Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
21-00035 MEP Issue of Permit
ST. LUCIE COUNTY MORNINGSIDE LIBRARY ROOFTOP EQUIPMENT REPLACEMENT ST. LUCIE COUNTY, FLORIDA PROJECT LOCATION ISSUE HISTORY REVISION ISSUE DATE DESCRIPTION 01/29/2021 100% OWNER REVIEW 02/09/2021 ISSUE FOR PERMIT 00or 40AVOW ST. LUCIE COUNTY 2410 S.E. MORNINGSIDE BLVD. PORT ST. LUCIE, FLORIDA 34952 DRAWING LIST SHEET TITLE REVISIONS COVER CVR I COVER SHEET MECHANICAL M0.1 LEGEND, SCHED. & NOTES - MECHANICAL M1.1 ROOF AND CONTROLS PLANS - MECHANICAL M7.1 SPECIFICATIONS - MECHANICAL ELECTRICAL E0.1 LEGEND, SPECS AND NOTES - ELECTRICAL E1.1 ROOF PLANS - ELECTRICAL r N N O N O H u.l a o� O LL W SALAS O'BRIEN expect a difference I 3501 Quadrangle Boulevard, Suite 100 Orlando, Florida 32817 (d07) 380.0 00 CERT. OF AUTH. NO. 6106 o CARY A. W ILKERSON, P.E. 43167 ■ KYLE J. CARTI ER, P.E. 53269 JEFF A. KIRKMAN, P.E. 65629 O ADAM S. LEVINE, P.E. 77010 21-00035 F S BEEN ELECIRONIC4LLYSIGNEDANDSEPLEDBY ER, PE ON DATE INDICATED IN DIGITAL USING A DIGITAL SIGNATURE. PIES OF THIS DOCUMENT ARE NOT CONSIDERED S EALED AND THE SIGNATURE MUST BE VERIFIED TRONIC COPIES. Digitally signed by Kyle J Kyle J Cartier Cartier Date: 2021.02.17 10:26:04-05'00' LU a ❑ z o m w y W O LU U O 1n z 3 4a z LU 2 LU } Q Q Z m LIJ OU o z LLj U _ C/) LU � J Z D E LU O 0- 0 w w LL p w O U N N C M O a O N o d UC 0 GENERAL ROOF WORK REQUIREMENTS 1. REFER TO MECHANICAL DRAWINGS FOR LOCATIONS OF NEW ROOFTOP EQUIPMENT. 2. MAINTAIN WATERTIGHT BUILDING ENVELOPE AT ALL TIMES DURING CONSTRUCTION. GENERAL NOTES 1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) SYSTEMS. 2. REFER TO TYPICAL DETAILS FOR ADDITIONAL INFORMATION REGARDING THE INSTALLATION OF DUCTWORK, AND EQUIPMENT. 3. THE CONTRACTOR IS EXPECTED TO ORDER MATERIALS IN SUFFICIENT TIME TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES WILL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR SUBSTITUTION OF MATERIALS. 4. THE CONTRACTOR SHALL COMPLY WITH THE 2020 FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE CODES AND STANDARDS. 5. ALL REQUESTS FOR INFORMATION (RFI'S) SUBMITTED BY THE CONTRACTOR SHALL INCLUDE A PROPOSED SOLUTION. 6. INSTALLATION OF EQUIPMENT SHALL COMPLY WITH EQUIPMENT MANUFACTURER'S INSTALLATION AND CLEARANCE REQUIREMENTS. THE CONTRACTOR SHALL VERIFY INSTALLATION CLEARANCES WILL BE MAINTAINED AND DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER PRIOR TO THE ACQUISITION OF EQUIPMENT. 7. THE CONTRACTOR SHALL COORDINATE THE WORK OF THE DIFFERENT TRADES SO THAT INTERFERENCE BETWEEN HVAC, PIPING, EQUIPMENT, STRUCTURAL, AND ELECTRICAL WORK WILL BE AVOIDED. ALL NECESSARY OFFSETS IN DUCTWORK, PIPING, AND FITTINGS REQUIRED TO INSTALL THE WORK PROPERLY SHALL BE PROVIDED COMPLETE IN PLACE AT NO ADDITIONAL COST TO THE OWNER. 8. THE CONTRACTOR IS RESPONSIBLE TO REPAIR, AT HIS COST, ANY DAMAGED ITEMS DUE TO WORK PERFORMED. DAMAGED ITEMS SHALL BE BROUGHT BACK TO LIKE -NEW CONDITION OR REPLACED WITH ORIGINAL. 9. PROVIDE COLD GALVANIZED FINISH ON UNIT ATTACHMENT BRACKETS BEING REUSED. 10. DISCONNECT AND REINSTALL EXISTING DUCT -MOUNTED SMOKE DETECTOR IN THE SUPPLY OF THE ROOFTOP UNIT. THE UNIT SHALL SHUT DOWN UPON ACTIVATION OF THE DEVICE.. ROOFTOP UNIT SCHEDULE MARK RTU-i LOCATION ROOF MANUFACTURER BANE MODEL SAHL 2 4 NOMINAL TONS 25 EVAPORATOR FAN TOTAL AIR FLOW (CFM) OUTSIDE AIR FLOW (CFM) 11,8201 EXTERNAL STATIC PRESSURE (IN.W.G.) 2.5 DRIVE/TYPE BELT/CENT. I BHP 11.89 DX COOLING COIL TOTAL CAPACITY (MBH) 297.14 SENSIBLE CAPACITY (MBH) ENTERING AIR TEMPERATURE (DB/WB) 8P56., LEAVING AIR TEMPERATURE (DB/WB) 5 7. 5 FACE AREA (SF) 20.30 ROWS/FINS PER INCH Im ELECTRIC HEAT CAPACITY (KW) CONTROLSTEPS NO HEAT ENTERING AIR TEMPERATURE (DEG F) LEAVING AIR TEMPERATURE (DEG F) COMPRESSOR COMPRESSOR TYPE SCROLL NUMBER OF COMPRESSORS 2 RLA (EA) 22.2/19.1 CONDENSER FAN NUMBER OF FANS 3 FLA (EA) 5.4 FILTERS QUANTITY/SIZE (12)/20"X20"X2" TYPE I THROWAWAY UNIT REOUIREMENTS VOLTS/PHASE/HZ 460/3/60 MCA 71.25A MOCP 90.00A IEER 14.5 OPERATING WEIGHT (LBS) 4628.3 ACCESSORIES 1-4 NOTES 1-2 A�l�cooumico trRVYIUC IInc rULLVVVIRU) 1. SINGLE POINT POWER CONNECTION, HINGED ACCESS DOORS, OUTSIDE AIR INTAKE WEATHER HOOD AND MOTORIZED OUTSIDE AIR DAMPER INTERLOCKED WITH UNIT OPERATION. 2. 24/7 PROGRAMMABLE ZONE THERMOSTAT WITH BATTERY BACK-UP OR NON-VOLATILE MEMORY. 3. CONTRACTOR SHALL REUSE EXISTING SUPPLY SIDE DUCT SMOKE DETECTOR. 4. PROVIDE CONDENSATE DRAIN PAN OVERFLOW SWITCH. NOTES 1. MOUNT UNIT TO EXISTING ISOLATION CURB ATOP EXISTING STRUCTURAL STEEL SUPPORT. REUSE EXISTING ATTACHMENT BRACKETS AND FASTENERS. 2. FIELD COAT CONDENSING COILS WITH XXXX COATING. COATING WARRANTY SHALL BE A MINIMUM OF X YEARS. ABBREV. DESCRIPTION AC ALTERNATING CURRENT AFF ABOVE FINISHED FLOOR AFMS AIRFLOW MEASURING STATION AH AIR HANDLER AHU AIR HANDLING UNIT AMP AMPERE ANSI AMERICAN NATIONAL STANDARDS INSTITUTE ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR CONDITIONING ENGINEERS ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS AN AUDIBLENISUAL AWG AMERICAN WIRE GAUGE B BOILER BCU BLOWER COIL UNIT BDD BACKDRAFT DAMPER BHP BRAKE HORSEPOWER BLDG BUILDING BMS BUILDING MANAGEMENT SYSTEM BTU BRITISH THERMAL UNITS CFM CUBIC FEET PER MINUTE CH CHILLER CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CRAC COMPUTER ROOM AIR CONDITIONER CT COMPRESSION TANK CU CONDENSING UNIT CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY CxA COMMISSIONING AGENT D DEPTH dB DECIBEL DB DRY BULB DC DIRECT CURRENT DOC DIRECT DIGITAL CONTROL DEG F DEGREE FAHRENHEIT DIA DIAMETER DOAS DEDICATED OUTDOOR AIR SYSTEM EA EXHAUST AIR, EACH EAT ENTERING AIR TEMPERATURE ECM ELECTRICALLY COMMUTATED MOTOR EDH ELECTRIC DUCT HEATER EFF EFFICIENCY EER ENERGY EFFICIENCY RATIO EF EXHAUST FAN ESP EXTERNAL STATIC PRESSURE ETC ET CETERA EWT ENTERING WATER TEMPERATURE FA FIRE ALARM FBC FLORIDA BUILDING CODE FBC-M FLORIDA BUILDING CODE - MECHANICAL FCU FAN COIL UNIT FD FIRE DAMPER, FLOOR DRAIN FLA FULL LOAD AMPS FPM FEET PER MINUTE FPS FEET PER SECOND FRP FIBERGLASS REINFORCED PLASTIC FT FEET FT-H20 FEET OF WATER GA GAGE GAL GALLON GPD GALLONS PER DAY GPH GALLONS PER HOUR GPM GALLONS PER MINUTE H HEIGHT HB HOSE BIBB HD HUB DRAIN H-O-A HAND -OFF -AUTOMATIC HP HORSEPOWER HR HOUR HVAC HEATING, VENTILATING, AND AIR CONDITIONING HX HEAT EXCHANGER HZ HERTZ MECHANICAL ABBREVIATIONS ABBREV. DESCRIPTION IN INCH IN.W.G. INCHES OF WATER - GAUGE IPS IRON PIPE SIZE KEF KITCHEN EXHAUST FAN KSF KITCHEN SUPPLY FAN KW KILOWATT L LENGTH LAT LEAVING AIR TEMPERATURE LBS POUNDS LF LINEAR FEET LWT LEAVING WATER TEMPERATURE MAX MAXIMUM MBH THOUSAND BTU PER HOUR MCA MINIMUM CURRENT AMPACITY MIN MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MSS MANUFACTURERS STANDARDIZATION SOCIETY MVD MANUAL VOLUME DAMPER N NORTH N/A NOT APPLICABLE, NONE ASSOCIATED, NONE AVAILABLE NC NOISE CRITERIA, NORMALLY CLOSED NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NO NUMBER, NORMALLY OPEN NTS NOT TO SCALE OA OUTDOOR AIR OAT OUTDOOR AIR TEMPERATURE OD OUTER DIAMETER OZ OUNCE P PUMP PH PHASE PPM PARTS PER MILLION PRESS PRESSURE PRV PRESS RELIEF VALVE, PRESS REGULATING VALVE PSI POUNDS PER SQUARE INCH PSI -A POUNDS PER SQUARE INCH - ABSOLUTE PSI-G POUNDS PER SQUARE INCH - GAUGE PVC POLYVINYL CHLORIDE QTY QUANTITY RA RETURN AIR RH RELATIVE HUMIDITY RLA RUNNING LOAD AMPS RM ROOM RPM REVOLUTIONS PER MINUTE RPZ REDUCED PRESSURE ZONE RTU ROOFTOP UNIT SA SUPPLYAIR SD SMOKE DETECTOR SEER SEASONAL ENERGY EFFICIENCY RATIO SF SQUARE FEET SC SHADING COEFFICIENT SHGC SOLAR HEAT GAIN COEFFICIENT SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION SP STATIC PRESSURE STD STANDARD T THERMOSTAT TSP TOTAL STATIC PRESSURE TYP TYPICAL UH UNIT HEATER UL UNDERWRITERS LABORATORIES LINO UNLESS NOTED OTHERWISE V VOLTAGE VA VOLTAMPERE VAV VARIABLE AIR VOLUME VFD VARIABLE FREQUENCY DRIVE W WATT, WIDTH WB WET BULB WWF WELDED WIRE FABRIC YR YEAR CONTROL SYSTEM LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION CONTROLS EQUIPMENT CS CURRENT SWITCH O FAN - CENTRIFUGAL SD SMOKE DETECTOR TS TEMPERATURE SENSOR VC COOLINGCOIL AI ANALOG INPUT AO ANALOG OUTPUT OPPOSED BLADE DAMPER BI BINARY INPUT PARALLEL BLADE DAMPER BO BINARY OUTPUT O POINT DESCRIPTION -REFER AIR FILTER SECTION TO DIRECT DIGITAL CONTROLS (DDC) POINTS SCHEDULE TU EXISTING TERMINAL ABBREVIATIONS UNIT (VAV BOX) E.C. ELECTRICAL CONTRACTOR N.C. NORMALLY CLOSED TS N.O. NORMALLY OPEN DUCT -MOUNTED SENSOR EA EXHAUSTAIR F/A FIRE ALARM OA OUTDOOR AIR RA RETURN AIR SA SUPPLY AIR TU TERMINAL UNIT UVL ULTRA -VIOLET LIGHT VAV VARIABLE AIR VOLUME MECHANICAL LEGEND SYMBOL DESCRIPTION GENERAL HVAC 24x12 RECTANGULAR DUCT, FIRST FIGURE IS DIMENSION OF SIDE SHOWN (IN INCHES) 24x12PJ FLAT OVAL DUCT, FIRST FIGURE IS DIMENSION OF SIDE SHOWN (IN INCHES) 240 ROUND DUCT, DIAMETER SHOWN (IN INCHES) FGSUPPLY DUCT RISER RETURN DUCT RISER EXHAUST DUCT RISER SUPPLY DUCT DOWN RETURN DUCT DOWN EXHAUST DUCT DOWN DUCT CONTINUES MVD MANUAL VOLUME DAMPER BDD BACKDRAFT DAMPER M MOTORIZED DAMPER FD FIRE DAMPER (HORIZONTAL) FD FIRE DAMPER (VERTICAL) sD SMOKE DAMPER (HORIZONTAL) SD SMOKE DAMPER (VERTICAL) F/SD COMBINATION FIRE/SMOKE DAMPER (HORIZONTAL) F/SD COMBINATION FIRE/SMOKE DAMPER (VERTICAL) s DUCT -MOUNTED SMOKE DETECTOR ® DUCT ACCESS DOOR - TOP ® DUCT ACCESS DOOR - BOTTOM DUCT ACCESS DOOR - SIDE a w O Ln pf DUCT RISE OR DROP IN DIRECTION OF FLOW SQUARE TO ROUND DUCT TRANSITION TERMINAL UNIT CROSS HATCHED AREA = MINIMUM CLEARANCE FOR HEATER ACCESS. MAINTAIN CLEARANCE. SINGLE LINE DUCTWORK BELL MOUTH TAP W/MVD MVD HAS REMOTE CONTROL IN RIGID CEILING FLEXIBLE DUCT SUPPLY OUTLET (SEE AIR DEVICE SCHEDULE) zRETURN INLET (SEE AIR DEVICE SCHEDULE) zEXHAUST INLET (SEE AIR DEVICE SCHEDULE) LINEAR DIFFUSER ELBOW W/TURNING VANES ROTATING BEACON LIGHT co CARBON MONOXIDE SENSOR co CARBON DIOXIDE SENSOR No NITROGEN OXIDE SENSOR ® N SMOKE DETECTOR AANNUNCIATOR Q HUMIDISTAT ® REFRIGERANT SENSOR Q DUCT SMOKE DETECTOR Q THERMOSTAT rs TEMPERATURE SENSOR NOTES 1. THIS IS A GENERAL COMPILATION OF SYMBOLS AND NOT ALL SYMBOLS SHOWN MAY BE USED ON THE CONTRACT DRAWINGS. 2. SCREENED SYMBOLS OR TEXT (EXAMPLE: AHU) INDICATE EXISTING EQUIPMENT OR CONDITIONS. 3. SCREENED AND DASHED AND LINES INDICATE LINES HIDDEN IN VIEW. CS -A SS/12X6 MARK -TYPE OR (INxIN) AIR DEVICE TAG 100 CFM OR 100 CFM AIRFLOW (CFM) UC UNDER CUT DOOR 100 AIR FLOW AMOUNT (CFM) OR O1 D1 REFERENCE NOTE X DETAIL NUMBER X-X SHEET DETAIL APPEARS TYPE OF EQUIPMENT X EQUIPMENT NUMBER X SECTION NUMBER X-X SHEET SECTION APPEARS Q POINT OF DISCONNECTION POINT OF CONNECTION SYMBOL DESCRIPTIONIN r 0 N 0 N 0 III�� W N� I.fr. W I SALAS O'BRIEN expect a difference 3501 Ouadrengla Boulevard, Suite 100 Orlando, Florida 32817 (407) 380-0400 CERT. OF AUTH. NO. 6106 o GARV A. W ILKERSON, P.E. 43167 ■ KYLE J. CARTIER, P.E. 53289 O JEFF A. KIRKMAN, P.E. 65829 o gDAM S. LEVINE, P.E. 77010 21-00035 THIS fIEM HAS BEEN aECTRONICPLLYSIGNED AND KYLEJ.CARTIER, PEON DATE INDICATED IN DIGITAL SIGNATURE USING A DIGITAL 81CitANRE. BIGNED PND SEAIED PND THE SIGNATURE MUST BE VERIFIED ON ANY B.ECTRON IC COPIES. Digitally signed by Kyle Kyle J Cartier J Cartier Date: 2021.02.17 10:26:32-05'00'UU LL D w Q ❑ z o rn w U Y w U x U O z � ga J Q U_ Z 2 w U w W } ' z L.1_ m wwN L.L w � W z O w Z U C� a-_ CONTROL POINTS LIST CONTROL POINT INPUT OUTPUT ANALOG I BINARY I ANALOG I BINARY SUPPLY FAN MOTOR VARIABLE SPEED DRIVE* FAN START/STOP FAN STATUS BMS COMMUNICATION CARD X X COOLING COIL LEAVING AIR TEMPERATURE (DEG F) X SMOKE DETECTOR SHUTDOWN X NOTES: * DENOTES FULL COMMUNICATION WITH DEVICE VIA COMMUNICATION CARD COORDINATED WITH BMS SYSTEM CONTROL SCHEMATIC TO FAN VFD FOR EXISTING XISTING SMOKE DETECTOR TO BE OA Al REUSED. TS SD RA / O SA VFD TO REMAINING EXISTING AIR BC TU TU TERMINAL UNITS POWER SA SA EXISTING AIR TERMINAL UNITS, TYPICAL. VARIABLE AIR VOLUME AHU WITH TERMINAL UNITS CONTROLS *NOT TO SCALE 7 8 8 8 8 8 8 0000 0 8 REFERENCE NOTES - NEW 1D MOUNT NEW ROOFTOP UNIT ON EXISTING PLENUM CURB AND STEEL DUNNAGE. NEW UNIT DIMENSIONS ARE EQUAL TO EXISTING UNIT DIMENSIONS. NEW UNIT INSTALLED WEIGHT IS APPROXIMATELY 250 LBS. HEAVIER THAN EXISTING UNIT. CONTRACTOR TO REUSE EXISTING ATTACHMENT BRACKETS, BRACKET SPACING, AND BOLT PATTERNS. O CONNECT SUPPLY AIR PORTION OF EXISTING PLENUM CURB TO NEW ROOFTOP UNIT SUPPLY AIR OPENING. CONTRACTOR SHALL RECONNECT EXISTING SUPPLY SIDE DUCT SMOKE DETECTOR AS REQUIRED FOR PROPER SHUT -DOWN OPERATION. O CONNECT RETURN AIR PORTION OF EXISTING PLENUM CURB TO NEW ROOFTOP UNIT RETURN AIR OPENING. ® CONNECT EXISTING ROOFTOP CONDENSATE PIPING TO NEW ROOFTOP UNIT CONDENSATE DRAINS (1 ON EACH SIDE OF ROOFTOP UNIT). APPLY UV RESISTANT COATING TO ENTIRE LENGTH OF EXISTING CONDENSATE PIPING. O5 EXISTING STEEL DUNNAGE TO BE REUSED. PRIOR TO INSTALLATION OF NEW ROOFTOP UNIT, CONTRACTOR TO SCRAPE EXISTING FINISH AND APPLY NEW (XXX) COATING TO ENTIRE STEEL SUPPORT. © EXISTING PLENUM CURB WITH INTEGRAL VIBRATION ISOLATION TO BE REUSED. O EXISTING ROOFTOP UNIT STRUCTURAL ATTACHMENT BRACKET TO BE REUSED, TYPICAL (3 EACH SIDE - TOTAL 12). PRIOR TO INSTALLATION OF NEW ROOFTOP UNIT, CONTRACTOR TO APPLY NEW COLD GALVANIZING FINISH TO ALL ATTACHMENT BRACKETS. ® EXISTING ROOFTOP UNIT ATTACHMENT HARDWARE INTENDED FOR REUSE. EACH OF THE 12 ATTACHMENTS BRACKETS (3 EACH SIDE OF UNIT) UTILIZES (6) GRADE 8 GALVANIZED BOLTS AND (14) GALVANIZED #8 SELF -TAPPING TEK FASTENERS. O INSTALL NEW CONTROL END DEVICES, COORDINATE WITH CONTROLS CONTRACTOR. IId 4ml _M�IMIIIW_ftw� EXISTING RETURN DUCTWORK TO REMAIN. UNIT ELEVATION - MECHANICAL M1.1 NTS r2_-� ROOF PLAN - NEW - MECHANICAL M1.1 1/8"=1'-0" REFERENCE NOTES - DEMOLITION D1 DISCONNECT EXISTING ROOFTOP UNIT FROM STEEL ATTACHMENT POINTS AND REMOVE UNIT. COORDINATE DISPOSAL/SALVAGE REQUIREMENTS WITH OWNER. CONTRACTOR TO PREPARE EXISTING STEEL DUNNAGE AND EXISTING ATTACHMENT BRACKETS FOR SPECIFIED COATINGS/FINISHES REQUIRED FOR REUSE. D2 DISCONNECT EXISTING ROOFTOP UNIT FROM EXISTING CONDENSATE PIPING (ONE CONNECTION ON EACH SIDE OF UNIT). D3 DISCONNECT EXISTING SUPPLY DUCT FLEX CONNECTION FROM PLENUM CURB. EXISTING PLENUM CURB TO REMAIN. ® DISCONNECT EXISTING RETURN DUCT FLEX CONNECTION FROM PLENUM CURB. EXISTING PLENUM CURB TO REMAIN. D5 EXISTING OVERFLOW ROOF DRAIN TO REMAIN. D6 EXISTING ROOF DRAIN AND EXISTING CONDENSATE PIPING TO REMAIN. CONTRACTOR TO PREPARE EXISTING CONDENSATE PIPING FOR SPECIFIED COATING/FINISH REQUIRED FOR REUSE. D7 EXISTING ROOF ACCESS HATCH TO REMAIN. DB REMOVE EXISTING CONTROL END DEVICES, COORDINATE WITH CONTROLS CONTRACTOR. EXISTING ROOF AND TU PARAPET WALLS, 1 TYPICAL. EXISTING SUPPLY DUCTWORKTO REMAIN. ROOF PLAN - DEMOLITION - MECHANICAL 1 /8"=V-0" r N N \ O N 0 SALAS O'BRIEN expect a diff. r e a c. 3501 Ouad—gle Boulevard, Suite 100 Orlando, Florida 32817 (407) 380M00 CERT. OF AUTH. NO. 6106 ■ GARY A. W ILKERSON, P.E. 43167 ■ KYLE J. CARTIER, P.E. 53269 ■ JEFF A. KIRKMAN, P.E. 65629 o ADAM S. LEVINE, P.E. 77010 21-00035 THIS f IEM HAS BEEN ELECTRONICALLY SIGNED AND KYLE J. CARTER PE ON DATE INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE. SIGNED AND SEALED AND THE SIGNATURE NUST BE VERIFIED ON ANY ELECTRONIC COPIES. Digitally signed by Kyle Kyle J Cartier J Cartier Date: 2021.02.17 10:26:49-05'00' w ❑ z O D) w Y Y LU 2 U O Hn z 3 ga J Q U_ Z 2 U �- w w ' w r �./ / 00 W QZ m J O U J 0 Z J w — w O U J (D Z a F �/ O 0 � a- O O LL U °o Z LL O O N N M O O a O N ■ m ❑ ci 0 t to 230000 - GENERAL REQUIREMENTS 1.1 GENERAL A. THE TERM "OWNER" SHALL REFER TO ST. LUCIE COUNTY FOR THIS PROJECT. B. THE TERM "DESIGN TEAM" SHALL REFER TO SALAS O'BRIEN FOR THIS PROJECT. C. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THE CONTRACT. THESE ARE NOT INSTALLATION DRAWINGS. DO NOT SCALE THE DRAWINGS. CONSULT THE ARCHITECTURAL DRAWINGS AND DETAILS FOR THE EXACT LOCATION OF STRUCTURE AND EQUIPMENT. D. ALL WORK SHALL COMPLY WITH THE 2020 FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE CODES, STANDARDS, AND THE RECOMMENDATIONS OF NFPA AND UL. E. THE CONTRACTOR GUARANTEES BY ACCEPTANCE OF THE CONTRACT THAT ALL WORK SHALL BE GUARANTEED AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE YEAR AFTER RECEIPT OF FINAL PAYMENT. ALL WORK DEEMED UNSATISFACTORY BY THE DESIGN TEAM, INCLUDING DAMAGE TO EXISTING FINISHES, SHALL BE CORRECTED AT NO COST TO THE OWNER OR DESIGN TEAM. THE CONTRACTOR SHALL SERVICE AND ADJUST ALL EQUIPMENT AS DIRECTED AND AS REQUIRED DURING THE ONE-YEAR GUARANTEE PERIOD AND ALL NECESSARY PARTS SHALL BE PROVIDED AT NO COST TO THE OWNER OR DESIGN TEAM. F. ALL MATERIALS SHALL BE NEW, THE BEST OF THEIR RESPECTIVE KINDS, SUITABLE FOR THE CONDITIONS AND DUTIES IMPOSED ON THEM AT THE BUILDING AND SHALL BE OF REPUTABLE MANUFACTURERS. G. THOROUGHLY CLEAN ALL EXPOSED SURFACES OF EQUIPMENT AND MATERIAL AND LEAVE IN A NEAT, CLEAN CONDITION. RESTORE AND TOUCH-UP FACTORY FINISHES WHICH WERE DAMAGED IN THE PERFORMANCE OF THE WORK. H. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS AND CERTIFICATES. I. THE CONTRACTOR SHALL FIELD -VERIFY ALL SITE CONDITIONS AND NOTIFY THE DESIGN TEAM OF ANY DISCREPANCIES, OMISSIONS, AND/OR ANY OTHER CONFLICTS OR IRREGULARITIES PRIOR TO THE COMMENCEMENT OF ANY WORK. 1.2 EXISTING CONDITIONS A. WHEN WORKING IN AND AROUND THE BUILDING, EXTREME CARE SHALL BE EXERCISED WITH REGARD TO PROTECTION OF THE EXISTING STRUCTURE AND MECHANICAL SYSTEMS. REPAIR OR REPLACE, TO THE SATISFACTION OF THE DESIGN TEAM, ANY EXISTING WORK DAMAGED IN THE PERFORMANCE OF THE NEW WORK. B. THE CONTRACTOR SHALL THOROUGHLY EXAMINE PREMISES AND OBSERVE ALL CONDITIONS UNDER WHICH THE WORK WILL BE PERFORMED. NO ALLOWANCE WILL BE MADE FOR ERRORS OR NEGLIGENCE IN THIS RESPECT. C. PERFORM ALL CUTTING AND PATCHING ASSOCIATED WITH THE NEW WORK. STRUCTURAL MEMBERS SHALL NOT BE CUT. PATCHING SHALL MATCH EXISTING ADJACENT SURFACES AS TO MATERIAL, TEXTURE, COLOR, AND QUALITY. UNDER NO CIRCUMSTANCES SHALL WATERPROOFING BE DAMAGED OR PENETRATED. SHOULD CONDITIONS ARISE WHICH INDICATE SUCH IS NECESSARY, NOTIFY THE DESIGN TEAM. 1.3 STANDARD OF CARE A. THIS PROJECT OCCURS IN AN EXISTING BUILDING AND THE CONTRACTOR SHALL, AT A MINIMUM, BE HELD TO THE FOLLOWING STANDARDS OF CARE: 1. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER TO ENSURE THAT ALL TOUCH-UP PAINT USED IN THE COURSE OF WORK MATCHES THE COLOR, FINISH, AND QUALITY OF THE EXISTING PAINT. 2. DEFICIENCIES FOUND IN EXISTING RATED -ASSEMBLY PENETRATIONS DURING THE COURSE OF CONSTRUCTION SHALL BE REPORTED TO THE OWNER. 1.4 PROTECTION A. SPECIAL CARE SHALL BE TAKEN FOR THE PROTECTION OF EQUIPMENT FURNISHED. EQUIPMENT AND MATERIAL SHALL BE COMPLETELY PROTECTED FROM WEATHER ELEMENTS, PAINTING, PLASTER, ETC., UNTIL THE PROJECT IS COMPLETED. DAMAGE SUCH AS RUST, PAINT, SCRATCHES, ETC., SHALL BE REPAIRED AS REQUIRED TO RESTORE EQUIPMENT AND SUPPLIES TO ORIGINAL INTEGRITY. B. WHERE INSTALLATION OR CONNECTION OF EQUIPMENT REQUIRES WORK IN AREAS PREVIOUSLY FINISHED BY OTHER CONTRACTORS, THE AREA SHALL BE PROTECTED AND NOT ALTERED OR OTHERWISE DAMAGED DURING THE COURSE OF THE SAID WORK. CONTRACTOR SHALL PROCURE THE SERVICES OF THE ORIGINAL CONTRACTORS FOR THE REPAIRING AND REFINISHING THE DAMAGED AREAS THEREOF. C. PROVIDE OFF -SITE STORAGE AND PROTECTION WHEN SITE DOES NOT PERMIT ON -SITE STORAGE OR PROTECTION. D. ADDITIONAL EQUIPMENT, PIPE, AND DUCTWORK PROTECTION DURING CONSTRUCTION 1. COVER PRODUCTS SUBJECT TO DETERIORATION OR DAMAGE WITH IMPERVIOUS SHEET COVERING. PROVIDE VENTILATION TO AVOID CONDENSATION. 2. KEEP OPEN ENDS OF AIR MOVING EQUIPMENT FREE FROM DUST AND DIRT. PROTECT OPENINGS WITH IMPERVIOUS SHEET COVERINGS. 3. KEEP OPEN ENDS OF PIPE FREE FROM SCALE AND DIRT. PROTECT OPEN ENDS WITH TEMPORARY PLUGS OR CAPS. 4. KEEP OPEN ENDS OF DUCTWORK FREE FROM DUST AND DIRT. PROTECT OPEN ENDS WITH IMPERVIOUS SHEET COVERINGS. E. PROVIDE GUARDS FOR BELT -DRIVEN EQUIPMENT AND AT CHAINS, GEARS, COUPLINGS, KEYS, PROJECTING SET SCREWS AND OTHER ROTATING OR MOVING PARTS. BELT GUARDS TO ENCLOSE BOTH PULLEYS AND BELTS ON EXPOSED SIDES. PROVIDE COUPLING GUARDS ON DIRECT CONNECTED EQUIPMENT. DESIGN AND MANUFACTURE GUARDS FOR EASY REMOVAL FOR SERVICE AND TO COMPLY WITH UL AND OSHA REQUIREMENTS. PROVIDE GUARDS SUPPLIED BY THE SAME MANUFACTURER OF THE SAID EQUIPMENT WHENEVER AVAILABLE. 1.5 WELDING A. ALL WELDING SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY (AWS) "STRUCTURAL WELDING CODE - STEEL". fl �:t ♦ ;ZiIU �TiTN7 :11 A. GENERAL 1. REFERENCE CURRENT ROOFING WARRANTY WHEN MAKING ANY NEW ROOF MEMBRANE PENETRATIONS. COORDINATE ALL REPAIRS OF EXISTING ROOFING TO INSURE EXISTING WARRANTY IS MAINTAINED. NOTIFY OWNER IMMEDIATELY IF ANY PROPOSED WORK VOIDS CURRENT WARRANTIES. 2. MAINTAIN WATER -TIGHT BUILDING ENVELOPE AT ALL TIMES DURING CONSTRUCTION. 1.6 ELECTRICAL COORDINATION A. THE EQUIPMENT INDICATED ON THE DRAWINGS HAS BEEN COORDINATED WITH THE ELECTRICAL SYSTEM DESIGN. IF THIS CONTRACTOR SELECTS TO USE ALTERNATE EQUIPMENT, THEY SHALL BE RESPONSIBLE FOR ALL COORDINATION WITH THE ELECTRICAL ENGINEER AND SHALL BEAR ANY ADDED EXPENSE TO THE ELECTRICAL CONTRACTOR AND THE DESIGN TEAM RESULTING FROM SUCH ALTERNATE SELECTION. 1.7 SUBMITTALS A. ALL SUBMITTALS SHALL BE DELIVERED IN PORTABLE DOCUMENT FORMAT (PDF). SUBMITTALS SHALL BE ANNOTATED TO CLEARLY INDICATE THE EQUIPMENT INTENDED FOR USE. SUBMITTALS THAT ARE NOT ANNOTATED WILL BE REJECTED WITHOUT REVIEW. B. CONSTRUCTION SCHEDULE 1. INCLUDE, AT A MINIMUM, MAJOR EQUIPMENT ORDERING DATES, CONSTRUCTION MILESTONES, DURATION OF MAJOR TASKS (I.E. DEMOLITION, AHU INSTALLATION, ETC.), TESTING, COMMISSIONING, AND TRAINING. C. WELDING METHODS AND CERTIFICATES D. PRODUCT DATA 1. PROVIDE MANUFACTURER'S CATALOG SHEET FOR EACH PIECE OF EQUIPMENT INDICATING DIMENSIONS, WEIGHTS, CAPACITIES, SPECIALTIES, ACCESSORIES, ELECTRICAL REQUIREMENTS, AND WIRING DIAGRAMS. 2. PROVIDE SUBMITTAL FOR CONTROLS, CONTROL DIAGRAMS, AND SEQUENCE OF OPERATIONS. F. OPERATION AND MAINTENANCE MANUALS 5. THE CONTRACTOR SHALL FURNISH AN ELECTRONIC COPY OF THE OPERATION AND MAINTENANCE MANUALS FOR REVIEW BY THE DESIGN TEAM BEFORE PROVIDING TO THE OWNER. 6. THE FINISHED PRODUCT SHALL BE A SINGLE ELECTRONIC FILE DELIVERED VIA USB FLASH DRIVE WITH THE FOLLOWING BOOKMARKS AND CORRESPONDING INFORMATION: a. COVER SHEET b. INDEX c. RECOMMENDED MAINTENANCE SCHEDULE d. COMPLETE SET OF APPROVED SHOP DRAWINGS e. EQUIPMENT OPERATION AND MAINTENANCE MANUALS f. CONTROL DIAGRAMS AND SEQUENCE OF OPERATIONS g. EQUIPMENT WARRANTIES 3. PROVIDE THE OWNER WITH (2) COMPLETE COPIES ON SEPARATE USB FLASH DRIVES FOLLOWING REVIEW BY THE DESIGN TEAM. G. RECORD DRAWINGS 1. THE CONTRACTOR SHALL KEEP ACCURATE RECORDS OF ALL DEVIATIONS IN WORK, AS ACTUALLY INSTALLED, FROM WORK INDICATED ON CONTRACT DOCUMENTS. 2. WHEN WORK IS COMPLETE, THE CONTRACTOR SHALL MINIMALLY PROVIDE (1) COMPLETE "RECORD" SET OF BONDS AND ONE (1) USB FLASH DRIVE WITH AN ELECTRONIC COPY (PDF) OF THE RECORD DRAWINGS. THE CONTRACTOR MAY OBTAIN ELECTRONIC COPIES OF THE BACKGROUNDS THROUGH THE DESIGN TEAM FOR ALTERATION. THE CONTRACTOR SHALL PAY ALL FEES FOR THE DRAWING REPRODUCTION THERETO. CONTRACTOR SHALL CERTIFY THE ACCURACY OF EACH DRAWING BY ENDORSEMENT AND SIGNATURE THEREON. H. CERTIFICATION OF SYSTEMS 1. PRIOR TO COMPLETION OF THE CONTRACT AND FINAL ACCEPTANCE OF THE FACILITY, THE CONTRACTOR SHALL PRESENT A CERTIFICATE TO THE OWNER AND DESIGN TEAM CONFIRMING THAT ALL SYSTEMS HAVE BEEN TESTED AND THAT THE INSTALLATION AND PERFORMANCE OF THESE SYSTEMS CONFORM TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. THE CERTIFICATE SHALL ALSO DOCUMENT THAT ALL CONTROL SYSTEMS HAVE BEEN TESTED, ARE OPERATING WITHIN THE REQUIRED TOLERANCES, AND THAT THE ENTIRE CONTROL SYSTEM INSTALLATION CONFORMS TO THE REQUIREMENTS OF THE CONTRACT DOCUMENTS. I. CLOSEOUT SUBMITTALS 1. THE PROJECT WILL NOT BE FINALIZED UNTIL THE FOLLOWING ITEMS ARE RECEIVED, REVIEWED, AND APPROVED BY THE DESIGN TEAM. a. OPERATION AND MAINTENANCE MANUALS b. CONTROLS FIELD VERIFICATION REPORT c. CONTROLS TRAINING REPORT d. RECORD DRAWINGS e. CERTIFICATION OF SYSTEMS 230500 - COMMON WORK RESULTS FOR HVAC 1.1 GENERAL A. SUMMARY 1. SECTION INCLUDES: a. HVAC DEMOLITION b. EQUIPMENT INSTALLATION REQUIREMENTS COMMON TO EQUIPMENT SECTIONS 1.2 EXECUTION A. HVAC DEMOLITION 1. DISCONNECT DEMOLISH AND REMOVE HVAC SYSTEMS EQUIPMENT AND COMPONENTS INDICATED TO BE REMOVED. a. EQUIPMENT TO BE REMOVED: DISCONNECT AND CAP SERVICES AND REMOVE EQUIPMENT. 2. IF PIPE, INSULATION, OR EQUIPMENT TO REMAIN IS DAMAGED IN APPEARANCE OR IS UNSERVICEABLE, REMOVE DAMAGED OR UNSERVICEABLE PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY. B. EQUIPMENT INSTALLATION - COMMON REQUIREMENTS 1. INSTALL EQUIPMENT TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING HEIGHTS ARE NOT INDICATED. 2. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED. 3. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF DISCONNECTING, WITH MINIMUM INTERFERENCE TO OTHER INSTALLATIONS. EXTEND GREASE FITTINGS TO ACCESSIBLE LOCATIONS. 4. INSTALL EQUIPMENT TO ALLOW RIGHT OF WAY FOR PIPING INSTALLED AT REQUIRED SLOPE. 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 1.1 GENERAL A. SUMMARY 1. SECTION INCLUDES: a. EQUIPMENT SUPPORTS B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE AN ADEQUATE EQUIPMENT SUSPENSION SYSTEM IN ACCORDANCE WITH RECOGNIZED ENGINEERING PRACTICES, USING STANDARD, COMMERCIALLY ACCEPTED SUSPENSION EQUIPMENT. 1.2 EXECUTION A. PAINTING 1. TOUCHUP: CLEAN FIELD WELDS AND ABRADED AREAS OF SHOP PAINT. PAINT EXPOSED AREAS IMMEDIATELY AFTER ERECTING HANGERS AND SUPPORTS. USE SAME MATERIALS AS USED FOR SHOP PAINTING. COMPLY WITH SSPC-PA 1 REQUIREMENTS FOR TOUCHING UP FIELD -PAINTED SURFACES. a. APPLY PAINT BY BRUSH OR SPRAY TO PROVIDE A MINIMUM DRY FILM THICKNESS OF 2.0 MILS. 2. GALVANIZED SURFACES: CLEAN WELDS, BOLTED CONNECTIONS, CUTS, AND ABRADED AREAS AND APPLY GALVANIZING -REPAIR PAINT TO COMPLY WITH ASTM A 780. 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 1.1 GENERAL A. SUMMARY 1. SECTION INCLUDES: a. EQUIPMENT LABELS 1.2 PRODUCTS AND EXECUTION A. NAMEPLATES: LAMINATED THREE -LAYER PLASTIC WITH ENGRAVED LETTERS. 1. INSTALLATION: DEGREASE AND CLEAN SURFACES TO RECEIVE ADHESIVE FOR IDENTIFICATION MATERIALS. INSTALL PLASTIC NAMEPLATES WITH CORROSIVE -RESISTANT MECHANICAL FASTENERS, OR ADHESIVE. APPLY WITH SUFFICIENT ADHESIVE TO ENSURE PERMANENT ADHESION AND SEAL WITH CLEAR LACQUER. 2. SCHEDULE: a. HVAC EQUIPMENT (WHITE LETTERS ON BLACK BACKGROUND): INDICATE EQUIPMENT MARK CORRESPONDING WITH THE CONTRACT DOCUMENTS. b. CONTROL PANELS (WHITE LETTERS ON BLACK BACKGROUND): INDICATE MARK CORRESPONDING WITH THE SUBMITTED AND APPROVED CONTROL DRAWINGS. r 0 N 0 N 0 N� 1••1� LU A O LL W /D I L "I LJ SALAS O'BRIEN expect a difference I 3601 Ouadraegle Boulevard, Suite 100 Orlando, Florida 32817 (407) 380-0400 CERT. OF ALITH. NO. 6106 0 GARY A. W ILKERSON, P.E. 43167 ■ KYLE J. CARTIER, P.E. 53269 0 JEFF A. KIRKMAN, P.E. 65629 o ADAM S. LEVINE, P.E. 77010 21-00035 THIS fIEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED KYLEJ.CARTIER, PE ON DATE INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE. SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES. Digitally signed by Kyle Kyle J Cartier] Cartier Date: 2021.02.17 10:27:11-05'00' w ❑ z U 0 w Of y Y U x U 0 to z ga ❑ z w J �Q w U_ Q Z zmN Q = O U J w z C) w � w 75 z z 1 V! U) Q Lu Z 0- o O LL 0 ULL CU W 0- v / N N m M O O a O N d 0 C 0 C N L POWER DUPLEX RECEPTACLE, 20 AMP, WITH FLUSH WALL OUTLET BOX. a, f DOUBLE DUPLEX RECEPTACLE, 20 AMPS EACH, WITH TWO -GANG FLUSH WALL OUTLET BOX. a, f (W WPG WEATHERPROOF GFI DUPLEX RECEPTACLE, 20 AMP, WITH FLUSH WALL OUTLET BOX AND STAINLESS STEEL WEATHERPROOF COVER. a, f J SURFACE MOUNTED JUNCTION BOX AND BLANK PLATE, WALL MTD. OR MTD. TO CEILING/STRUCTURE AS INDICATED. e, f, h, i J WP SURFACE MOUNTED WEATHERPROOF JUNCTION BOX AND BLANK PLATE, WALL MTD. OR MTD. TO CEILING/STRUCTURE AS INDICATED. f, h, i Q FLUSH WALL JUNCTION BOX AND BLANK PLATE. f Eli DISCONNECT SWITCH. REFER TO EQUIPMENT FEEDER SCHEDULE FOR REQUIREMENTS (I.E. SIZE, FUSED, NON -FUSED, ETC.) h' / © CONTROL AND/OR POWER EQUIPMENT CONNECTION. j 120/208V BRANCH CIRCUIT PANELBOARD, FLUSH MOUNTED j 120/208V BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED h, j BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN WALL. MINIMUM TWO CONDUCTORS PLUS GROUND. REFER TO SPECIFICATIONS AND EQUIPMENT FEEDER SCHEDULE FOR CONDUCTOR REQUIREMENTS. ARROWS INDICATE CIRCUIT CONNECTIONS AND HOMERUNS TO PANEL AS INDICATED ON PLANS. TYPICAL FOR ALL RACEWAY TYPES, U.O.N. \ BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR UNDERGROUND BRANCH CIRCUIT CONDUIT EXPOSED CONDUIT CONTINUED ] CONDUIT CAPPED OFF CONDUIT RUN UP - CONDUIT RUN DOWN SYMBOL LEGEND NOTES: 1. THE COLOR OF ALL DEVICES SHALL MATCH EXISTING. COVER PLATES COLOR SHALL BE SELECTED BY OWNER, UNLESS OTHERWISE NOTED. 2. SCREENED ELECTRICAL ITEM DENOTES EXISTING. 3. "R" BY DEVICE DENOTES EXISTING TO BE REMOVED COMPLETELY. 4. "H" BY DEVICE DENOTES DEVICE TO BE MOUNTED HORIZONTALLY. 5. ALL DIMENSIONS INDICATED ARE TO THE BOTTOM OF FIXTURE, OUTLET, OR EQUIPMENT AND SHALL BE THE DIMENSIONS USED UNLESS INDICATED OTHERWISE ON THE DRAWINGS. DIMENSIONS INDICATED ON THE DRAWINGS AND IN THE SPECIFICATIONS ARE TO THE BOTTOM OF THE FIXTURE, OUTLET, OR EQUIPMENT UNLESS INDICATED OTHERWISE. ALL MOUNTING HEIGHTS SHALL COMPLY WITH ADA REQUIREMENTS. VERIFY AND COORDINATE THE EXACT HEIGHT AND LOCATION OF ALL FIXTURES, OUTLETS, AND EQUIPMENT WITH ALL DOCUMENTS AND DISCIPLINES (I.E., ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, FIRE PROTECTION, KITCHEN EQUIPMENT, MILLWORK, ETC.) PRIOR TO ROUGH -IN; ADJUST TO MEET ALL REQUIREMENTS. 6. ALL SYMBOLS INDICATED IN THIS LEGEND MAY NOT BE USED ON THE PLANS. 7. ALL WIRING DEVICES SHALL BE PROVIDED WITH A GROUNDING TERMINAL SCREW. 8. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 9. U.O.N. = UNLESS OTHERWISE NOTED. 10. A.H.J. = AUTHORITY HAVING JURISDICTION. 11. A.F.F. = ABOVE FINISHED FLOOR 12. ELECTRICAL CONTRACTOR TO PROVIDE PULL STRINGS IN ALL CONDUIT(S). REMARKS: a. MOUNTED 16" ABOVE FINISHED FLOOR TO THE BOTTOM. b. MOUNTED 44" ABOVE FINISHED FLOOR TO THE BOTTOM. c. MOUNTED 50" ABOVE FINISHED FLOOR TO THE BOTTOM. d. OUTLET BOX SHALL BE SIZED PER SYSTEM INSTALLERS REQUIREMENTS. e. SUPPORT OUTLET BOX FROM STRUCTURE WITH (1) 3/8" ALL THREADS MINIMUM. BOXES LARGER THAN 25" SQUARE INCHES SHALL BE SUPPORTED WITH (2) 3/8" ALL THREADS MINIMUM. f. JUNCTION/OUTLET BOX SHALL BE SIZED AS REQUIRED FOR CONDUCTOR/DEVICES FILL PER N.E.C. g. THREADED CONDUIT HUBS SHALL BE SIZED AND CONFIGURED AS REQUIRED FOR APPLICATION. h. PROVIDE KINDORF MOUNTING RACK FOR FREE STANDING APPLICATIONS. KINDORF SHALL BE PAINTED FOR EXTERIOR APPLICATIONS. i. WHEN SURFACE JUNCTION BOX SYMBOL IS COMBINED WITH DEVICE SYMBOL, PROVIDE APPROPRIATE SURFACE PLATE FOR OUTLET APPLICATION. j. MAINTAIN WORKING CLEARANCES IN STRICT ACCORDANCE WITH N.E.C. COORDINATE EXACT LOCATION OF EQUIPMENT WITH ALL DISCIPLINES (I.E. ARCHITECTURAL, STRUCTURAL, HVAC, PLUMBING, FIRE PROTECTION, KITCHEN EQUIPMENT, MILLWORK, ETC.) PRIOR TO ROUGH -IN TO MAINTAIN CLEARANCES. k. "NL" INDICATES FIXTURE CONNECTED AHEAD OF ALL SWITCHES FOR 24 HOUR NIGHTLIGHT OPERATION. I. MOUNTED 80" ABOVE FINISHED FLOOR TO BOTTOM. m. ALL STROBES SHALL BE ADJUSTABLE INTENSITY TYPE SET AT 75cd UNLESS OTHERWISE NOTED. n. MOUNTED 72" ABOVE FINISHED FLOOR TO THE TOP. GENERAL NOTES 1. ALL BRANCH CIRCUIT CONDUCTORS WILL BE SIZED PER NEC MINIMUM. THE MINIMUM ALLOWABLE BRANCH CIRCUIT CONDUCTOR SIZE IS #12 AWG COPPER. INCREASE CONDUCTOR SIZE FOR APPLICATION PER NEC AND AS NOTED ON THE PLANS. 2. CONDUCTOR SIZES INDICATED ON CIRCUIT HOMERUNS OR IN SCHEDULES SHALL BE INSTALLED OVER THE ENTIRE LENGTH OF THE CIRCUIT UNLESS OTHERWISE NOTED ON THE DRAWINGS. 3. UP TO THREE PHASE CONDUCTORS, CORRESPONDING SWITCHLEGS AND NEUTRALS ARE ALLOWED IN THE SAME RACEWAY UNLESS INDICATED OTHERWISE ON THE DRAWINGS. DO NOT COMBINE HOMERUNS. 4. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDERS AND BRANCH CIRCUITS. 5. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL INSTALLER PRIOR TO ROUGH -IN. 6. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH PULL STRINGS IN THEM. 7. COORDINATE THE REQUIRED SIZE OF ALL CIRCUIT BREAKERS FEEDING EQUIPMENT, (I.E. MOTORS, HVAC, OWNER FURNISHED EQUIPMENT, E.T.C.) WITH APPROVED EQUIPMENT SHOP DRAWINGS AND OWNER REPRESENTATIVES. BREAKERS SHALL BE SIZED PER THE NEC, THE EQUIPMENT NAME PLATE AND MANUFACTURERS RECOMMENDATIONS. 8. THE USE OF ANY PROCESS INVOLVING ASBESTOS OR PCB, AND THE INSTALLATION OF ANY PRODUCT, INSULATION, COMPOUND OF MATERIAL CONTAINING OR INCORPORATING ASBESTOS OR PCB, IS PROHIBITED. THE REQUIREMENTS OF THIS SPECIFICATION FOR A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM SHALL BE MET WITHOUT THE USE OF ASBESTOS OR PCB. 9. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED. 10. CONTRACTOR SHALL INCLUDE IN HIS BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL RULES, REGULATIONS AND GUIDELINES APPLICABLE. 11. EXISTING CONDITIONS AND UTILITIES INDICATED ARE TAKEN FROM EXISTING CONSTRUCTION DOCUMENTS, VARIOUS SURVEYS AND FIELD INVESTIGATIONS. IT IS TO BE UNDERSTOOD THAT UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AS DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE ENGINEER MAY BE NECESSARY AND IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED A PART OF THIS CONTRACT. IT IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE. THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL EXISTING CONDITIONS PRIOR TO BID AND INCLUDE ANY DEVIATIONS IN THE CONTRACT. 12. LOCATE ALL EXISTING UTILITIES AND PROTECT THEM FROM DAMAGE. 13. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH THE CONSTRUCTION OF THE PROJECT. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR THE FACILITY TO BE FULLY FUNCTIONAL. 14. ALL RECEPTACLES, DEVICES, LIGHTING, SYSTEMS, AND EQUIPMENT NOT SHOWN, AND IN AREAS OUTSIDE OF REMODELING SHALL REMAIN ACTIVE UNLESS OTHERWISE NOTED. FURNISH AND INSTALL ACCESSIBLE JUNCTION BOXES AND REWORK EXISTING CIRCUITS AS REQUIRED TO MAINTAIN CIRCUIT CONTINUITY TO RECEPTACLES, DEVICES, LIGHTING, SYSTEMS AND EQUIPMENT. 15. ALL CONDUIT TO BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E. EXPOSED STRUCTURAL CEILINGS, BUILDING EXTERIOR WALLS). CONCEAL ALL CONDUITS ABOVE CEILINGS OR WITHIN WALLS AND COUNTERS. 16. ALL ITEMS REMOVED AND NOT REUSED SHALL BE TURNED OVER TO OWNER. DISCARD COMPLETE ITEMS WHICH OWNER ELECTS TO REFUSE. 17. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. WHEN WORK MUST BE PERFORMED ON ENERGIZED EQUIPMENT OR CIRCUITS, USE PERSONNEL EXPERIENCED IN SUCH OPERATIONS AND USE APPROPRIATE PERSONNEL PROTECTION EQUIPMENT. FOLLOW ALL SAFETY PROCEDURES INCLUDED IN NFPA 70E. 18. EXISTING ELECTRICAL SERVICE: MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR SERVICE. DISABLE SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER AT LEAST 72 HOURS BEFORE PARTIALLY OR COMPLETELY DISABLING SYSTEM. MINIMIZE OUTAGE DURATION. 19. REMOVE EXPOSED ABANDONED CONDUIT, INCLUDING ABANDONED CONDUIT ABOVE ACCESSIBLE CEILING FINISHES. 20. CLEAN AND REPAIR EXISTING MATERIALS AND EQUIPMENT WHICH REMAIN OR ARE TO BE REUSED. 21. ALL NEW CIRCUIT BREAKERS WITHIN EACH EXISTING PANELBOARD SHALL BE THE SAME MANUFACTURER TYPE, STYLE AND A.I.C. RATING OF EXISTING PANELBOARD. 22. SCREENED ELECTRICAL INDICATES EXISTING TO REMAIN ACTIVE, UNLESS NOTED OTHERWISE. 23. ALL CONDUIT AND WIRE REMOVED SHALL BE TAKEN BACK TO THE SOURCE OR SUPPLY. 24. CIRCUITING AND PANELS SHOWN ARE TAKEN FROM EXISTING CONSTRUCTION DRAWINGS, VARIOUS SURVEYS, AND FIELD INVESTIGATIONS OF READILY OBSERVABLE CONDITIONS. IT IS UNDERSTOOD THAT THE INSTALLED (CONCEALED) CIRCUITING MAY DIFFER FROM THE CONDITIONS SHOWN. THE ELECTRICAL CONTRACTOR SHALL TRACE ALL EXISTING CIRCUITS IN EXISTING PANELS ASSOCIATED WITH THIS SCOPE OF WORK AND UPDATE THE EXISTING PANEL SCHEDULE AS NEEDED. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER. DIV. 26 - ELECTRICAL SPECIFICATIONS 260500 BASIC ELECTRICAL REQUIREMENTS A) ALL WORK AND EQUIPMENT UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE WITH THE APPLICABLE PROVISIONS OF THE FOLLOWING CODES AND STANDARDS: 1. LIFE SAFETY CODE - NFPA 101 2. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS 3. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 4. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 5. NATIONAL ELECTRICAL CODE - NFPA 70 - 2017 EDITION 6. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE) 7. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA) 8. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPECAC) 9. NATIONAL ELECTRICAL SAFETY CODE 10. REQUIREMENTS OF LOCAL POWER CORPORATION 11. AMERICANS WITH DISABILITIES ACT (ADA) 12. FLORIDA BUILDING CODE - 7th EDITION - 2020 13. LOCAL CITY AND COUNTY CODES B) ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND SHALL BE EITHER UL LABELED, UL LISTED OR BEAR THE SEAL OF A NATIONALLY RECOGNIZED ELECTRICAL TESTING LABORATORY. C) THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR AND AUXILIARIES REQUIRED TO INSTALL A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM. D) THE CONTRACTOR SHALL FURNISH, PERFORM, OR PROVIDE ALL LABOR INCLUDING PLANNING, PURCHASING, TRANSPORTING, STORING, INSTALLING, TESTING, CUTTING AND PATCHING, TRENCHING, EXCAVATING, BACKFILLING, COORDINATION, FIELD VERIFICATION, EQUIPMENT (INSTALLATION AND SAFETY), SUPPLIES, AND MATERIALS NECESSARY FOR THE CORRECT INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS (AS DESCRIBED OR IMPLIED BY THESE SPECIFICATIONS AND THE APPLICABLE DRAWINGS) IN STRICT ACCORDANCE WITH APPLICABLE CODES, WHICH MAY NOT BE REPEATED IN THESE SPECIFICATIONS, BUT ARE EXPECTED TO BE COMMON KNOWLEDGE OF QUALIFIED BIDDERS. PRIOR TO SAW CUTTING OR CORE DRILLING, THE AREA SHALL BE CERTIFIED CLEAR OF EMBEDDED ELECTRICAL WIRING. E) THE SPECIFICATIONS (DIVISION 26) AND CONTRACT DOCUMENTS REFERS TO WORK REQUIRED IN ADDITION TO (OR ABOVE) THE MINIMUM REQUIREMENTS OF THE NEC AND APPLICABLE LOCAL CODES. ALL WORK SHALL COMPLY WITH ALL APPLICABLE CODES AS A MINIMUM AND WITH THE ADDITIONAL REQUIREMENTS CALLED FOR IN THESE CONTRACT DOCUMENTS (PLANS AND SPECS). F) SPECIAL REQUIREMENTS: SUBMIT TECHNICAL INFORMATION ON ALL EQUIPMENT. MARK UP PRINTS OF THE DESIGN DRAWINGS WITH RED PENCIL SHOWING AN ACCURATE "AS -BUILT" RECORD OF THE ENTIRE SYSTEM. TEST EACH ITEM OF EQUIPMENT. 260519 BUILDING WIRE AND CABLE A) ALL BRANCH CIRCUITS SHALL BE STRANDED COPPER WITH THWN INSULATION. MINIMUM SIZE #12 AWG. B) FEEDERS SHALL BE THWN STRANDED COPPER. C) COLOR CODING SHALL COMPLY WITH THE APPLICABLE NATIONAL ELECTRICAL CODE FOR GROUNDED CONDUCTORS. PHASE CONDUCTORS SHALL BE BLACK, RED, BLUE FOR 120/208V SYSTEMS AND BROWN, ORANGE, YELLOW FOR 277/480V SYSTEMS. D) ALL FEEDERS AND BRANCH CIRCUITS SHALL BE PROVIDED WITH AN EQUIPMENT GROUNDING CONDUCTOR. E) EXTERIOR LOCATIONS: ALL TAPS AND SPLICES SHALL BE MADE WITH COMPRESSION TYPE CONNECTORS AND COVERED WITH RAYCHEM HEAVY WALL CABLE SLEEVES (TYPE CRSM-CT, WCSM OR MCK) WITH TYPE "S" SEALANT COATING WITH SLEEVE KITS AS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS OR BE TERMINATED/DISCONNECTED TO TERMINAL STRIPS IN ABOVE GRADE TERMINAL BOXES SUITABLE FOR USE. F) INTERIOR LOCATIONS: ALL (NON -ELECTRONIC SYSTEMS) COPPER TAPS AND SPLICES IN #8 AWG AND SMALLER SHALL BE FASTENED TOGETHER BY MEANS OF SPRING TYPE WIRE NUT CONNECTORS. ALL COPPER TAPS AND SPLICES LARGER THAN #8 AWG SHALL BE MADE WITH COMPRESSION TYPE CONNECTORS OR SPLIT BOLT CONNECTORS AND PROVIDED WITH INSULATION EQUAL TO THE CONDUCTOR INSULATION. G) CONDUCTOR INSULATION AND MULTI -CONDUCTOR CABLE APPLICATIONS AND WIRING METHODS: 1. SERVICE ENTRANCE, FEEDER AND BRANCH CIRCUIT: TYPE THWN/THHN, SINGLE CONDUCTORS IN RACEWAY. 2. CLASS 1 CONTROL CIRCUITS: TYPE THWN/THHN, IN RACEWAY. 3. CLASS 2 CONTROL CIRCUITS: TYPE THWN.THHN, IN RACEWAY. 260529 SUPPORTING DEVICES A) ALL EQUIPMENT SHALL BE FIRMLY MOUNTED USING APPROVED HANGERS ATTACHED TO STRUCTURAL PORTIONS OF THE BUILDING. B) SUPPORTING WITH TIE WIRE IS PROHIBITED. 260533 RACEWAYS AND OUTLET BOXES A) ALL WIRING SHALL BE INSTALLED IN APPROPRIATE RACEWAY SYSTEMS OF RIGID GALVANIZED CONDUIT, ELECTRICAL METALLIC TUBING, SCHEDULE 40 PVC, FLEXIBLE STEEL CONDUIT AND LIQUID-TITE FLEXIBLE CONDUIT AS CONDITIONS AND CODE DICTATE. EMT SHALL BE JOINED WITH STEEL SET SCREW TYPE FITTINGS. PVC SHALL BE USED BELOW GRADE OR IN SLABS ONLY. B) ALL CONDUIT SHALL HAVE AN INSULATED COPPER EQUIPMENT GROUNDING CONDUCTOR THROUGHOUT THE ENTIRE LENGTH OF CIRCUIT WITHIN CONDUIT. C) MINIMUM CONDUIT SIZE TO BE 1/2" C. D) ALL PENETRATIONS THROUGH FIRE RESISTANCE RATED PARTITIONS AND OTHER ASSEMBLIES, INCLUDING EMPTY OPENINGS AND OPENINGS CONTAINING CABLES, CONDUITS AND OTHER PENETRATING ITEMS, SHALL BE FIRE -STOPPED TO PRESERVE THE FIRE RESISTANCE RATING OF THE ASSEMBLY. FIRE -STOPPING SHALL COMPLY WITH THE FOLLOWING: 1. COMPATIBILITY: PROVIDE FIRESTOPPING COMPOSED OF COMPONENTS THAT ARE COMPATIBLE WITH EACH OTHER, THE SUBSTRATES FORMING OPENINGS, AND THE ITEMS, IF ANY, PENETRATING THE FIRESTOPPING UNDER CONDITIONS OF SERVICE AND APPLICATION, AS DEMONSTRATED BY FIRESTOPPING MANUFACTURER BASED ON TESTING AND FIELD EXPERIENCE. 2. FIRESTOPPING SHALL BE LISTED IN THE UNDERWRITERS LABORATORIES FIRE RESISTANCE DIRECTORY AND INSTALLATION SHALL BE IDENTICAL TO THAT SHOWN IN THE DIRECTORY. 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS E) PROVIDE WIRE MARKERS FOR NEW CONDUCTORS AT ALL JUNCTION BOXES, WIREWAYS, ETC. F) IDENTIFY ALL CONCEALED JUNCTION BOXES WITH PERMANENT BLACK MARKER INDICATING PANEL AND CIRCUIT NUMBER, OR TYPE OF SYSTEMS (FIRE ALARM, TELECOMM, ETC.). G) PROVIDE PHENOLIC NAMEPLATES FOR ALL NEW EQUIPMENT TO MATCH EXISTING EQUIPMENT IN ELECTRICAL ROOM. r N 40 0 0 1 N� Ii W a. w O LL W I SALAS O'BRIEN expect a difference I 3501 Quadrangle Boulevard, Suite 100 Orlando, Florida 32817 (407) 380-0400 CERT. OF ALITH. NO. 6106 0 GARY A. WILKERSON, P.E. 43167 o KYLE J. CARTIER, P.E. 53260 0 JEFF A. KIRKMAN, P.E. 65629 ■ ADAM S. LEVINE, P.E. 77010 21-00035 THIS ITEM HAS BEEN aECTRONIC4LLYSIGNEDANDSEALED BY ADAM S. LEVINE, PE ON DATE INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE 'SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED ON ANY ELECTRONIC COPIES Date: Adam S Levine 2021.02.17 10:29:14-05'00' w Q ❑ z 0 D) LU J a w U x U O z 3 ga U_ I.L U W J W � � Cw G ) w LU }QQ 0/ Iny O z m w Z U J w Z Zw winn C-) w � ' ^ V J V Z D u) IY Lu C.) �O W F__ LL ON r� �/ / L (_ 0 Z (W V W J N N O a O M R N � O O C � 6 ry , ■ 1 WO m t REFERENCE NOTES - NEW O PROVIDE A MINIMUM 8"X8"X6" WALL MOUNTED, NEMA 3R ENCLOSURE. SPLICE CONDUCTORS INSIDE ENCLOSURE PER '260519 BUILDING WIRE AND CABLE' SPECIFICATION ON SHEET E0.1. 0 CONNECT NEW ROOFTOP UNIT'RTU-1' TO EXISTING CONDUIT AND CONDUCTORS. 0 UNIT MOUNTED, NON -FUSED DISCONNECT SWITCH PROVIDED WITH EQUIPMENT. REPLACE EXISTING FUSES WITH (3) NEW 90A, CLASS RK5, TYPE ECSR FUSES, EXIST. WITH BLADE TERMINALS TO MSB FIT IN EXISTING SWITCH. ELECTRICAL RM 207 E1.1 1/8"=1'-0" (2) ROOF PLAN - NEW - ELECTRICAL E1.1 1/8"=1'-0" REFERENCE NOTES - DEMOLITION D1 REMOVE EXISTING 100A HEAVY DUTY SAFETY SWITCH AND ASSOCIATED FUSES. MAINTAIN AND PROTECT EXISTING CONDUIT AND WIRING FOR RENOVATION. D2 MAINTAIN EXISTING (3) #3 AWG AND #6 AWG GND IN 1-1/4" CONDUIT. D3 DISCONNECT EXISTING ROOFTOP UNIT'RTU-1'. MAINTAIN EXISTING CONDUIT AND WIRING FOR RENOVATION. ROOF PLAN - DEMOLITION - ELECTRICAL GENERAL NOTES 1. SCREENED ITEMS ARE EXISTING TO REMAIN. 2. DASHED ITEMS ARE TO BE REMOVED. W GRAPHIC SCALE 1/8"=1'-0" 0® SALAS O'BRIEN expect a difference I 3601 Quadrangle Boulevard, Suite 100 Orlando, Florida 32817 (4071380-0400 CERT. OF AUTH. NO. 6106 o GARY A. W ILKERSON, P.E. 43167 o KYLE J. CARTIER, P.E. 53269 O JEFF A. KIRKMAN, P.E. 65629 ■ ADAM S. LEVINE, P.E. 77010 21-00035 TF II --BEEN B.ECTRONICPLLYSIGNEDANDSEALEDBY ADAM S. LEVINE, PE ON DATE INDICATED IN DIGITAL SIGNATURE USING A DIGITAL SIGNATURE. SIGNED AND SEALED AND THE SIGNATURE MUST BE VERIFIED CN ANY ELECTRON IC ODPIES. Date: Adam S Levine 2021.02.17 10:29:34-05'00' w QJ ❑ Z O N w Q w LU 2 U O to Z � ga Z Cw G w ` NN Q J Q z D m w U J o z _ w 75 U U Jz� (D J U) Lu LL.I O O U) `� Z O Q J U- O O N N O a O M O N � c 1 1 I 1 1 1 m ❑ t m