft³840.00ft²84.00Bath 412
YesYesYes100Noft³790.00ft²79.001st flr stairs13
YesYesYes110Noft³2090.00ft²209.00Bedroom 214
YesYesYes100Noft³790.00ft²02nd Flr Stairs15
YesYesYes100Noft³475.00ft²47.50Bedrm 3 WIC16
YesYesYes100Noft³490.00ft²49.002nd flr hall17
YesYesYes101Noft³2445.00ft²244.50loft18
YesYesYes110Noft³1500.00ft²150.00Bedrm 319
YesYesYes100Noft³467.50ft²46.75Bath 320
YesYesYes100Noft³510.00ft²51.00Bath 221
(Total Exposed Area = 2121 sq.ft.)FLOORS
CarpetWoodTileU-FactorAreaR-ValuePerimeterSpaceFloor Type#
01.000.989ft²256.000ft29FamilyBg floor, light dry soil, on grade depth1
01.000.989ft²268.250ft10KitchenBg floor, light dry soil, on grade depth2
01.000.989ft²120.000ft23DiningBg floor, light dry soil, on grade depth3
01.000.989ft²330.000ft50Master BdrmBg floor, light dry soil, on grade depth4
01.000.989ft²57.000ft10Master WICBg floor, light dry soil, on grade depth5
01.000.989ft²117.000ft10Master BathBg floor, light dry soil, on grade depth6
01.000.989ft²15.000ft0WC RmBg floor, light dry soil, on grade depth7
01.000.989ft²55.250ft15LaundryBg floor, light dry soil, on grade depth8
01.000.989ft²22.750ft4G HallBg floor, light dry soil, on grade depth9
01.000.989ft²150.250ft23FoyerBg floor, light dry soil, on grade depth10
01.000.989ft²222.000ft40StudyBg floor, light dry soil, on grade depth11
01.000.989ft²84.000ft7Bath 4Bg floor, light dry soil, on grade depth12
01.000.989ft²79.000ft81st flr stairsBg floor, light dry soil, on grade depth13
1.0000.050ft²47.5019ft6Bedrm 3 WICFlr floor, frm flr, 12" thkns, carpet flr fnsh, r14
1.0000.050ft²34.5019ft02nd flr hallFlr floor, frm flr, 12" thkns, carpet flr fnsh, r15
1.0000.050ft²78.2519ft14loftFlr floor, frm flr, 12" thkns, carpet flr fnsh, r16
1.0000.050ft²150.0019ft25Bedrm 3Flr floor, frm flr, 12" thkns, carpet flr fnsh, r17
001.00.050ft²34.0019ft4Bath 3Flr floor, frm flr, 12" thkns, tile flr fnsh, r-118
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 4... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
FORM R405-2017
ROOF
PitchDeckEmittEmittSASolarRoofGableRoof
(deg)Insul.TestedTestedAbsor.ColorAreaAreaMaterialsType#
270No0.90No0.75Medium1178 ft²RoofMetalHip1
270No0.90No0.75Medium1102 ft²RoofMetalHip2
ATTIC
IRCCRBSAreaVent Ratio (1 in)VentilationType#
NNft²1053.750UnventedFull attic1
NNft²986.000UnventedFull attic2
(Total Exposed Area = 2119 sq.ft.)CEILING
Truss TypeFraming FractionAreaU-FactorR-ValueSpaceCeiling Type#
Wood0.10ft²256.000.40820FamilyAttic ceiling, mtl roof mat, r-20 ro1
Wood0.10ft²176.000.40820KitchenAttic ceiling, mtl roof mat, r-20 ro2
Wood0.10ft²120.000.40820DiningAttic ceiling, mtl roof mat, r-20 ro3
Wood0.10ft²330.000.40820Master BdrmAttic ceiling, mtl roof mat, r-20 ro4
Wood0.10ft²45.000.40820Master WICAttic ceiling, mtl roof mat, r-20 ro5
Wood0.10ft²24.750.40820FoyerAttic ceiling, mtl roof mat, r-20 ro6
Wood0.10ft²222.000.40820StudyAttic ceiling, mtl roof mat, r-20 ro7
Wood0.10ft²68.250.40820Bath 4Attic ceiling, mtl roof mat, r-20 ro8
Wood0.10ft²209.000.40820Bedroom 2Attic ceiling, mtl roof mat, r-20 ro9
Wood0.10ft²79.000.408202nd Flr StairsAttic ceiling, mtl roof mat, r-20 ro10
Wood0.10ft²47.500.40820Bedrm 3 WICAttic ceiling, mtl roof mat, r-20 ro11
Wood0.10ft²49.000.408202nd flr hallAttic ceiling, mtl roof mat, r-20 ro12
Wood0.10ft²244.500.40820loftAttic ceiling, mtl roof mat, r-20 ro13
Wood0.10ft²150.000.40820Bedrm 3Attic ceiling, mtl roof mat, r-20 ro14
Wood0.10ft²46.750.40820Bath 3Attic ceiling, mtl roof mat, r-20 ro15
Wood0.10ft²51.000.40820Bath 2Attic ceiling, mtl roof mat, r-20 ro16
(Total Exposed Area = 4360 sq.ft.)WALLS
Below
Grade%
Solar
Absor.
Frm.U-Sheathing
R-Value
HeightWidthCavityAdjacent
To Frac.FactorAreaInFtInFtR-ValueSpaceWall TypeOrnt#
00.750.220.1090ft²352.00220164FamilyBlk wall, stuccoExteriorE1
00.750.220.1090ft²275.00226124FamilyBlk wall, stuccoExteriorS2
00.750.220.1090ft²109.00221144KitchenBlk wall, stuccoExteriorSW3
00.750.250.0660ft²209.00226919KitchenFrm wall, 5/8" gyPartition-4
00.750.220.1090ft²80.0010084DiningBlk wall, stuccoExteriorE5
00.750.220.1090ft²150.00100154DiningBlk wall, stuccoExteriorS6
00.750.220.1090ft²170.00100174Master BdrmBlk wall, stuccoExteriorE7
00.750.220.1090ft²150.00100154Master BdrmBlk wall, stuccoExteriorS8
00.750.220.1090ft²175.00106174Master BdrmBlk wall, stuccoExteriorW9
00.750.220.1090ft²95.0010694Master WICBlk wall, stuccoExteriorW10
00.750.220.1090ft²100.00100104Master BathBlk wall, stuccoExteriorW11
00.750.220.1090ft²65.0010664LaundryBlk wall, stuccoExteriorW12
00.750.250.0660ft²85.00106819LaundryFrm wall, 5/8" gyPartition-13
00.750.250.0660ft²35.00106319G HallFrm wall, 5/8" gyPartition-14
00.750.220.1090ft²65.0010664FoyerBlk wall, stuccoExteriorN15
00.750.250.0790ft²160.001001619FoyerFrm wall, 5/8" gyPartition-16
00.750.220.1090ft²145.00106144StudyBlk wall, stuccoExteriorN17
00.750.220.1090ft²150.00100154StudyBlk wall, stuccoExteriorE18
00.750.220.1090ft²105.00106104StudyBlk wall, stuccoExteriorW19
00.750.220.1090ft²65.0010664Bath 4Blk wall, stuccoExteriorE20
00.750.220.1090ft²75.00106741st flr stairsBlk wall, stuccoExteriorE21
00.750.220.1090ft²160.00100164Bedroom 2Blk wall, stuccoExteriorE22
00.750.220.1090ft²5.0010604Bedroom 2Blk wall, stuccoExteriorS23
00.750.250.0630ft²150.001001519Bedroom 2Frm wall, stuccoExteriorS24
00.750.220.1090ft²110.00100114Bedroom 2Blk wall, stuccoExteriorW25
00.750.250.0750ft²60.001006192nd Flr StairsFrm wall, stuccoExteriorN26
00.750.220.1090ft²75.00106742nd Flr StairsBlk wall, stuccoExteriorE27
00.750.220.1090ft²145.001061442nd Flr StairsBlk wall, stuccoExteriorS28
00.750.220.1090ft²50.0010054Bedrm 3 WICBlk wall, stuccoExteriorN29
00.750.220.1090ft²5.0010604Bedrm 3 WICBlk wall, stuccoExteriorE30
00.750.220.1090ft²0.0010004loftBlk wall, stuccoExteriorN31
00.750.250.0630ft²190.401001919loftFrm wall, stuccoExteriorN32
00.750.250.0630ft²110.001001119loftFrm wall, stuccoExteriorE33
00.750.220.1090ft²125.00106124loftBlk wall, stuccoExteriorS34
00.750.250.0630ft²125.001061219Bedrm 3Frm wall, stuccoExteriorN35
00.750.220.1090ft²120.00100124Bedrm 3Blk wall, stuccoExteriorW36
00.750.220.1090ft²55.0010654Bath 3Blk wall, stuccoExteriorW37
00.750.220.1090ft²60.0010064Bath 2Blk wall, stuccoExteriorW38
(Total Exposed Area = 41 sq.ft.)DOORS
HeightWidth
AreaInFtInFtU-ValueStormsSpaceDoor TypeOrnt#
ft²19.8071020.390NoneG HallDoor, wd sc typeN1
ft²21.007030.600NoneFoyerDoor, mtl fbrgl typeN2
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 5... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
FORM R405-2017
(Total Exposed Area = 543 sq.ft.)WINDOWS
InteriorOverhangWall
ScreeningShadeSeparationDepthAreaImpactSHGCU-FactorNFRCPanesFrameIDOrnt#
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.331.010YesDouble (Clear)Metal1E1
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.261.050YesDouble (Clear)Metal1E2
NoneNone0 ft 0 in0 ft 0 inft²54.0No0.331.010YesDouble (Clear)Metal2S3
NoneNone0 ft 0 in0 ft 0 inft²72.0No0.291.040YesDouble (Clear)Metal2S4
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.261.050YesDouble (Clear)Metal5E5
NoneNone2 ft 0 in10 ft 0 inft²72.0No0.291.040YesDouble (Clear)Metal6S6
NoneNone2 ft 0 in10 ft 0 inft²24.0No0.241.030YesDouble (Clear)Metal7E7
NoneNone0 ft 0 in0 ft 0 inft²53.0No0.261.050YesDouble (Clear)Metal8S8
NoneNone0 ft 0 in0 ft 0 inft²25.0No0.331.010YesDouble (Clear)Metal11W9
NoneNone0 ft 0 in0 ft 0 inft²15.0No0.261.050YesDouble (Clear)Metal12W10
NoneNone2 ft 0 in6 ft 0 inft²14.7No0.331.010YesDouble (Clear)Metal15N11
NoneNone0 ft 0 in0 ft 0 inft²36.0No0.261.050YesDouble (Clear)Metal17N12
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.261.050YesDouble (Clear)Metal18E13
NoneNone0 ft 0 in0 ft 0 inft²8.0No0.331.010YesDouble (Clear)Metal20E14
NoneNone0 ft 0 in0 ft 0 inft²11.8No0.331.010YesDouble (Clear)Metal23S15
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.261.050YesDouble (Clear)Metal25W16
NoneNone0 ft 0 in0 ft 0 inft²18.5No0.331.010YesDouble (Clear)Metal27E17
NoneNone0 ft 0 in0 ft 0 inft²18.0No0.261.050YesDouble (Clear)Metal29N18
NoneNone0 ft 0 in0 ft 0 inft²18.5No0.261.050YesDouble (Clear)Metal31N19
NoneNone0 ft 0 in0 ft 0 inft²6.0No0.331.010YesDouble (Clear)Metal37W20
NoneNone0 ft 0 in0 ft 0 inft²6.0No0.331.010YesDouble (Clear)Metal38W21
GARAGE
Exposed Wall InsulationAvg. Wall HeightExposed Wall PerimeterCeiling AreaFloor Area#
01
INFILTRATION
ACH 50ACHEqLAELACFM 50SLAMethodScope#
7.000.65395.5210.638290.000586SimplifiedWholehouse1
HEATING SYSTEM
DuctsBlockCapacityEfficiencySubtypeSystem Type#
sys#1126.3 kBtu/hrAFUE: 100.0Electric strip1
sys#2226.3 kBtu/hrAFUE: 100.0Electric strip2
COOLING SYSTEM
DuctsBlockSHRAir FlowCapacityEfficiencySubtypeSystem Type#
sys#110.861000 cfm29.2 kBtu/hrSEER: 16.5Split air conditioner1
sys#220.871000 cfm29.2 kBtu/hrSEER: 16.5Split air conditioner2
HOT WATER SYSTEM
ConservationSetPntUseCapEFLocationSubtypeSystem Type#
None120 °F60 gal50 gal0.93Electric conventional1
DUCTS
HVAC #PercentCFM 25AirReturn ------------------Supply ------------------
CoolHeatRLFQNLeakageOutHandlerLeakage TypeAreaLocationAreaR-ValueLocation#
116.00(Default)2nd Flr AHUDefault Leakage38 ft²2nd Flr AHU Att191 ft²6.02nd Flr AHU Att1
226.00(Default)1st Flr AHUDefault Leakage182 ft²1st Flr AHU409 ft²6.01st Flr AHU2
TEMPERATURES
Ceiling Fans:YProgrammable Thermostat:
Dec]X[Nov]X[Oct]X[Sep]X[Aug]X[Jul]X[Jun]X[May]X[Apr]X[Mar]X[Feb]X[Jan]X[Cooling
Dec]X[Nov]X[Oct]X[Sep]X[Aug]X[Jul]X[Jun]X[May]X[Apr]X[Mar]X[Feb]X[Jan]X[Heating
Dec]X[Nov]X[Oct]X[Sep]X[Aug]X[Jul]X[Jun]X[May]X[Apr]X[Mar]X[Feb]X[Jan]X[Venting
HoursFlorida Building Code, 6th Edition
(2017)
Thermostat Schedule:
121110987654321Schedule Type
757575757575757575757575AMCooling (WD)
757575757575757575757575PM
757575757575757575757575AMCooling (WEH)
757575757575757575757575PM
727272727272727272727272AMHeating (WD)
727272727272727272727272PM
727272727272727272727272AMHeating (WEH)
727272727272727272727272PM
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 6... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX = 98
The lower the EnergyPerformance Index, the more efficient the home.
1. New home or addition 12. Ducts, location & insulation levelNew (From Plans)1. _______________
6.0R______________a. Supply ducts:
2. Single-family or multiple-family Single-Family2. _______________ 6.0R______________b. Return ducts:
1st Flr AHU,2nd Flr AHU______________c. AHU location:
3. Number of units, if multiple-family 13. _______________
58.4Capacity_______________13. Cooling systems
4. Number of bedrooms 16.50SEER______________a. Split system:34. _______________
SEER______________b. Single package:
5. Is this a worst case? (yes/no) Yes5. _______________ SEER/COP______________c. Ground/water source:
EER______________d. Room unit/PTAC:
6. Conditioned floor area (ft²) 2574.256. _______________ ______________e. Other:
7. Windows, type and area*52.5Capacity____________14. Heating systems
HSPF______________a. Split system heat pump:Dbl(Avg), 1.0347a. ______________a. U-Factor:
HSPF______________b. Single package heat pump:0.297b. ______________b. Solar Heat Gain Coefficient (SHGC):
100.00COP_______________c. Electric resistance:6037c. ______________c. Area (ft²)
AFUE______________d. Gas furnace, natural gas:
8. Skylights AFUE______________e. Gas furnace, LPG:
______________f. Other:8a. ______________a. U-Factor:
8b. ______________b. Solar Heat Gain Coefficient (SHGC):
15. Water heating systems
9. Floor type, insulation level 0.930EF______________a. Electric resistance:
EF______________b. Gas fired, natrual gas:0.09a. ______________a. Slab-on-grade (R-value):
EF______________c. Gas fired, LPG:19.09b. ______________b. Wood, raised (R-value):
EF______________d. Solar system with tank:9c. ______________c. Concrete, raised (R-value)
EF______________e. Dedicated heat pump with tank:
10 Wall type and insulation:______________HeatRec%f. Heat recovery unit:
______________g. Other:a. Exterior:
1910a1. ____________1. Wood frame (Insulation R-value):
16. HVAC credits claimed (Performance Method)410a2. ____________2. Masonry (Insulation R-value):
Yes______________a. Ceiling fans:b. Adjacent:
______________b. Cross ventilation:1910b1. ____________1. Wood frame (Insulation R-value):
______________c. Whole house fan:10b2. ____________2. Masonry (Insulation R-value):
Yes______________d. Multizone cooling credit:
11. Ceiling type and insulation level Yes______________e. Multizone heating credit:
Yes______________f. Programmable thermostat:20.011a. _____________a. Under attic (R-value):
11b. _____________b. Single assembly (R-value):
11c. _____________c. Knee walls/skylight walls (R-value)
11d. _____________d. Radiant barrier installed
*Label required by Section 303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation,through the above energy saving features
which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed
based on installed Code compliant features.
Builder Signature: _________________________ Date: ______________________
Address of New Home: _____________________Avalon by the Beach Lot #23 St Lucie County, FL 32963City/FL Zip: _________________
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 7... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
FORM R405-2017
Florida Building Code, Energy Conservation, 6th Edition (2017)
Mandatory Requirements for Residential Performance, Prescriptive and ERI Methods
PERMIT #:Avalon by the Beach Lot #23ADDRESS:
St Lucie County, FL 32963
MANDATORY REQUIREMENTS - See individual code sections for full details.
SECTION R401 GENERAL
The building official shall require that an energy performance level (EPL)R401.3 Energy Performance Level (EPL) display card (Mandatory).
display card be completed and certified by the builder to be accurate and correct before final approval of the building for occupancy. Florida law
(Section 553.9085, Florida Statues) requires the EPL display card to be included as an addendum to each sales contract for both presold and
nonpresold residential buildings. The EPL display card contains information indicating the energy performance level and efficiencies of components
installed in a dwelling unit. completed and signed by the builder The building official shall verify that the EPL display card accurately reflects the plans
and specifications submitted to demonstrate compliance for the building. A copy of the EPL display card can be found in Appendix RD.
The building thermal envelope shall be constructed to limit air leakage in accordance with the requirements ofR402.4 Air leakage (Mandatory).
Sections R402.4.1 through R402.4.5.
Dwelling units of R-2 Occupancies and multiple attached single family dwellings shall be permitted toException:
comply with Section C402.5.
The building thermal envelope shall comply with Sections R402.4.1.1 and R402.4.1.2. The sealingR402.4.1 Building thermal envelope.
methods between dissimilar materials shall allow for differential expansion and contraction.
The components of the building thermal envelope as listed in Table R402.4.1.1 shall be installed in accordanceR402.4.1.1 Installation.
by the code official, an approved third party shall inspect all components and verify compliance.
The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding seven airR402.4.1.2 Testing.
changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in
accordance with ANSI/RESET/ICC 380 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be conducted by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i) or
an approved third party. A written report of the results of the test shall be signed by the party conducting the test and provided to the code
official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Testing is not required for additions, alterations, renovations, or repairs, of the building thermal envelope of existingException:
buildings in which the new construction is less than 85 percent of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended
weatherstripping or other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond
intended infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
New wood-burning fireplaces shall have tight-fitting flue dampers or doors, and outdoor combustion air. WhereR402.4.2 Fireplaces.
using tight-fitting doors on factory-built fireplaces listed and labeledin accordance with UL 127, the doors shall be tested and listed for the
fireplace. Where using tight-figging doors on masonry fireplaces,the doors shall be listed and labeled in accordance with UL 907.
Windows, skylights and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm perR402.4.3 Fenestration air leakage.
square foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2), when tested according to NFRC 400 or
AAMA/WDMA/CSA 101/I.S.2/A440 by an accredited, independent laboratory and listed and labeled by the manufacturer.
Site-built windows, skylights and doors.Exception:
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 8... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
MANDATORY REQUIREMENTS - (Continued)
In Climate Zones 3 through 8, where open combustion air ducts provide combustion air toR402.4.4 Rooms containing fuel-burning appliances
open combustion fuel burning appliances, the appliances and combustion air opening shall be located outside the building thermal envelope or
enclosed in a room, isolated from inside the thermal envelope. Such rooms shall be sealed and insulated in accordance with the envelope requirements
of Table R402.1.2, where the walls, floors and ceilings shall meet not less than the basement wall R-value requirement. The door into the room shall be
fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403. The combustion air duct shall be insulated where it
passes through conditioned space to a minimum of R-8.
Exceptions:
1. Direct vent apliances with both intake and exhaust pipes installed continuous to the outside.
2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code, Residential.
Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakageR402.4.5 Recessed lighting.
between conditioned and unconditioned spaces. All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not
more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM E283 at a 1.57 psf (75 Pa) pressure differential. All recessed
luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.
SECTION R403 SYSTEMS
R403.1 Controls
At least one thermostat shall be provided for each separate heating and cooling system.R403.1.1 Thermostat provision (Mandatory).
Heat pumps having supplementary electric-resistance heat shall have controlsR403.1.3 Heat pump supplementary heat (Mandatory).
that, except during defrost, prevent supplemental heat operation when the heat pump compressor can meet the heating load.
All ducts, air handlers, filter boxes and building cavities that form the primary air containment passagewaysR403.3.2 Sealing (Mandatory).
for air distribution systems shall be considered ducts and plenum chambers, shall be constructed and sealed in accordance with Section
C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below.
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5) or (7),
Florida Statutes, or individuals licensed as set forth in Section 489.105(3)(f), (g), or (i), Florida Statutes, to be "substantially leak free" in
accordance with Section R403.3.3.
R403.3.2.1 Sealed air handler.
of the design air flow rate when tested in accordance with ASHRAE 193.
Ducts shall be pressure tested to determine air leakage by one of the following methods:R403.3.3 Duct testing.
1. Rough-in test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the system, including the
manufacturer's air handler enclosure if installed at the time of the test. All registers shall be taped or otherwise sealed during the test.
2. Post construction test: Total leakage shall be measured with a pressure differential of 0.1 inch w.g. (25 Pa) across the
entire system, including the manufacturer's air handler enclosure. All registers shall be taped or otherwise sealed during the test.
Exceptions:
1. A duct leakage test shall not be required where the ducts and air handlers are located entirely within the building thermal envelope.
2. Duct testing is not mandatory for buildings complying by Section 405 of this code.
A written report of the results of the test shall be signed by the party conducting the test and provided to the code official.
Building framing cavities shall not be used as ducts or plenums.R403.3.5 Building Cavities (Mandatory).
Mechanical systempiping capable of carrying fluids above 105°F (41°C)R403.4 Mechanical system piping insulation (Mandatory).
or below 55°F (13°C) shall be insulated to a minimum of R-3.
Piping insulation exposed to weather shall be protected from damage, including thatR403.4.1 Protection of piping insulation.
caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause
degradation of the material. Adhesive tape shall not be permitted.
Heated water circulation systems shall be inR403.5.1 Heated water circulation and temperature maintenance systems (Mandatory).
accordance with Section R403.5.1.1. Heat trace termperature maintenance systems shall be in accordance with Section R403.5.1.2.
Automatic controls, temperature sensors and pumps shall be accessible. Manual controls shall be readily accessible.
Heated water circulation systems shall be provided with a circulation pump. The system return pipeR403.5.1.1 Circulation systems.
shall be dedicated return pipe or a cold water supply pipe. Gravity and thermosiphon circulation systems shall be prohibited.
Controls for circulating hot water system pumps shall start the pump based on the identification of a demand for how water within the
occupancy. The controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and
when there is no demand for hot water.
Electric heat trace systems shall comply with IEEE 515.1 or UL 515. Controls for such systemsR403.5.1.2 Heat trace systems.
shall automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance
with the times when heated water is used in the occupancy.
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 9... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
MANDATORY REQUIREMENTS - (Continued)
Storage water heaters not equipped with integral heat traps and having vertical pipe risers shall have heatR403.5.5 Heat traps (Mandatory).
traps installed on both the inlets and outlets. External heat traps shall consist of either a commercially available heat trap or a
downward and upward bend of at least 3 1/2 inches (89 mm) in the hot water distribution line and cold water line located as close as
possible to the storage tank.
R403.5.6 Water heater efficiencies (Mandatory).
R403.5.6.1 Storage water heater temperature controls.
Service water heating systems shall be equipped with automatic temperature controls capableR403.5.6.1.1 Automatic controls.
of adjustment from the lowest to the highest acceptable temperature settings for the intended use. The minimum temperature
setting range shall be from100°F to 140°F (38°C to 60°C).
A separate switch or a clearly marked circuit breaker shall be provided to permit the power suppliedR403.5.6.1.2 shut down.
to electric service systems to be turned off. A separate valve shall be provided to permit the energy supplied to the main burner(s)
of combustion types of service water heating systems to be turned off.
Water heating equipment installed in residential units shall meet the minimum efficiencies ofR403.5.6.2 Water heating equipment.
Table C404.2 in Chapter 4 of the Florida Building Code, Energy Conservation, Commercial Provisions, for the type of equipment
installed. Equipment used to provide heating functions as part of a combination system shall satisfy all stated requirements for the
appropriate water heating category. Solar water heaters shall met the criteria of Section R403.5.6.2.1.
Solar systems for domestic hot water production are rated by the annual solar energyR403.5.6.2.1 Solar water heating system.
factor of the system. The solar energy factor of a system shall be determined from the Florida Solar Energy Center Directory of
Certified Solar Systems. Solar collectors shall be tested in accordance with ISO Standard 9806, Test Methods for Solar Collectors,
and SRCC Standard TM-1, Solar Domestic Hot Water System and Component Test Protocol. Collectors in installed solar
water-heating systems should meet the following criteria:
1. Be installed with a tilt angle between 10 degrees and 40 degrees of the horizontal; and
2. Be installed at an orientation within 45 degrees of true south.
The building shall be provided with ventilation that meets the requirements of the FloridaR403.6 Mechanical ventilation (Mandatory).
Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation, including:
Natural, Infiltration or Mechanical means. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the
ventilation system is not operating.
When installed to function as a whole-house mechanicalR403.6.1 Whole-house mechanical ventilation system fan efficacy.
ventilation system, fans shall meet the efficacy requirements of Table R403.6.1.
Where mechanical ventilation fans are integral to tested and listed HVAC equipment, they shall be powered byException:
an electronically commutated motor.
Residential buildings designed to be operated at a positive indoor pressure of for mechanicalR403.6.2 Ventilation air.
ventilation shall meet the following criteria:
1. The design air change per hour minimums for residential buildings in ASHRAE 62.2, Ventilation for Acceptable
Indoor Air Quality, shall be the maximum rates allowed for residential applications.
2. No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics,
crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
3. If ventilation air is drawn from enclosed spaces(s), then the walls of the space(s) from which air is drawn shall be
insulated to a minimum of R-11 and the ceiling shall be insulated to a minimum or R-19, space permitting, or R-10 otherwise.
R403.7 Heating and cooling equipment (Mandatory).
Heating and cooling equipment shall be sized in accordance with ACCA Manual S based on theR403.7.1 Equipment sizing.
equipment loads calculated in accordance with ACCA Manual J or other approved methodologies, heating and cooling calculation
based on building loads for the directional orientation of the building. The manufacturer and model number of the outdoor and
indoor units (if split system) shall be submitted along with the sensible and total cooling capacities at the design conditions
described in Section R302.1. This code does not allow designer safety factors, provisions for future expansion or other factors that
affect equipment sizing. System sizing calculations shall not include loads created by local intermittent mechanical ventilation such
as standard kitchen and bathroom exhaust systems. New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by federal law for the geographic location where the equipment is installed.
TABLE R403.6.1
WHOLE-HOUSE MECHANICAL VENTILATION SYSTEM FAN EFFICACY
AIRFLOW RATE MAXIMUMMINIMUM EFFICACY (a)AIRFLOW RATE MINIMUMFAN LOCATION
CFMCFM/WATTCFM
Any2.8 cfm/wattAnyRange hoods
Any2.8 cfm/wattAnyIn-line fan
< 901.4 cfm/watt10Bathroom, utility room
Any2.8 cfm/watt90Bathroom, utility room
(a) When tested in accordance HVI Standard 916For SI: 1 cfm - 28.3 L/min.
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 10... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
MANDATORY REQUIREMENTS - (Continued)
Cooling only equipment shall be selected so that its total capacity is not lessR403.7.1.1 Cooling equipment capacity.
than the calculated total load but not more than 1.15 times greater than the total load calculated according to the procedure selected in
equipment shall not be less than the calculated latent load.
expanded performance data shall be used to select cooling-only equipment. This selection shall be based on the outdoor design dry-bulb
temperature for the load calculation (or entering water temperature for water-source equipment), the blower CFM provided by the expanded
performance data, the design value for entering wet-bulb temperature and the design value for entering dry-bulb temperature
Design values for entering wet-bulb and dry-bulb temperatures shall be for the indoor dry bulb and relative humidity used for the load
calculation and shall be adjusted for return side gains if the return duct(s) is installed in an unconditioned space.
Exceptions:
1. Attached single- and multiple-family residential equipment sizing may be selected so that its cooling capacity is
less than the calculated total sensible load but not less than 80 percent of that load.
2. When signed and sealed by a Florida-registered engineer, in attached single- and multiple-family units, the
capacity of equipment may be sized in accordance with good design practice.
R403.7.1.2 Heating equipment capacity.
Heat pump sizing shall be based on the cooling requirements as calculated according to SectionR403.7.1.2.1 Heat pumps
R403.7.1.1, and the heat pump total cooling capacity shall not be more than 1.15 times greater than the design cooling load even if
the design heating load is 1.15 times greater than the design cooling load.
Electric resistance furnaces shall be sized within 4 kW of the designR403.7.1.2.2 Electric resistance furnaces.
requirements calculated according to the procedure selected in Section R403.7.1
The capacity of fossil fuel heating equipment with natural draft atmospheric burnersR403.7.1.2.3 Fossil fuel heating equipment.
shall not be less than the design load calculated in accordance with Section R403.7.1.
Residences requiring excess cooling or heating equipment capacity on anR403.7.1.3 Extra capacity required for special occasions.
intermittent basis, such as anticipated additional loads caused by major entertainment events, shall have equipment sized or controlled to
prevent continuous space cooling or heating within that space by one or more of the following options:
1. A separate cooling or heating system is utilized to provide cooling or heating to the major entertainment areas.
2. A variable capacity system sized for optimum performance during base load periods is utilized.
Systems serving multiple dwelling units shall comply with SectionsR403.8 Systems serving multiple dwelling units (Mandatory).
Snow- and ice-melting systems, supplied through energy service to the building,R403.9 Snow melt and ice system controls (Mandatory).
shall include automatic controls capable of shutting off the systemw hen the pavement temperature is above 50°F (10°C), and no
precipitation is falling and an automatic or manual control that w ill allow shutoff when the outdoor temperature is above 40°F (4.8°C).
The energy consumption of pools and permanent spasR403.10 Pools and permanent spa energy consumption (Mandatory).
shall be in accordance with Sections R403.10.1 through R403.10.5.
The electric power to heaters shall be controlled by a readily accessible on-off switch that is anR403.10.1 Heaters.
integral part of the heater mounted on the exterior of the heater, or external to and within 3 feet (914 mm) of the heater. Operation
of such switch shall not change the setting of the heater thermostat. Such switches shall be in addition to a circuit breaker for the
power to the heater. Gas-fired heaters shall not be equipped with continuously burning ignition pilots.
Time switches or other control methods that can automatically turn off and on according to a preset scheduleR403.10.2 Time switches.
shall be installed for heaters and pump motors. Heaters and pump motors that have built-in time switches shall be in compliance with this
section.
Exceptions:
1. Where public health standards require 24-hour pump operations.
2. Pumps that operate solar- and waste-heat-recovery pool heating systems.
3. Where pumps are powered exclusively from on-site renewable generation.
Outdoor heated swimming pools and outdoor permanent spas shall be equipped with a vapor- retardant cover on or atR403.10.3 Covers.
the water surface or a liquid cover or other means proven to reduce heat loss.
Where more than 70 percent of the energy for heating, computed over an operation season, is from site-recoveredException:
energy, such as from a heat pump or solar energy source, covers or other vapor-retardant means shall not be required.
All gas- and oil-fired pool and spa heaters shall have a minimum thermalR403.10.4 Gas- and oil-fired pool and spa heaters.
efficiency of 82 percent for heaters manufactured on or after April 16, 2013, when tested in accordance with ANSI Z 21.56. Pool
heaters fired by natural or LP gas shall not have continuously burning pilot lights.
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 11... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
MANDATORY REQUIREMENTS - (Continued)
Heat pump pool heaters shall have a minimum COP of 4.0 when tested in accordanceR403.10.5 Heat pump pool heaters.
with AHRI 1160, Table 2, Standard Rating Conditions-Low Air Temperature. A test report from an independent laboratory is
required to verify procedure compliance. Geothermal swimming pool heat pumps are not required to meet this standard.
The energy consumption of electric-powered portable spas shall be controlled by theR403.11 Portable spas (Mandatory).
requirements of APSP-14.
SECTION R404
ELECTRICAL POWER AND LIGHTING SYSTEMS
Not less than 75 percent of the lamps in permanently installed lighting fixtures shall beR404.1 Lighting equipment (Mandatory).
high-efficacy lamps or not less than 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps.
Low-voltage lighting.Exception:
Fuel gas lighting systems shall not have continuously burning pilot lights.R404.1.1 Lighting equipment (Mandatory).
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 12... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Builder NameAvalon Beach Custom HomeProject Name:
Permit Office:Avalon by the Beach Lot #23Street:
Permit Number:St Lucie County, FL 32963City, State, Zip:
St Lucie CountyJurisdiction:Gelcorp. Industries Avalon by the Beach Custom HomeOwner:
FL, St Lucie Co IntlDesign Location:
INSULATION INSTALLATION CRITERIAAIR BARRIER CRITERIACOMPONENT
A continuous air barrier shall be installed in theGeneral
requirements Air-permeable insulation shall not be used as abuilding envelope. The exterior thermal envelope sealing material.contains a continuous barrier. Breaks or joints in the
air barrier shall be sealed.
The insulation in any dropped ceiling/soffitThe air barrier in any dropped ceiling/soffitCeiling/attic
shall be aligned with the air barrier.shall be aligned with the insulation and any
gaps in the air barrier shall be sealed.
Access openings, drop down stairs or knee wall doors
to unconditioned attics paces shall be sealed.
Cavities with corners and headers of frame wallsThe junction of the foundation and sill plateWalls
shall be insulated by completely filling the cavityshall be sealed.The junction of the top plate
with a material having a thermal resistance of R-3and the top of exterior walls shall be sealed.
per inch minimum.Knee walls shall be sealed.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier
The space between window/door jambs and framing,Windows, skylights
and skylights and framing shall be sealed.and doors
Rim joists shall be insulated.Rim joists are insulated and include an air
barrier.Rim joists
Floor framing cavity Insulation shall be installedThe air barrier shall be installed at any exposedFloors (including
to maintain permanent contact with the undersideedge of insulation.above-garage and
of subfloor decking, or floor framing cavitycantilevered floors)
insulation shall be permitted to be in contact
with the top sideof sheathing, or continuous
insulation installed on the underside of floor
framing and extends from the bottom to the top of
all perimeter floor framing members.
Where provided in lieu of floor insulation,Exposed earth in unvented crawl spaces shall beCrawl space
insulation shall be permanently attachedcovered with a Class I vapor retarder withwalls
to the crawlspace walls.overlapping joints taped.
Duct shafts, utility penetrations, and flue shaftShafts, penetrations
openings to exterior or unconditioned space shall
be sealed.
Batts in narrow cavities shall be cut to fit, orNarrow cavities
narrow cavities shall be filled by insulation that
on installation readily conforms to the available
cavity spaces.
Air sealing shall be provided between the garageGarage
and conditioned spaces.separation
Recessed light fixtures installed in theRecessed light fixtures installed in the buildingRecessed
building thermal envelope shall be air tightthermal envelope shall be sealed to the drywall.lighting
and IC rated.
Batt insulation shall be cut neatly to fit aroundPlumbing and
wiring and plumbing in exterior walls, orwiring
insulation that on installation readily conforms
to available space shall extend behind piping
and wiring.
Exterior walls adjacent to showers and tubsThe air barrier shall be installed behindShower/tub on
shall be insulated.electrical or communication boxes or air-sealedexterior wall
boxes shall be installed.
The air barrier shall be installed behindElectrical/phone
electrical or communication boxes or air-sealedbox on exterior
boxes shall be installed.walls
HVAC register boots that penetrate buildingHVAC register
thermal envelope shall be sealed to the subfloorboots
or drywall.
When required to be sealed, concealed fireConcealed
sprinklers shall only be sealed in a manner thatsprinklers
is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be
used to fill voids between fire sprinkler cover
plates and walls or ceilings.
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 13... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
FORM R405-2017
Envelope Leakage Test Report (Blower Door Test)
Residential Prescriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Permit Number:St Lucie CountyJurisdiction:
Job Information
Lot:Community:Builder:
Unit:Avalon by the BeachAddress:
32963Zip:FLState:St Lucie CountyCity:
Air Leakage Test Results Passing results must meet either the Performance, Prescriptive, or ERI Method.
The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceedingPRESCRIPTIVE METHOD 7 air changes per hour at a pressure of 0.2 inch w.g. (50 pascals) in Climate Zones 1 and 2.
The building or dwelling unit shall be tested and verified as having an air leakage rate of not
exceeding the selected ACH(50) value, as shown on FORM R405-2017 (Performance) or
R406-2017 (ERI), section labeled as Infiltration, sub-section ACH50.
PERFORMANCE or ERI METHOD
7.000ACH(50) specified on Form R405-2017-Energy Calc (Performance) or R406-2017 (ERI):
Method for calculating building volume:32824_________ x60 ÷ _______________ = _________
ACH(50)Building VolumeCFM(50)Retrieved from architectural plans
PASS Code software calculated
Field measured and calculated
When ACH(50) is less than 3, Mechanical Ventilation installation
must be verified by building department.
Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.R402.4.1.2 Testing.
(50 Pascals). Testing shall be conducted by either individuals as defined in Section 553.993(5) or (7), Florida Statues, or individuals
licensed as set forth in Section 489.105(3)(f), (g), or (i) or and approved third party. A written report of the results of the test shall be
signed by the party conducting the test and provided to the code official. Testing shall be performed at any time after creation of all
penetrations of the building thermal envelope.
During testing:
1. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
2. Dampers including exhaust, intake, makeup air, back draft and flue dampers shall be closed, but not sealed beyond intended
infiltration control measures.
3. Interior doors, if installed at the time of the test, shall be open.
4. Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.
6. Supply and return registers, if installed at the time of the test, shall be fully open.
Testing Company
Company Name: ___________________________________ Phone: __________________
I hereby verify that the above Air Leakage results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: ____________________________________ Date of Test: _____________
Printed Name of Tester: __________________________________________________________
License/Certification #: __________________________ Issuing Authority: _________________
FORM R405-2017
2021-Mar-09 16:25:22
Section 405.4.1 Compliant SoftwareRight-Energy® Florida 2017Right-Suite® Universal 2019 19.0.21 RSU25986 Page 14... Custom HVAC calcs EXP_ENERGY CALCS.new win.rup Calc = MJ8 Front Door faces: S
Duct Leakage Test Report
Residential Perscriptive, Performance or ERI Method Compliance
2017 Florida Building Code, Energy Conservation, 6th Edition
Permit Number:St Lucie CountyJurisdiction:
Job Information
Lot:Community:Builder:
Unit:Avalon by the BeachAddress:
32963Zip:FLState:St Lucie CountyCity:
Duct Leakage Test Results
cfm25 (Total)Prescriptive Method_______ cfm25System 1
To qualify as "substantially leak free" Qn Total must be less
than or equal to 0.04 if air handler unit is installed. If air handler
unit is not installed, Qn Total must be less than or equal to
0.03. This testing method meets the requirements in
accordance with Section R403.3.3.
_______ cfm25System 2
_______ cfm25System 3
Is the air handler unit installed_______ cfm25Sum of any
(<= 0.04 Qn)YESadditional systems
(<= 0.03 Qn)NOduring testing?
Total of all _______ cfm25systems
cfm25 (Out or Total)Performance / ERI Method
To qualify using this method, Qn must be not greater than the
proposed duct leakage Qn specified on Form R405-2017 or
R406-2017.
2574_________ ÷ _______________ = _________ Qn
Total Conditioned
Square Footage
Total of all
systems
Qn specified on Form R405-2017Leakage Type selected on Form
(Energy Calc) or R406-2017R405-2017 (Energy Calc) or R406-2017
FAILPASS Default Leakage
Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC380 by either
individuals as defined in Section 553.993(5) or (7), Florida Statutes, or individuals licensed as set
forth in Section 489.105(3)(f), (g) or (i), Florida Statues.
Testing Company
Company Name: ___________________________________ Phone: __________________
I hereby verify that the above duct leakage test results are in accordance with the 2017 6th Edition Florida Building Code
Energy Conservation requirements according to the compliance method selected above.
Signature of Tester: ____________________________________ Date of Test: _____________
Printed Name of Tester: __________________________________________________________
License/Certification #: __________________________ Issuing Authority: _________________
Reference Home Characteristics
Gelcorp. Industries Avalon by the Beach Custom HomeTitle: Avalon Custom HVAC calcs EXP_ENERGY CALCS.new winTMY City: FL_Vero_Beach_Muni
Avalon by the Beach Lot #23
St Lucie County, FL 32963 FLBase2017
0.084Above-grade Walls (Uo)
0.75Above-grade Wall Solar Absorptance
0.90Above-grade Wall Infared Emittance
n/aBasement Walls (Uo)
n/aAbove-grade Floors (Uo)
0.0Slab Insulation R-Value
0.030Ceilings (Uo)
0.75Roof Solar Absorptance
0.90Roof Infared Emittance
3.51Attic Vent Area (ft²)
n/aCrawlspace Vent Area (ft²)
355.30Exposed MasonryFloor Area (ft²)
2.0Carpet & Pad R-Value
40.00Door Area (ft²)
0.400Door U-Factor
39.52North Window Area (ft²)
96.53South Window Area (ft²)
96.53East Window Area (ft²)
96.53West Window Area (ft²)
0.400Window U-Factor
0.2169Window SHGC (Heating)
0.2169Window SHGC (Cooling)
7.00ACH50
109379Internal Gains * (Btu/day)
120.00Water heater gallons per day
120.00Water Heater set point temperature
0.47Water heater efficiency rating
HSPF = 8.2Labeled Heating System Rating and Efficiency
SEER = 14.0Labeled Cooling System Rating and Efficiency
0.88Air Distribution System Efficiency
ManualThermostat Type
72.0 (All hours)Heating Thermostat Settings